Health Care Facility Rehabilitation
|
|
- Walter Bates
- 6 years ago
- Views:
Transcription
1 2017 NFPA Conference & Expo Health Care Facility Rehabilitation Effective Application of NFPA , Life Safety Code Chapter 43 Building Rehabilitation Ron Coté, P.E. NFPA Health Care Facility Rehabilitation Effective Application of NFPA , Life Safety Code Chapter 43 Building Rehabilitation Ron Coté, P.E. NFPA National Fire Protection Association. All rights reserved. 1
2 At the conclusion of this program (and with a bit of self study) participants will be able to: 1. Differentiate among the rehabilitation work categories so as to properly classify any planned rehabilitation projects 2. Apply Chapter 43 rehabilitation requirements commensurate with the scope of the work planned 3. Understand the impact of conducting different categories of rehabilitation work simultaneously 4. Blend the specialized Chapter 18/19 health care occupancy requirements for Major Rehabilitation projects with the requirements of Chapter Building Rehabilitation 2
3 5 Chapter 4 meet, as nearly as practicable, the requirements for new construction Chapters 18/19 major renovation (undefined) perform planned work per New plus, sprinkler the smoke compartment minor renovation perform planned work per New 6 3
4 Chapter 4 meet Chapter 43, Building Rehabilitation Chapters 18/19 major renovation defined: >4500 ft 2 or >50% smoke compartment area perform planned work per Chapter 43 plus, sprinkler the smoke compartment minor renovation if not sprinklered (NS) perform planned work per Chapter 43 meet the NS provisions of Chapter 43 Building Rehabilitation 8 4
5 Modeled after HUD s 1997 NAARP N Nationally A Applicable R Recommended R Rehabilitation P Provisions 9 Must comply with provisions for existing 10 5
6 Missing handrails leave Chapter 43 add handrails 1 side, not 2 position handrails in. height range, not in. 11 Repair Renovation Modification Reconstruction Change of occupancy Change of use Addition 12 6
7 Patching 13 Replacement in kind 14 7
8 Reconfiguration of a space Addition or relocation of door Reconfiguration or extension of system Installation of additional equipment 15 Reconfiguration of space, plus: affects exit or corridor used by more than one space or 16 8
9 Reconfiguration of space, plus: work area not permitted to be occupied because features are impaired or 17 Rehabilitation work area for the Modification exceeds 50% of the area of the building 18 9
10 Rehabilitation work area for the Modification exceeds 50% of the area of the building 19 The change of occupancy classification of a structure or portion thereof 20 10
11 Change in purpose or level of activity, without a change of occupancy, that involves a change in application of the Code 21 An increase in aggregate building area, floor area, height, or number of stories of a structure 22 11
12
13
14 28 14
15
16 Chapter 18/19 major rehabilitation sprinkler Chapter 18/19 major rehabilitation compartments sprinkler compartments A, B, F, G, A, B, F, G, H H Chapter 43 Reconstruction Chapter 43 Reconstruction Sprinkler all compartments A Sprinkler all through compartments A through H 31 Patient room used for storage 32 16
17 33 nfpa.org National Fire Protection Association. All rights reserved. If: Existing health care occupancy Building is sprinklered Create new hazardous area Room 250 ft 2 Then: 1 hour walls exempted 34 17
18 1 2 Health care Detention/correctional Residential B&C Within or to lesser hazard category existing sprinklers per new alarms per new hazardous areas per new Change to higher hazard category new 36 18
19 Per requirements for new
20 39 Document information pages nfpa.org/aboutthecodes nfpa.org/101 Technical questions member benefit nfpa.org/101 Handbook 40 20
21 Questions? 2017 NFPA Conference & Expo CEUs: To receive CEUs for this session, scan your badge at the back of the room before leaving Evaluation: Complete a session evaluation on the mobile app. (Search app store for NFPA 2017 C&E. ) Handouts: Handouts will be available via the mobile app and at nfpa.org/conference Recordings: Audio recordings of all sessions will be available free of charge via NFPA Xchange. 21
Changes to NFPA 101A 2013 Edition for Health Care Facilities
2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager
More informationEffective Messaging on School Door Locking
2017 NFPA Conference & Expo Effective Messaging on School Door Locking Ron Coté, P.E. NFPA At the conclusion of this program participants will be able to: 1. Understand the conflicting needs of security
More informationLarge Airports Maintaining Fire Safety through the years
2017 NFPA Conference & Expo through the years Presented by: Panos Samaras Fire Safety Officer Athens International Airport Greece 1 Main Points Part 1 Identify Regulatory Environment Recent Fires in Airports
More informationThe Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo
2014 NFPA Conference & Expo Modeling Storage Occupancies Under Sloped Ceilings Presented by: Kenneth E. Isman NFSA Victoria B. Valentine NFSA Andre Marshal CSS NFPA 13 defines a sloped ceiling as one where
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationProtecting Special Industrial Hazards with NFPA Codes & Standards
2017 NFPA Conference & Expo Protecting Special Industrial Hazards with NFPA Codes & Standards Different Facilities & Similar Risks Presented by: Bruce H. Clarke, CFPS, UL- CRP Head of Global Property Engineering
More informationHands On Training for Fire Door Products and Fire Door Assemblies
2017 NFPA Conference & Expo Hands On Training for Fire Door Products and Fire Door Assemblies Presented by: Paul M. Goldense, FDAI Goldense Building Products, Inc. Jeffery S. Batick, FDAI Allegion Why
More informationDust Hazard Assessments
2017 NFPA Conference & Expo Dust Hazard Assessments The Importance of DHAs in Establishing Work Practices and Facilities Presented by: Jason Reason, CIH, CSP, CHMM Lewellyn Technology, LLC Learning Objectives
More informationPublic. Mike Free Health. State of Alabama Department of
State of Alabama Department of Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management Public 334-206-5221 334-206-5177 Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt
More information2014 NFPA Conference & Expo
2014 NFPA Conference & Expo NFPA Wildland Standards Development: Where We ve Been and Where We re Going Presented by: Ryan Depew NFPA Emergency Services Spc. OVERVIEW NFPA Technical Committees NFPA Wildland
More informationPublic Health Fax: Web Site:
State of Alabama Department of Public Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management 334-206-5221
More informationFire Dynamics Research Applied to. Fire Investigation. Overview
2017 NFPA Conference & Expo Fire Dynamics Research Applied to Fire Investigations Presented by: Daniel Madrzykowski Research Engineer UL Firefighter Safety Research Institute Fire Investigation What is
More informationArtificial Trees and Fire Performance
2017 NFPA Conference & Expo Artificial Trees and Fire Performance Presented by: Dwayne Sloan Manager, Principal Engineers Building Materials & Suppression UL LLC Learning Objectives Frame the Fire Problem
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More informationProposed Changes to NFPA
2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationWelcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo
2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationApplications of California Historical Building Code in Fire Safety Upgrades
Applications of California Historical Building Code in Fire Safety Upgrades California Preservation Foundation 37 th Annual Conference May 3-6, 2012 Presented by: Cheryl L. Domnitch, P.E. Hughes Associates,
More information5/9/2017. Understanding Risk Analysis and Emergency Planning and How They Affect the Design of Emergency Communications Systems
Understanding Risk Analysis and Emergency Planning and How They Affect the Design of Emergency Communications Systems Wayne D. Moore, P.E., CFPS, CET Vice President, Corporate Strategy JENSEN HUGHES Understanding
More informationChapter 2: Definitions
FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationE25 (D) Automatic controls for general means of egress lighting
Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed
More informationGROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101
More informationPreview of the MA Building Code (780 CMR) 9 th edition
Preview of the MA Building Code (780 CMR) 9 th edition Presented by: Ron Melucci, P.E. Engineering Planning and Management, Inc rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering Planning and Management,
More informationDepartment of Health Life Safety Code Update
Department of Health Life Safety Code Update Presented by: Charlie Schlegel, Director Division of Safety Inspection Overview CMS Adoption of the 2012 Life Safety Code (LSC) and 2012 Health Care Facilities
More informationFHCA 2014 Annual Conference & Trade Show
FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More informationFirst Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable
More informationFire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code
Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationInterim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017
Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationFirst Revision No NFPA [ Section No ]
of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to
More informationChapter 1 - General Design Guidelines CHAPTER 1 GENERAL DESIGN GUIDELINES
CHAPTER 1 GENERAL DESIGN GUIDELINES 1.0 INTRODUCTION This Publication has been developed to provide current, uniform procedures and guidelines for the application and design of safe, convenient, efficient
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationProposed Changes to NFPA
2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Daniel O Connor (SIG-IDS), Jensen Hughes Robert Schifiliti (SIG-NAS), R.P. Schifiliti Associates William Koffel (SIG-ECS), Koffel
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationBCBC 2012 CHANGES TO PART 3
BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT N.A GARMENTS PLOT # 36, ROAD # 46, GULSHAN NORTH C/A, DHAKA OTHER FACTORIES: SIDKO LIMITED, SIDKO APPARELS LIMITED, DELTA TIES LIMITED April 17, 2014 Page 2 SUMMARY was surveyed
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT HAN A HATS & CAPS LTD. ACCORD ID: 12339 DAG NO. CS &SA-115/117, RS-188/181, KHOTION NO. CS-128, SA-274, BAIPAIL, ASHULIA, SAVAR, DHAKA. OTHER FACTORIES: TEXTSTREAM FASHION
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,
More informationFor the Florida Building Commission And the Fire Code Advisory Council
Life-Safety Modifications Mechanical and Existing Building Compared to the 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission
More informationRooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options
2016 NFPA Conference & Expo Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options Presented by: Joel Sipe Senior Managing Engineer Exponent Inc. Outline Project Background Fire
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationFIRE AND SAFETY PROJECT REVIEW REPORT
1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally
More informationBCAC Egress Work Group
2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. BCAC item E-17.1 E?? 15 1006.2.1, 1006.3 1006.2.1 Egress based on occupant load and common path of egress travel distance.
More information2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)
CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationGlenwood Springs Fire Protection District Amendments to the 2009 International Fire Code
Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code 060.090.010 Adoption of International Fire Code; Violations; Conflict A. Pursuant to the power and authority conferred
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT KAROONI KNIT COMPOSITE RATANPUR, SHAFIPUR KALIAKOIR OTHER FACTORIES: NONE April 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/5/2014 by Hughes Associates, Inc.
More information5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;
ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities
More information12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS)
11I058 ALLOWABLE HEEIGHTS AND AREAS IN THE INTERNATIONAL BUILDING CODE 12F052 ADVANCED FLORIDA BUILDING CODE (MULTIPLE OCCUPANCY BUILDINGS) www.codeaccess.net 2 AIA HSW LUH S AIA COURSE NUMBER 12F052 FLORIDA
More informationFIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES
FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)
More informationVERMONT DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE SAFETY OFFICE OF THE STATE FIRE MARSHAL, STATE FIRE ACADEMY and THE STATE HAZ-MAT TEAM www.firesafety.vermont.gov EFFECTIVE DATE ~ November 5, 2012
More informationFIRE/SMOKE BARRIER FUNDAMENTALS
FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationOccupancy Classification and Layout Guidelines
Occupancy Classification and Layout Guidelines H3? S1? F1? B? U? H6? M? H7? A1? Presented to PIBA Seminar Group Todd LaBerge, P.E. Senior Fire Protection Engineer Presentation Overview Occupancy Groups
More informationNfpa 101 Life Safety Code Handbook 2012 Edition File Type
Nfpa 101 Life Safety Code Handbook 2012 Edition File Type We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,
More informationINSPECTOR I SKILLS ADMINISTRATION
INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..
More informationAgency for Health Care Administration
Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination
More informationCodes and Standards FFP1510, BFST1510, ATCP1510
DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards & Training Title: Master Syllabus Date: July, 2017 Codes and Standards FFP1510, BFST1510, CP1510 Course Title Codes
More informationChapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.
3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;
More informationFIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH
FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationHealth Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities
More informationQuestions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG )
Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG ) 1. Condo and co-op associations believed that the Life Safety
More informationMajor Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014
Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Philip Rizcallah, P. Eng. NRC-IRC Canadian Codes Centre Presented by Stan Dueck CRBO Overview Where are the major
More informationTiny Homes PREPARED BY: MATT CUE-BALL BAILEY AND BCDC
2017 NFPA Conference & Expo PRESENTED BY: NFPA BCDC TINY HOMES PREPARED BY: MATT CUE-BALL BAILEY AND BCDC 1 This is a collaborative effort of the members of the BCDC (Building Code Development Committee)
More informationCODE SUMMARY REQUIREMENTS (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI))
Code Summary Handout - Last revised 09/30/2014 CODE SUMMARY REQUIREMENTS WASHINGTON COUNTY OREGON (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI)) NOTE: Washington County Building Services requires all commercial
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report
More informationNFPA 99 for Facility Managers
NFPA 99 for Facility Managers Application to Existing Facilities October 13, 2015 Jonathan Hart: Senior Fire Protection Engineer Learning Objectives Review the layout of NFPA 99 Understand the application
More informationCorrectly Classifying and Determining Fire Protection Requirements for High- Hazard Group H Occupancies in New York State (2010 codes)
Correctly Classifying and Determining Fire Protection Requirements for High- Hazard Group H Occupancies in New York State (2010 codes) Presented by: Chad R. Barnes, CFPS, SFPE, CPP Agenda Objectives Statistics
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT CHAITY COMPOSITE LTD. CHOTTO SHILMONDI, TRIPURDI, SONARGAON OTHER FACTORIES: NONE April 7, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/7/2014 by Hughes Associates,
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More information