Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

Size: px
Start display at page:

Download "Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES"

Transcription

1 SUPPLEMENT 3 Fire Tests for Life Safety Code Users Marcelo M. Hirschler Editor s Note: This supplement is written to assist the reader in determining the applicability of fire test standards, especially those found in the Life Safety Code. Dr. Marcelo M. Hirschler is a fire safety consultant with GBH International. He chairs the NFPA Technical Committee on Hazard and Risk of Contents and Furnishings and the Advisory Committee on the Glossary on Terminology and is a member of various other NFPA technical committees, including the Technical Committee on Fire Tests. He is also active in the ASTM committee E05 on Fire Standards and in a number of other codes and standards arenas. FIRE PROPERTIES Fire test standards typically relate to two types of fire properties: fire resistance and reaction-to-fire. Fire resistance is associated with fire barriers and opening protection. Thus, fire resistance tests are concerned with preventing fire from penetrating into a compartment. Reaction-to-fire is associated with materials and products, including interior finishes, furnishings and contents. Reaction-to-fire tests are concerned with preventing the fire from causing damage, by minimizing or eliminating the release of heat, smoke, and combustion products or the spread of flame. Performancebased provisions related to fire modeling use primarily results of reaction-to-fire tests. Evaluating the level of performance or prescribed function offered by tested materials or assemblies requires an understanding of both the mechanics of a particular test and its limitations. Every test standard contains, in its scope and applicability, information explaining what it is supposed to do (namely what properties it measures) and for what type of materials it should be used. This is very important because it is a common error to use a test for the wrong material or to test for the wrong issue. A test that is commonly specified for an incorrect use is ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, originally identical to NFPA 255, Standard Method of Test of Surface Burning Characteristics of Building Materials. This is a test that is so extensively used in many codes (including the Life Safety Code ) that it is often specified for assessing fire properties it cannot measure or for testing materials that it should not be used with. ASTM E 84 is a reaction-to-fire test that is suitable to determine the flame spread index and smoke developed index of materials. Moreover, in order for a material to be suitable for this test, the material must, by its own structural quality or the manner in which it is applied, be capable of supporting itself in position or of being supported in the test apparatus. This test has often been specified, incorrectly, to obtain results on properties like fire resistance (which should be measured using NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials), or to determine whether a material is noncombustible (which should be assessed with a test like ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C), or whether it is limited combustible (which is determined by testing in accordance with NFPA 259, Standard Test Method for Potential Heat of Building Materials). See also the discussion on combustibility fire testing below. Other misapplications 1181

2 1182 Supplement 3 Fire Tests for Life Safety Code Users include using the test for products, such as furniture, that cannot be physically placed in the apparatus, or for materials that cannot be supported in the apparatus throughout the test. Many of the tests referred to in the Life Safety Code have equivalent counterparts administered by other standards-writing organizations such as the American Society for Testing and Materials (ASTM) and Underwriters Laboratories (UL). In recent years all three organizations have withdrawn some of their standards for harmonization purposes. Section 1.4 of the Life Safety Code permits the application or use of equivalent alternatives. Alternatives could include fire test documents different from those specified, or different test protocols if the proper technical documentation is provided to demonstrate equivalency between the tests and verify that the alternative approach fulfills the intended purpose of the applicable code requirement. The 2009 edition of the Life Safety Code officially recognizes the technical equivalence of ASTM and UL standard test methods to the corresponding NFPA test methods: ASTM E 119 and UL 263 for NFPA 251, ASTM E 2074 and UL 10B for NFPA 252 (both sets of fire resistance tests) and ASTM E 84 and UL 723 for the uses where NFPA 255 was previously required, ASTM E 648 for NFPA 253, ASTM E 108 and UL 790 for NFPA 256, ASTM E 1352 for NFPA 261, and ASTM E 1353 for NFPA 260 (all sets of reactionto-fire tests). See Table S3.1. Table S3.1 Fire Test Standards NFPA ASTM UL 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials 252, Standard Methods of Fire Tests of Door Assemblies 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source 255, Standard Method of Test of Surface Burning Characteristics of Building Materials (proposed for withdrawal) 256, Standard Methods of Fire Tests of Roof Coverings (withdrawn) E 119, Standard Test Methods for Fire Tests of Building Construction and Materials1 E 2074, Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies (replaced ASTM E 152, withdrawn) E 648, Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source E 84, Standard Test Method for Surface Burning Characteristics of Building Materials E 108, Standard Test Methods for Fire Tests of Roof Coverings 263, Standard for Fire Tests of Building Construction and Materials 10B, Standard for Fire Tests of Door Assemblies 723, Standard for Test for Surface Burning Characteristics of Building Materials 790, Standard for Standard Test Methods for Fire Tests of Roof Coverings 257, Standard on Fire Test for Window and Glass Block Assemblies 258, Recommended Practice for Determining Smoke Generation of Solid Materials (withdrawn) 259, Standard Test Method for Potential Heat of Building Materials 260, Standard Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture 261, Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes E 2010, Standard Test Method for Positive Pressure Fire Tests of Window Assemblies (replaced ASTM E 163, withdrawn) E 662, Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials E 1353, Standard Test Methods for Cigarette Ignition Resistance of Components of Upholstered Furniture E 1352, Standard Test Method for Cigarette Ignition Resistance of Mock-Up Upholstered Furniture Assemblies 9, Standard for Fire Tests of Window Assemblies 2009 Life Safety Code Handbook

3 Fire Properties 1183 Table S3.1 Continued NFPA ASTM UL 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces 263, Standard Method of Test for Heat and Visible Smoke Release Rates for Materials and Products (withdrawn) 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile Coverings on Full Height Panels and Walls 266, Standard Method of Test for Fire Characteristics of Upholstered Furniture Exposed to Flaming Ignition Source (withdrawn) 267, Standard Method of Test for Fire Characteristics of Mattresses and Bedding Assemblies Exposed to Flaming Ignition Source (withdrawn) 268, Standard Test Method for Determining Ignitibility of Exterior Wall Assemblies Using a Radiant Heat Energy Source 269, Standard Test Method for Developing Toxic Potency Data for Use in Fire Hazard Modeling 270, Standard Test Method for Measurement of Smoke Obscuration Using a Conical Radiant Source in a Single Closed Chamber 271, Standard Method of Test for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter 272, Standard Method of Test for Heat and Visible Smoke Release Rates for Upholstered Furniture Components or Composites and Mattresses Using an Oxygen Consumption Calorimeter (withdrawn) 285, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing Wall Assemblies Containing Combustible Components E 906, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products E 1537, Standard Test Method for Fire Testing of Upholstered Furniture E 1590, Standard Test Method for Fire Testing of Mattresses E 1678, Standard Test Method for Measuring Smoke Toxicity for Use in Fire Hazard Analysis E 1822, Standard Test Method for Fire Testing of Stacked Chairs E 1995, Standard Test Method for Measurement of Smoke Obscuration Using a Conical Radiant Source in a Single Closed Chamber, with the Test Specimen Oriented Horizontally E 1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter 910, Standard for Safety Test for Flame- Propagation and Smoke-Density Values for Electrical and Optical-Fiber Cables Used in Spaces Transporting Environmental Air (withdrawn) 1715*, Standard for Fire Test of Interior Finish Material 1056, Standard for Safety Fire Test of Upholstered Furniture (withdrawn) 1895, Standard for Safety Fire Test of Mattresses (withdrawn) (continues) Life Safety Code Handbook 2009

4 1184 Supplement 3 Fire Tests for Life Safety Code Users Table S3.1 Continued NFPA ASTM UL 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth 287, Standard Test Methods for Measurement of Flammability of Materials in Cleanrooms Using a Fire Propagation Apparatus (FPA) 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire Resistance Rated Floor Systems 289, Standard Method of Fire Test for Individual Fuel Packages 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films 705, Recommended Practice for a Field Flame Test for Textiles and Films E 2058, Standard Test Methods for Measurement of Synthetic Polymer Material Flammability Using a Fire Propagation Apparatus (FPA) D 568, Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Flexible Plastics in a Vertical Position) (withdrawn) D 1929, Standard Test Method for Ignition Properties of Plastics D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C E 162, Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops E 1529, Standard Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies E 1623, Test Method for Determination of Fire and Thermal Parameters of Materials, Products, and Systems Using an Intermediate Scale Calorimeter (ICAL) E 1966, Standard Test Method for Fire- Resistive Joint Systems E 2257, Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies 1715*, Standard for Fire Test of Interior Finish Material 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes 214, Standard for Safety Tests for Flame- Propagation of Fabrics and Films (withdrawn) 1479, Standard for Fire Tests of Through- Penetration Firestops 1709, Standard for Rapid Rise Fire Tests of Protection Materials for Structural Steel 2079, Standard for Tests for Fire Resistance of Building Joint Systems Note: This table contains NFPA fire test standards and those fire test standards from other organizations, ASTM and UL, that are either similar to NFPA fire test standards or relevant to the Life Safety Code. *UL 1715 is different from both NFPA 265 and NFPA 286, but is a room-corner fire test, normally used for the same purposes as those other tests. That is, it assesses the fire behavior of an interior finish material in a full-scale scenario. See the section on interior wall and ceiling finish later in this supplement. UL 1975 is similar but not identical to NFPA 289 but can be used for the same applications Life Safety Code Handbook

5 Fire Resistance Testing 1185 FIRE RESISTANCE TESTING Buildings or structures occupied or used in accordance with the individual occupancy chapters of the Life Safety Code (Chapters 11 through 43) are required to meet the minimum construction requirements of those chapters. NFPA 220, Standard on Types of Building Construction, 1 is referenced in Chapter 8 of the Life Safety Code. It describes the types of building construction (that is, construction classifications) and the fire resistance ratings applicable to each construction element for each type of building. The fire test to be used to assess fire resistance ratings of elements of building construction is NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials. See also Table S3.1 for alternative similar fire test methods. NFPA 251 (also referenced primarily in Chapter 8) applies to assemblies of masonry units, composite assemblies of structural materials for buildings (including interior and exterior bearing and other walls and partitions, columns, girders, beams, slabs, and composite slab and beam assemblies for floors and roofs), as well as other assemblies and structural units that constitute permanent integral parts of a finished building. The fire test has specific testing criteria for each type of assembly. Fire barriers, or fire barrier assemblies, are intended to be used as separation barriers or to provide protection of building elements from the effects of fire for a given time as required by Chapter 8, Features of Fire Protection. It is important to note that a fire resistance rating applies to the entire assembly as tested. A fire resistance rating is never assigned to an individual material or product; rather it represents the composite performance of an assembly including all of the components and the specific construction details of the rated assembly. NFPA 251 exposes one side of an assembly (construction element), except for columns and beams, to a standard time-temperature curve (as shown in Exhibit S3.1) inside a furnace leaving the other side unexposed. This is known as a time-temperature curve because the test method specifies the temperature that needs to be measured in the furnace at each point in time. The furnace used must be capable of providing the prescribed temperatures over a given period of time, by following the time-temperature curve shown in Exhibit S3.1. The test method provides criteria for assessing how long (in hours or minutes) it takes for heat to penetrate each assembly and reach an unacceptable temperature rise on the unexposed side or protected element, and how long it takes for the flame or hot gases penetrating through the assembly to ignite cotton waste placed on the unexposed side, during the test. The fire resistance rating will be the time at which the first of the failure criteria is reached, as assessed either by the transmission of heat, the passage of hot gases sufficient to ignite cotton waste, or by structural collapse of the test specimen assembly. The temperature rise failure criterion on the unexposed side is 250 F (140 C) above the test specimen s initial temperature for walls and partitions. For load bearing elements, the test also monitors the load carrying capability of the test specimen during the test exposure. When required, the fire exposure is followed by the application of a specified standard fire hose stream. If the assembly to be evaluated will be used as a load-bearing element, the test is conducted with a load placed on the assembly, to evaluate the load-bearing capacity of the assembly. Some construction assemblies are simply intended to limit the transmission or temperature and/or flames to the unexposed surface. On the other hand, many construction assemblies, such as beams and columns, and floor and roof assemblies, must also sustain an applied load for a pe- Temperature (deg F) Temperature (deg C) Exhibit S3.1 Standard timetemperature curves for NFPA 251/252 and for NFPA Time (minutes) NFPA 251/252 F NFPA 257 F NFPA 251/252 C NFPA 257 C Life Safety Code Handbook 2009

6 1186 Supplement 3 Fire Tests for Life Safety Code Users riod of time equal to the desired fire resistance rating, and must therefore be tested under the relevant applied load. Walls and partitions are thus permitted to be tested either with load or without. Depending on the structural design of the assembly, certain levels of temperature must not be exceeded at any one point, or an average temperature cannot be exceeded, with temperature limitations ranging from 800 F to 1300 F (427 C to 704 C). An alternative test exists for structural steel columns, whereby the column is not loaded during the test. The test measures the ability of the added protection to control the transmission of heat through the specimen during the specified period of fire exposure. The average temperature of the steel in such columns must not rise above 1000 F (538 C), and the temperature in any one of the measured points cannot exceed 1200 F (649 C). In many cases, the assembly is also subjected to a hose stream test. The use of such a test was inspired by the interest in simulating the effect of water hoses used by emergency personnel to fight fires; in fact, however, the hose stream test itself is not intended to simulate that effect. If required to pass a hose stream test, an assembly with a fire rating of 1 hour or more would have to survive exposure to a hose stream test for half the period of its fire resistance rating, but not for more than 1 hour. When the condition of acceptance requires a hose stream test, after the fire resistance rating has been established, a duplicate assembly is exposed in the furnace to the time-temperature curve for the period required by the hose stream test conditions, then removed from the furnace and immediately subjected to the hose stream test. The hose stream is delivered under pre-set conditions (based on a certain hose, play pipe nozzle, distance from the test specimen, nozzle pressure, and test duration). The hose stream is applied in a specific pattern to fully develop the effects of impact, cooling, and erosion on the entire test specimen. The specimen must withstand the hose stream test such that no openings are created that would permit projection of water from the hose stream beyond the unexposed surface. Further information on specific testing criteria and testing limitations can be found in NFPA 251, which should be consulted before making any firm decisions about the applicability of certain tests, or testing of certain assemblies. Other fire resistance tests used by the Life Safety Code are NFPA 252, Standard Methods of Fire Tests of Door Assemblies; NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies; NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire Resistance Rated Floor Systems; and ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops. All of these tests use basically the same standard time-temperature curve that NFPA 251 uses (except that the curve in NFPA 257 includes more detail over the short initial time periods; see Exhibit S3.1). However, there are also some differentiating characteristics, which are related to the products being tested. NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2 contains installation requirements for all types of fire doors and windows, and thereby regulates the installation and maintenance of assemblies and devices used to protect openings in walls, floors, and ceilings against the spread of fire and smoke within, into, or out of buildings. NFPA 80 is extensively referenced in the Life Safety Code, especially in Chapter 7 (Means of Egress) and Chapter 8 (Features of Fire Protection). Building Products Fire Doors. Door assemblies in fire barriers must be tested according to NFPA 252, Standard Methods of Fire Tests of Door Assemblies (see also Table S3.1 for alternative similar fire test methods). NFPA 252 provides methods for measuring the relative performance of fire door assemblies where subjected to a prescribed fire test exposure followed by a prescribed hose stream application, using the same time-temperature curve as NFPA 251 (see Exhibit S3.1). The fire door assembly must be tested as a complete assembly, because the effectiveness of the opening protective depends on a satisfactory performance of the entire door assembly, which consists of the door, door frame, and associated hardware. In NFPA 252, the fire door assembly specimen is mounted in a furnace wall and exposed to the standard time-temperature curve. The door assembly is not permitted to develop gaps or openings through the assembly, nor is flaming permitted to occur on the unexposed surface of a door assembly during the first 30 minutes of the fire resistance-rating period, although some intermittent light flames no greater than 6 in. (150 mm) are permitted for periods not exceeding 10-second intervals. After that 30-minute period, intermittent flames are permitted to occur along the edges of the unexposed surface area of the door, if they do not exceed 5 minutes and are no greater than 6 in. (150 mm). For doors having a fire protection rating of 45 minutes or greater, flames not greater than 6 in. (150 mm) in length are permitted to occur on the unexposed surface area of the door during the last 15 minutes of the fire protection rating period during the fire test, provided such flaming is contained within a distance of 1 / 2 in. (38 mm) from the vertical edge and 3 in. (76 mm) from the top edge of the door or frame of the vision panel. When the door hardware is also evalu Life Safety Code Handbook

7 Fire Resistance Testing 1187 ated for use on fire doors, it must keep the door in a closed position for an exposure period of 3 hours. The latch bolt must remain projected and be intact after the fire exposure test. Note the absence of any criterion addressing temperature transmission to the unexposed side. The fire doors must usually also be exposed to a hose stream test, which subjects the test assembly to the impact, erosion, and cooling effects of the hose stream, immediately following the fire resistance test. The hose stream is directed at the middle and then at all parts of the exposed surface, slowly making changes in direction. However, certain provisions within the Life Safety Code provide for the installation of door assemblies having a fire protection rating of 20 minutes without the hose stream test. One must carefully evaluate the particular requirements associated with the opening protective so that it satisfies the minimum acceptable criteria. A modern trend within code-writing organizations is to require certain applications of fire door assemblies (typically side-hinged and swinging doors) to be tested under a positive pressure scenario. This provision requires that the door assemblies be tested with a neutral pressure plane located 40 in. (1015 mm) above the finished floor. NFPA 252 does not stipulate the height of the neutral plane but records the height in the test results. This permits the test standard to accommodate the many gradients of pressure planes at which a furnace can be operated. The test report document issued following a classification test records the location of the neutral pressure plane to which the door assembly has been tested. The Life Safety Code does not stipulate the minimum required height of the neutral pressure plane for testing the door. If a neutral plane is not established along the height of the test specimen, then it is assumed that the door will be tested under normal testing procedures, which is running the furnace at near atmospheric pressure. This would establish the neutral pressure plane at the top of the door assembly. It is generally recognized that, if a lower neutral pressure plane is established on the door assembly within the furnace, then the test could be considered to be more severe. A door tested under a positive pressure should be accepted as meeting the requirements established for a door tested at atmospheric pressure. Listing agencies have different approaches on how to list and label doors being tested under positive pressure. Additional information associated with these criteria can be found in NFPA 80, Standard for Fire Doors and Other Opening Protectives, which should be consulted for the installation requirements associated with all types of fire doors. Fire protection rating is the appropriate term for the fire resistance associated with an opening protective as detailed in NFPA 252 (for fire doors) and in NFPA 257 (for fire window assemblies). Fire resistance rating is the appropriate term for use with a fire barrier, such as used in walls or floors. In the Life Safety Code and NFPA 5000, Building Construction and Safety Code 3, the technical committees have been very careful to use each term appropriately and consistently. However, there are fire doors and glazing assemblies that have a fire resistance rating by virtue of the fact that they were tested using NFPA 251; in that case the code does not consider them to be opening protectives. Fire Window Assemblies. Fire window assemblies are permitted to be used in fire barriers having a fire resistance rating of one hour or less if they have a fire protection rating of 45 minutes and represent up to 25 percent of the fire barrier. Fire windows must be tested in accordance with NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies (see also Table S3.1 for alternative similar fire test methods and Exhibit S3.1 for the time-temperature curve). The NFPA 257 test method is intended to evaluate the ability of a window or other light-transmitting assembly to remain in an opening during a predetermined test exposure period. Recent editions of NFPA 257 have no references to a particular time limit for testing, and time-temperature guidelines are included for up to 3 hours. Earlier editions limited testing to 45 minutes, but now the test is permitted to be run for the length of time a test sponsor requests. The period of time is then recorded on the appropriate test records. A testing time limit is no longer relevant because new materials and technology exist for window assemblies that will permit increased exposure times and maintain the integrity of the fire barriers in which they are installed. Note that, just as in NFPA 252, there is no criterion addressing temperature transmission to the unexposed side. Discussions are continuing on the amount of radiant heat permitted to transfer through the window assembly to the unexposed side of the window. Currently, the radiant heat transferred is not required to be recorded. A test procedure is available to measure this radiant heat flux and is detailed in Annex C of NFPA 257, with some additional information on radiant heat transmissions in Annex B. The conditions associated with radiant energy could be considered as a factor in the application of a fire-modeling program that might have an occupant passing by such opening protectives, or could, in principle, be used as pass/fail criteria. All considerations and applications for a material s particular use should be reviewed with the limitations of the test results in mind. In NFPA 257, the test specimen is mounted in a furnace wall and exposed to the standard time-temperature curve. A window assembly is considered to have Life Safety Code Handbook 2009

8 1188 Supplement 3 Fire Tests for Life Safety Code Users met the requirements for acceptable performance if it remains in the opening during the fire resistance and hose stream tests, within the following five criteria: 1. No flaming shall occur on the unexposed surface of the assembly. 2. There shall be no separation of the glazing material edges from the glazing frame that creates openings. 3. At the perimeter of operable components, movement from the initial closed position shall not exceed the thickness of the frame member at any point. 4. The window assembly shall not move away from the wall to the extent that an opening is created. 5. There shall be no openings in the window assembly. Exhibits S3.2 and S3.3 represent two views of an assembly that has been exposed to both the fire resistance and the hose stream tests. As with fire doors, fire windows are installed in accordance with the provisions of NFPA 80, Standard for Fire Doors and Other Opening Protectives, which should be consulted for the installation requirements associated with all types of fire windows. NFPA 80 includes limitations on the size and total area permitted for the glazing material installed in fire window assemblies, and also requires that each individual glazing unit have a label that is visible after installation. Also, in NFPA 80, fire window assemblies having a rating of 20 minutes or 30 minutes are limited to the size that has been tested. A window protection of 45 minutes is limited to the maximum area tested and must have no exposed area of individual glazing material exceeding 1296 in. 2 (0.84 m 2 ) and no dimension exceeding 54 in. (1370 mm), unless it has been specifically tested with dimensions in excess of those values. Glazing is currently available that has been tested with dimensions exceeding that size limitation. One should review the appropriate listing associated with the protection rating given to a fire window assembly. Many types of glazing materials are being introduced into the market, and several types of fire-rated glazing products (including wired glass) can satisfy the acceptance criteria of NFPA 257. Nonsymmetrical fire protection rated glazing systems are tested with each face exposed to the furnace, and the assigned fire protection rating is that of the shortest duration obtained from the two tests conducted. It is important that the installation and testing limitations be reviewed for the particular installation. Technological advances within the glazing industry have provided systems using fire-resistant glazing Exhibit S3.2 Unexposed side of window assembly after fire exposure and hose stream application. Exhibit S3.3 Exposed side of window assembly after fire exposure and hose stream application Life Safety Code Handbook

9 Fire Resistance Testing 1189 materials that are actually fire barrier walls. These glazing walls would have been tested in accordance with NFPA 251 and satisfy the particular pass/fail criteria for fire barriers. The pass/fail criteria include a limitation in the temperature rise on the unexposed side of the test specimen, and a successful hose stream application. The installation requirements and limitations for these glazing wall assemblies would be highlighted in the applicable listing requirements and the manufacturers specifications. This type of glazing would not be required to comply with the installation requirements, because it is not considered an opening protective device. Through-Penetrations. Generally, when fire barriers are tested for a particular hourly rating, these assemblies are tested without any penetrations. It is recognized that within a building these fire barriers will have various penetrations for building services, utilities, and other applications. Penetrations of fire barriers require the appropriate protection by devices or materials that have been tested and listed for that particular application to maintain the fire barrier s integrity. In this edition of the Life Safety Code (see and ), through-penetration and membrane penetrations for cables, cable trays, conduits, pipes, tubes, combustion vents, exhaust vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a wall, floor, or floor/ceiling assembly constructed as a fire barrier are required (rather than recommended) to be protected by a firestop system or device, and must be tested in accordance with ASTM E 814, Standard Method for Fire Tests of Through-Penetration Fire Stops, which establishes the testing protocols for through-penetrations. Penetrations of a rated assembly that require special consideration are usually tested using a recognized test procedure based on the standard time-temperature curve, normally that contained within ASTM E 814. Additional information can be found in documents published by the individual listing agencies for assemblies that have been tested for specific fire ratings. The ASTM E 814 test protocol establishes F and T ratings as one part of the acceptance criteria for through-penetration systems. The F rating signifies the ability of the penetrating firestop system to withstand a prescribed fire test for a period of time without permitting the passage of flame through the opening or the occurrence of flaming on any element of the unexposed side of the penetrating firestop system. The T rating relates to the transmission of heat through the penetrating firestop system for a given period of time. An acceptable T rating is one that limits the rise of the temperature on the unexposed surface of the penetrating firestop system or penetrating item to no more than 325 F (181 C) above the initial temperature, and for which there is no flame occurrence on the unexposed side. The penetrating firestop is exposed to the same fire test conditions created by the time-temperature curve in NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials. The Life Safety Code; NFPA 5000, Building Construction and Safety Code; NFPA 221, Standard for High-Challenge Fire Walls, and Fire Barrier Walls; 4 and other codes require that the penetrating firestop be under a minimum positive pressure differential of 0.01 in. of water (2.5 Pa) at the location of the penetrating item. This positive pressure must be maintained for the duration of the time for which it is being tested. The penetrating firestop system must be tested for the same time period as that of the fire barrier in which it is installed. The penetrating firestop system must also be subjected to the effects of an applied hose stream test. Joints. Joints used in the construction of fire barriers can include expansion, seismic, and control joints. These joints are tested at their maximum joint width in accordance with NFPA 251. The test includes joints to their full height or length of the test assembly. The fireresistive joint system tested must include a splice or a method of connecting two or more lengths of the joint system. The test must be conducted so that the joint system is tested under a minimum positive pressure differential of 0.01 in. of water (2.5 Pa) for the total time of the test. There is an exception for expansion or seismic joints designed to prevent the penetration of fire and shown to have a fire resistance rating of not less than the required fire resistance rating of the floor when tested in accordance with ANSI/UL 2079, Test of Fire Resistance of Building Joint Systems (see of NFPA 101). Fire-resistive joint systems that are designed to accommodate movement must be preconditioned by cycling under the conditions of ASTM E 1399, Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems. 5 Fire Dampers. Chapter 7, Means of Egress, states that fire barriers forming horizontal exits shall not be penetrated by ducts, unless such ducts are existing penetrations protected by fire dampers approved and listed for the particular application. Fire dampers are tested either for static systems, where the HVAC system is automatically shut down in the event of a fire, or for dynamic systems, where the HVAC system does not shut down. Fire dampers used in dynamic systems are Life Safety Code Handbook 2009

10 1190 Supplement 3 Fire Tests for Life Safety Code Users investigated for closure under their maximum recommended airflow. Fire dampers are tested in accordance with ANSI/UL 555, Standard for Fire Dampers. Fire dampers used in rated fire-resistive floor-ceiling and roof-ceiling assemblies are tested in accordance with ANSI/UL 555C, Standard for Ceiling Dampers. The fire dampers are tested in assemblies under the conditions of the fire exposure of the same time-temperature curve as in NFPA 251. The ANSI/UL standards provide the acceptance criteria in regard to the flaming on the unexposed side, closing time of the damper, air leakage, if applicable, and hose stream application. It should be noted that fire dampers are not tested for the limitation of heat transmission through the fire damper assembly. This particular condition is recognized in the requirements of NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 6 associated with the limitation on the number of fire dampers permitted to be installed in a vertical duct that has multiple floor penetrations. Smoke Dampers. Paragraph discusses the use of smoke dampers. Where a smoke barrier is penetrated by a duct or air transfer opening, a smoke damper designed and tested in accordance with the requirements of ANSI/UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems, must be installed. Where a smoke barrier is also constructed as a fire barrier, a combination fire/smoke damper designed and tested in accordance with the requirements of both ANSI/UL 555S and ANSI/UL 555 must be installed. Floor Fire Doors. Paragraph regulates floor fire doors. It states that floor fire door assemblies shall be tested in accordance with NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire Resistance Rated Floor Systems, and shall achieve a fire resistance rating not less than the assembly being penetrated. It also states that floor fire door assemblies shall be listed and labeled for the application. The time-temperature curve in NFPA 288 is the same as that in NFPA 251, but there is no required hose stream test. The transmission of heat through the specimen during the fire resistance rating period shall not raise the average temperature on its unexposed surface more than 250 F (139 C) above its initial temperature. Additionally, a temperature rise of 325 F (181 C) shall not be exceeded at any one point. Critical Test Limitations of Fire Resistance Tests Although test assemblies have been rated for a specific period using a fire resistance test, it must be recognized that the test is only intended to be a comparative test. Therefore, under actual field conditions, some assemblies fail prematurely and others remain in place longer than expected. The simulated test exposure used in the test protocol was established around 1920; it represents one level of fire severity considered to be a typical office building scenario of that era. Research continues to determine whether the varying types of fuel loads found in more modern occupancies would require a different type of time-temperature curve. Such research is always ongoing and differing opinions are expressed by various investigators. It is worth mentioning, however, that the time-temperature curve from the test used by European countries for assessing fire resistance, namely ISO 834, Fire-resistance tests Elements of building construction, 7 is very similar to that in NFPA 251. Currently, discussions are ongoing regarding the application of particular fire modeling programs to predict the results of testing of assemblies, as well as what the pass/fail criteria should be. An ASTM standard guide, ASTM E 2032, Standard Guide for Extension of Data from Fire Resistance Tests Conducted in Accordance with ASTM E 119, has been issued to address the extension of fire resistance results obtained from fire tests performed in accordance with NFPA 251 or ASTM E 119 to constructions that have not been tested. The guide is based on principles involving the extension of test data using simple considerations. The acceptance of these principles and their application is on a worst-case scenario. It is always important to remember that new materials may present unforeseen issues that will need to be resolved. A good example is the recent understanding that high-strength concrete can cause explosive spalling to occur at relatively low temperatures. This finding could have an adverse effect on the fire protection properties assumed for a construction element using such materials. Another area of concern for the fire resistance of a test assembly is its integrity, or the protection of through-penetrations. The test criteria in NFPA 251 do not address conventional openings found in assemblies, such as those needed for incorporation of electrical receptacles, or penetrations by electrical wires, cables or raceways, plumbing pipes, utility services, and construction joints, unless they have been specifically tested as part of the assembly. All penetrations require special review and consideration. A source for evaluating certain penetrations permitted in rated assemblies is found in the introduction of the UL Fire Resistance Directory. 8 This document addresses the hourly ratings for beams, floors, roofs, columns, walls, and partitions. Its design information section provides in Life Safety Code Handbook

11 Reaction-To-Fire Testing 1191 formation pertaining to the different penetrations found in rated assemblies and the required protection or limitations. The publication Guideline on Fire Ratings of Archaic Materials and Assemblies, by Robert Brady Williamson, Cecile Grant, Joseph Zicherman, Fred Fisher, Harry Hasegawa, Herman Spaeth, Harriet Watson, Vytenis Babrauskas, and Norman Kornsand, for the National Institute of Building Sciences for the Department of Housing and Urban Development, contains information on construction materials typical of an earlier time, generally prior to It contains data on fire resistance and reaction-to-fire, including flame spread, smoke production, and degree of combustibility. The information has also been included in NFPA 914, Code for Fire Protection of Historic Structures, 9 as Annex O. REACTION-TO-FIRE TESTING Major Properties and Products Interior finish as it relates to the Life Safety Code refers to the exposed interior wall surfaces, exposed interior ceiling finishes, and exposed interior floor finishes. The reaction-to-fire properties associated with the regulation of interior wall and ceiling finish are flame spread and smoke development in a traditional standard test (ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials; see also Table S3.1 for alternative similar fire test methods). Alternatively, in a room-corner test or in a specialized large-scale test, the reaction-to-fire properties associated with wall and ceiling finish are heat and smoke release and flame propagation (potentially leading to flashover). The reaction-to-fire properties associated with interior floor finish are ignition characteristics (in accordance with ASTM D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials) and critical radiant flux (in accordance with NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source; see also Table S3.1 for alternative similar fire test methods). These provisions should not be associated or confused with fire resistance ratings. As discussed above, the properties associated with interior finish are reaction-to-fire properties and not fire resistance properties. They refer to the ability of a material to contribute to overall fire and smoke growth and spread. An interior finish classification should also not be compared or confused with a material s combustibility or the degrees of combustibility. Interior Wall and Ceiling Finish. There are two types of approaches being used to evaluate interior wall and ceiling finishes. Each use of a material for a particular application of interior finish needs to be coordinated with the appropriate testing procedure, and each interior finish testing method has a specific scope and application. There is a possibility that a single product could be used in different applications and be tested using different fire test methods. The end use application must be identified, because that knowledge stipulates the appropriate test method and applicable results. Steiner Tunnel Test. The traditional approach to testing interior wall and ceiling finish for use within a code involves ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, a test conducted in a piece of equipment known as the Steiner tunnel. Depending on occupancy and use within the occupancy, the Life Safety Code limits the use of interior wall and ceiling finish materials to minimize flame propagation and smoke development on the exposed wall and ceiling surfaces. This approach consists of evaluating the flame spread over the surface of a material, and the smoke developed, when the material is exposed to a prescribed gas-fed fire. The Life Safety Code provides, in , three classifications for interior finish, based on a flame spread index (FSI) and a smoke development index (SDI), as tested in accordance with ASTM E 84 (see also Table S3.1 for alternative similar fire test methods). The classifications (with their corresponding flame spread index and smoke development index values) are shown in Table S3.2. The flame spread index and the smoke development index both reflect the comparative fire-test response of a material when compared with two established benchmarks: a 1 / 4 in. (6.3 mm) thick inorganic reinforced cement board (assigned both an FSI and an SDI of 0) and a nominal 25 / 32 in. (19.8 mm) select grade red oak flooring board (assigned both an FSI and an SDI of 100). The FSI is a comparative nondimensional figure and does not directly represent a flame speed, flame velocity, or flame propagation. The SDI is also a comparative nondimensional figure and does not directly represent optical density or smoke release rate. Table S3.2 Flame Spread Index (FSI) and Smoke Development Index (SDI) Values for Interior Wall and Ceiling Finish Classifications Class FSI SDI Class A Class B Class C The testing apparatus used in ASTM E 84 is shown in Exhibits S3.4 and S3.5. The specimens are required to be at least 20 in. (508 mm) wide by 24 ft (7.3 m) long Life Safety Code Handbook 2009

12 1192 Supplement 3 Fire Tests for Life Safety Code Users A Fire end Air-inlet port for air supply, 76.2 ± 1.6 mm (3 in. ± in.) Adjustable air-intake shutter 7.62 m (25 ft) length of test chamber Draft gauge connection B A B Gas burner for ignition fire 0.30 m (1 ft) 1372 ± 127 mm 4.11 m (13 ft 0 in.) (54 in. ± 5 in.) 448 mm ± 9.5 mm ( in. ± in.) mm ± 12.7 mm (12 in. ± 0.5 in.) Insulated gradual rectangularto-round sheet-metal vent pipe Thermocouple Vent end Photoelectric cell 4.88 m (16 ft) min. Manometer draft-gauge connection 6.40 m (21 ft) Thermocouples min. from 3.2 mm (¹ ₈ in.) from surface vent end Access for 12.2 m (40 ft) max. velocity measurements Automatically 406 mm (16 in.) inside diameter controlled damper 50.8-mm (2-in.) min. high-temperature mineral-composition material C C To induceddraft system Light source Section A-A Section C-C Exhibit S3.4 Schematic diagram of tunnel test apparatus used to characterize the surface burning of materials. Liquid seal Removable metal-and-mineral composite top panel 6.4-mm (0.25-in.) mineral-fiber/cement board 3-mm (0.125-in.) fibered glass belting Water-cooled structural-steel tube mm ± 9.5 mm ( in. ± in.) 305 mm ± 12.7 mm (12 in. ± 0.5 in.) ± 12.7 mm (4.0 ± 0.5 in.) Panes Double-pane observation window, 70 ± 6 by mm (2.75 ± 0.25 by in.) 127.0±12.7 mm (5.0 ± 0.5 in.) Fire brick mm x mm x 63.5 mm (9.0 in. x 4.5 in. x 2.5 in.), max. temp C (2600 F) 19 mm (0.75 in.) Exhibit S3.5 Cross-sectional view of the tunnel test apparatus. and are placed within the test apparatus. A gas flame of approximately 300,000 Btu/sec (89 kw) is applied at one end of the tunnel, and a regulated constant draft is applied through the tunnel from the flame end. The progress of the flame front is observed through side windows for 10 minutes. The FSI is a relative indication of flame propagation, but is not in any way an indication of fire resistance or of combustibility only of the ability of the material to resist propagation of flame spread across its surface. It is possible that a ma Life Safety Code Handbook

13 Reaction-To-Fire Testing 1193 terial with a low ability to spread flame (for example, bare sheet metal) could also exhibit little or no fire resistance when exposed to the testing criteria of NFPA 251. The smoke development represents a degree of obscuration and is measured by a photoelectric cell mounted in the test chamber s exhaust outlet, opposite a light source. A reduction in the light transmitted, due to the smoke particulates that pass by the photoelectric cell, is recorded and used to calculate the SDI. It should be noted that there is no direct relationship between the flame spread and smoke development values. It is possible that a material having a low flame spread index could also exhibit a very high smoke development index. Specimens tested in the Steiner tunnel test must be representative of the material for which test results are desired. When specific materials and products are considered for use or are reviewed for compliance with a provision of the Life Safety Code, it is critical that the intended end use correspond with the tested configuration. If the material or product differs in composition or is mounted or applied in a manner that deviates from the tested specimen, it could have an adverse effect. The actual FSI and SDI are likely to be different from those established in the original test results. It is very important therefore, to follow the manufacturer or listing instructions when installing or applying the interior finish material. Section 6.8 of ASTM E 84 discusses the mandatory methods for specimen preparation and mounting for testing some materials, as discussed below. The Appendix of ASTM E 84 provides guidance on the different mounting configurations for some other types of building materials when tested in the Steiner tunnel. This appendix is provided as a guide and cannot be used as a requirement, and so caution should be used when applying it to particular materials. As stated above, information on the mandatory required procedures for mounting and testing some materials in the Steiner tunnel test has been developed and incorporated into ASTM E 84, in Section 6.8, and more of them are under development (see Table S3.3). The ASTM committee on Fire Standards, ASTM E05, is working on such mounting methods and is developing further standard practices. Not all of them are critical in the Life Safety Code. Some materials that cannot support themselves in the tunnel and that are artificially supported by a wire mesh have been demonstrated to have FSI characteristics that are significantly different from those found in actual field installations. Therefore, the permitted use of wire mesh to support test specimens has been limited in recent editions of ASTM E 84. It has also been established that the ASTM E 84 test method is not suitable for certain building materials. Included Table S3.3 Steiner Tunnel Specimen Preparation and Mounting Practices to Assess Surface Burning Characteristics of Specific Materials Designation E 2231 E 2404 E 2573 E 2579 E XXXX In progress Applications In progress In progress Application Pipe and Duct Insulation Systems Textile, Paper and Vinyl Wall and Ceiling Coverings Site-Fabricated Stretch Systems Wood Products Reflective Insulation Materials and Radiant Barrier Materials for Building Applications Plastic Pipe and Tubing for Building Floor Covers Vapor Barriers are those that, due to their own structural quality or the manner in which they are applied, are not capable of supporting themselves in position or of being supported in the test furnace at a thickness comparable to their recommended use. When using these materials as interior finishes, a different test protocol might be required. An appropriate test for these types of materials would be NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth. Table A provides a compilation of the interior finish requirements of the occupancy chapters (Chapters 11 through 43) of the Life Safety Code, based on ASTM E 84. Wherever the use of Class C interior wall and ceiling finish is required, Class A or Class B is permitted, and wherever Class B interior wall and ceiling finish is required, Class A is also permitted. Room-Corner Test. As an alternative to the Steiner tunnel test, explains that interior wall and ceiling finish materials can be tested in accordance with a room-corner test, namely NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and, if they meet the appropriate conditions (from ), they can be used anywhere a material is required to meet Class A, Class B, or Class C finish requirements in accordance with ASTM E 84, as explained above. This is a critical difference in approach, since a room-corner test exposes an interior wall or ceiling finish material when applied to walls (or walls and ceilings) of a room, and it measures heat and smoke release. Historically, codes have regulated materials on walls and ceilings using ASTM E 84. Full-scale room-corner fire test research has shown that flame spread indices produced by ASTM E 84 may not reliably predict all aspects of the fire behavior of textile wall and ceiling Life Safety Code Handbook 2009

14 1194 Supplement 3 Fire Tests for Life Safety Code Users coverings. NFPA 286, known as a room-corner test, was developed for assessing the fire and smoke obscuration performance of interior wall and ceiling finish materials. As long as an interior wall or ceiling finish material is tested by NFPA 286 using a mounting system, substrate, and adhesive (if appropriate) that are representative of actual use, the room-corner test provides an adequate evaluation of a product s flammability and smoke obscuration behavior. Manufacturers, installers, and specifiers should be encouraged to use NFPA 286, because this standard fire test has the ability to characterize actual product behavior, as opposed to data generated by tests using ASTM E 84, which only allow comparisons of one product s performance with that of another. If a manufacturer or installer chooses to test a wall finish in accordance with NFPA 286, additional testing in accordance with ASTM E 84 is not necessary. The test results from ASTM E 84 are suitable for classification purposes but should not be used as input for fire models, because they are not generated in units suitable for engineering calculations. Actual test results for heat, smoke, and combustion product release from NFPA 286 are suitable for use as input for fire models for performance-based design. In NFPA 286, the test compartment is a standard room, with dimensions of 8 ft 12 ft 8 ft high (2.4 m 3.7 m 2.4 m high), including a 30 in. 80 in. (0.76 m 2.03 m) doorway in the center of the 8 ft 8 ft (2.4 m 2.4 m) wall. (See Exhibit S3.6.) The test material is installed completely covering the three walls of the standard room (all except for the wall containing the doorway), as well as the entire ceiling (if appropriate). If a ceiling covering only is being tested, the test material covers the ceiling only. The ignition source for NFPA 286 is a gas burner with a nominal 12 in. 12 in. (305 mm 305 mm) porous top surface of a refractory material, as shown in Exhibit S3.7, which produces a diffusion flame that will expose the walls in the corner of the room where the specimens are mounted to a predetermined energy source. The gas burner is located flush against the two back walls and is used at a net heat output of 40 kw ± 1 kw for the first 5 minutes, followed by a net heat output of 160 kw ± 5 kw for the next 10 minutes. The combustion products from the test room are collected in a hood that is fed into a 3 ft 3 ft (0.91 m 0.91 m) plenum just outside the doorway connected to an exhaust duct. Within this exhaust duct, measurements of gas velocity, temperature, and concentrations of selected gases are made. The hood is designed to develop a minimum flow rate, sufficient to capture all the products of combustion being expelled from the fire test room. The canopy hood and exhaust duct are shown in Exhibit S3.8. All the measuring instrumentation is placed in that exhaust duct. The room-corner test method assesses heat release (by the principle of oxygen consumption calorimetry), smoke release into the duct, and the release of combustion products. It is understood that heat release rate is the most critical reaction-to-fire property, as it parallels the intensity of 305 mm (12 in.) 152 mm (6 in.) White Ottawa silica sand 3.66 m ± 0.05 m (12 ft ± 2 in.) 305 mm (12 in.) A 152 mm (6 in.) 76 mm (3 in.) A Gas 2.44 m ± 0.05 m (8 ft ± 2 in.) 0.76 m ± 6.4 mm (30 in. ± 0.25 in.) 2.03 m ± 6.4 mm (80 in. ± 0.25 in.) 2.44 m ± 0.05 m (8 ft ± 2 in.) Exhibit S3.6 Interior fire test room dimensions and interior doorway dimensions for the NFPA 286 test. 152 mm (6 in.) Top view 28 mm (1.125 in.) Side view A A White Ottawa silica sand Exhibit S3.7 Gas burner for the NFPA 286 test. Nominal 19-mm (0.75-in.) pipe Gas 2009 Life Safety Code Handbook

15 Reaction-To-Fire Testing m (3 ft) 306-mm (12-in.) circular aperture 150 mm (6 in.) 3.66 m (12 ft) 3.5 m (11.5 ft) 3.3 m (11 ft) 1.5 m ( 5 ft) to exhaust system 0.9 m (3 ft) (min.) Plenum 406-mm (16-in.) circular duct Exhaust Smoke meter 1.1 m (3.5 ft) Hood Gas sampling probe Thermocouples and bidirectional probe 2.44 m 2.44 m (8 ft 8 ft) square hood (min. dimensions) Top of door opening 2.44 m 3.66 m (8 ft 12 ft) burn room Burner Exhibit S3.8 Canopy hood and exhaust duct for the NFPA 286 test. the fire. The Life Safety Code, like most other codes, requires that an interior finish material in this test meet the following conditions: 1. Flames shall not spread to the ceiling during the 40 kw exposure. 2. During the 160 kw exposure, the following criteria shall be met: a. Flames shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2.4 m 3.7 m) wall. b. Flashover shall not occur. 3. The peak heat release rate throughout the test shall not exceed 800 kw. 4. For new installations, the total smoke released throughout the test shall not exceed 1000 m 2. Values derived from NFPA 286 are in SI units; there is no straightforward inch-pound equivalent. Flashover is determined to have occurred in the test chamber when any two of the following conditions have been attained: 1. A heat flux at the floor reaches 25 kw/m The average upper air temperature exceeds 1200 F (650 C). 3. Flames exit the doorway. 4. A paper target on the floor ignites spontaneously. The pass/fail criterion for smoke release was determined following an assessment of smoke released in a room-corner test and in the Steiner tunnel test by a number of interior finish materials, which suggested that a material with a total smoke released value exceeding 1000 m 2 in a room-corner test would be likely also to exceed an SDI of 450 in the Steiner tunnel test. (See Exhibit S3.9.) It should be noted that the requirement for smoke release within the Life Safety Code does not apply to existing installations. The technical committee determined that this new requirement should not be applied retroactively. A separate room-corner test had been developed earlier for use with textile materials that are used as wall coverings: NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile Coverings on Full Height Panels and Walls. The room, burner, and instrumentation are identical to those in NFPA 286. However, NFPA 265 differs from NFPA 286 in two ways: 1. The exposure after 5 minutes at 40 kw increases only to 150 kw for 10 minutes. 2. The gas burner is recessed slightly [approximately 2 in. (51 mm) in each direction] from the walls. This is a critical difference in that the flames from the burner itself in the NFPA 265 test do not reach the Life Safety Code Handbook 2009

16 1196 Supplement 3 Fire Tests for Life Safety Code Users Total smoke released in room corner test Room corner test smoke criterion SDI in Steiner Tunnel Test Exhibit S3.9 Comparison of smoke values in different test methods. ceiling during the initial test period (i.e., at 150 kw), while those from the NFPA 286 burner do have direct flame impingement on the ceiling even during the initial test period. Therefore, the Life Safety Code and other codes limit the application of NFPA 265 only to textile wall coverings (and to expanded vinyl wall covering materials). Interior finishes that are classified as textile materials require special consideration and appropriate testing, due primarily to their very low thickness. Textile wall covering materials can include napped, tufted, looped, woven, and nonwoven or similar materials. The NFPA 265 test procedure was developed because fire research had shown that a Class A flame spread index in a textile material does not accurately predict the overall burning characteristic behavior of this material in this particular end use. Two test protocols, Method A and Method B, used to be approved for testing a textile material in accordance with NFPA 265. Method A uses a corner-test exposure and mounts the test specimen on only sections of two walls of the test compartment. The test specimens are mounted only on the rear wall and on the left side wall and extend 2 ft (0.6 m) down from the ceiling. Method B uses the same test compartment configuration but requires that the test specimens be mounted so that they fully cover the three complete walls (not the wall containing the doorway) with the test specimen. Since the 2006 edition of the Life Safety Code, Method B of NFPA 265 has been eliminated from the permitted test methods. The test compartment is identical to that in NFPA 286, as is the gas burner (but not its intensity or location, as described above). (See Exhibit S3.10.) Interestingly, when a textile wall covering is tested in accordance with Method A of NFPA 265 (a frequent occurrence), the corresponding results used to be suitable for code approval, but have never been considered suitable for computer modeling of the fire hazard. For a textile wall covering material to be considered acceptable by the Life Safety Code when tested in accordance with NFPA 265, flames must not spread to the ceiling during the 40 kw exposure, flames must not spread to the outer extremity of the test specimen during the 150 kw exposure, and the test specimen in the room cannot reach flashover. Fire research involving the full-scale room-corner fire test scenarios has documented that textile materials found to be Class A via the Steiner tunnel test can have a burning behavior that is unsatisfactory. So, the fire safety conclusions drawn from the two test methods can be different. It was decided that the conclusions drawn from the more realistic room-corner tests were more likely to be correct. Thus, the Life Safety Code now requires that textile wall covering materials be tested in accordance with NFPA 265 and pass the requirements of , or be tested in accordance with NFPA 286 and pass the requirements of , or be tested in accordance with ASTM E 84 and obtain a Class A rating and be installed in an occupancy that is fully sprinklered if it extends from the floor to the ceiling (see ). It is important to note that the pass/fail criteria associated with NFPA 265 are similar to those associated with NFPA 286, with two exceptions: the measurement of smoke release is not a requirement, and the added requirement for a peak heat release rate of 800 kw is not included. Expanded vinyl wall and ceiling covering materials can be tested in the same way as textile wall covering materials, namely using ASTM E 84 or NFPA 265, but with the same limitations of use. Alternatively, they can be tested as other interior finish materials, namely using NFPA 286, without limitations of use. Foam plastic insulation cannot be used exposed as an 2009 Life Safety Code Handbook

17 Reaction-To-Fire Testing m (2 ft) 1.22 m (4 ft) 0.6 m (2 ft) 2.44 m (8 ft) 0.6 m (2 ft) Rear wall Note: Screened areas represent test materials. The test material is applied so that the machine direction is vertical. The burner is located 51 mm (2 in.) from both the rear wall and the left sidewall m (8 ft) 0.6 m (2 ft) 1.22 m (4 ft) 1.22 m (4 ft) Note: Burner measures 305 mm 305 mm (1 ft 1 ft) in plan view. Burner height = 305 mm (1 ft). 0.6 m (2 ft) Left sidewall Floor plan Front wall 0.76 m (2 ft 6 in.) Right sidewall Ceiling plan 2 m (6 ft 8 in.) Exhibit S3.10 Specimen mounting for Method A test protocol of NFPA 265. interior finish material, except as tested using NFPA 286. Alternatively, foam plastic insulation can be protected from the occupied interior of the building by being covered with a thermal barrier. Another widely used room-corner test, not used in the Life Safety Code, is ASTM E 2257, Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies (similar to ISO 9705, Fire Tests Full Scale Room Fire Tests for Surface Products 10 ). It is used by the European Union for regulation of building products; by NFPA 301, Code for Safety to Life from Fire on Merchant Vessels, 11 for case furniture; and by the High Speed Craft Code 12 of the International Maritime Organization (IMO) for regulation of interior finish fire restricting materials. The test is basically the same as NFPA 286 (see Exhibits S3.5 through S3.7, which describe the room, ignition burner, and instrumentation), except that the ignition source is a gas burner, which has an output of 100 kw for the first 10 minutes, followed by an output of 300 kw for a subsequent 10 minutes. Just like NFPA 286, this test assesses heat and smoke release and the development of flashover. Tested materials can be required to meet different sets of pass/fail criteria or classifications into categories. UL 1715, Standard for Fire Test of Interior Finish Material, is an early version of a room-corner test, which is widely used in codes, including the Life Safety Code, for assessing the fire performance of cellular or foamed plastic materials (foam plastics) used as interior finish. It uses a 30 lb (13.6 kg) wood crib in a corner of the same basic room as NFPA 265 or NFPA 286. In the test, the specimen, the interior finish material, is mounted on the back wall of the room and on 8 ft (2.4 m) of one of the side walls. Measurements are based on temperature and visual observations of extent of flame spread within the room (i.e., whether the flame reaches the extremities and whether it exits the room and indicates flashover). Of course, optional measure- Life Safety Code Handbook 2009

18 1198 Supplement 3 Fire Tests for Life Safety Code Users ments of heat and smoke release are also possible. It has been shown that UL 1715 is less severe than NFPA 286. FM 4880, Approval Standard for Class 1 Insulated Wall or Wall and Roof/Ceiling Panels; Plastic Interior Finish Materials; Plastic Exterior Building Panels; Wall/Ceiling Coating Systems; Interior or Exterior Finish Systems, 13 is a fire test suitable for assessing the fire performance (heat release or flame spread) of cellular or foamed plastic materials (foam plastics) used as interior finish. It requires that the assembly tested not support a selfpropagating fire when subjected to a 25 ft (7.6 m) high corner test, as evidenced by flaming or material damage, after exposure to a 750 lb (340 kg) wood crib fire. Other test options exist within the standard, depending on the application of the product tested: the FM equivalent to NFPA 287/ASTM E 2058, a 50 ft (15.2 m) high corner test, and a room corner test (such as NFPA 265, NFPA 286, or ISO 9705). No smoke measurements are made. UL 1040, Standard for Fire Test of Insulated Wall Construction, is similar to FM 4880 in that it uses a 764 lb (347 kg) wood crib ignition source in a corner configuration and assesses whether surface burning extends beyond 19 ft (5.5 m) from the intersection of the two walls. Smoke release is not assessed. UL 1040, UL 1715, and FM 4880 are all used, together with NFPA 286, for assessing the fire performance (but not the smoke release) of foam plastics as interior finish. The tests are also widely used in codes for assessing the suitability of a material as a thermal barrier separating foam plastics and/or metal composite materials (MCMs) from the interior of the building or from plenums. The 2009 edition of the Life Safety Code added the requirements that new installations of cellular or foamed plastic materials for use as interior finish tested in accordance with UL 1040 or FM 4880, tests which do not include a smoke component, must also be tested for smoke release. It explains further that suitable smoke release tests include the following: 1. Additional measurements of smoke release into the duct that demonstrate that the total smoke released throughout the test does not exceed 1000 m 2 2. NFPA 286, with the acceptance criterion of (4) 3. ASTM E 84, with a smoke developed index not exceeding 450 A new test was developed for 2009: NFPA 275, Standard Method of Fire Tests for the Evaluation of Thermal Barriers Used Over Foam Plastic Insulation, which consists of two parts: (a) a fire resistance test and (b) an integrity fire test. The fire resistance test can be conducted using the time-temperature curve of NFPA 251, ASTM E 119, or UL 263, but the test specimen can be significantly smaller ( in. or mm exposed surface area), and the thermal barrier must exhibit a 15-minute fire resistance rating so that during the 15-minute test period, the average measured temperature rise above the average temperature at the start of the fire test for the thermocouples on the unexposed side does not exceed 250 F (139 C), and the measured temperature rise of any such single thermocouple does not exceed 325 F (181 C). The integrity fire test exposes the thermal barrier and the underlying foam plastic or MCM to be protected, and it can be conducted using any of the following four tests: NFPA 286, UL 1040, UL 1715, or FM The pass-fail criteria for NFPA 286 are those discussed above, and those for the other tests are as specified in the respective standards. A common misapplication of test methods needs to be pointed out here: textile materials normally used as floor coverings, such as carpets or carpet-like materials, that have achieved a Class I or a Class II rating (see details in the following section) are not permitted to be installed as interior wall or ceiling finish. In other words, carpets cannot be used to cover walls or ceilings where an interior wall or ceiling finish rating is required unless they have been tested as wall or ceiling coverings. The reason for this is that a classification is obtained by testing with NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, and this test method, which generates a critical radiant flux and not a flame spread or heat release, is applicable only when the material is installed as a floor covering or as an interior floor finish. Another common misapplication of test methods is one whereby a textile material is tested by means of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films (see more details later in this supplement), and then installed as interior finish on walls, ceilings, or floors. NFPA 701 is intended to apply to fabrics or other materials used in curtains, draperies, or other window treatments. It is also suitable, in Test 1, to a number of materials having an area density not greater than 21 oz/yd 2 (700 g/m 2 ), and, in Test 2, to fabrics and films, with or without reinforcement or backing, with area densities greater than 21 oz/yd 2 (700 g/m 2 ). NFPA 701 assesses vertical flame propagation performance criteria, which are suitable for draperies, curtains, and other similar loosely hanging furnishings and decorations (see of the Life Safety Code). However, NFPA 701 is an unsuitable test for assessing the fire problem potentially associated with textiles applied to a solid backing and used as wall linings or textiles installed horizontally on floors 2009 Life Safety Code Handbook

19 Reaction-To-Fire Testing 1199 or ceilings. This is explained in Annex A of the Life Safety Code. It has recently also been understood that the fire performance of site-fabricated stretch systems (which often have a textile cover) is not properly assessed using NFPA 701 but needs to be assessed using ASTM E 84, with the test specimen preparation and mounting procedure specified in ASTM E As stated above, it is critical that every material be assessed using the tests appropriate to the end-use application. Thus, if the same type of material is employed in different end-use applications, it may require testing via various test methods to be qualified for all applications. Interior Floor Finish. Interior floor finish is defined in the Life Safety Code as the interior finish of floors, ramps, stair treads and risers, and other walking surfaces. Interior floor finish needs to meet the requirements of two different fire tests: an ignition test and a critical radiant flux test. The United States Flammable Fabrics Act requires that all carpets and rugs manufactured, imported, distributed, or marketed in the United States must comply with the requirements of 16 CFR 1630, Standard for the Surface Flammability of Carpets and Rugs (FF 1 70). 14 Because the Life Safety Code is applicable outside of the United States, it references (in and ) a standard test method that is substantially similar to 16 CFR 1630: ASTM D (The Code does explain that the two are basically equivalent.) In the test method, a No methenamine timed burning tablet (commonly known as methenamine pill) weighing oz (0.149 g) is placed flat on a test specimen consisting of a section of carpet and ignited with a lighted match (ensuring that the match does not ignite the carpet). If the charred portion of the test specimen does not exceed 3 in. (76 mm) in length, the test specimen passes the test. This test method is only applicable to interior floor finish that is a textile, because most hard surface flooring materials are known to meet the test requirements. Interior floor finish materials used in regulated environments, as determined by the Life Safety Code or where the authority having jurisdiction determines that their particular burning characteristics are unknown, often must also meet a minimum critical radiant flux when tested in accordance with NFPA 253 (see also Table S3.1 for alternative similar fire test methods). Paragraph of the Life Safety Code specifies when interior floor finishes are required to have a fire safety classification rating, and describes the criteria needed. Interior floor finishes are grouped in two classes in accordance with their critical radiant flux ratings: 1. Class I Interior Floor Finish: critical radiant flux not less than 0.45 W/cm 2 2. Class II Interior Floor Finish: critical radiant flux not less than 0.22 W/cm 2 but less than 0.45 W/cm 2 The Life Safety Code also states ( ) that a critical radiant flux of 0.1 W/cm 2 (which is basically considered to be equivalent to a pass in the ASTM D 2859 test) is minimally required for floor coverings other than carpets. This applies to floor coverings with unknown fire performance, and is discussed in more detail in A and A The NFPA 253 test method measures the critical radiant flux (CRF) behavior of a horizontally mounted floor covering system exposed to a radiant heater, inside a test chamber (see Exhibits S3.11 through S3.13, which show the apparatus used to test the floor covering specimens in this test method). A gas-fired panel serving as a radiant heat energy source is installed at one end of the test chamber, on an incline (at a 30 angle) so that it extends over the test specimen. The radiant heater applies a graded heat flux that ranges between approximately 0.1 and 1.1 W/cm 2 close to the two ends of the test specimen. The test specimen is ignited by a pilot flaming ignition source at the end of the test chamber where the heat flux applied is highest. Exhibit S3.11 Flooring radiant panel tester apparatus. (Courtesy of Fire Testing Technology Ltd.) Life Safety Code Handbook 2009

20 1200 Supplement 3 Fire Tests for Life Safety Code Users Exhibit S3.12 Flooring radiant panel test showing carpet specimen and gas-fueled panel. The test chamber is calibrated by assigning a heat flux to each position along the length of the test chamber. Thus, the test method measures the heat flux at the point of flame out, which is when the material does not continue to support flaming, and that value is considered the CRF. The test specimens are required, to the extent possible, to simulate actual field installation practices. For example, if a carpet is to be mounted with a pad and/or an underlayment, it must be tested in that same way. The CRF provides a basis for estimating a critical aspect of fire exposure behavior for floor covering systems. It should be noted that this test is intended primarily for regulating floor coverings installed in building corridors, exits, and exit access corridors, which often have little or no combustible wall or ceiling finish. An occupancy with combustible finishes would be expected to contribute much more to fire hazard. The CRF is determined by measuring the distance that has burned. The test specimen is tested for 10 minutes following the exposure to a radiant energy source to a maximum of 1 W/cm 2. The distance burned is converted to a CRF value by plotting the distance on the standard radiant heat energy flux profile, as shown in Exhibit S3.14, which shows the calibration curve Exhibit S3.13 Flooring radiant panel schematic side elevation. >7.6 cm 15.2 cm 31.8 cm 10.2 cm 5.1 cm Thermocouples 71 cm 51 cm 10 cm 2.5 cm Radiating surface Gasfueled panel Chamber sheathing Material: inorganic millboard 0.74 g/cm cm Specimen holder Specimen Pilot burner 14 cm 10.5 ± 1 cm Specimen transport system 137 cm 8.9 cm 140 cm Protective sleeve Radiation pyrometer Note: in. = cm x Life Safety Code Handbook

Fire Test Methods ASTM NFPA UL ISO IEC

Fire Test Methods ASTM NFPA UL ISO IEC Fire Test Methods ASTM NFPA UL ISO IEC D2859 (Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials) E84 (Standard Test Method for Surface Burning Characteristics

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX 1. Call to Order. The meeting of the Technical Committee on Fire Tests

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E. Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions

More information

Report on Public Input June 2014 NFPA 101

Report on Public Input June 2014 NFPA 101 101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method

More information

2009 NFPA Text 2009 International Building Code Text Recommendation. NFPA IBC 2009 IBC is most recent

2009 NFPA Text 2009 International Building Code Text Recommendation. NFPA IBC 2009 IBC is most recent 2009 Changes of the Referenced Standards of the National Fire Protection Association- 101 Compared to the International Building Code- 2009 Referenced Standards For the Florida Building Commission And

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS Page 20 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL-11035-03-00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 25.10.2017 to 24.10.2022 Holder of certificate: DMT

More information

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.

More information

Report on First Revision June 2014 NFPA 101

Report on First Revision June 2014 NFPA 101 101 FR500 SAF-FUR (10.2.1.2 and 10.2.1.3) Recommendation: 10.2.1.2 The provisions of Section 10.2.1.1 shall not apply to mmaterials having a total thickness of less than 1/28 in (0.9 mm) that are applied

More information

We Identify and S.T.O.P. Your Noise Problems

We Identify and S.T.O.P. Your Noise Problems ASTM E-84 TESTING FOR MANUFACTURER, RENDERED TO: Acoustical Surfaces Inc. 123 Columbia Court North, Suite 201 Chaska, MN 55318 Noise S.T.O.P. Fabrisorb Acoustical Wall Panels TESTED: OCTOBER 3, 2002 October

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by Norman Alvares & Harry Hasegawa First Paragraph of E-691 Tests performed on presumably identical materials in presumably

More information

Materials Testing by Gregory Havel

Materials Testing by Gregory Havel Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Schedule of Accreditation 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 26385 Corner of 46th and 47th Streets Jebel Ali Industrial Area 1 Dubai United Arab Emirates Contact: Mr

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

F, T, L and W Ratings - What are the Code & Testing Requirements?

F, T, L and W Ratings - What are the Code & Testing Requirements? F, T, L and W Ratings - What are the Code & Testing Requirements? Rich Walke Underwriters Laboratories Inc. April 27, 2010 Copyright 1995-2007 Underwriters Laboratories Inc. All rights reserved. No portion

More information

NFPA 80 Overview January 21, 2016

NFPA 80 Overview January 21, 2016 NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider. by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing

More information

Code Technologies Committee Report Fire Rated Glazing Group A changes: Fire rated glazing

Code Technologies Committee Report Fire Rated Glazing Group A changes: Fire rated glazing Code Technologies Committee Report Rated Glazing Group A changes: There are 11 areas of study currently listed under CTC. 1. Balanced Protection 1.1. Vertical Opening 1.2. Roof Vents 2. Carbon Monoxide

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SGS GOVMARK TESTING SERVICES, INC. 96 Allen Boulevard, Suite D Farmingdale, NY 11735 Doug Lipp Phone: 631 293 8944 THERMAL Valid To: May 31, 2018 Certificate

More information

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur. First Revision No. 1-NFPA 501-2015 [ Section No. 5.3.1.3 ] 5.3.1.3 The following conditions shall be met when an interior finish material is tested using the test protocol of NFPA 286, Standard Methods

More information

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method. Public Input No. 4-NFPA 287-2014 [ Section No. 1.2.3.2 ] 1.2.3.2 Indices resulting from the test methods include critical heat flux (CHF), thermal response parameter (TRP), fire propagation index (FPI),

More information

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Collars for Floor Wastes Understanding BCA Compliance Options Fire Collars for Floor Wastes Understanding BCA Compliance Options February 2005 Introduction There has been a great deal of discussion in recent times regarding fire testing requirements for fire collars

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN ULC Subject C80.1 ULC G 5.2 ULC CCF February 14, 2012 CERTIFICATION BULLETIN 2012-01 Second Edition of ULC/ORD-C80.1 NMETALLIC TANKS FOR OIL-BURNER FUELS AND OTHER COMBUSTIBLE LIQUIDS Members of the Council

More information

#5 Proposed Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-1011-R1 (RB/MB) John D. Nicholas Representing Background Relevant to AC179 18 Years in the Building

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

SIGMADEK, LTD. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION

More information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES

More information

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions Smoke Characterization Study October 29, 2008 Paul E. Patty, P.E. Senior Research Engineer Northbrook, IL 847-664-2752

More information

Appendix: Standards and Specifications for Evaluation of Thermal Management in Electronic Industry

Appendix: Standards and Specifications for Evaluation of Thermal Management in Electronic Industry Appendix: Standards and Specifications for Evaluation of Thermal Management in Electronic Industry A. Standards for Thermal Analysis JEDEC Standard JESD51 JEDEC Standard JESD51-1 JEDEC Standard JESD51-2

More information

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

HORIZONTAL COMPLEMENT TO THE MANDATES TO CEN/CENELEC CONCERNING THE EXECUTION OF STANDARDISATION WORK FOR

HORIZONTAL COMPLEMENT TO THE MANDATES TO CEN/CENELEC CONCERNING THE EXECUTION OF STANDARDISATION WORK FOR EUROPEAN COMMISSION DIRECTORATE-GENERAL III INDUSTRY Industrial affairs II: Capital goods industries Construction M 117 HORIZONTAL COMPLEMENT TO THE MANDATES TO CEN/CENELEC CONCERNING THE EXECUTION OF

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of

More information

Cone Calorimeter. (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test THE BENCHMARK IN FIRE TESTING

Cone Calorimeter. (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test THE BENCHMARK IN FIRE TESTING Cone Calorimeter (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test THE BENCHMARK IN FIRE TESTING Cone Calorimeter (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test The

More information

Fire Safety Fire Resistant Building Components

Fire Safety Fire Resistant Building Components Fire Safety Fire Resistant Building Components NBN 713-020 1968 Fire fighting - Fire performance of building materials and products - Fire resistance of building materials NBN 713-020/A1 1982 Protection

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6 Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS SPANK 9901101 REPORT NO. 75157 Septemer 11, 00 Prepared For: Pollack 150 Varick Street New York, NY 10013 F-316-A 555 76TH STREET S.W., GRAND RAPIDS.

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Schedule of Accreditation 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 26385 Corner of 46th and 47th Streets Jebel Ali Industrial Area 1 Dubai United Arab Emirates Contact: Mr

More information

FUNDERMAX GMBH FIRE TEST REPORT

FUNDERMAX GMBH FIRE TEST REPORT FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter 1 Introduction AUGUST 2017 The Passive Fire Protection Handbook Contents Chapter 1: Introduction2 Applications

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook Useful Contact Numbers Promat Technical Services Department Telephone: 01344 381 400 Fax: 01344 381 401 E-mail: technicaluk@promat.co.uk Promat Marketing Services Department Telephone: 01344 381 350 Fax:

More information

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6 Art3d LLC Test Report No. AJFS1809009217FF Date: OCT.17, 2018 Page 1 of 6 1600 N State Route 291 Unit 250, Sugar Creek, Missouri 64058 USA 中国认可国际互认检测 TESTING CNAS L4743 The following sample(s) was / were

More information

C-01 FIRE DECKS AND BULKHEADS

C-01 FIRE DECKS AND BULKHEADS Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415 ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and

More information

Annex to the Accreditation Certificate D PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D PL 17819 01 00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 29.06.2017 to 10.08.2019 Holder of certificate: MPA

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

Adv. 8.4 Guidelines for Biosafety Cabinets Rev UNIVERSITY OF CINCINNATI Environmental University Health Services 556-4968 Health and Safety ADVISORY NO. 8.4: GUIDELINES FOR THE SELECTION, INSTALLATION AND USE OF BIOSAFETY CABINETS (INCLUDING ISSUES

More information

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San

More information

"Spray area" is the term that is used throughout the document. This change is for consistency.

Spray area is the term that is used throughout the document. This change is for consistency. of 78 5/30/2014 2:08 PM Public Comment No. 39-NFPA 33-2013 [ Global Input ] For Chapter 18, replace "spray paint area" with "spray area". "Spray area" is the term that is used throughout the document.

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

FACADES AND FIRE The Essential Elements

FACADES AND FIRE The Essential Elements FACADES AND FIRE The Essential Elements Andy Dean BSc (Hons), MCIOB, FSFE Head of Façade Engineering WSP Middle East Manama, Bahrain, Jun 2014 Reaction to fire versus fire resistance LEARNING OBJECTIVES

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

ICC CODE TECHNOLOGY COMMITTEE Area of Study Labeling of Fire Rated Glazing

ICC CODE TECHNOLOGY COMMITTEE Area of Study Labeling of Fire Rated Glazing ICC CODE TECHNOLOGY COMMITTEE Area of Study Labeling of Fire Rated Glazing Code Change History for 2006 IBC Section 75 Opening Protectives October, 2008 2006 IBC 200 IBC 2000 IBC APPLICABLE CODE CHANGES

More information

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED DG TM DualGuard 2000 Fluoropolymer Barrier FRP Duct C U L LISTED US Fluoropolymer Barrier FRP Duct Composites USA A Critical Process Systems Group Company Worried about meeting Insurance Underwriter and

More information

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &

More information

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection 6 Inside buildings there are two types of fire protection systems: Active Fire Protection and Passive Fire Protection. Both systems should actively work together in the event of a fire. 6.1.1 The four

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information