1 SITESTAR CABINET DESCRIPTION Product No: D000100/1 Revision: 03 SiteTel Sweden AB Haukadalsgatan 8A, SE Kista, Sweden

2 Contents 1 INTRODUCTION TARGET GROUP DOCUMENTS ILLUSTRATIONS PREREQUISITES ABBREVIATIONS DESCRIPTION PRODUCT OVERVIEW MAIN FEATURES PRODUCT APPROVALS UNITS IN THE SYSTEM CABINET EARTH GROUNDING DOOR Climate Control Unit Locking System CONNECTION FIELD Cable Entries DC Connection Unit CLU Power Connection Terminal Circuit Breaker Surge Protection Device External Alarm Connection BATTERIES EQ ZONE 4 CABINET VERSION PLINTH CUSTOMER EQUIPMENT SIZE AND WEIGHT SPACE REQUIREMENTS Doc. No: D INS-01, Rev I Page 2 of 35

3 2.5.1 AIRFLOW CLEARANCE CLIMATE SYSTEM GENERAL Normal Operational Mode Factory Test Mode TEMPERATURE REGULATION OPERATING ENVIRONMENT ELECTRICAL PERFORMANCE BATTERY CAPACITY OPERATING CONFIGURATION CHARGING AND DISCHARGING CHARACTERISTICS Doc. No: D INS-01, Rev I Page 3 of 35

4 1 INTRODUCTION This document describes the SiteStar Cabinet, an outdoor/indoor battery backup system providing -48 V DC backup power in the event of AC mains failure, and for Hybrid powered Sites. The cabinet is available in two sizes, 1.8 m and 1.1 m high. The 1.8 m cabinet is available in an EQ Zone 4 version for areas exposed to earthquake risk. The cabinet is available in the following electrical versions: 230 V AC 115 V AC -48 V DC If not otherwise stated, the content of this documentation applies to all versions. Figure m and 1.1 m high SiteStar Cabinets Doc. No: D INS-01, Rev I Page 4 of 35

5 1.1 TARGET GROUP The target group for this document is the personnel involved in the site installation engineering process and those responsible for the installation, integration and maintenance of the site. 1.2 DOCUMENTS The following documents are available to provide detailed information on the SiteStar Cabinet and its handling: 1.3 ILLUSTRATIONS D000100/2, SiteStar Cabinet Installation D000100/3, SiteStar Cabinet Maintenance D000100/4, SiteStar Spare Parts Illustrations in this document can show alternative designs. 1.4 PREREQUISITES All performance statement in this document relies on the following: Only approved hardware are used Proper hardware handling 1.5 ABBREVIATIONS Installation and maintenance instructions as well as documentation for external equipment are followed Abbreviations used in this document. AC CB CCU CLU DC DCCU EN ESD Alternating Current Circuit Breaker Climate Control Unit Climate Unit Direct Current Direct Current Connection Unit European Norm Electrostatic Discharge Doc. No: D INS-01, Rev I Page 5 of 35

6 EQ LED PE PSU RoHS SPD WEEE Earthquake Light Emitting Diode Protective Earth Power Supply Unit Restriction of Hazardous Substances Surge Protection Device Waste Electrical and Electronic Equipment 2 DESCRIPTION This section describes the SiteStar Cabinet. 2.1 PRODUCT OVERVIEW The SiteStar Cabinet supports external equipment with battery backup power. The SiteStar cabinet features an active climate solution which maximizes battery lifetime in warm climates and battery capacity in cold climates. SiteStar cabinets are designed for both indoor and outdoor environments, with a unique combination of low thermal conductive materials and a highefficiency climate solution. With an extremely cost-effective cooling technology and a cabinet shell that allows minimal transfer of temperatures, we keep your batteries at optimal operating temperature, with the energy usage equivalent to a single light bulb. This means the SiteStar cabinets offer up to 95% power savings compared to airconditioned cabinets. In case additional battery capacity is required, the SiteStar cabinet can be extended with a second SiteStar cabinet. The system is approved for operation throughout the world. For areas exposed to earthquake risk, the Earthquake Zone 4 Cabinet version shall be considered MAIN FEATURES The SiteStar Cabinet: Is designed for outdoor use Is IP 55 shielded Doc. No: D INS-01, Rev I Page 6 of 35

7 2.1.2 PRODUCT APPROVALS The SiteStar Cabinet complies with the following standards: Transport ETSI EN Class 2.3 Storage ETSI EN Class 1.2 Operation ETSI EN Class 4.1, extended temperature range Chemical and mechanical substances EMC: ETSI EN Class 4.1 EMC directive 2004/108/EC ETSI EN FCC CFR 47 part 15 ICES-003 Safety: CB, CE IEC IEC LVD: Applies only for the AC versions IEC IEC LVD 2006/95/CE IP55 Cooling system Low voltage directive ETL: UL UL UL 50 E UL 1995 Cooling system Doc. No: D INS-01, Rev I Page 7 of 35

8 2.2 UNITS IN THE SYSTEM This section contains descriptions of the units in the system. Figure 2 EQ Zone 4 Cabinet and Cabinet without EQ Zone 4 Reinforcement Key to Figure 2 A Cabinet See section B Earth Grounding See section C Door See section D Climate Control Unit See section E Connection Field See section F Batteries See section G EQ Zone 4 Reinforcement Valid only for the EQ Zone 4 Cabinet See section H Plinth See section Doc. No: D INS-01, Rev I Page 8 of 35

9 2.2.1 CABINET The cabinet structure consists of an inner and an outer liner. The volume between the liners is filled with foam insulation. With this design there is virtually no heat-bridges in the climate insulation and thus giving the cabinet an excellent thermodynamic performance. The top of the cabinet is provided with four M8 threaded holes that are provided for the usage of lifting eye bolts. The roof of the cabinet is designed with a small overhang in the front to protect the top of the environmental seal from direct sunlight and water EARTH GROUNDING The cabinet is equipped with earth grounding points as follows: Cabinet without EQ Zone 4 Reinforcement The cabinet is equipped with a double M8 earth point at each side of the plinth, A in the figure below, for connection to site earth grounding point. Figure 3 Earth Grounding in Cabinet without EQ Zone 4 Reinforcement The PE wire of the incoming AC feed (if any) is terminated in a green/yellow PE terminal located inside the CF, securely connected to the cabinet ground. EQ Zone 4 Cabinet The cabinet is equipped with four earth grounding studs in the bottom of the cabinet, Figure 4, for connection to site earth grounding point. Doc. No: D INS-01, Rev I Page 9 of 35

10 Figure 4 Earth Grounding Studs in EQ Zone 4 Cabinet The PE wire of the incoming AC feed (if any) is terminated in a green/yellow PE terminal located inside the CF, securely connected to the cabinet ground DOOR The door is of the same design concept as the cabinet when it comes to the thermal insulation, with an inner and outer liner and insulation foam in between. The SiteStar Cabinet Door contains the climate unit, the climate control unit and the door locking system. This section describes the: Climate Control Unit Locking System Doc. No: D INS-01, Rev I Page 10 of 35

11 CLIMATE CONTROL UNIT The Climate Control Unit (CCU) is monitoring the temperature inside the cabinet and regulates the Climate Unit (CLU). The external alarm interface on the CCU is wired to the Connection Field, which includes the interface for the outgoing external alarm cables. The control unit and its panel are located at the inside of the bottom part of the door. Figure 5 shows the panel. The panel also exists with an ECO indicator and switch, see Figure 6. Fault indicator is red, Operational green and Information yellow. Figure 5 CCU Panel Doc. No: D INS-01, Rev I Page 11 of 35

12 Figure 6 below shows the CCU panel for Cabinets with Eco mode. Figure 6 CCU Panel with Eco mode Eco and operational indicators are green, test is yellow and fault is red. To the left of the LED indicators a plug is located. Behind the plug, the switch for the eco operation is located LOCKING SYSTEM The doors are equipped with a locking system. As default, the locking system is factory installed at the right side of the door. It is possible to shift the locking installation to right hanging door. See D000100/2, SiteStar Cabinet Installation, for how to do. Doc. No: D INS-01, Rev I Page 12 of 35

13 2.2.4 CONNECTION FIELD This section contains information about the Connection Field (CF) and equipment installed there in. Figure 7 Connection Field Parts Key to Figure 7 A Cable Entries See section B DC Connection Unit (optional) See section C CLU Power Connection Terminal See section D Circuit Breaker See section E Surge Protection Device (SPD) (optional) See section F External Alarm Connection See section CABLE ENTRIES The cabinet is prepared for installation of cable entries at both sides of the connection frame. At delivery the entries are equipped with covers. Doc. No: D INS-01, Rev I Page 13 of 35

14 DC CONNECTION UNIT In cabinets with DC powered CLU the batteries and the CLU can be connected direct to an external power supply unit or through the optional DC Connection Unit (DCCU). The DCCU is a connection point, including fuses, for up to 4 battery strings. Cable lugs for cables up to 95 mm 2 can be used with the DCCU. All connections are M8 studs and the distances between the studs are 1 inch. The DCCU is installed at the bottom of the cabinet, Figure 8. For further information, see D000108, SiteStar DCCU Kit. Figure 8 DCCU Warning! If the SiteStar cabinet is configured without the DCCU, it is of vital importance that the Battery cables are provided with adequate protection at the site to ensure compliance to national wiring regulations. It is recommended to use SiteTel Cables to ensure a safe connection. Risk of personal injury and property damage. Doc. No: D INS-01, Rev I Page 14 of 35

15 CLU POWER CONNECTION TERMINAL The cabinet is equipped with a CLU power connection terminal, at the bottom of the CF, for the connection of power to the CLU CIRCUIT BREAKER The Circuit Breaker (CB) is located at the same DIN rail as the CLU power connection terminal SURGE PROTECTION DEVICE The CF can include an optional Surge Protection Device (SPD) hardware to protect the CCU from over voltage. The SPD is located at the same DIN rail as the CLU power connection terminal EXTERNAL ALARM CONNECTION The system supports sending 3 external alarms. The alarms are sent by relays, connected as normally closed (NC). The external alarms will be trigged by: CLU failure: fan fail or controller fail Temperature: Internal temperature outside regulation window or external temperature outside system specification Door switch open Mains failure The following table shows the connection between the alarm signals and the alarm relays K1, K2, and K3. Alarm Routing K1 K2 K3 Temperature, indoor Temperature, outdoor Fan Door alarm Compressor fail Heater fail CLU Mains failure X X X X X During the startup sequence the external alarm will be triggered several times. X X X X Doc. No: D INS-01, Rev I Page 15 of 35

16 The following figure shows the connections between the alarm D-sub connector and the external connection terminal. Figure 9 External Alarm Outputs Alarm Output Markings Terminal Number Marking 1 K1-NO 2 COM 3 K1-NC 4 Door-NC 5 K3-NC 6 GND V DC 8 Shield Doc. No: D INS-01, Rev I Page 16 of 35

17 Figure 10 shows the physical location and the marking of the external alarm terminal block. Figure 10 Terminal Block Location and Marking Doc. No: D INS-01, Rev I Page 17 of 35

18 2.2.5 BATTERIES The specified performance and warranties stipulate the usage of batteries that have been approved for the SiteStar Cabinet. The table below shows approved battery blocks: Manufacturer Battery Block Designation Battery Block Data NorthStar NSB 100 FT Silver 12 V DC, 101 Ah, AGM 101 Ah NorthStar NSB 100 FT Blue 12 V DC, 84 Ah, AGM 84 Ah NorthStar NSB 100 FT Blue+ 12 V DC, 100 Ah, AGM 84 Ah NorthStar NSB 100 FT Red 12 V DC, 100 Ah, AGM 100 Ah NorthStar NSB 170 FT Silver 12 V DC, 172 Ah, AGM 172 Ah NorthStar NSB 170 FT Blue 12 V DC, 141 Ah, AGM 141 Ah NorthStar NSB 170 FT Blue+ 12 V DC, 170 Ah, AGM 170 Ah NorthStar NSB 180 FT Red 1 12 V DC, 180 Ah, AGM 180 Ah Battery Capacity per -48 V DC String For information about OPzV batteries, see D001490, SiteStar OPzV Battery Installation EQ ZONE 4 CABINET VERSION For areas exposed to earthquake risk, the EQ Zone 4 Cabinet version shall be considered. The EQ Zone 4 Cabinet is a standard cabinet equipped with a factory installed optional EQ Zone 4 reinforcement. The EQ Zone 4 reinforcement consists of: Reinforced wall structure Reinforced shelves Stronger attachment to the foundation 1 Will be replaced with NSB 190 FT Red Doc. No: D INS-01, Rev I Page 18 of 35

19 Figure 11 EQ Zone 4 Cabinet Key to Figure 11 A B C D E Reinforced Wall Structure Reinforced Shelf Front Bar Cross Braces Stronger Attachment to the Foundation PLINTH The cabinet can be equipped with different bottom solutions for the installation to the foundation. Cabinet Without EQ Zone 4 reinforcement With EQ Zone 4 reinforcement With EQ Zone 4 / NEBS reinforcement Mounting Plinth D N/A NSC0001-OPT5 Doc. No: D INS-01, Rev I Page 19 of 35

20 2.3 CUSTOMER EQUIPMENT If customer equipment is to be installed into the cabinet, the heat dissipation must not exceed the values in Table 1. Table 1 Maximum Heat Load SiteStar Tall SiteStar Small DC AC DC AC Maximum Ambient Temperature 1 [ C] P max [W] P max [W] P max [W] P max [W] N/A N/A N/A N/A N/A N/A N/A N/A 45 N/A N/A N/A N/A 50 N/A N/A N/A N/A 1 2 Temperature outside the cabinet Power-outs needs to be considered when designing system. Notes: - If DC cabinets are used in hybrid sites, no additional heat load is allowed. - Cabinets needs to be placed in free air (minimum 1 meter to nearest object). - Sun screen must be used. - If equipment with heat dissipation over 20 W is installed, the system must be tested in the environment where intended to be used. - All configurations with additional active equipment is the responsibility of the system designer. Doc. No: D INS-01, Rev I Page 20 of 35

21 2.4 SIZE AND WEIGHT Area Tall Cabinet Small Cabinet Units Size (l*w*h) Standard Cabinet 782*660* *660*1100 mm Size (l*w*h) EQ Zone 4 Cabinet 782*660*1800 mm Size (l*w*h) EQ Zone 4 / NEBS Cabinet Weight: Standard Cabinet Complete Weight: EQ Zone 4 Cabinet Complete Weight: EQ Zone 4 / NEBS Cabinet Complete 782*660*1813 mm Kg 196 Kg 202 Kg Weight: Mounting Plinth D Kg Weight: Mounting Plinth NSC0001-OPT5 12,5 Kg Weight: Battery Shelf 5 5 Kg Internal load handling for each shelf Kg Doc. No: D INS-01, Rev I Page 21 of 35

22 2.5 SPACE REQUIREMENTS Figure 12 shows the necessary minimum height to roof for raising the 1.8 m high cabinet to standing position. Figure 12 Minimum Height Doc. No: D INS-01, Rev I Page 22 of 35

23 Figure 13 shows the clearance between the cabinet and walls. Figure 13 Cabinet Clearance to Wall Minimum Recommended A 0 mm 10 mm B 20 mm 200 mm C 210 mm 450 mm Doc. No: D INS-01, Rev I Page 23 of 35

24 Figure 14 shows the clearance to the roof when the cabinet is standing up. Figure 14 Cabinet Clearance to Roof Minimum Recommended D 50 mm 200 mm AIRFLOW CLEARANCE Airflow clearance around the cabinet must be secured. 2.6 CLIMATE SYSTEM This section describes the climate system GENERAL The cabinet features a climate system including heating and active cooling systems. The system ensures maximum battery life in cold and warm climates. SiteStar can be set to power-up and operate in one of two modes: Normal Operational Mode Factory Test Mode Doc. No: D INS-01, Rev I Page 24 of 35

25 The mode is selected when the system is powered up based on the state of the door switch. Normal Operational Mode is selected if the door switch is open when the power is switched on and Factory Test Mode if the door switch is closed NORMAL OPERATIONAL MODE In Normal Operational Mode the system operates as follows: Power-up SW initiation Self test Module test Relay test Indicator test Operation Temperature regulation ECO Operation ECO operation (if available) Power-up When the system is powered up in Operational mode, it will automatically initiate the SW s start-up sequence. Self-test The system does a self test at start-up. The start-up sequence is up to 2 minutes long. During the self test, all components in the system are tested, i.e. compressor, fan, heater (if equipped), temperature sensors, etc. The yellow indicator is lit during the self test sequence. After the self-test is completed the system will go into operation mode, or indicate a fail. As the system goes into operation, the yellow indicator will go out, and the green Operational will be lit. Doc. No: D INS-01, Rev I Page 25 of 35

26 After approximately 1 minute in operation mode, Door Alarm is activated. The alarm is revoked 1 minute after closing the door. Operation After the system has completed the self test sequence the system will start to regulate the temperature inside. If necessary the system can be equipped with a heater. If so, the system will remain the optimum temperature for the batteries in sub zero temperatures down to -40 C. ECO Operation Some SiteStar systems have an ECO Operation mode. This mode will reduce power consumption up to 20%. Fail The following fails can be detected: Compressor fail Temperature sensor fail Fan fail Internal Heater fail (if equipped) Over temperature, inside Under temperature, Inside Over temperature, outside FACTORY TEST MODE Factory test mode is only used during factory test before delivery to site and should not be used when the system is installed on site due to long test cycle. In Factory test mode the factory technicians can carefully test the system temperature regulation function. No alarm indications or external alarms are activated in this mode TEMPERATURE REGULATION In normal operation mode the temperature can vary between 21 C and 24 C. In ECO mode the temperature can vary between 10 and 27 C. Doc. No: D INS-01, Rev I Page 26 of 35

27 If the ambient temperature, T a, is above +55 C the temperature alarm will be active.. The cooling system has the following protective functions: Reduced running time for the compressor at high temperature Automatic de-icing Thermal shut down of compressor Temperature limits and functions: The following table shows the regulation functions and temperature limits. Function Temperature Comment DC Cabinet 2 AC Cabinet Cabinet temperature high Cabinet temperature low Compressor reduced cooling power Compressor reduced cooling power Compressor thermal shut down Ambient temperature high +40 C inside cabinet +0 C inside cabinet +55 C inside cabinet +50 C ambient +30 C inside cabinet +5 C inside cabinet +43 C ambient Temperature alarm is sent. Temperature alarm is sent Alarm is still active Alarm is still active +55 C +55 C Temperature alarm is sent +55 C +55 C Temperature alarm is sent De-icing N/A N/A Runs after compressor has been running continuously for 24 hours. De-icing cycle is 30 minutes long. 2 Different limits may apply see documentation delivered with each cabinet. Doc. No: D INS-01, Rev I Page 27 of 35

28 To force the compressor to run, the inside temperature needs to be above 24 C (in normal operation) or 25 C (in ECO Operation) If the outside temperature is too high, the running time of the compressor is reduced to approx 30% (9 minutes running/25 minutes resting) 2.7 OPERATING ENVIRONMENT Operating Environment Highest ambient temperature Lowest ambient temp. (optional heater) Tall Cabinet AC Cabinet Units Small: C Tall: C Humidity 100% 100% RH Air pressure 70 to to 106 kpa Doc. No: D INS-01, Rev I Page 28 of 35

29 2.8 ELECTRICAL PERFORMANCE General Alarm connection Power consumption max at cooling Power consumption max at heating AC powered CLU AC connection Tall Cabinet Small Cabinet Units Individual; CLU, internal and door. D-sub Individual; CLU, internal and door. D-sub W W Tall Cabinet Small Cabinet Units or or V AC Frequency 60 ±5% or 50/60 ±5% 60 ±5% or 50/60 ±5% Hz DC powered CLU Tall Cabinet Small Cabinet Units DC connection -42 to to -60 V DC BATTERY CAPACITY See section on page 18 for batteries and battery capacity. Doc. No: D INS-01, Rev I Page 29 of 35

30 2.8.2 OPERATING CONFIGURATION The table below shows the basic configuration. Replaceable Units Amount Comments Door including Climate Unit 1 Climate only for battery zone Internal battery strings Battery fuse internal (DCCU) Circuit Breaker 4 strings 170 Ah each maximum Maximum four fuses Maximum 405 A totally Maximum 3 x 150 A (F1, F2, F3) Maximum 1 x 250 A (F4) 1 x 20 A (DC powered CLU) 2 x 10 A (AC powered CLU) Depending on battery configuration Depending on battery configuration Three battery strings for external loads One battery string for external load or extension cabinet For the CCU Figure 15 to Figure 19 shows examples of different DC configurations with AC or DC powered CLU, with or without DCCU. Doc. No: D INS-01, Rev I Page 30 of 35

31 Figure 15 DC configuration with DCCU. AC Powered CLU. Doc. No: D INS-01, Rev I Page 31 of 35

32 Figure 16 DC configuration without DCCU. AC Powered CLU. Doc. No: D INS-01, Rev I Page 32 of 35

33 Figure 17 DC configuration with DCCU. DC Powered CLU. Doc. No: D INS-01, Rev I Page 33 of 35

34 Figure 18 DC configuration without DCCU. DC Powered CLU, Connected to External PSU. Doc. No: D INS-01, Rev I Page 34 of 35

35 Figure 19 DC configuration without DCCU. DC Powered CLU, Connected to Internal Batteries CHARGING AND DISCHARGING CHARACTERISTICS Charging and discharging characteristics are defined and controlled by the control system of the external equipment connected to the cabinet. For more information, please refer to relevant documentation for the external equipment. Doc. No: D INS-01, Rev I Page 35 of 35

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

TruPortal Wireless Locks Quick Reference

TruPortal Wireless Locks Quick Reference TruPortal Wireless Locks Quick Reference en-us Introduction This document describes how to connect the following wireless locks to TruPortal hardware: Schlage AD-400, which connects to TruPortal hardware

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand 5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net

More information

NEO XL NEO XL NEO XL POWER SUPPLIES - MADE IN SWEDEN ENGLISH

NEO XL NEO XL NEO XL POWER SUPPLIES - MADE IN SWEDEN ENGLISH NEO 27 50-XL NEO 27 100-XL POWER SUPPLIES - MADE IN SWEDEN ENGLISH Milleteknik supplies reserve power which ensures operation. All our products are designed for optimum operational reliability and long

More information

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1 Lodam Compressor Protection Module Technical manual Version 3.0 SE-G1 Contents 1. Read this first... 4 1.1. Reading instructions... 4 1.2. User manual... 4 1.3. Safety... 4 2. General... 5 3. Definitions...

More information

FIL-SPL Flow-through heater for central heating USER MANUAL

FIL-SPL Flow-through heater for central heating USER MANUAL FIL-SPL Flow-through heater for central heating with 0-10 V EP 15-30 control unit USER MANUAL Kaukora LTD. D106159 r3.0 Contents 1. Important information... 5 Safety information... 5 General... 5 Marking...

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Undercounter Refrigerator Operation Manual i.series and Horizon Series

Undercounter Refrigerator Operation Manual i.series and Horizon Series Undercounter Refrigerator Operation Manual i.series and Horizon Series Blood Bank Models i.series: ib105 (Version B) Horizon Series: HB105 (Version B) Laboratory/Pharmacy Models i.series: ilr105 (Version

More information

Operating instructions Page 12

Operating instructions Page 12 Operating instructions Page 12 Refrigerator with explosion-proof interior container Read the operating instructions before switching on for the first time 7082 271-00 LKEXv 910 Disposal notes The appliance

More information

KM300 Carbon Monoxide Detection System Installation Manual

KM300 Carbon Monoxide Detection System Installation Manual GE Security KM300 Carbon Monoxide Detection System Installation Manual P/N 1068922 REV 2.0 16SEP09 Copyright Copyright 2009 GE Security, Inc. All rights reserved. This document may not be copied in whole

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Fan speed controller Type Saginomiya XGE

Fan speed controller Type Saginomiya XGE Data sheet Fan speed controller Type Saginomiya Fan speed controller stabilizes condensing pressure by changing condenser s fan speed. The controller reduces fan noise and saves energy in low ambient conditions.

More information

1U ULTRA Compact System

1U ULTRA Compact System en atel Supervisory Module SM32 Load 60 00 A IE C60947-2 G B140 4 8.2 CHNT NB1-63 C32 23 0/40 0 V e NaT el OK enatel RM 1848 enatel RM 1848 Battery 60 00A IE C60947-2 G B1 4 04 8.2 CHNT NB 1-63 C32 23

More information

Silent Alert Fire Safe System

Silent Alert Fire Safe System Silent Alert Fire Safe System Technical Manual This manual covers the FSTX-2225-EU Fire alarm interface PG3A-2204-EU Pager FSCH-2226-IN Fire Safe Charger or CH3A-2205-IN Alarm clock charger SW3A-2208-EU

More information

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics... 14 Ex SOLENOID / ALARM DRIVER PRepower 5203B Table of contents Warnings... 16 Safety instructions... 17 Declaration of Conformity... 19 How to dismantle SYSTEM 5000... 20 Application... 21 Technical characteristics...

More information

G4 Pulsed Fiber Laser

G4 Pulsed Fiber Laser G4 Pulsed Fiber Laser OEM Safety and System Integration Manual Module types B1 and B4 Module type B1 - fitted with ILLK beam delivery optic Module type B4 - fitted with ILOC beam delivery optic 1 1 Preface

More information

GPF Dimming Panels. GRAFIK Systems SPECIFICATION SUBMITTAL

GPF Dimming Panels. GRAFIK Systems SPECIFICATION SUBMITTAL DESCRIPTION Controls all Lutron 3-Wire Fluorescent Dimming Ballasts (Hi-Lume, ECO-0, and Compact SE). Provide power and dimming for up to 4 fluorescent circuits. Models available for: 0V: 8 to 4 circuits.

More information

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

INSTALLATION GUIDE. AXIS A1001 Network Door Controller INSTALLATION GUIDE AXIS A1001 Network Door Controller Liability Every care has been taken in the preparation of this document. Please inform your local Axis office of any inaccuracies or omissions. Axis

More information

Installation Manual. Wiegand Interface Unit Four-State (WIU-4) North America T F Asia T F

Installation Manual. Wiegand Interface Unit Four-State (WIU-4) North America T F Asia T F North America T 888 437 3287 F 561 998 6224 Asia T 65 639 19314 F 65 639 19306 Wiegand Interface Unit Four-State (WIU-4) Installation Manual Australia T 61 3 9239 1200 F 61 3 9239 1299 Canada T 800 267

More information

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10

More information

User Manual WMF Cup&Cool WMF Cup

User Manual WMF Cup&Cool WMF Cup coffee wakes up the world User Manual WMF Cup&Cool WMF Cup Add-on Equipment English bistro! 2000S presto! 1400 prestolino! 1300 Model Series 9018 / 9019 Order Nr. 33 0916 1000 Edition 04.2010 General Information

More information

G4 Pulsed Fiber Laser

G4 Pulsed Fiber Laser G4 Pulsed Fiber Laser OEM Safety and System Integration Manual Module types C1 and C2 Module type C1 - fitted with IBeam1 delivery optic Module type C2 - fitted with IBeam2 delivery optic 1 1 Preface Definition

More information

LORAIN CIP 4890/48120 DC Power System

LORAIN CIP 4890/48120 DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet

More information

T3/E3 Fiber Optic Line Drivers

T3/E3 Fiber Optic Line Drivers MT618A-ST-R3 January 2004 MT619A-ST-R2 MT620AE-R2 T3/E3 Fiber Optic Line Drivers CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard.

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard. COMMUNICATOR ET08 User Manual v1.0 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator (gateway) ET08 (further

More information

Interface Modules for SENTRI

Interface Modules for SENTRI EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface

More information

Undercounter Refrigerator Operation Manual

Undercounter Refrigerator Operation Manual Undercounter Refrigerator Operation Manual i.series and Horizon Series Model Group i.series Horizon Series Blood Bank ib105 (Version A) HB105 (Version A) Laboratory/Pharmacy ilr105 (Version A) HLR105 (Version

More information

3M Benchtop Air Ionizer 963E. User s Guide

3M Benchtop Air Ionizer 963E. User s Guide 3M Benchtop Air Ionizer 963E User s Guide 1 Table of Contents Section Page Safety Information...3 1. Description...4 2. Performance...4 3. Power Requirements...4 4. Installation...4 5. Operation...5 6.

More information

Technical Speci fications 220V AC 50Hz or 110V AC 60Hz Accessories operational voltage. 2x 12V / 7Ah sealed lead acid gel batteries

Technical Speci fications 220V AC 50Hz or 110V AC 60Hz Accessories operational voltage. 2x 12V / 7Ah sealed lead acid gel batteries EN54 General Speci fications Advanced analog fire alarm control panel for small or medium installations. Number of zones: 4, 8, 12, 16, 20 or 24. Maximum number of detectors per zone 20. Two wire zone

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301 Refrigeration and Air Conditioning Technical leaflet Electronic controller EKC 201 and EKC 301 RC.5L.A1.02 RC.5L.A2.02 09-1998 Introduction EKC 201 and 301 are used for temperature control compressor control

More information

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

Dimension drawing. Main feature. Dimension (H x W x D) Cooling capacity *Note. Standalone temperature control. Rated voltage.

Dimension drawing. Main feature. Dimension (H x W x D) Cooling capacity *Note. Standalone temperature control. Rated voltage. External door mount HEX100PC series Dimension drawing Features Main feature Unit Specification IP55 waterproof at external side "One touch" dry run test and dust cleaning Dimension (H x W x D) mm (inch)

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

Power Supply Display Module PSDM. Installation and Operation Manual

Power Supply Display Module PSDM. Installation and Operation Manual Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious

More information

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply   - Tel: Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical

More information

Product Manual. TZ Analog Sensors. TZ Sensors 8115CF 8116CF 8117CF 8118CF. Date: January 2015 Document Number: _B

Product Manual. TZ Analog Sensors. TZ Sensors 8115CF 8116CF 8117CF 8118CF. Date: January 2015 Document Number: _B Product Manual Date: January 2015 Document Number: 112409-01_B About TZ Telezygology, Inc. (TZ) is a wholly owned subsidiary of publicly listed intellectual property and technology development company

More information

OMC Ex interface unit. Manual. Version 1.2 August Author: Observator Instruments

OMC Ex interface unit. Manual. Version 1.2 August Author: Observator Instruments OMC-158-2 Ex interface unit Manual Version 1.2 August 2017 Author: Observator Instruments Revisions: 0.1 (October 2016) First issue 0.2 (December 2016) Prototype 0.3 (January 2017) Test release 1.0 (March

More information

Room thermostats with LCD for wall mounting

Room thermostats with LCD for wall mounting s 3 181 RDG100 / RDG110 RDG140 / RDG100 RDG100/H Room thermostats with LCD for wall mounting for fan coil unit applications for universal applications for use with compressors in dx type equipment RDG1

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Satchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES

Satchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES Satchwell DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL DC1100 Specification No. 04-03-105 The DC1100 energy controller is a self configuring optimiser/

More information

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net

More information

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point GMA 313 CO 2 Gas Monitor for one detection point Operations Manual 1194 Oak Valley Dr, Ste 20, Ann Arbor MI 48108 USA (800) 959-0329 (734) 769-0573 www.gfg-inc.com GfG Products for Increased Safety Congratulations

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2017-01-25 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

EC3-X33 Stand-alone Superheat Controller Technical Data

EC3-X33 Stand-alone Superheat Controller Technical Data Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps,

More information

Flame Simulator User Manual. Publication Rev. A

Flame Simulator User Manual. Publication Rev. A Flame Simulator User Manual Publication Introduction This manual contains information for the Flame Simulator from Forney Corporation, 16479 Dallas Parkway, Suite 600, Addison, Texas. www.forneycorp.com

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2018-07-06 2001-2018 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification Dual Technology Wall Switch Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 November 19, 2014 1. INTRODUCTION

More information

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor CellarSafe Carbon Dioxide and Oxygen Safety Monitor Installation and operating instructions for the CellarSafe Monitor and the CellarSafe Calibration Unit M07234 May 2008 Issue 6 Warning Please take care

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

THERMAL MANAGEMENT THERMAL MANAGEMENT. Accessories: GV 400/500 or GV 600/700 AM 420P TRS 60, TRW 60, TWR 60, TKW 60 FILTER FANS SERIES LV

THERMAL MANAGEMENT THERMAL MANAGEMENT. Accessories: GV 400/500 or GV 600/700 AM 420P TRS 60, TRW 60, TWR 60, TKW 60 FILTER FANS SERIES LV FILTER FANS SERIES LV ROOF MOUNTED FAN For the ventilation of control cabinets, enclosures and housings Different filter mats for dust collection LV series offers low shape and quick mounting EMC versions

More information

HR150 SERIES DEHYDRATOR USER MANUAL

HR150 SERIES DEHYDRATOR USER MANUAL HR150 SERIES DEHYDRATOR USER MANUAL Bulletin AE01B-A0595-001 Rev: A 2014 CommScope, Inc. All rights reserved (06/14) Page 1 of 12 HR150 SERIES DEHYDRATOR USER MANUAL Contents Section 1 General Information...

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

User Guide. Luxxor. 35 LED Light Source Fax: Tremont Street, Rochester, New York gradientlens.

User Guide. Luxxor. 35 LED Light Source Fax: Tremont Street, Rochester, New York gradientlens. User Guide Luxxor 35 LED Light Source 207 Tremont Street, Rochester, New York 14608 800.536.0790 Fax: 585.235.6645 REV. 0116 gradientlens.com warnings & cautions Warnings & Cautions PORTABLE CAMERA Luxxor

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Installation and Operation Manual Low Power (LP) DC Power System

Installation and Operation Manual Low Power (LP) DC Power System Installation and Operation Manual Low Power (LP) DC Power System LPS Power Enclosure LPB Battery Enclosure 2051259 R3 Information in this document is subject to change without notice and does not represent

More information

Ultra low temperature freezers. -40 C and -86 C. Green Line

Ultra low temperature freezers. -40 C and -86 C. Green Line Ultra low temperature freezers -40 C and -86 C Green Line by by Ultra low freezer series Brouwer ultra low temperature freezers are available in two temperature ranges: -40ºC and -86ºC. The standard internal

More information

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems LINETRAXX RCMA420 Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems RCMA420_D00059_01_D_XXEN/06.2016 LINETRAXX RCMA420 Residual current monitor for monitoring AC,

More information

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver IP Access Adapters Installation Guide Entrada2DMK - IP Access Adapter Kit Kit Includes: - IP Access Receiver - IP Access Transmitter I.T.E. 43KC Doc. No. IIEntrada2DMK Rev. 062015 More than just power.

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification test to validate the

More information

S304 and S305 Dust Emission Monitors. User Manual. Distributor

S304 and S305 Dust Emission Monitors. User Manual. Distributor S304 and S305 Dust Emission Monitors User Manual Distributor Version 6.4 30/5/2012 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 Principle of operation... 4 2. INSTALLATION...

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL temperature / static pressure DIFF Opn Clo ALARM HI F2 DELAY ALARM LO OPEN DELAY CLOSE ADJUST Varifan + CPS-1 CPS-1 Although the manufacturer has made every

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

5000 Series Rack Panels

5000 Series Rack Panels 5000 Series Rack Panels The operation and functions described in this manual are available from Software Version Mx5000-050-04 onwards. Specifications & Ordering: Models, Sales Order Parts: Mx-5101xR Panel

More information

Table of Content

Table of Content Table of Content 43402001 1. User manual... 2 2. Legal regulations... 2 3. Safety instructions... 3 4. Technical information... 4 5. Functional principle... 5 6. Technical data... 6 7. Mounting... 7 8.

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

Smoke Vent Control Panel PCB4 V4 Installation Manual

Smoke Vent Control Panel PCB4 V4 Installation Manual Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel www.besafedirect.com Page 1 Contents Page 3) Important Regulations, Safety, Maintenance,

More information

OPERATING INSTRUCTIONS MAXIMAT LW CX COMPACT LEAKAGE SENSOR

OPERATING INSTRUCTIONS MAXIMAT LW CX COMPACT LEAKAGE SENSOR Safety Precautions Installation, initial start-up and maintenance may only be performed by trained personnel! The device may only be connected to power which complies with the specifications included in

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

SMART Electronic control for towel radiators

SMART Electronic control for towel radiators SMART is an electronic thermostat for the automatic control of electric towel radiators. By means of an internal sensor it is capable of keeping the temperature of the towel radiator to a desired value.

More information

HEX200PB Heat Exchanger Instruction Manual

HEX200PB Heat Exchanger Instruction Manual HEX200PB Heat Exchanger Instruction Manual USA 46101 Fremont Blvd, Fremont, CA 94538, U.S.A. TEL : 1-510-668-5100 FAX : 1-510-668-0680 Cabinet-Thermal-Solutions@deltaww.com Taiwan Delta Electronics, Inc.

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

EW 40 Wireless Fan Control

EW 40 Wireless Fan Control Installation & Operating Manual EW 40 Wireless Fan Control USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS APPLICATION OVERVIEW Control and monitoring systems can play an essential role in heat tracing applications which

More information

Retroreflective sensor with polarization filter

Retroreflective sensor with polarization filter Dimensions 45 49 Receiver 27 74 Emitter 92 56 23 6 x 9 slots S 23 25 32 Internal thread (1/2-14 NP) External thread (M30 x 1.5) ø 6 mm Cable 10 Model Number Retroreflective sensor with fixed cable Features

More information

Unison Echo Contact Interfaces

Unison Echo Contact Interfaces GENERAL INFORMATION Distributed system integration - Echo Contact Interfaces are available with 4-Input, Demand Response or 4-Output versions that provide simple and seamless integration with other control

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

LORAIN CSP DC Power System

LORAIN CSP DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides more space for revenue generating equipment Constant power delivers more current at lower voltages to meet load or recharge

More information

Rack Mount Series Installation Guide

Rack Mount Series Installation Guide Rack Mount Series Installation Guide Models Include: Maximal1RHV Maximal1RV - 12VDC @ 4 amp or 24VDC @ 3 amp. - 12VDC @ 4 amp or 24VDC @ 3 amp. - Eight (8) Fuse Protected Outputs. - Sixteen (16) Fuse Protected

More information

Galaxy Pulsar Plus Digital Battery Plant Controller

Galaxy Pulsar Plus Digital Battery Plant Controller Galaxy Pulsar Plus Digital Battery Plant Controller Features Supports up to 60 Power Modules rectifiers and converters Supports dual voltage plants, with rectifiers and converters Auto-sensing dual voltage

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions Approvals / Certifications Hazardous Locations Class I, Division 2 Groups A, B, C, D Touch 1500-HAZ-CPU and Touch 1500-HAZ-TS

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

47LV BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL DC INPUT DIGITAL PANEL METER MODEL. (4 1/2 digit, LED display type)

47LV BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL DC INPUT DIGITAL PANEL METER MODEL. (4 1/2 digit, LED display type) INSTRUCTION MANUAL DC DIGITAL PANEL METER ( / digit, LED display type) MODEL LV BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

SecuriFire SecuriLine extended board B5-DXI2

SecuriFire SecuriLine extended board B5-DXI2 SecuriFire SecuriLine extended board B5-DXI Technical description Securiton AG Alpenstrasse 0 305 Zollikofen Switzerland T 8 3 en c Imprint Imprint This document, T 8 3, is valid only for the product

More information