S000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM

Size: px
Start display at page:

Download "S000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM"

Transcription

1 APPR NO. FIRE CODE COMPLIANCE ITEM S000 S001 S005 (Automobile Access Aisle) shall be a minimum of 5 ft wide, a common access aisle may be shared by 2 vehicles. Surface slopes shall not exceed 1:50(2%) in any direction ADA Standards 502. (Van Access) aisle shall be a minimum of 8 ft wide. A common access aisle may be shared by 2 vehicles. The access aisle shall be to the right of the van parking space for angled spaces. Surface slopes shall not exceed 1:50(2%) 2010 ADA Standards, 502. S010 An (Address) to include an approved Numerical and Street name designation shall be provided. Provide designations for each building on the submitted plans. International Fire Code, Chapter 5, Section 505.1, 2012 Edition. S015 S020 S025 S030 S035 S040 S045 S050 S055 S060 S065 S070 S075 Provide a (Flow Test) certified by the appropriate water department on the nearest fire hydrant to the proposed building is required if the existing main size is 8 inch inside diameter. Minimum flow to be 1250 gpm with a residual of 20 psi. If existing main is 6 inch, the minimum flow is to be 1000 gpm with a residual of 20 psi. Gwinnett County Ordinance For Fire Protection And Life Safety, Section (Water Main) location and sizes are to be shown on plan. (Entrances) to the Building in new construction shall be provided per the requirements of 2010 ADA Standards Accessible entrances must be provided in a number at least equivalent to the number of exits required by the applicable building/fire codes. At least one (Accessible Route) complying with 2010 ADA Standards shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site. Every (Dead-End Access Roads) in excess of 150 feet in length shall be provided with an approved area for turning around fire apparatus. International Fire Code, Chapter 5, Section , 2012 Edition. Gwinnett County Ordiance For Fire Protection and Life Safety, Section 46-43(e) (Fire Lanes) shall be installed in streets or roads adjacent to buildings, on at least one side which presents major point(s) of access into the building. International Fire Code, 2012 Edition. Gwinnett County Ordinance For Fire Protection And Life Safety, Section October 26, Fire Code Compliance Checklist

2 S080 (Edge Protection) shall be provided per 2010 ADA Standards S085 S090 S095 S100 S102 S105 S110 S115 S120 S125 S130 (Sprinkler Connection) for fire department use is to be a maximum of 150 ft from a fire hydrant on an 8 inch water main. The connection shall be between 18 inches and 40 inches above ground level per NFPA Edition. (Fire Department Sprinkler Connection) locations shall be shown on the site plan. e on the site plan that a Georgia Certificate of Competency holder for automatic fire sprinkler systems will be responsible for the design and installation of the underground supply piping. (Installation or Repair) of Underground Fire Sprinkler water supplies shall be performed by a utility or fire sprinkler contractor or licensed plumbing contractor. Chapter 11. (Fire Department Connections) if installed underground shall have a listed check valve, an auto-drip valve, a sign on a plate or fitting reading, "Auto-Sprinkler or Auto- Sprinkler/Standpipes", and hose connections shall have standard threads as specified. Post Indicator Valves (PIV) in the underground piping shall be omitted unless specifically permitted by the Gwinnett County Fire Marshal's Office. (Hydrant) locations are to be shown on plans. (Placement of Fire Hydrants) shall be a minimum of 3 ft. and a maximum of 15 ft. from the back of the curb or road edge with the large fire department connection facing the nearest fire department access point and set a minimum of 18" and a maximum of 36" above finished grade to the center of the large fire department connection.gwinnett County Ordiance For Fire Protection And Life Safety, Section (b) (Fire Hydrants and Water Mains) are to be installed, flushed and under pressure before any combustible construction is started. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-38(a). (Fire Hydrants) in Single Family Residential shall be spaced no more than 450 ft. apart. Gwinnett County Ordinance For Fire Protection and Life Safety, Section 46-37(a). (3-way Fire Hydrants) in Multi Family residential subdivisions shall be located such that all portions of the building can be reached by fire hose lays not to exceed 400 ft. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-37(c). (Fire Hydrant Spacing) in Industrial & Commercial developments. Additional hydrants may be required to permit all portions, of all buildings, to be reached by hose lays not to exceed 400 ft by road travel. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-37(c). S135 S140 S145 (Marking and Signage) of Fire Lanes shall be provided per the requirements of The International Fire Code, Chapter 5, Section 503.3, 2012 Edition. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-65(c)(1)(2). (Grades) shall be no more than 10%. International Fire Code, 2012 Edition, Section (Ground & Floor Surfaces) along accessible routes and walks, ramps, stairs, and curb ramps, shall be stable, firm, slip-resistant, and shall comply with 2010 ADA Standards S150 (Handrails) shall be designed per 2010 ADA Standards October 26, Fire Code Compliance Checklist

3 S155 S156 "e on Plan" During construction and for Permanent Access, roadways constructed of an all weather surface capable of supporting 75,000 pounds gross weight shall be provided per International Fire Code, Chapter 5, Section , 2012 Edition. Approved Fire Apparatus Access Roads shall be provided for every facility, building or portion of a building. The fire apparatus access road shall extend to within 150 feet of all portions of the facility or any portion of the exterior wall of the first story of the building as measured by an approved route around the exterior of the building or facility. International Fire Code, Chapter 5, Section , 2012 Edition. S160 (Islands) at marked crossings shall be designed per 2010 ADA Standards S165 (Landings) shall be designed per 2010 ADA Standards S170 S175 S180 S185 S190 S195 S200 S205 (Location) of accessible parking spaces shall be provided per 2010 ADA Standards The (Maximum Slope) of the accessible parking spaces & access aisles shall be 2% in all directions. (Curb Ramps) at Marked Crossings shall be wholly within the markings excluding flared sides. Signage shall be located so it cannot be obstructed by a vehicle per 2010 ADA Standards (Accessible Parking Spaces) shall be provide in the amount per the requirements of 2010 ADA Standards (A detail can be downloaded from our website at gwinnettfireplanreview.com under documents) (Curb Ramps) shall be located or protected to prevent their obstruction by parked vehicles per 2010 ADA Standards (Outdoor Ramps & Their Approaches) shall be designed so that water will not accumulate on walking surfaces per 2010 ADA Standards (Passenger Loading Zones) shall be provided per the requirements of 2010 ADA Standards If an (Accessible Route) has less than 60 inches clear width, then passing spaces at least 60 inches by 60 inches shall be located at reasonable intervals not to exceed 200 ft. A T - intersection of two corrdors or walks is an acceptable passing place per 2010 ADA Standards October 26, Fire Code Compliance Checklist

4 S210 Separation from Transformers. Space separation for transformers shall be as follows: (1) Transformer pad locations shall be a minimum of 10 feet (3 m) from any building, building overhangs, canopies, exterior walls, balconies, exterior stairs and/or walkways connected to the building. (2) Transformer pad edges shall be not less than 14 feet (4.3 m) from any doorway. (3) Transformer pad edges shall be not less than 10 feet (3 m) from any window or other opening. (4) If the building has an overhang, the 10 foot (3 m) clearance shall be measured from a point below the edge of the overhang only if the building is three stories or less. If the building is four stories or more, the 10 foot (3 m) clearance shall be measured from the outside building wall. (5) Fire escapes, outside stairs, and covered walkways attached to or between buildings, shall be considered as part of the building. Exception No. 1: For (1), transformer pads may be located closer to noncombustible walls than the above required minimum clearances upon written approval of the authority having jurisdiction, however, in no case shall the transformer location be less then 3 feet (0.9 m) from the building. Exception No. 2: Transformer pads existing prior to December 31, 1994, are exempted from this requirement. When buildings are modified, reductions in space separations may be less than the above required minimum clearances upon written approval of the authority having jurisdiction IFC 2012 S215 Ramps shall be provided where required by 2010 ADA Standards S220 S225 S230 S235 S240 S245 S250 Place ramp details on the plans.(a detail can be downloaded from our website at gwinnettfireplanreview.com under documents) (Fire Lanes) shall be at least 20 ft. in width with the road edge closest to the structure a minimum of 10 Ft. from the structure. Gwinnett County Ordinance For Fire Protection And Life Safety, Section (Access Road) width for one way roads shall be a minimum of 14 feet (SECURITY GATES ONLY). (Clear Width) of a ramp between handrails shall be 36 inches per 2010 ADA Standards (Security Gate Installation) shall be reviewed and permitted prior to installation. Installation shall comply with the Fire Marshal's General Order on "Security Gate Access" dated September 15, 2001.Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-43(a). International Fire Code, Chapter 5, Section 506, 2012 Edition. (Plans) for retail Self-Service gasoline operations shall be reviewed and permitted by the Georgia State Fire Marshal's Office Hazardous Material Section and a copy of the approvals shall be provided before final Certificate of Occupancy is issued. (Sides of Curb Ramps) shall be provided per the requirements 2010 ADA Standards October 26, Fire Code Compliance Checklist

5 S255 S260 S265 S266 S270 S273 S275 S280 S285 S290 S295 S300 S305 S310 S315 S320 S325 (Signage) shall be provided per the attached detail. "Van Accessible" shall be mounted immediately below the standard sign for van accessible spaces. Signs for Automobile accessible spaces shall be minimum of 60 inches to the bottom of the sign above finished grade per 2010 ADA Standards Place handicap signage detail on the plans. (A detail can be downloaded from our website at gwinnettfireplanreview.com under documents) Site Plan appears to be okay as submitted. (FYI)**ALL COMMENTS** Shall be addressed on plans, NO PERMITS will be issued if any comments are outstanding. (FYI) Permit fees for Civil Plans are payable at the time of final plan review (****check made payable to Gwinnett County****): Total $ Two (2) sets of complete site plans and One (1) CD are required for final plan approval. EACH PAGE OF THE PLANS SHALL BE IDENTIFIED ON THE CD AND MATCH THE PLANS. The plans on the CD shall bear the seal of an engineer. The CD should be in PDF format submitted in a jewel case. NOTE: Any revisions to the approved plans will require a revised CD for our records. (FYI) Please be advised that in order to keep our records current it has become standard procedure for the Engineering Plan Review Unit to purge files regularly. If there is no action toward addressing the review comments within the (6) month period following the initial review of this submittal, this review file will be discarded. (FYI) If the Structure only has restrooms and a pump room or storage room, no plan approvals or inspections are needed by this office. (FYI) Town Homes, separated by a (2) hour fire barrier, will be considered single family residential. This office requires no permits or inspections. (Permit Approvals and Inspections) are not required for this project by this office. Any (Accessible Route) with a running slope greater than 1:20 is a ramp and shall comply with 2010 ADA Standards (Slope & Rise) shall meet the requirements of 2012 ADA Standards 405.2, of having a running slope not steeper than 1:12 At least one (Accessible Route) complying with 2010 ADA Standards shall be provided within the boundary of the site from public transportation stops, accessible parking spaces, passenger loading zones if provided, and public streets or sidewalks, to an accessible building entrance. Place curb ramp detail on the drawings.(a detail can be downloaded from our website at gwinnettfireplanreview.com under documents) (Water Mains) in Single Family residential subdivisions shall be 8" or larger water mains with three-way hydrants spaced no more than 450 feet apart Gwinnett County Ordiance For Fire Protection And Life Safety, Section (a) (Water Main) size in in Multi-Family residential subdivisions shall be 8" inside diameter or larger water mains. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-37(b). Exception: Hose lays may be extenced to 500 feet in fire sprinklered projects. (Water Main) size in Industrial and Commercial developments shall be 12" diameter or larger with water mains installed with three-way fire hydrants, with a minimum of two 2 1/2 and one large diameter discharge nozzles, spaced no more than 300 ft along the street. Additional hydrants may be required to permit all portions, of all buildings, to be reached by hose lays not to exceed 400 ft by road travel.gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-37(c). October 26, Fire Code Compliance Checklist

6 S330 S335 S340 S345 S350 S355 S360 (FYI) The (Minimum Water Main) size, for Industrial & Commercial projects, shall be 8 '' from the point the main is tapped at the street until it ends. (FYI) The (Minimum Water Main) size may be 6 inch from the point the main is tapped until is ends, if the distance is not more than 50 feet. During construction and for permanent access, roadways width shall be 20 feet minimum per International Fire Code, and an un-obstructed vertical clearance of not less than 13 feet 6 inches Edition. Gwinnett County Ordinance For Fire Protection And Life Safety, Section 46-43(d). Provide (Minimum Vertical Clearance) of 114 inches at accessible passenger loading zones and along at least one vehicle access route to such areas from site entrance(s) and exit(s).at parking spaces complying with shall provide minimum vertical clearance of 98 inches at the parking space and along at least one vehicle access route to such spaces from site entrance(s) and exit(s) per 2010 ADA Standards (Clear Height) of access roadway shall be 13 ft. 6 in. minimum per International Fire Code, Chapter 5, Section , 2012 Edition. For every (6) six parking spaces or fraction of six accessible parking spaces required by to comply with 502, at least one shall be van parking space complying with 502. Per 2010 ADA Standard The (Minimum Clear Width) of an accessible route shall be 36 inches except at doors. If a person in a wheelchair must make a turn around an obstruction, the minimum clear width of the accessible route shall comply with 2010 ADA Standards **Exception, The clear width shall be permitted to be reduced to 32 inches minimum for a length of 24 inches maximum provided that reduced width segments are separated by segments that are 48 inches long mimnum and 36 inches wide minimum. S365 S370 October 26, Fire Code Compliance Checklist

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up) GWINNETT COUNTY Department of Fire & Emergency Services Office of the Fire Marshall S001 Access Aisle (Car) S005 S010 S015 S020 S025 S030 S035 S040 S045 S050 S055 S060 S065 S070 S075 S080 S085 Access Aisle

More information

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. North Operating Center 11945 SW 70 th Avenue Tigard, OR 97223 Phone:

More information

Fire & Life Safety Requirements For Fire Department Access and Water Supplies

Fire & Life Safety Requirements For Fire Department Access and Water Supplies Fire & Life Safety Requirements For Fire Department Access and Water Supplies This brochure is being provided as a resource only. The items listed inside are the requirements most generally cited on plans

More information

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,

More information

Louisville Metro Ordinance (Chapter 94: Fire Prevention) FIRE HYDRANTS, WATER MAINS AND WATER SUPPLY.

Louisville Metro Ordinance (Chapter 94: Fire Prevention) FIRE HYDRANTS, WATER MAINS AND WATER SUPPLY. Louisville Metro Ordinance (Chapter 94: Fire Prevention) To search for all Metro Ordinances, click here to be directed to American Legal Publishing's website. 94.82 FIRE HYDRANTS, WATER MAINS AND WATER

More information

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system

More information

TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions

TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition Chapter I General Provisions SECTION 1.1: TITLE. This Resolution shall be known as the Teton County Fire Protection Resolution

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

INTERIOR FINISH REVIEW

INTERIOR FINISH REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM I000 I001 I005 I010 I015 I020 INTERIOR FINISH Plans shall bear the seal of a licensed Architect currently registered with the State of Georgia are required for final

More information

FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE

FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE City of Conroe Fire Department Fire Marshal s Office 300 W. Davis 1 st Floor Conroe, Texas 77301 T: (936) 522-3080 F: (936) 522-3079 firecodes@cityofconroe.org FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2016-14 AN ORDINANCE AMENDING THE CODE OF ORDINANCES, CITY OF BOERNE, TEXAS, BY AMENDING CHAPTER 5 - BUILDINGS AND BUILDING REGULATIONS, ARTICLE VIII, LIFE & SAFETY CODE, SECTION 5-236; AND

More information

3.10 ROW Overlay District

3.10 ROW Overlay District 3.10 A. Purpose The purpose of this Overlay District is to regulate items which could be placed or constructed within the Rights-of-way lying wholly or partially within the jurisdictional area of the Town

More information

Site Plans. Fire Code Requirements

Site Plans. Fire Code Requirements Site Plans Fire Code Requirements Outline Before you start Critical building information drives requirements Access Requirements Access, aerial access, road design, remoteness, fire lanes, residential

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code

FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code One of the basic essentials needed to control and extinguish a structure fire is an adequate water supply.

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE FIRE LANES

MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE FIRE LANES MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE FIRE LANES This guide is intended to be a resource for when a building, structure, or facility, within the City of McKinney, is required to be provided with

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY

FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY This guide is intended to provide assistance in the application of the fire code in Unincorporated Multnomah County. October

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

Fire Sprinkler Submittal Requirements and Acceptance Testing

Fire Sprinkler Submittal Requirements and Acceptance Testing Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL SECTION: 4 POLICY NO.: 1257.1 DATE: April 1, 2006 PAGE: 1 SUBJECT: Fire Apparatus Access Road Standards for

More information

COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE

COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE DEPARTMENT CONTACT: York County Development Coordinating Center (c/o Bea McCarter) 1070 Heckle Boulevard, Suite 107 Rock Hill, South Carolina 29732 Phone

More information

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly. SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.

More information

FIRE PREVENTION CODE

FIRE PREVENTION CODE 164.01 Purpose 164.03 Amendments to Fire Prevention Code 164.02 Adoption of Fire Prevention Code 164.04 Board of Appeals 164.01 PURPOSE. The purpose of this chapter is to prescribe regulations governing

More information

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels DEPARTMENT OF PUBLIC SAFETY FIRE MARSHAL S OFFICE 9611 SE 36 TH ST Mercer Island, WA 98040 (206) 236-3515 direct; (206) 236-3622 FAX Rod Mandery, Fire Marshal Updated version: 03-19-2002 Fire & Life Safety

More information

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL SECTION: 4 POLICY NO.: 1258.1D DATE: September 11, 2006 PAGE: 1 SUBJECT: Fire Apparatus Access Road Standards

More information

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3

More information

To expedite the plan review and inspection processes, please refer to the information below.

To expedite the plan review and inspection processes, please refer to the information below. Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity

More information

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. North Operating Center 11945 SW 70 th Avenue Tigard, OR 97223 Phone:

More information

TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...

TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES... TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES... 4 SITE AND DEVELOPMENT PLAN REVIEW TURNAROUND TIMES... 4 DEVELOPMENT

More information

We have reviewed the proposed concept plans for Beehive Homes and have the following comments:

We have reviewed the proposed concept plans for Beehive Homes and have the following comments: 12800 Arbor Lakes Parkway, P.O. Box 1180, Maple Grove, MN 55311-6180 FIRE-RESCUE DEPARTMENT Fire Operations Fire Prevention 763-494-6300 763-494-6090 763-494-6421 Fax 763-494-6439-Fax August 22, 2018 RE:

More information

Orange Township Fire Department Fire Prevention Bureau

Orange Township Fire Department Fire Prevention Bureau Orange Township Fire Department Fire Prevention Bureau Under Ground Fire Protection Plan Submittal Checklist Project Name: Project Address: Date: Designers Name: Company Name: Phone Number: Email: Fax:

More information

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This

More information

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code SECTION 504 ACCESS TO BUILDING OPENINGS AND ROOFS 504.1 Required access. Exterior doors and openings required by this code or the International Building Code shall be maintained readily accessible for

More information

ALABAMA. Downloaded

ALABAMA. Downloaded Housekeeping/Laundry/Maintenance ALABAMA Downloaded 01.15.11 (e) Maintain an effective pest control program so that the facility is free of pests and rodents. In the laundry, provision shall be made to

More information

SITE PLAN REVIEW APPLICATION AND CHECKLIST

SITE PLAN REVIEW APPLICATION AND CHECKLIST SITE PLAN REVIEW APPLICATION AND CHECKLIST PROJECT SUMMARY: Project Name: City/ETA Location: City ETA (Application fee & number of copies needed are based on location) Property Location (Legal Description

More information

MULTI-LEVEL & COVERED BOOTH CONDITIONS

MULTI-LEVEL & COVERED BOOTH CONDITIONS MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the

More information

Construction and Development Guide

Construction and Development Guide Construction and Development Guide **Based on the 2014 Indiana Fire Prevention Code and relevant NFPA Codes and Standards ** Copyright 2018 Clay Fire CRRD 1 P a g e Table of Contents Map of Jurisdiction...

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

PLANNED DEVELOPMENT (MASTER PLAN & UNIT PLAN)

PLANNED DEVELOPMENT (MASTER PLAN & UNIT PLAN) Central Permit Center 555 Santa Clara Street Vallejo CA 94590 Business License Building Fire Prevention Planning Public Works 707.648.4310 707.648.4374 707.648.4565 707.648.4326 707.651.7151 PLANNED DEVELOPMENT

More information

SECTION POLICY MANUAL

SECTION POLICY MANUAL Menlo Park Fire Protection District Bureau of Fire Prevention and Life Safety 170 Middlefield Rd. Menlo Park, CA 94025 650-688-8425 Bureau of Fire Prevention and Life Safety SECTION 101.6 POLICY MANUAL

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES

More information

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954) TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida 33321 Telephone: (954) 597-3800, Fax: (954) 597-3810 SITE PLAN REVIEW CHECKLIST A goal of the Tamarac Fire

More information

PLAN REVIEW CHECKLIST

PLAN REVIEW CHECKLIST PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor

More information

VIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT Rustic Drive Pickerington, Ohio (614) Fax (614)

VIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT Rustic Drive Pickerington, Ohio (614) Fax (614) VIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT 12970 Rustic Drive Pickerington, Ohio 43147 (614) 575-5559 Fax (614) 575-5562 To: From: Subject: All Commercial Zoning and Building Permit Applicants Don Day,

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT

More information

Site Development Plan (SDP) Checklist

Site Development Plan (SDP) Checklist Development Services Department 100 N. Wilcox Street, Castle Rock CO 80104 303-660-1393 or CRGov.com Site Development Plan (SDP) Checklist A complete Site Development Plan (SDP) submittal will contain

More information

Construction & Development Procedures Guide

Construction & Development Procedures Guide Construction & Development Procedures Guide Updated December 2018 TABLE OF CONTENTS Welcome to Front Range Fire Rescue... 3 About This Guide... 3 Getting Started: Planning Approval and Building Permit

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Commercial Application/Plan Review Submittal Checklist

Commercial Application/Plan Review Submittal Checklist Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to

More information

City of Vista Fire Department

City of Vista Fire Department City of Vista Fire Department Development Services Section 600 Eucalyptus Avenue, Vista CA 92084 Guideline: Underground Piping for Private Fire Hydrants & Fire Sprinkler Supply. Updated: January, 2008

More information

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:

More information

OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805)

OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805) OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 REQUIREMENTS FIRE HYDRANT STANDARDS Fire hydrants and required access roads shall be provided prior to and

More information

Application for Site Plan Review

Application for Site Plan Review Application for Site Plan Review City of Pontiac Office of Land Use and Strategic Planning 47450 Woodward Ave, Pontiac, MI 48342 T: 248.758.2800 F: 248.758.2827 Property/Project Address: Sidwell Number:

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;

More information

Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Type A Units Accessibility Requirements rev.

Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Type A Units Accessibility Requirements rev. Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Units Accessibility s rev. 11/12/12 Unit 2005 CT State Building Code () A117.1 (2003) **indicates CT Amendment to

More information

Department of Planning & Development Planning Unit

Department of Planning & Development Planning Unit Department of Planning & Development Planning Unit Website: www.cityofmadison.com Madison Municipal Building 215 Martin Luther King, Jr. Boulevard P.O. Box 2985 Madison, Wisconsin 53701-2985 TDD 608 266

More information

CCCFPD RESIDENTIAL BUILDING REQUIREMENTS

CCCFPD RESIDENTIAL BUILDING REQUIREMENTS Coal Creek Canyon Fire Protection District P.O. Box 7187 Crescent Branch Golden, Colorado 80403 303-642-3121 Fax 303-642-1652 www.coalcreekcanyonfd.org CCCFPD@aol.com Dear Property Owner / Contractor:

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

FIRE PREVENTION GUIDELINE

FIRE PREVENTION GUIDELINE Title: Fire Escapes Number: FPG-07 Effective Date: 01/01/2008 Revised Date: 03/01/2009 Code References: California Fire Code (CFC), California Code of Regulations (CCR) Title 19, Merced Municipal Code

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

REQUIREMENTS & GUIDELINES

REQUIREMENTS & GUIDELINES SMALL CENTERS IN A RESIDENCE (6-12 Children) REQUIREMENTS & GUIDELINES Mecklenburg County Code Enforcement and the North Carolina Department of Health and Human Services Division of Child Development are

More information

Consumer Fireworks in Georgia

Consumer Fireworks in Georgia Consumer Fireworks in Georgia What are consumer fireworks? Most people call them: The Good Stuff An expert explanation: What are NOT consumer fireworks? (a) Model rockets and model rocket engines designed,

More information

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT Amendments for 2015 IFC CHAPTER 1 SCOPE AND ADMINISTRATION Section 101.2.1 Appendices. All appendices to be adopted Section 113.2 Schedule of permit fees. Is AMENDED to read: A fee for each permit shall

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 2017 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD SPECIAL EVENT PUBLIC ASSEMBLY PURPOSE This standard is applicable to any public event, exhibit space, booth, festival or any other similar

More information

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and

More information

P: Site Plan Approval

P: Site Plan Approval STAFF REPORT 2016-39P: Site Plan Approval Community Development Department Council Chambers, 7:30 PM, January 5, 2017 To: From: Re: Paul Luke, Plan Commission Chairperson Steve Marciani, AICP, Planning

More information

CITY OF CHESAPEAKE PUBLIC FACILITIES MANUAL CHAPTER XIII FIRE PROTECTION

CITY OF CHESAPEAKE PUBLIC FACILITIES MANUAL CHAPTER XIII FIRE PROTECTION CITY OF CHESAPEAKE PUBLIC FACILITIES MANUAL CHAPTER XIII FIRE PROTECTION I. INTRODUCTION A. The Fire Department s role in the development plan review process is to ensure that the effects of an emergency

More information

Summary Notes for a pre-application meeting for a proposed Cheddar s restaurant south of the southeast corner of East 104 th Avenue and Grant Street

Summary Notes for a pre-application meeting for a proposed Cheddar s restaurant south of the southeast corner of East 104 th Avenue and Grant Street City Hall City Development Department 9500 Civic Center Drive 303-538-7295 Thornton, Colorado 80229-4326 FAX 303-538-7373 www.cityofthornton.net Mark Rogers Chief Operating Officer Roaring Fork Restaurants

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

FIRE SERVICE FEATURES

FIRE SERVICE FEATURES CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

City of Los Angeles January FIRE PROTECTION

City of Los Angeles January FIRE PROTECTION ENVIRONMENTAL SETTING 2. FIRE PROTECTION Fire Protection Fire prevention, fire suppression, and life safety services are provided throughout the City of Los Angeles by the Los Angeles Fire Department (LAFD),

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

Fire Sprinkler System Design and Installation Requirements

Fire Sprinkler System Design and Installation Requirements Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah

More information

MONTECITO FIRE PROTECTION DISTRICT

MONTECITO FIRE PROTECTION DISTRICT Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic

More information

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: Contractors From: Charles Jenkins, Fire Marshal Subject: Contractor s Guide This guide is provided by the Fire Marshal as a service to the construction

More information

Certificate of Occupancy Application

Certificate of Occupancy Application Certificate of Occupancy Application Mailing Address: Town of Sunnyvale 127 North Collins Road Sunnyvale, Texas 75182 Phone: 972 203 4188 Project Information $50.00 permit fee Square Footage: Name/Description:

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

The Owner will provide the QEI inspection and certification services.

The Owner will provide the QEI inspection and certification services. General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

RED BOOK CONTRACTOR S. Fire Department Access and Design Engineering Information

RED BOOK CONTRACTOR S. Fire Department Access and Design Engineering Information RED CONTRACTOR S BOOK Fire Department Access and Design Engineering Information Orange County Fire Rescue Department An Accredited; Class One Department OFFICE OF THE FIRE MARSHAL David G. Kilbury, Fire

More information

ADA Checklist Transient Lodging, Hotels, Motels, Inns, Boarding Houses, Dormitories and similar facilities

ADA Checklist Transient Lodging, Hotels, Motels, Inns, Boarding Houses, Dormitories and similar facilities ADA Checklist Transient Lodging,, Motels, Inns, Boarding Houses, Dormitories and similar facilities 205 North 400 West Salt Lake City, Utah 84103 (800) 662 9080 (800) 550 4182 TTY www.disabilitylawcenter.org

More information

C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX

C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) 922-3210 - PHONE (951) 922-0318 - FAX CITY OF BANNING FIRE SERVICES STANDARD CONDITIONS OF APPROVAL FOR RESIDENTIAL BUILDINGS

More information

Fire Flow Requirements Standard

Fire Flow Requirements Standard Fire Flow Requirements Standard Scope This standard documents the requirements for fire flow within the Fresno County Fire Protection District (FCFPD). This includes areas that have a water purveyor who

More information