DuraLife TM FPL. Installation Guide. UL 2196 Fire Rated Alarm Cables. Authorities Having Jurisdiction should be consulted before installation.
|
|
- Amberlynn Wright
- 6 years ago
- Views:
Transcription
1 UL LISTED FPL FIRE ALARM CABLES; 2-HOUR FIRE RATED Unshielded - 16AWG - 14AWG; 2-conductor NEC Type FPL; for use in Electrical Circuit Integrity System FHIT.28A. Installation Guide Authorities Having Jurisdiction should be consulted before installation. 5_14
2 CRITICAL INSTALLATION INFORMATION INDEX Radix DuraLife TM FPL fire rated cables must be installed in accordance with ALL requirements of the UL 2196 Electrical Circuit Protective System Listing, plus national and local codes. Read carefully and follow the installation instructions in this booklet. Ensure that cable is stored properly in a moisturefree environment and that cable jacket is in good condition prior to installation. Take all precautions when installing cables by following OSHA and other applicable regulations. Store pull ropes in a clean, dry area, out of direct sunlight and away from extreme heat. While cables are exposed and during cable pulling activities, protect cables from nearby or overhead work to prevent damage to the cable jacket or insulation. Do not pull cables around corners with sharp edges as this may damage cable jacket/insulation. Pull cable only into clean EMT tubing. Visually check for debris, abrasions or sharp edges that might damage the cable prior to cable installation. Use only steel support systems. No other materials are acceptable. Support the cable in the manner and intervals detailed in the Electrical Circuit Protective System listing. INSTALLATION OVERVIEW... 2 CABLE RATINGS/APPROVALS... 2 CERTIFICATIONS... 2 & EMT FILL LISTING DURALIFE TM FPL CABLE OVERVIEW... 3 TYPICAL APPLICATIONS... 3 CABLE STORAGE & HANDLING PRE-INSTALLATION... 6 INSTALLATION SPLICE PROCEDURE FOR FIRE ALARM CABLES PULL-BOX AND SPLICE INSTALLATION EXAMPLES TESTING Radix Wire. All rights reserved. DuraLife TM is a registered trademark of Radix Wire. Made in USA 1
3 INSTALLATION OVERVIEW / CABLE RATINGS & APPROVALS CERTIFICATIONS & EMT FILL UL 2196 System Requirements The reliability of a fire rated cable system depends on correct system design, installation and use of approved components/materials. Failure to comply with these specific guidelines may result in a system that fails in fire conditions. Radix DuraLife TM FPL cables must be installed in Wheatland FasTrak Plus EMT tubing. Additional UL 2196 System Components include: Halex or Raco EMT Compression Couplings Cooper Crouse-Hinds Compression Fittings Hubbell Set-screw Fittings Cooper B-Line NEMA 1 Splice Enclosure/Pull Box Penn-Union Copper Off-Set Fixed Lug Connector with 1/4-20 Set-Screw Certifications & EMT Fill Listings CERTIFICATIONS 16 AWG 14 AWG Solid Conductor Strand Conductor - 3 Single-Cable EMT ¾ ¾ Install - Horizontal Wheatland Wheatland Single-Cable EMT ½ to 2 ½ to 2 Install - Vertical Wheatland Wheatland Multi-Cable EMT ¾ to 2 ¾ to 2 Install - Vertical Wheatland Wheatland FILL RATES 16 AWG 14 AWG ½ EMT 1 cable 1 cable ¾ - 1 EMT Up to 3 cables Up to 2 cables 1¼ EMT Up to 4 cables Up to 3 cables 1½ EMT Up to 6 cables Up to 4 cables 2 EMT Up to 10 cables Up to 8 cables Polywater J Lubricant Ratings & Approvals UL 2196 Certified/UL 1424 Listed FHIT SYSTEM No. 28A Low-Smoke, Zero-Halogen Unshielded 16AWG - 14AWG; 2-Conductor Maximum Voltage Rating: 72V (for fire applications) NEC Type FPL; for Use in Protective Electrical System (EMT) DuraLife FPL cables of different gauge sizes can be installed together in a single conduit up to the maximum allowed by the 14 AWG cable. No other cables or wires can be installed in the same conduit with DuraLife FPL cables. Authorities Having Jurisdiction should be consulted before installation 2
4 DURALIFE TM FPL CABLE OVERVIEW APPLICATIONS Radix DuraLife TM FPL fire rated power cables are designed to be flexible for easier installation. Oxygen-free bare copper (OFHC) conductors, solid and stranded Radix proprietary ceramifiable silicone rubber insulation; color-coded black and red insulation on leads Maximum cable voltage rating: 300V Low-smoke zero-halogen FRPE outer jacket. Red jacket standard. Black jacket available at an additional charge. PRINT LEGEND: RADIX WIRE-II DURALIFE X/C #Y AWG FPL 90C / (UL) CLASSIFIED FIRE-RESISTIVE CABLE FOR USE IN ELECTRICAL CIRCUIT INTEGRITY SYSTEM #28A. SEE UL FIRE RESISTANCE DIRECTORY R21213 (MONTH/YEAR). [where, X is the number of conductors and Y is the size of the cable in AWG]. Radix DuraLife TM FPL fire rated power cables are constructed and approved for the following applications: Fire alarm circuit integrity (NEC Article 760). Emergency systems (NEC Articles 700 and 517). Suitable for 2-hr. certified fire-resistive applications in Wheatland EMT tubing. Fire-resistive certified for Power-Limited system use at 72V phase-to-phase utilization voltage. Meets fire alarm survivability circuit requirements in the National Fire Protection Code (NFPA 72). UL 1424 Listed FPL for Power-Limited Fire Alarm Circuits; 300V/90 C classified. UL Certified to UL hour fire rating in FHIT System 28A. COMPLIANCE UL 1424 Listed FPL for Power-Limited Fire Alarm Circuits; 300V/90 C classified; UL Certified to UL hour fire rating in FHIT System 28A Meets fire alarm survivability circuit requirements in the National Fire Protection Code (NFPA 72). Meets vertical flame requirement for cable tray rating per UL
5 CABLE STORAGE & HANDLING Radix DuraLife TM FPL fire rated power cables are designed for durability. However, proper cable handling procedures must be followed to ensure the cable is not damaged prior to installation. Protect from Damage Choose a storage area that is cool, dry and protected from weather, construction activities, equipment collisions, falling objects, chemical spills, moving vehicles and other related hazards. Initial Inspection When cable reels are first received, inspect the protective reel wrap for evidence of shipment damage. Whenever possible, leave the Radix factory-applied protective cover in place until just before installation. Radix highly recommends the use of additional covering to protect cable reels when stored outdoors or in dirty, dust-prone areas. Use a cover that is resistant to moisture and shields cables from the sun. If possible, provide ventilation to avoid excessive heat in the storage area. Storage Procedure Store 1000 and 2000 reels on sides to avoid damaging reels. Store 5000 reels upright on flanges. Do not stack reels. Handle reels carefully to avoid physical damage to reel and cable. Store cables on a firm, dry surface or on planking in an area with good drainage. Arbor Hole Reel Flange Protective Reel Wrap Always store and transport reels as shown below. To avoid reel damage, do not stack and 2000 Reels 3 Stored on Side 5000 Reel Packaging: Available on 1,000 ft., 2,000 ft. and 5,000 ft. reels. Smaller length reels may be available from Radix Wire distribution partners. 3 Stored Upright on Flange Radix highly recommends storing cable reels indoors or in a weather-protected enclosure. 4
6 CABLE STORAGE & HANDLING Moving Reels A Radix DuraLife TM cable reel, depending on gauge and reel size, weighs pounds, so handle carefully by using equipment designed specifically for this task. Make sure the lifting/handling device does not come in direct contact with the cable or its protective covering. Take care to ensure that the flange of one reel does not impact cable on another reel. Do not drop reels from any height, especially from trucks or transport equipment. If any of these situations occur, immediately examine the DuraLife TM cable for damage. Recommended Reel Rolling Method It is a natural instinct to roll cable reels. However, Radix recommends only doing so for short distances over firm, level and dry surfaces. Roll reels in direction the cable is wound (see below) to keep the cable winding tight. Rolling in the wrong direction loosens the winding and may damage the cable or make it more difficult to deploy. Secure end of cable with tape or thread through flange hole and knot before rolling. Always roll reels at a slow speed to maintain control and prevent collisions with equipment, other reels or personnel. Recommended Lifting Methods Crane or boom-type equipment - Insert a suitably strong, properly secured shaft through the reel arbor hole and lift with slings. - Use a spreader or other device to minimize sling pressure against the reel flange. Forklift - Place fork tines so that lifting pressure is on both reel flanges, not the cable. Secure Loose Cable End with Tape Prior to Rolling Flange Hole Arbor Hole 5
7 PRE-INSTALLATION INSTALLATION Radix DuraLife TM FPL fire rated power cables must be installed in accordance with ALL requirements of the UL 2196 Electrical Circuit Protective System Listing, plus national and local codes. UL Electrical Circuit Integrity Systems (FHIT) Prior to installation, Radix highly recommends you visit and reference the Fire-Resistive and Circuit Integrity Cables section for the latest information and updates on UL Electrical Circuit Integrity Systems (FHIT). Checklist Check cable for presence of moisture or evidence of damage that may have occurred in storage. Take precautions if system routing comes in close proximity to abnormally high heat sources such as pipes. Long-term exposure to high heat could cause damage to cable jacket. Examine conduit supports prior to pulling cable to assure total system integrity. Inspect cable entry and exit points for any sharp, jagged edges which could damage cable jacket in pulling process. Authorities Having Jurisdiction should be consulted before installation. Radix recommends you follow the installation guidelines documented in the new NEC 2014 Article 728, Fire-Resistive Cable Systems. Article 728 covers the installation of fire-resistive cables, fire-resistive conductors and other system components used for survivability of critical circuits to ensure continued operation during a specified time under fire conditions as required in this Code. Wheatland EMT Tubing Installation Wheatland EMT support brackets must be installed no further apart than 72 in vertical orientation and 48 in horizontal orientation. These maximum support dimensions apply to all EMT tubing sizes. For complete overview of Wheatland EMT tubing installation, reference 2014 NEC Article 358 which covers Electrical Metallic Tubing (EMT) and all applicable Articles of the Code, as well as any listing, labeling or manufacturer s instructions. WEIGHT/1000 FT CABLE SIZE (LBS) 16 AWG Solid 2-Conductor AWG 7-Strand Conductor AWG Solid 2-Conductor For installation of all other UL 2196 certified system components, consult each manufacturer s installation instructions. See page 2 for list of manufacturers. 6
8 INSTALLATION Cable Pulling Use Polywater J lubricant prior to pulling cables. Use a pulling rope which can handle the maximum allowable pulling tension on each cable pull without causing damage to the equipment or cables. Refer to the pulling equipment/rope manufacturer s specifications for capacity limitation. Bend Radius DuraLife TM FPL is designed to be highly flexible for easier installation. No special equipment is required to bend or straighten this cable. Maximum Recommended Bend Radius: 2X Cable Diameter Maximum Allowable Pulling Tension TENSION CABLE SIZE (LBS) Solid 16 AWG & 14 AWG 15 7-Strand 14 AWG 15 Cable Preparation for Splicing DuraLife requires no special tooling or procedures for jacket/insulation stripping. Take care when stripping jacket not to damage cable insulation. Follow all NEC splicing and termination standard practices for this category of cable. Do not exceed Radix s recommended pulling tension for DuraLife TM FPL as this may damage the jacket, insulation or conductor which can lead to failure in a fire event. Conduit fill should not exceed allowable limits. See page 3 for Fill Ratings. Install Procedure for NEMA Splice Enclosures/Pull Boxes See pages 9-12 for step-by-step instructions. DuraLife FPL cables of different gauge sizes can be installed together in a single conduit up to the maximum allowed by the 14 AWG cable. (see chart on page 3) No other cables or wires can be installed in the same conduit with DuraLife FPL cables. 7
9 INSTALLATION OVERVIEW Vertical Installation Maximum of 28 Feet Between Terminating Points Wheatland EMT support brackets must be installed no further apart than 72 inches in vertical runs Horizontal Installation No length limit between Terminating Points Wheatland EMT support brackets must be installed no further apart than 48 inches in horizontal runs See Page 13 for Representative Pull-Box Installation Photo No other cables or wires can be installed in the same conduit with DuraLife FPL cables. See Page 2 for UL 2196 Approved System Components See Page 2 for UL 2196 EMT Fill list and DuraLife Certifications Authorities Having Jurisdiction should be consulted before construction in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials. 8
10 SPLICE PROCEDURE FOR FIRE ALARM CABLES Cooper B-Line NEMA 1 Splice Enclosure/Pull Box Required Materials: Cooper B-Line NEMA 1 Box (i.e., Cooper B-Line 884 SC Series) Steel ¼ -20 X ½ Hex Head Cap Screws Steel ¼ Screw Size Washers Rubber -010 Size O-Rings (i.e., McMaster Carr Product No.9452K18) Ceramic 1 Length, ¾ OD, ¼ -20 Female Thread Standoffs (i.e., McMaster Carr Product No.94335A151) Steel ¼ -20 X 1¼ Fully Threaded Studs Copper Set Screw Lug Offset Tongue Terminal (i.e., McMaster Carr Product No. 6923K32) Steel ¼ -20 Hex Nuts 17/64 Drill Bit (not shown) DuraLife TM FPL cable must be installed in Wheatland EMT tubing to comply with UL DuraLife cables are not approved for use in rigid conduit systems. Conduit fill should not exceed allowable limits. See page 3 for Fill Ratings. Alternative Components: Longer Ceramic Standoff (i.e., McMaster Carr Product No A152) Straight Tongue (Non-Offset) Copper Terminal (i.e., McMaster Carr Product No. 6923K62) 9
11 SPLICE PROCEDURE FOR FIRE ALARM CABLES 1. Drill two holes into the back of the NEMA 1 box spaced at least 1¼ apart to mount ceramic standoffs. 3. Apply O-rings to screws inside NEMA box. Spaced at Least 1 1/4 Apart 4. Install ceramic standoffs to screws until O-rings are slightly compressed. 2. Insert ¼ hex cap screws with washers from back of NEMA 1 box. Washer/ Hex Nut 10
12 SPLICE PROCEDURE FOR FIRE ALARM CABLES 5. Insert threaded studs into ceramic standoffs. 7. Affix hex nuts to studs until O-rings are slightly compressed. 6. Apply O-rings to studs. 8. Strip leads for termination. O-Ring 11
13 SPLICE PROCEDURE FOR FIRE ALARM CABLES 9. Bend stripped end 180 to provide more secure terminal attachment. 11. Place terminals onto studs. 12. Install washers onto studs. 10. Securely attach terminals to stripped ends. 13. Fasten hex nuts onto stud and, while holding ceramic insert to immobilize assembly, tighten hex nut. This installation segment is now completed 12
14 REPRESENTATIVE PULL BOX INSTALLATION. TESTING UL 2196 should be referenced as the test standard used to evaluate fire-resistive performance of electrical cables. UL 2196 is one of the testing standard for FHIT Certified assemblies. All manufacturers installation instructions should include any design elements beyond the minimum NEC requirements used to pass the performance testing. REPRESENTATIVE SPLICE INSTALLATION. If you have any questions about the installation of this system, please contact: Radix Wire Lakeland Blvd. Euclid, OH Toll-Free: Local:
Comtran s VITALink 2 Hour Fire Resistive CIC & CI Free Air Cables. Your trusted solution for fire safety
Comtran s VITALink 2 Hour Fire Resistive CIC & CI Free Air Cables Your trusted solution for fire safety When it comes to life and fire safety, trust the experts! Comtran has been a trusted source in the
More information2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK
PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 27 12 23 FIBER OPTIC DATA NETWORK A. Furnish, install, terminate, and test all fiber optic equipment and cabling necessary for a complete and functional data highway
More informationCorra/Clad MC Cable The contractors cable of choice in place of conduit and wire.
Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire. Installs fast and easy Lowers labor costs Replaces conduit and wire Provides superior grounding UL Listed Corra/Clad MC
More informationVITALink. FAQs I. GENERAL QUESTIONS
I. GENERAL QUESTIONS 1) Why do I need to use Circuit Integrity cables? Circuit Integrity cables are utilized to protect critical emergency circuits and maintain operability of fire alarm system in order
More informationHeat Exchanger Block Replacement Instructions
Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement
More informationInstalling Protectowire Linear Heat Detector
PROTECTOWIRE FireSystems 1. Purpose The purpose of this guide is to ensure coverage of the area to be protected in accordance with accepted fire protection principles and to assure uniform installations.
More informationQuartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE
Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath
More information52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.
Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging
More informationHome Theater Cables. Your complete solution for high-end audio transmission, stereo, professional audio systems and home theater systems.
Home Theater Cables Your complete solution for high-end audio transmission, stereo, professional audio systems and home theater systems. Home Theater Sound Jacketed Cables Shielded: Twisted Bare Copper
More informationDAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz
DAGNY LK Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 110V~60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any
More informationMEDIUM, LOW AND CONTROL VOLTAGE CABLES
Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with
More informationPHOTOVOLTAIC CABLES. Photovoltaic Cable 2000V/1500V Photovoltaic Cable 2000V/1000V
PHOTOVOLTAIC CABLES PHOTOVOLTAIC CABLES INDEX n AmerSol Dual-Certified (UL / ETL) Photovoltaic Cable 2000V/1500V....................... 2-3 n AmerSol Dual-Certified (UL / ETL) Photovoltaic Cable 2000V/1000V.......................
More informationInstallation Manual PS-200 & PS-201
Installation Manual PS-200 & PS-201 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal
More information42 Kevlar. Instruction Manual. Kichler Lighting 7711 East Pleasant Valley Road P.O. Box Cleveland, Ohio
42 Kevlar Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Customer Service 866.558.5706 8:30 AM to 5:00 PM EST, Monday - Friday Instruction Manual 1 1. SAFETY
More informationSWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL
SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationProduct Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.
Fire Alarm Cables Initiating Device, SLC Lines, and NAC Cables Product Guide STANDARDS Fire Alarm Systems A fire alarm system is number of devices working together to detect and warn people through visual
More informationInstructions. Duct Mount Accessory Q Rev: 11/
Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4
More informationInstallation Instructions
GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover
More informationFRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1
FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1 Hotfoil, Inc. Robbinsville, New Jersey Phone: 609.259.4118 Fax: 609.259.4119 http:\\hotfoil.com INDEX Section I Product Specification
More informationTIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL
TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR PUMP 88 PUMP PARTS BREAKDOWN REF # Order # Mfr # Description 1 NEP4 AC 348 Lid Knobs NEP AC 380 Strainer Lid 3 NEP6
More informationXC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard.
XC-18 NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard. EXTREMA MACHINERY COMPANY, INC. PO BOX 1450, ALBANY, LOUISIANA
More informationInstallation Manual PS-225 & PS-275
Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal
More informationInstallation. Leveling
Your refrigerator was packed carefully for shipment. Remove and discard shelf packaging and tape. Do not remove the serial plate. Location Do not install refrigerator near oven, radiator or other heat
More informationFireSystems PROTECTOWIRE. Installing Protectowire Linear Heat Detector
PROTECTOWIRE FireSystems Installing 1. Purpose The purpose of this guide is to ensure coverage of the area to be protected in accordance with accepted fire protection principles and to assure uniform installations.
More informationReference Guide 2.1. Certificate Number
SAFE Reference Guide 2.1 This reference guide provides general information for the installation, servicing, and maintaining of a Linear Heat Detection System. For more detail, please refer to the Installation
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)
SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill
More informationTeflon Rotary Drum Pump
Operating Instructions & Parts Manual 6005 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and
More informationSuperKlean Washdown Products
DURAREEL DR8 & DR8S INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** GENERAL WARNINGS High pressure and hot
More informationINSTALLATION INSTRUCTIONS
Page 1 INSTALLATION INSTRUCTIONS DEKORON / UNITHERM ELECTRIC TRACED BUNDLES, HEATED HOSES, HYBRID BUNDLES, AND PROBE SUPPORT BUNDLES FOR CEM APPLICATIONS Form INSTCEM040103 This bulletin provides the Field
More informationC Electrical Connection Kit
1548-4010C Electrical Connection Kit For Use With Dekoron 2700 and 2300 Family of Heating Cables Installation Instructions Kit Description The Dekoron 1548-4010C electrical connection and end seal kit
More informationInstallation Instructions Air Pump
Important Read all instructions and identify all parts before assembling and installing pump. Observe all local plumbing and electrical codes and the National Electric Code. Electrical installation should
More informationInstallation Instructions
GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover
More informationSelect. Sutter PlaceTM. Instruction Manual. A Kichler Select ceiling fan
Sutter PlaceTM A Kichler ceiling fan Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Customer Service 866.558.5706 8:30 AM to 5:00 PM EST, Monday - Friday Instruction
More information1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.
1 1. SAFETY RULES 1. To reduce the risk of electric shock, insure electricity has been turned off at the circuit breaker or fuse box before beginning. 2. All wiring must be in accordance with the National
More informationDishwasher Installation Instructions DW 24XT/DW 24XV
Dishwasher Installation Instructions DW 24XT/DW 24XV Installation Instructions Dishwasher BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT Observe all governing codes and ordinances.
More informationInstallation Instructions 30 French Door Built-in Wall Ovens
Installation Instructions 30 French Door Built-in Wall Ovens Questions? Call 1.800.GE.CARES (1.800.432.2737) or visit www.geappliances.com In Canada, call 1.800.561.3344 or visit www.geappliances.ca DESIGN
More informationSECTION ELECTRICAL GENERAL PROVISIONS
PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling
More information36"x17" Portable Tool Chest and 6-Drawer Tool Cabinet
36"x17" Portable Tool Chest and 6-Drawer Tool Cabinet CHEST 24571 CABINET 24572 CAUTION: 1. Read and follow all safety information and instructions before using this product for the first time. 2. Fill
More informationC-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz
C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company
More informationUMA-1020 Light Weight Suspended Ceiling Kit
INSTALLATION INSTRUCTIONS UMA-1020 Light Weight Suspended Ceiling Kit The provides a sturdy support for LCD/DLP hanging brackets (and certain other products weighing less than 50 pounds) when installing
More information52 DorsetTM. Instruction Manual. Basic Function Wall Control System Included. A Kichler Decor ceiling fan
Basic Function Wall Control System Included 52 DorsetTM II A Kichler Decor ceiling fan Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Customer Service 866.558.5706
More information60" Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan
60" Tulle PatioTM A Kichler Select ceiling fan cul Certified for Wet Location Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Customer Service 866.558.5706 8:30
More informationUSER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS
USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS APPLICATION INDEECO Explosion proof Electric Immersion Heaters for Hazardous Locations are ccsaus Certified for use in areas (external
More information1SC-SSC Splice Connection Kit Installation Instructions
1SC-SSC Splice Connection Kit Installation Instructions Description The 1SC-SSC is a NEMA 4 rated splice connection kit for use with Raychem 1SC30, 40, 50, 60, 70, 80 (-CT) and 1SC/H30, 40, 50, 60, 70,
More informationCartridge Heaters. Metric FIREROD Cartridge. Applications and Technical Data
W A T L O W The Watlow FIREROD not only set the industry standard for cartridge heaters, it continues making improvements in construction and design. Among those improvements is the metric FIREROD, a variation
More informationFlexible Power Cable DLO
37-119 Flexible Power Cable DLO 2000 Volts 90 C Diesel Locomotive Cable Limited Smoke (Sizes 2/0 and higher) EP/CPE RHH, RHW-2 Flexible-stranded, tin-coated annealed copper Flame retardant, oil and sunlight
More informationTT3000 and TT5000 Series
TT3000 and TT5000 Series Bulk Sensing Cable Installation Instructions General Notes Do s and Don ts General Information These instructions detail techniques used to install TT3000 or TT5000 bulk sensing
More informationGE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y
GE Monogram Installation Instructions Component Cooktop System Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y Before you begin Read these instructions completely and carefully. IMPORTANT: Save
More informationInstallation Instructions. For the 18 Built-In Dishwasher and Front Color Panels
Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,
More informationINSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP
INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................
More informationMAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP
MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP 8104 MAXI-PUMP PARTS BREAKDOWN Re f # 1 2 3 4 5 6 7a 7b 8 9 10 11 12 13 14 15 16 2 Part # NEP2134 NEP2135
More informationInstallation & Maintenance Instructions
B2451 & B2452 Series Wall Heaters SPECIFICATIONS MODEL VOLTS HZ AMPS WATTS BTUH B2451 120 60 12.5 1500 5120 B2452 240 60 8.3 2000 6826 208 60 7.2 1500 5120 DIMENSIONS OVERALL Height - 14 1/4 Width - 11
More informationREAD AND SAVE THESE INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS CEILING FAN INSTALLATION AND OPERATION INSTRUCTION FAN RATING AC 120V. 60Hz UL LISTED MODEL: AC-552OD WEIGHT OF FAN: 6.82 KGS 1. TOOLS AND MATERIALS REQUIRED Philips screw
More informationINSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS
INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.
More informationRevisions to this application specification include: Updated document to corporate requirements Changed product types in table in Figure 6
This specification covers the requirements for application of PLASTI GRIP Terminals and Splices for commercial applications. The terminals and splices consist of precision formed metal wire barrel insulated
More informationELECTRIC COOKTOP INSTALLATION INSTRUCTIONS
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER. IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. U.S.A. WARNING FOR YOUR
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationDISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:
DISHWASHER Models DW2432 and DW2432SS Installation Manual Write Serial Number (on inner door of unit) here: Felix Storch, Inc. Summit Appliance Division 770 Garrison Avenue Bronx, New York 10474 www.summitappliance.com
More informationINSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS
RV Products Division INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330C755 CONTROL BOX KIT (12 VDC HEAT READY) 8530-750 CONTROL BOX KIT
More informationCIR CRUSH & IMPACT RESISTANT ARCTIC GRADE OIL & GAS CABLES
CIR CRUSH & IMPACT RESISTANT ARCTIC GRADE OIL & GAS CABLES Gexol CIR ARCTIC GRADE (AG) Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by
More informationChromalox. Installation, Operation. Screw Plug Heating Solution Control Panel Assembly for Screw Plug Heaters RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation and RENEWAL PARTS IDENTIFICATION DIVISION SALES REFERENCE DATE 4 (Supersedes PG422-) DECEMBER, 2000 SECTION RAD PE440 6-058074-002 Screw Plug Heating Solution Control
More informationBuilt-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be
Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these instructions completely and carefully.
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS - Wall-mount indoor unit - OPERATING LIMITS Cooling Maximum conditions Heating Maximum conditions Outdoor temperature : 122 F (50 C) D.B. Outdoor temperature : 75 F (24 C) D.B.
More informationINSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330A755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)
More informationInstallation Instructions
Installation Instructions Built-In Dishwasher If you have questions, call 800-944-9400(US),800-245-8352(Canada)or visit our website at: www.frigidaire.com BEFORE YOU BEGIN Read these instructions completely
More informationSPECIFICATIONS FEATURES
FEATURES Excellent for collecting the large chips which will drop into the garbage can before reaching the impeller. The filter bag filters out the remaining sawdust down to 5 microns. With the cyclone
More informationMODELS 304GC, 304GCX, 314GC, and 314GCX
2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited
More informationFEB 16 Rev T
ORIGINAL INSTRUCTIONS Hand Crimping Tools 46673, 46673-1, and 46988 for STRATO-THERM* Terminals Instruction Sheet 408-1535 12 FEB 16 Rev T PROPER USE GUIDELINES Cumulative Trauma Disorders can result from
More informationEUTECTIC EC-10DV Series
EUTECTIC EC-10DV Series DIRECT VENT OIL-FIRED WATER BOILER/NO. 2 OIL VENTING INSTALLATION INSTRUCTIONS CONTENTS..........................................PAGE Basic Guidelines..........................................1
More information2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP
2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP 8308 PUMP PARTS BREAKDOWN Ref # Part # Manf. # Descrip on 1 NEP2134 AC 81361 PUMP LID 2 NEP2135 AC 81396 PUMP LID
More informationInstallation Electric Dryers Instructions 01
Installation Electric Dryers Instructions 01 Questions? Call 800.GE.CARES (800.432.2737) or visit our Web site at: GEAppliances.com This is the safety alert symbol. This symbol alerts you to potential
More informationInstallation Instructions
Installation Instructions Built-In Dishwasher If you have questions, call 800-GECARES or visit our website at: www.geappliances.com BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT
More informationWATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00
I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be
More informationIMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS. Electric Wall Panel. Owner s Manual & Installation Instructions L
Electric Wall Panel Owner s Manual & Installation Instructions 8 Element Wall Panel Front View 8 & 6 Element Wall Panel Side View 6 Element Wall Panel Back View Top 23 1 8 EWP 8 EWP 6 Bottom 17 1 4 2 3
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control
More informationStandard Downrod for ceilings 8-10 feet high. Longer Downrod for ceilings 10 feet or higher
Table of Contents www.casablancafanco.com To register your fan, please visit: www.casablancafanco.com/register What to Expect with Your Installation Save your receipt for proof of purchase. Ceiling Bracket??
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationInstallation Instructions Built-In Dishwasher
GE Consumer & Industrial Appliances Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these
More informationSafety. Rinse Kit for Multi-Pro 1200 and 1250 Turf Sprayers Model No Safety and Instructional Decals. Installation Instructions
Rinse Kit for Multi-Pro 1200 and 1250 Turf Sprayers Model No. 106-4842 Form No. 3353-529 Rev B Installation Instructions Note: Determine the left and right sides of the machine from the normal operating
More informationPart#: 26B113 HEAVY DUTY CAST IRON ROTARY DRUM PUMP
Part#: 26B113 Part # 26B113 Description HEAVY DUTY CAST IRON ROTARY DRUM PUMP Operating Instructions & Parts Manual Please read and save these instructions. Read carefully before attempting to assemble,
More informationINSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended
More informationHatteras BayTM. Patio. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.
Hatteras BayTM Patio A Kichler Décor ceiling fan Designed to coordinate with a popular Kichler Lighting collection. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go!
More informationCIR AG Power Cables. CIR AG Control Cable. CIR Type VFD Cable. CIR AG Ratings & Approvals. n UL Listed as Type TC-ER n UL Listed as TC-ER-HL (E123629)
Gexol CIR ARCTIC GRADE (AG) Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Shortest Lead Times Standard 8-10
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44
More informationIMPORTANT INFORMATION. Revised Dishwasher Installation Instructions
IMPORTANT INFORMATION Revised Dishwasher Installation Instructions To obtain a revised copy of the entire Dishwasher User s Manual, go to www.eurotechappliances.com. SPECIAL EDITION 11-20-02 SAVE THESE
More informationINSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY DESIGNED AND MANUFACTURED BY THE MAKERS
More informationElectric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada
Electric Floor Warming Systems Installation and Operation Instructions Mat Heating Systems and Cable Heating Systems UL Listed for USA and Canada Thank you for your purchase of a Warming Systems electric
More informationCEILING FAN OWNER'S MANUAL
Style that revolves around you. CEILING FAN OWNER'S MANUAL QUATRO 10/09 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. GENERAL INSTALLATION & OPERATION
More informationI-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS I-VICFLEX.AB Victaulic VicFlex Style AB Sprinkler Fitting for Hat Furring Channel Ceiling Systems Read and understand all instructions before attempting to install any Victaulic
More informationOwner s Guide and Installation Manual
For Your Records and Warranty Assistance For reference, also attach your receipt or a copy of your receipt to the manual. Model Name Type 2A Models Owner s Guide and Installation Manual Model No. Date
More informationMODELS ASHP, ASHH, ASUP, and ASUH
2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY
More informationWATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2
I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More informationINSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER
INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER TABLE OF CONTENTS 1. Warnings...................................................... 3 2. Component Match-Up...........................................
More informationCIR CRUSH & IMPACT RESISTANT OIL & GAS CABLES
CIR CRUSH & IMPACT RESISTANT OIL & GAS CABLES Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL Index
More informationMODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload
2900 FIREGUARD Electromechanical Closer-Holder Device Models 12-2960, 9-2960 and 2960 Multipoint Hold Open with Rigid Arms Pull (Hinge) Side Installation Instructions CAUTION: FAILURE TO INSTALL OR ADJUST
More informationKE-Series Constant-Wattage Heating Cable
KE-Series Constant-Wattage Heating Cable Installation Instructions Read and understand this material before installing this heater. Failure to understand how to safely install the heater could result in
More informationCEILING FAN OWNER'S MANUAL
CEILING FAN OWNER'S MANUAL READ AND SAVE THESE INSTRUCTIONS MODEL: 52-854-5RV-234 52-854-5RV-CH 52-854-5RV- FAN RATING AC 120V. 60Hz CUL LISTED MODEL : AG-962MC 1. TOOLS AND MATERIALS REQUIRED Philips
More informationan ISO 9001:2015 Registered Company
an ISO 9001:2015 Registered Company Mark IV (672001-VHY) 18865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com www.vintageair.com 902001-VHY
More informationECONO FLO VSA 165 VARIABLE SPEED PUMP OWNER S MANUAL
ECONO FLO VSA 165 VARIABLE SPEED PUMP OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING: Before installing this product, read and follow all
More informationINSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP
INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings...2 2. Component Match-Up...2 3. Unit Depiction Figures...3 4. Blower Performance Data...5 5. General
More information