APPENDIX E LIGHTING CONTROL DATA

Size: px
Start display at page:

Download "APPENDIX E LIGHTING CONTROL DATA"

Transcription

1 APPENDIX E LIGHTING CONTROL DATA

2 P o w e r P a c k s B Power and Auxiliary Relay Packs Fully selfcontained transformer and relay Snaps in for easy installation Plenum rated Essential component for ceiling mounted occupancy sensor Overview Power packs provide 24VDC operating voltage to all Watt Stopper 24VDC occupancy sensors and LightSaver controllers. Auxiliary relay packs are similar to power packs but have no transformer power supply, only an isolated relay. Power packs consist of a transformer and highcurrent relay combined in one small, powerful package. The transformer has a primary high voltage input and a secondary, low voltage output (24 VDC,115 ma, 114 ma with relay connected). The secondary voltage provides operating power to Watt Stopper sensors. When the occupancy sensors detect motion or light sensors detect inadequate ambient light, they electrically close an internal circuit which sends 24 VDC back to the power or auxiliary relay packs that control the lighting system. Plenum rated Power packs are UL 2043 plenum rated with teflon coated low voltage leads and plenum rated plastic. This means that they do not need to be installed in the junction box, but can be installed in the plenum. Power and auxiliary relay packs are housed in ABS, ULrated 94V0 plastic enclosures. Applications The Watt Stopper s power and auxiliary relay packs are designed to be flexible enough to control almost any lighting or HVAC load. For example, power packs can control lighting circuits, selfcontained air conditioners, pumps, fans, motors, VAV systems, motorized damper controls and setback thermostats. They are excellent for any application which requires high voltage switching through low voltage controls. By linking power packs and sensors, an almost unlimited number of configurations can be obtained. Features Selfcontained transformer relay system Available for 120, 220 to 240, 277 and 347 volt systems Capable of switching up to 20 Amps of electrical load (ballast) Installation in Jbox not required UL2043 Plenum rated plastic Low voltage leads are teflon coated for use in plenum applications Can be used as a low voltage switch for other applications or as standalone low voltage switch 1/2 inch snapin nipple attaches to standard electrical enclosures via 1/2 inch knockouts

3 P o w e r P a c k s Power Pack Technical Information Secondary voltage of 24 VDC Secondary output of 150 ma, 114 ma with relay connected Low voltage leads are rated for 300 volts ULrated 94V0 plastic enclosure ABS UL 2043 plenum rated plastic and wiring Dimensions: 1.6" x 2.75" x 1.6" (41mm x 70mm x 41mm) with a 1/2 inch snapin nipple UL and CUL listed; Five year warranty Installation Diagram & Schematic Power Pack Installation Power Pack Schematic White Neutral Red (+24 VDC) Black (Hot) Black (COM) Red Power Pack High voltage connection made inside Jbox Red (High Voltage) (Low Voltage) Blue (+SW) Wiring Diagrams Power Pack with Ceiling Sensor Neutral Hot White Black Power Pack Red Red Load Load Auxiliary Relay Pack with Sensor N White Hot Black Power Pack RED BLK BLU White (neutral) Red (line) Red (load) Off Switch BLU Control Output BLK Common RED +24VDC L O A D Red Black Blue 24VDC Sensor Switch Hot BLK Slave Pack BLU Red (load) Red (line) Off Switch Occupancy Sensor L O A D Neutral Low Voltage Switching 3Way Low Voltage Switching N White Hot Black Red Red +24 VDC Red Common Black 24 VDC SL Blue * 3Way Switches Low Voltage System Control N White Hot Black Red Red +24 VDC Red Common Black 24 VDC SL Blue * Power Pack 3Way Switches Power Pack *Capacitor between Red and Black 220 µf, 35 V Control Panel or Switch Ordering Information Installation Notes The Watt Stopper, Inc. Pub. No Input Load Ratings Catalog No. /Type Voltage Ballast (A) Incan (A) Motor (HP) Output B120EP Power Pack B277EP Power Pack B230EP Power Pack B347DP Power Pack S120/277/347EP Relay Pack 120 VAC; 60 Hz 277 VAC; 60 Hz VAC; 5060 Hz 347 VAC; 60 Hz 120/277/347 VAC; 60 Hz /20/ // // 24 VDC; 150 ma** 24 VDC; 150 ma** 24 VDC; 150 ma** 24 VDC; 150 ma** Power packs are white; auxiliary relay packs are black. **Output is 150 ma before relay is connected and 114 ma after relay is connected. 1. All Watt Stopper power packs should be installed in accordance with state, local, and national electrical codes and requirements. 2. Power packs are designed to attach to existing or new electrical enclosures with 1/2 inch knockouts. (Check electrical codes in your area.) 3. Most applications require UL listed, 1822 AWG, 3conductor, Class 2 cable for low voltage wiring. For plenum return ceilings use UL listed plenumapproved cables.

4 P o w e r P a c k s Special Power Packs & Supplies Overview AT Power Supply The Watt Stopper has several power packs and power supplies that fill the needs of a variety of special applications. These products can help to make a lighting control installation more cost efficient and flexible. AT Power Supplies The AT120 and AT277 power supplies provide up to 800 ma of 24 VDC to Watt Stopper occupancy sensors and control products. The units are designed for applications where many sensors are being used. They contain a transformer and no relay. Watt Stopper power and/or auxiliary packs are needed to do the switching. The AT120 and AT 277 are useful in large, open office applications and in large warehouses. AT & Wiring Up to 800 ma of 24 VDC power Secondary voltage of 24 VDC Housed in NEMA 1 enclosure Black (HOT) White (NEUTRAL) (High Voltage) U1 Red (+24VDC) Black (COM) (Low Voltage) Form C Power Pack Form C Power Packs The Form C power packs contain a single pole, doublethrow isolated relay with a normally open and normally closed output. These power packs can be used with a standard occupancy sensor to interface with HVAC or other systems. Special attention needs to be made to the load ratings as they vary and are significantly lower than standard power packs. Form C & Wiring Up to 100 ma of 24 VDC power before relay is connected; 64 ma after relay is connected Secondary voltage of 24 VDC UL rated 94V0 plastic enclosure with snapin installation Neutral (WHT) Hot (BLK) Normally Open (RED) Common (BRN) Normally Closed (BLU) +24 VDC (RED) COM (BLK) +SW (BLU) (High Voltage) (Low Voltage) 2 Relay Power Pack 2 Relay Power Packs The Watt Stopper CSeries power packs contain 2 isolated relays. These power packs can be used where 2 circuits need to be controlled at the same point. They provide a convenient alternative to using 2 power packs thus reducing installation time and costs. They are also useful where installation space is limited. 2 Relay & Wiring Up to 150 ma of 24 VDC power before relays are connected; 114 ma after single relay is connected, 78 ma when both relays are connected Secondary voltage of 24 VDC Housed in 4 metal junction box Black (HOT) White (NEUTRAL) Yellow LOAD 1 Yellow Red (+24 VDC) (150mA) Black (COM) Yellow (+SW1) LOAD 2 Orange Orange Orange (+SW2) Ordering Information (High Voltage) (Low Voltage) Input Load Ratings Catalog No. /Type Voltage Ballast (A) Incan (A) Motor (HP) Output AT120 AT277 A120CP A277CP C120EP C277EP Power Supply Power Supply Form C Power Pack Form C Power Pack 2 Relay Power Pack 2 Relay Power Pack 120 VAC, 60 Hz 277 VAC, 60 Hz 120 VAC, 60 Hz 277 VAC, 60 Hz 120 VAC, 60 Hz 277 VAC, 60 Hz 8NO/5NC 6NO/3NC 20** 20** 5NO/3NC 5NO/2.5NC 13** 1NO/.25NC 2NO/.5NC 1** 24 VDC; 800 ma 24 VDC; 800 ma 24 VDC; 100 ma* 24 VDC; 100 ma* 24 VDC; 150 ma 24 VDC; 150 ma *Contains an isolated relay with normally open (NO) and normally closed (NC) contacts.**rating per relay. Pub No. 6802

5 Basic Relay Panel Lowvoltage switching platform Userselectable number of factory installed relays Direct control of individual relays by switches or occupancy sensors Optional automation modules for indoor and outdoor control applications Automation modules accept contact closure from switch, timeclock, or security system for scheduling input UL and CUL listed, one year warranty System Basic Features Applications Modular in design, The Watt Stopper basic relay panel provides automated lighting control from a low voltage switching platform. Users can implement exterior and/or interior control with one or more automation modules. The basic relay panel consists of a tub and cover, power supply, and panel interior with relays. Users can select the number of relays needed (in multiples of four). The tub, cover, and power supply provide the basic housing and power components. The panel interior provides the mounting framework for the system s relays, power supply, and the optional automation modules. Users can select the panel configuration with up to 12, 24, or 48 relays, depending on the size and complexity of their application. Each lighting load is wired through a relay, which can be controlled by either a lowvoltage switch or an occupancy sensor. Users may select optional automation modules for additional functionality. The Basic Indoor Controller (HBIC12BC) offers Master ON/OFF control for a group of 12 relays, as well as options for selectable time delays, blink warnings for individual overrides, and automatic ON for the whole group. At the same time, it retains individual switch overrides for each relay. The Indoor Controller utilizes an occupied/unoccupied (regular business hours/after hours) approach, and accepts scheduling input from timeclocks and building management systems. For outdoor lighting, the Basic Outdoor Controller provides simple, photocellbased control for security, parking, and signage lighting. The Controller package includes an exterior photosensor that detects natural light levels that, in turn, trigger ON or OFF control signals. Other optional components include the Basic Switch Interface, which enables any 2 or 3wire maintained or momentary input to control a group of relays (up to 12) while retaining individual switch overrides. The Basic relay panel provides a flexible way to achieve essential interior and exterior automated lighting control, and provide the conveniences of low voltage switching.

6 Relay Panel Technical Information Panel Checklist Panel Options Panels available in 12, 24, or 48relay configurations Direct switch to relay control Userselectable number of factoryinstalled relays (multiples of four) Optional automation modules for interior and exterior control applications Basic Indoor Controller includes options for adjustable time delay, blink warning, and Auto ON, accepts contact closure from switch, timeclock, or security system for scheduling input Exterior control capabilities include a single photocell input for three separate outputs providing ON/OFF control for security, parking with optional egress delay, and signage lighting Basic switch interface module allows any switch input to drive a momentary relay output UL and CUL listed, one year warranty A basic relay panel includes the following: group Catalog No. Panel interior Power Supply Tub Cover HINxxy12BC HINxxy24BC HINxxy48BC HPSM115/277 HTUBxx HCVRxxSL HCVRxxFL Basic relay panel interior (12.25 W x H x 4.38 D) Basic relay panel interior (15.88 W x H x 4.38 D) Basic relay panel interior (15.88 W x H x 4.38 D) Power Supply 115/277 VAC Tub Enclosure for 12, 24, or 48relay system (specify 12, 24, or 48 relays in place of xx in product catalog number) Enclosure cover for 12, 24, or 48relay tub; Surface mount, lockable (Specify # of relays in place of xx in catalog number) Enclosure cover for 12, 24, or 48relay tub; Flush mount, lockable (Specify # of relays in place of xx in catalog number) Optional panel enhancements include: Automation Modules Other HBIC12BC HPCP3BC HUSM12BC Basic Indoor Controller Basic Outdoor Controller with photosensor Basic Switch Interface Wiring Diagrams Relay Panel with Basic Indoor Controller Relay Panel with Basic Outdoor Controller Basic Indoor Controller Individual 3 3 occupant switch Photocell Security Parking Occupied contacts Signage Timeclock or building management system Basic Outdoor Controller System Layout Relay Panel with Automation Modules Photocell Interior lighting Exterior lighting Basic relay panel The Watt Stopper, Inc. Pub. No Basic Indoor Controller Basic Outdoor Controller

7 O c c u p a n c y S e n s o r s D T200 Dual Technology Sensor Combines passive infrared and ultrasonic t e c h n o l o g i e s Builtin light level s e n s o r Accepts low voltage switch input for manualon operation SmartSet automatically selects optimal settings for each space Walkthrough mode increases savings potential Overview The Watt Stopper s DT200 Dual Technology occupancy sensors combine passive infrared (PIR) and ultrasonic technologies into one unit to achieve precise coverage. The DT200 turns lighting on when both PIR a n d ultrasonic technologies detect occupancy. It can also work with a low voltage switch for manualon operation. PIR technology senses the difference between infrared energy from a human body in motion and the background space. Ultrasonic technology uses the Doppler Principle and high frequency (40 khz) ultrasound to sense motion within the space. Once lighting is on, detection by either technology holds lighting on. When no occupancy is detected for the length of the time delay, lighting turns off. The DT can also be set so that only one technology is needed to trigger lighting on or both technologies are needed to hold lighting on. The sensors are low voltage and utilize a Watt Stopper power pack. SmartSet Using SmartSet technology, the DT200 sensors require no adjustment at installation. SmartSet monitors the controlled space to identify usage patterns. Using this information, it automatically adjusts the time delay and sensitivity for optimal performance and energy efficiency. The sensor assigns short delays (as low as 5 minutes) for times when the space is usually vacant, and longer delays (up to 30 minutes) for busier times. Applications The Watt Stopper dual technology sensors have the flexibility to work in a variety of applications. Mounted at 10 feet, the sensors can cover up to 2000 square feet of walking motion and 1000 square feet of desktop motion. The sensors are designed to control lighting in difficult applications, such as classrooms, where one technology alone could encounter false triggers. In addition to classrooms, the DT200 works well in warehouses, large offices, open office spaces, and computer rooms. Features Advanced control logic based on RISC microcontroller provides: Detection Signature Processing eliminates false triggers and provides immunity to RFI and EMI SmartSet automatically adjusts sensitivity and time delay settings to fit occupant patterns Walkthrough mode turns lights off 3 minutes after the area is initially occupied ideal for brief visits such as mail delivery Available with builtin light level sensor featuring simple, onestep setup Sensors work with low voltage momentary switches to provide manual control LEDs indicate occupancy detection 8 occupancy logic options give users the ability to customize control to meet application needs Available with isolated relay for integration with BAS or HVAC Swivel mounting bracket for convenient corner mounting to wall or ceiling

8 O c c u p a n c y S e n s o r s D T200 Technical Inform a t i o n 24 VDC/VAC and halfwave rectified AC 40 khz frequency ultrasonic transmission Time delays: SmartSet (automatic), fixed (5, 10, 15, 20, or 30 minutes), walkthrough, testmode Sensitivity adjustment: SmartSet (automatic) or reduced sensitivity (for PIR sensitivity); ultrasonic sensitivity is variable with trimpot Builtin light level sensor (DT200) works from 2 to 200 footcandles Low voltage, momentary switch input for manual operation DT200 contains an isolated relay with N/O and N/C outputs; rated for 1 Amp at 24 VDC/VAC 2000 sq ft of walking motion mounted at 10 ft; 1000 sq ft of desktop motion Units per power pack: DT200: up to 2 (B), up to 3 (BZ); DT205: up to 3 (B), up to 4 (BZ) Dimensions: 4.4" x 3.4" x 2" (110.3mm x 85.9mm x 49.6mm) LxWxD UL and CUL listed; Five year warranty Wiring & Mounting Wiring Diagram Mounting A swivel mounting bracket, attached to the sensor, allows the sensor to be angled for wal or ceiling mounting. Grooves on the bracket help to achieve desired angle for coverage. Controls Wiring diagram includes bilevel control and manualon option with momentary switch DIP Switch Settings Coverage Coverages shown are maximum and represent halfstep walking motion. Under ideal conditions, with no barriers or obstacles, coverage for halfstep walking motion can reach up to 2000 sq ft while coverage for typical desktop activity can reach up to 1000 sq ft. Ordering Information The Watt Stopper, Inc. Pub. No Catalog No. Voltage Current Coverage DT200 DT205 Dual technology sensor, fullfeatured; dense wide angle lens Dual technology sensor; dense wide angle lens 24 VDC 24 VDC 43 ma 35 ma up to 2000 sq ft up to 2000 sq ft All units are white and use Watt Stopper power packs. Current consumption can be slightly higher when only one sensor per power pack is used.

9 D a y l i g h t i n g C o n t r o l s LS301 Dimming Photo s e n s o r Automatic dimming based on ambient light levels All setup performed remotely with handheld Controls standard 010 VDC electronic dimming ballasts Optional occupant adjustment via handheld remote Single zone control Closed loop daylighting control PROJECT LOCATION/TYPE Overview The LightSaver LS301 is a ceiling mount, low voltage indoor photosensor that works with standard, 010 VDC electronic dimming ballasts to dim lighting as daylight increases. The LS301 mounts on a ceiling and utilizes a spectral filtering system to measure daylight and electric light levels. A closed loop daylighting system, the LS301 measures the total light level from daylight and electric light in the controlled area to adjust electric lighting levels. As the daylight contribution increases, the lights dim down. The photosensor utilizes sliding setpoint control, which responds to the different spatial distribution qualities of electric light and daylight. The LS301 calculates the required light level for current daylight contribution based on two setpoints. One represents the target level when no daylight is present (night setpoint) and the other when significant daylight is present (day setpoint). Adjustment via Handheld Remote Control All LS301 adjustments are made with one of two handheld remotes. The LSR301S provides five buttons for initial setup, which is easily completed by first raising or lowering electric light levels to desired levels, then programming this target level into the photosensor. The LSR301P provides three buttons for occupants to adjust light levels. With this optional tool, users can increase target light levels by up to 25% or reduce them to the lamp/ballast minimum level. Pressing the Auto button returns the control to programmed levels. Applications The LS301 is designed to blend into its surroundings when installed in any environment. It provides one zone of daylighting control in a private office or classroom. In these applications, the LS301 can be combined with an occupancy sensor. Often, it is possible for the LS301 to share a single power pack with occupancy sensor(s). Features Provides precise control of lighting to maintain desired light level Extremely linear photocell response with greater than 1% accuracy Designed to measure light as the human eye perceives it, eliminating overreporting illumination levels provided by daylight Separate handheld remote controls for setup and occupant adjustment to prevent tampering Boosts energy savings by reducing maximum lamp output, often resulting in a 20% reduction or more compared with lights at full output Achieves lumen maintenance by holding target light level as lamp output decreases over time

10 D a y l i g h t i n g C o n t r o l s Controls LS301 Te c h n i cal Info r m a t i o n Full range dimming:.2 VDC (minimum) to 10 VDC (100% lighting) output voltage Current consumption: VDC In typical applications, setpoints are adjustable from 2060 footcandles ( lux) Controls up to 50 standard dimming ballasts in one zone Sensor leads: gray and violet to ballast, red and black to 24 VDC Dimensions: 2.35 diam. x depth (60mm x 22mm), threaded piece extends 1.25 (31.8mm) from back, fits.5 knockout 5 year warranty Remote Controls Nighttime setpoint Spectral Response Curve Button activation LED Auto button for a u t o m a t i c d i m m i n g R a i s e / l o w e r light levels L S R S Daytime setpoint L S R P Wiring & Installation Remote handheld (above left) enables easy setup while optional occupant remote provides adjustability for individual lighting preferences. Wiring The spectral response of the LS301 photocell closely matches the sensitivity of the human eye. Mounting and Installation Coverage Placement Guidelines Mount photocell between 6 and 12 feet (1.8m 3.7m) from w i n d o w. Do not mount directly above direct/indirect pendant fixtures. Mount at least 4 feet (1.2m) from pendant fixtures. Ordering Information Catalog No. Output Voltage LS301 LSR301S LSR301P Dimming Photosensor Setup Remote Control (2 AAA batteries included) Occupant Remote Control (2 AAA batteries included).2 VDC (min.) to 10 VDC (max.) Watt Stopper/Legrand Pub. No

11 D a y l i g h t i n g C o n t r o l s L i g h t S a ve r LCD203 Dimming Contro l le r Low voltage automatic dimming control module Three control channels with individually programmable s e t t i n g s LCD display of photocell r e a d i n g s Optional wall switch override for manual control Pushbutton programming and automated setup Open loop control PROJECT LOCATION/TYPE Overview The Watt Stopper LightSaver LCD203 daylighting controller provides automatic dimming control for fluorescent and HID fixtures. It is an open loop controller providing up to three zones of control from a single photocell. It also integrates with occupancy sensors and accommodates individual occupant overrides via an optional wall switch. The LCD controller is part of a system that includes the LS290C photocell and the BT203 Power Pack. Each of the LCD controller s three channels has a 010 VDC output and connects to its own dedicated relay in the power pack. The photocell measures daylight and transmits the data to the controller. Each channel in the controller raises or lowers light levels, while the respective relays in the power pack switch lighting on or off. When daylight is adequate for a channel to fully dim, lights switch off after an adjustable time delay. This capability can be disabled for zones where lighting should remain on. Multiple Channel Control To achieve balanced dimming control, users group fixtures receiving comparable daylight levels into up to three control groups or zones. Zones closest to the daylight source are dimmed the most, while zones further away from the daylight source dim less. Unused channels may be disabled. Applications The LCD controller is suitable for a wide range of applications, such as open office areas, classrooms, retail stores, and any application with skylights. It is particularly suitable for applications that require independently dimming fixtures in adjoining zones. The load shedding capability can further reduce light levels during critical periods or during periods of reduced occupancy. If an occupancy sensor is used, its nonoccupancy signal initiates dimming by the LCD controller prior to turning lighting off. Features Simplified setup and calibration Optional dimming wall switch (LS4C) provides manual dimming and ON/OFF control so users can adjust lighting as desired Seven individually adjustable parameters for each channel: setpoint, minimum output, maximum output, ramp rate, fade rate, cutoff time delay, load shed limit Menudriven, pushbutton programming without special tools Automatic internal calculation for dimming requirements of individual channels for simplified setup DIN rail mounting California Title compliant

12 D a y l i g h t i n g C o n t r o l s System Layout & Wiring LCD Te c h n i cal Info r m a t i o n Class 2 low voltage device Compatible with standard 010 volt dimming b a l l a s t s Supports up to 50 ballasts per dimming channel Photocell range from 3 6,000 footcandles (30 64,000 lux) Programmable dimming and fade rates from 560 seconds Selectable cut off delay from 020 minutes or can be disabled LCD System Layout Programmable minimum output from 04VDC Programmable maximum output from 610VDC Load shed output from 010 VDC Setpoint range from 560 fc 24VDC supply voltage provided by BT203 Control output voltage to ballasts 010VDC Dimensions: 3.5 x 2.81 x 2.5 (89mm x 71mm x 64mm) LxWxD UL and CUL listed; five year warranty The LCD Dimming Control System consists of an LCD control module, an LS290C photocell, and a BT203 power pack. Users may add options to the system to increase functionality, such as the LS4C wall switch and occupancy s e n s o r s. LCD203 Wiring and Settings Ordering Information Watt Stopper/Legrand Pub. No Catalog No. Voltage Control Channels LCD203 LS290C BT203 Dimming control module Photocell footcandle range Power Pack 24 VDC t h r e e Dimming control system options: group Catalog No. Switch Enclosure LS4C LSE8 LSE12 Wall Switch Screwcover enclosure 8 x 8 x 4 (203.2mm x 203.2mm x 101.6mm) Screwcover enclosure 12 x 12 x 4 (304.8mm x 308.8mm x 101.6mm)

13 D a y l i g h t i n g C o n t r o l s L i g h t S a ve r LS290C Photo ce l l Photocell for LightSaver LCD203 and LCO203 c o n t r o l l e r s Mounts vertically or h o r i z o n t a l l y Footcandle range from Architecturally attractive d e s i g n PROJECT LOCATION/TYPE Overview The Watt Stopper LightSaver LS290C photocell provides the daylight data necessary for operation of the LCD203 and LCO203 daylighting control systems. Utilizing a photodiode element, the LS290C continuously measures ambient light levels. The sensor is positioned to see incoming daylight from either a window or skylight without seeing electrical light. Users select the applicable footcandle range by a jumper beneath the front cover. Photocell Placement Three jumperselectable footcandle ranges: fc, fc, fc Protective hard plastic cover 3 conductor 22 AWG twisted cable equal to Belden 8443 Maximum wire length is 250 feet (76.2m) Low voltage, Class 2 device Dimensions: 2 diameter x 1.2 deep (50.8mm diameter x 30.5mm deep) UL and CUL listed, five year warranty Installation and Wiring Ordering Information Catalog No. LS290C Photocell Footcandle range (32 64,000 lux) Pub. No. 9605

14 D a y l i g h t i n g C o n t r o l s L i g h t S a ve r BT203 Power Pa c k Power pack for LightSaver LCO203 and LCD203 c o n t r o l l e r s Quick connect to LCD203 and LCO203 control modules Three relays DIN rail mount Fully selfcontained transformer PROJECT LOCATION/TYPE Overview The Watt Stopper LightSaver BT203 Power Pack powers the LightSaver LCO203 and LCD203 control modules. Voltages: VAC, 50/60 Hz Secondary power: 1 24 VDC 3 normally open relays, or 277 VAC Dimensions: 2.76 x 3.57 x 2.36 (70.0mm x 90.5mm x 60.0mm) LxWxD UL and CUL listed, five year warranty The BT203 supplies low voltage power to LCO and LCD controllers. It connects via a quick connect cable. It has three normally open relays used to switch line voltage in response to signals from the connected controller. In addition, the power pack has an automatically resetting fuse. If the current drawn from the BT203 exceeds the specifications, the +24VDC output will turn off and the LED w i l l turn off. Upon removal of the fault condition and primary power, the BT203 will restore the power. Wiring & Mounting Mounting Wiring Catalog No. Input Voltage Output BT203 Power Pack VAC, 50/60 Hz 1 24 VDC Pub. No. 9804

15 D a y l i g h t i n g C o n t r o l s L i g h t S a ve r LS4C Wall Switc h Wall switch for LCD203 or LCO203 controllers Manual dimming or manual ON/OFF switching Automatic mode LED indicator Low voltage operation; Class 2 device Manual mode LED i n d i c a t o r Includes colorcoded leads PROJECT LOCATION/TYPE Overview & Installation The Watt Stopper LightSaver LS4C wall switch allows occupants to override automatic daylighting control. It provides manual dimming when used with LCD203 controllers or ON/OFF switching when used with LCO203 or LCD203 controllers. The LS4C has four buttons and two LED indicators. One LED indicates the lights are being manually overridden and the other that they are dimming automatically. Pressing the I/O button puts the controller into manual mode and switches the lights on or off. Pressing and holding the up or down button increases or decreases light level. All three channels are dimmed or switched in unison. The Auto button switches the controller into automatic operation. Wiring is 7 conductor 18 AWG twisted cable (equal to Belden 8467) Maximum wire length from controller is 150 feet (45.72m) Dimensions: 4.88 x 3.13 x.38 (124mm x 80mm x 10mm) LxWxD U L and CUL listed, five year warranty Applications When an LS4C is used with a controller and an occupancy sensor, manual overrides terminate when occupancy ends. When occupancy resumes, the controller automatically resumes automatic control. Up to four LS4C switches may be wired to a single controller for multiway switching. With customizable dimming and switching control, the LS4C is ideal for applications such as classrooms, offices, and conference rooms. Installation & Controls A u t o m a t i c M a n u a l ON/OFF toggle Lower Lights Wiring Diagram Raise Lights Ordering Information Catalog No LS4C Wall Switch Pub. No LCD Wiring LCO Wiring

16 L i g h t i n g C o n t r o l P a n e l s E M P h o t o c e l l Low voltage photocell automatically turns lighting on and off Mounts on building exterior or roof Compatible with all Watt Stopper lighting control panels and power packs Simple to wire and install Raintight gray plastic enclosure Adjustable aperture window for varying ON setpoint Overview Ordering Information The EM is a low voltage photocell used for controlling exterior lighting. It works with Watt Stopper power packs and lighting control panels (Lighting Integrator and LP series panels) by signalling a change in light levels to the panel. Typically mounted so the light level window faces the northern sky, the EM photocell provides an ON signal when the ambient light level drops below a preset dark setpoint. It then provides a signal OFF as the ambient light level rises above the preset light setpoint. The setpoint can be changed for specific applications by opening and closing the photocell s aperture window. Normally, a lighting control panel or a power pack supplies power to the photocell. The photocell s relay contact red wires are connected to the panel or to a low voltage controlled load footcandle range ( lux) Isolated relay contacts 1 30 VAC/VDC Power input: 24 VAC, 1 VA or 24 VDC, 1 VA Dimensions: 2.64 x 1.57 x 1.89 (67.1mm x 39.9mm x 48.0mm) One year warranty Catalog No. Voltage EM24A2 Exterior photocell 24 VAC EM24D2 Exterior photocell 24 VDC Pub. No Features One set of normally open, isolated relay contacts; contacts are closed when sensed light level is below dark setpoint, open when light level is above light setpoint 8second time delay and builtin setpoint deadband prevent cycling 1/2 threaded male conduit base for easy mounting on conduit fittings or junction boxes. Wiring Mounting

17 Basic Control System System Basic Features Applications Linevoltage multicontactor panel for interior and exterior lighting control Automated facilitywide control combined with flexible local occupant control Eight channel outputs to normally closed contactors Optional System Clock for timescheduled or astronomic control Compatibility with AS110 Automatic Control Switches Optional photocell for exterior lighting control UL and CUL listed, one year warranty The Watt Stopper Basic Control contactor panel combines multipole contactors with a system clock in a preassembled, easytoinstall panel. The system provides linevoltage control for interior and exterior lighting. Modular in design, a Basic Control contactor panel consists of a tub, cover, and panel interior that contains the contactors and system clock. The contactors respond to control signals from the system clock to make and break power to lighting circuits, turning lights on and off. Using fourpole contactors, the Basic Control panel controls both single and multiphase lighting loads. The system clock provides both scheduled and astronomic signals. Users may control up to eight separate groups of lighting, defining the parameters of each control channel independently. Basic Control panels utilize normally closed contactors so the system reliably provides power to lighting. Accompanying each of the Basic Control s eight control channels are LED indicators and ON/OFF/Auto switches. The latter enable users to remove a channel from the system s automatic operation and place it in a manual mode. When used with a System Clock, these panels also feature eight individual override inputs, which can be used to connect external devices, such as photocells, occupancy sensors, switches, or other building control systems, to the panel. Administrators can configure these inputs to control any combination of channels. The panel also provides an auxiliary power source (24 VAC and VDC) for external devices. For expandability, the panel includes eight terminals that can be used to connect additional panels (in a multiple panel system, the main panel must include a System Clock while expansion panels do not). For exterior lighting control, users can utilize the System Clock for astronomic control or add the optional photocell for photosensitive control. For interior lighting control, users can implement optional AS110 Automatic Control Switches. These switches automate after hours shut off of lighting for basic code compliance while providing occupants with manual override control to keep needed lighting on. The Basic Control system offers users simple, effective control for indoor and outdoor applications. Because the panel interiors are preassembled, design and installation are greatly simplified. Basic Control contactor panels are ideal choices for any type of exterior lighting, such as parking lot lighting, site night lighting, sign lighting, and more. Their use promotes energy savings by turning off outside lighting when not necessary, as well as providing a secure illuminated environment when occupants might be present. For interior lighting, Basic Control panels provide effective shut off control with the builtin flexibility afforded by the optional AS110 switch. Companies can save energy by automating after hours shutoff control while occupants can override this control locally to meet individual needs.

18 Basic Control Technical Information Checklist Panels available in 16, 32 or 64pole configurations Contactor ratings: V for ballast loads, 20 V for tungsten loads Userspecified number of fourpole contactors preassembled Eight channel outputs to normally closed contactors Supports up to ten panels in a multiple panel system Eight individual override inputs compatible with photocells, occupancy sensors, switches, or other building systems (requires SC100CP System Clock) Individual ON/OFF/Auto switches for each channel output Compatibility with AS110 Automatic Control Switch System clock: 8 channel, 7day, multiyear holiday scheduling, astronomic, automatic daylight savings, battery back up, nonvolatile memory (system clock is optional) DIN rail for easy mounting of contactors UL and CUL listed, one year warranty A Basic Control contactor panel includes the following: group Catalog No. Poles Panel interior Cover Tub HINCPxx16y115 HINCPxx32y115 HINCPxx64y115 HINCPxx16y277 HINCPxx32y277 HINCPxx64y277 HCVRzzSL HCVRzzFL HTUBzz Basic Control contactor panel interior up to 16 Basic Control contactor panel interior up to 32 Basic Control contactor panel interior up to 64 Basic Control contactor panel interior up to 16 Basic Control contactor panel interior up to 32 Basic Control contactor panel interior up to 64 Enclosure cover for 12 (16 poles), 24 (32 poles), or 48 (64 poles) tub (surface mount) Enclosure cover for 12 (16 poles), 24 (32 poles), or 48 (64 poles) tub (flush mount) Tub Enclosure (12 (16 poles), 24 (32 poles), or 48 (64 poles) tub) xx = Number of poles (multiples of four only). y = C for System Clock, N for no System Clock. zz = 12, 24, or 48 size. System Options Optional system enhancements include: System Clock SC100CP Automatic Control Switch AS110 Photocell EM24A2 System Clock Automatic Control Switch Low Voltage Photocell Basic Control Applications H BC Outdoor Application Indoor Application Photocell Load Indoors, users can add Automatic Control Switches (AS110) to achieve manual and override control. AS Load Multiple Basic Control Panels Expansion Panel Expansion Panel Bldg. C Bldg. B Admin. Bldg. A Main Panel Expansion Panel Bldg. D Bldg. E Expansion Panel The Watt Stopper, Inc. Pub. No H BC Optional System Clocks and photocells enable access to astronomic or photocellbased exterior lighting control. Main panel in Admin. Bldg., Expansion panels in other buildings A main Basic Control panel (containing a System Clock) can support up to nine expansion panels. The System Clock in the main panel commands the expansion panels.

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor TECHNICAL SPECIFICATIONS PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor Basic Features Line voltage version: 120-277VAC, 60Hz Low voltage version: 24VDC, requires separate class 2 power supply PIR sensor

More information

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature DT-300 v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature Specifications Voltage...18-28VDC/VAC, half wave rectified AC Current Consumption...25

More information

Installation Instructions

Installation Instructions DT-300 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On features Specifications Voltage................18-28VDC/VAC, half wave rectified AC Current Consumption...............................43mA

More information

Versatile wall switch sensors maximize payback and simplify code compliance

Versatile wall switch sensors maximize payback and simplify code compliance Versatile wall switch sensors maximize payback and simplify code compliance Commercial Wall Switch Occupancy Sensors MANUAL-ON MULTI-WAY NIGHTLIGHT Achieve the best energy savings for every wall switch

More information

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system

More information

ENERGY EFFICIENCY EXPERTS

ENERGY EFFICIENCY EXPERTS ENERGY EFFICIENCY EXPERTS Sensors maximize energy savings by ensuring that lights are turned off or to a lower level when spaces are unoccupied or adequate daylight exists. WattStopper s sensors provide

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

Daylighting Control Design and Application Guide

Daylighting Control Design and Application Guide Daylighting Control Design and Application Guide DAYAPPS_1206 Design Guide Introduction Introduction Daylighting controls transform a day lit area into an energy-saving opportunity. The U.S. Environmental

More information

INTEGRATED LIGHTING CONTROLS

INTEGRATED LIGHTING CONTROLS INTEGRATED LIGHTING CONTROLS With many facilities looking at lighting upgrades as a great energy-saving strategy, embedding controls directly into the fixture makes good economic sense. Choose just the

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification Dual Technology Wall Mounted Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 December 16, 2013 1. INTRODUCTION

More information

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2 Passive Infrared Sensors (PIR) Using a patented fresnel lens which minimizes optical aberrations, each Legrand/Pass & Seymour PIR sensor breaks its coverage area into zones. Upon detecting an infrared

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS SECTION 26 09 23 LIGHTING CONTROL DEVICES AND CONTROL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Remote control lighting relays. 2. Lighting contactors. 3. Switches. 4. Switch plates.

More information

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification Dual Technology Wall Switch Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 November 19, 2014 1. INTRODUCTION

More information

CS1200 WHT Pir Ceiling Mount Occupancy Sensor

CS1200 WHT Pir Ceiling Mount Occupancy Sensor 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 Catalog Number Manufacturer Description Weight per unit Product Category Features Area Coverage Field of View Load Type

More information

F series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC

F series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC echoflex Powered by ETC Complete Room Controller F series ERDRC-FC This guide covers the F series of the Complete Room Controller, model number ERDRC-FCU equipped with a 902 MHz radio. The box contents

More information

GE LightSweep Lighting Control System Guideform Specification

GE LightSweep Lighting Control System Guideform Specification GE Lighting Control GE LightSweep Lighting Control System Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative,

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Product Specifications Dialog Room Controller* (*patent pending)

Product Specifications Dialog Room Controller* (*patent pending) 1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,

More information

600 Watt Dimmer Install Guide

600 Watt Dimmer Install Guide 600 Watt Dimmer Install Guide ER6CD This guide covers all models of the ER6CD lighting controller. The box contents includes the controller with lock nut and installation guide. Overview The ER6CD controller

More information

Lighting Control Strategies. to meet code requirements save energy and improve building performance

Lighting Control Strategies. to meet code requirements save energy and improve building performance Lighting Control Strategies to meet code requirements save energy and improve building performance 1 Lighting Control Strategies Agenda Why Lighting Control Manual Light Reduction Scheduling Occupancy

More information

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1 Occupancy and Vacancy Sensors ENERLITES offers a wide variety of lighting sensors. They are designed to bring convenience to your life and business while helping to reduce energy consumption in commercial,

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

National Grid Small Business Program Rebate Manual

National Grid Small Business Program Rebate Manual National Grid Small Business Program Rebate Manual Rebate Manual Munro Distributing has prepared this manual to aid you and your clients in taking advantage of available rebate programs offered by National

More information

PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor

PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor TECHNICAL SPECIFICATIONS PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor Overview Quad Element PIR sensor 0-10V configurable output: set to 0% (OFF)*, 10%, 25% or 50% dimming Photocell for ambient light

More information

miniz Quick Start Guide

miniz Quick Start Guide miniz Quick Start Guide Congratulations on purchasing the miniz Daylight Harvesting Controller. The miniz is designed to be easy to install and configure with a few simple steps. Simplest Install Steps:

More information

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC echoflex Powered by ETC ER1S-FC Slim Line Dimming Controller F series This guide covers the F series of the Complete Room Controller, model number ER1S-FCU equipped with a 902 MHz radio. The box contents

More information

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA EL7611A/EL7612A Ultrasonic Occupancy Sensors and PRODUCT DATA Proven 30% to 60% utility cost savings because lights are on only when needed. Low initial cost allows fast payback. Models available for 1000

More information

Dual Relay Multi-Technology Wall Switch Occupancy Sensors

Dual Relay Multi-Technology Wall Switch Occupancy Sensors Dual Relay Multi-Technology Wall Switch Occupancy Sensors The OSSMD line of dual relay multi-technology Decora style wall switch occupancy sensors features several models to provide automatic lighting

More information

Wherever the best is needed. Sensors for professionals.

Wherever the best is needed. Sensors for professionals. Wherever the best is needed. Sensors for professionals. 3 Presence Detectors Motion Detectors (indoor) Power Packs Wallswitches from page 14 from page 4 from page 52 from page 6 IR Quattro HD IR Quattro

More information

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings A Title 24 Code Review for Electrical Professionals By: Brian Friedel LEED AP brian.friedel@wattstopper.com

More information

Sensors and Detectors

Sensors and Detectors 12/12/2017 Sensors and Detectors - Clipsal by Schneider Electric Sensors and Detectors Add sensors and detectors to make an environment smarter and more efficient. C-Bus sensors and detectors allow environmental

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Mini Product Guide.

Mini Product Guide. Mini Product Guide www.acuitybrands.com/sensorswitch Better Performance Through Advanced Technology 100% Digital Passive Infrared (PIR) Detection Dual Technology Detection utilizing Microphonics Contractor

More information

Installation Instructions

Installation Instructions HB-15NB High Bay Line Voltage Passive Infrared Occupancy Sensors with Nipple Backbox SPECIFICATIONS HB-15NB Power Module Voltages.............................12/277VAC, 6Hz Load Requirements @ 12VAC, 6Hz.............-8W

More information

LIGHTING CONTROL DEVICES

LIGHTING CONTROL DEVICES SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this

More information

VESICA LINEAR SUSPENDED VES L

VESICA LINEAR SUSPENDED VES L PROJECT INFORMATION Project Name Catalog # VESICA LINEAR SUSPENDED APPLICATIONS Office Spaces Conference Rooms Municipal Facilities Medical Facilities Type Date Financial Institutions Retail Spaces Hospitality

More information

Applied Lighting Controls

Applied Lighting Controls Better Buildings By Design 2010 Applied Lighting Controls Steven Mesh, LC, IESNA Senior Lighting Program Coordinator Pacific Energy Center (Pacific Gas & Electric) 851 Howard Street, San Francisco, CA

More information

DHL-LP-LED Low Profile LED Linear High/Low Bay

DHL-LP-LED Low Profile LED Linear High/Low Bay Job Information Type: Catalog #: Project: Comments: Prepared by: WARRANTY WARRANTY YEAR TEN INCLUDES LABOR ALLOWANCE 2 65W/90W Version 23.81 2 135W Version For 4 dimensions see pg 2 23.81 23.81 23.81 12.6

More information

Unison Echo Room Controller

Unison Echo Room Controller Unison Echo Room Controller GENERAL INFORMATION The Echo Room Controller offers a full power and control solution for standalone and integrated room controls. With up to eight zones of relay switching

More information

HUNTERSVILLE, NORTH CAROLINA USA EFFECTIVE SEPTEMBER 1, 2004

HUNTERSVILLE, NORTH CAROLINA USA EFFECTIVE SEPTEMBER 1, 2004 HUNTERSVILLE, NORTH CAROLINA USA EFFECTIVE SEPTEMBER 1, 2004 EPA Green Lights A L L Y USE OF THIS LOGO DOES NOT IMPLY EPA ENDORSEMENT APRIL 2008 www.nsiindustries.com E-mail: nsi@nsiindustries.com Fax:

More information

Never forget to turn the lights off again. Motion Sensors

Never forget to turn the lights off again. Motion Sensors Never forget to turn the lights off again. Motion Sensors by Why use motion sensors? Motion Sensors Everyone knows that you can save energy by turning off lights when they re not being used. Even so, sometimes

More information

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit Instruction Bulletin 63249-420-418A1 02/2014 Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit Commercial Grade with Ground SLSPWD1277C Retain for Future Use INTRODUCTION The Passive Infrared

More information

Infrared Ceiling Mount Sensor

Infrared Ceiling Mount Sensor Infrared Ceiling Mount Sensor LOS-CI Series LOS-CI- 0.0.06 The LOS-CI Series ceiling-mount passive infrared sensors can integrate into Lutron systems or function as standalone controls using a Lutron power

More information

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS PART - 1 GENERAL 1 SYSTEM DESCRIPTION A. The distributed lighting control system as specified herein shall be comprised

More information

SECTION LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS

SECTION LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS SECTION 260923 LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Wall box mounted, wall/corner

More information

LS-CM Series. Overview. Applications. Features & Benefits. Datasheet. Ceiling mount occupancy sensors

LS-CM Series. Overview. Applications. Features & Benefits. Datasheet. Ceiling mount occupancy sensors Datasheet Ceiling mount occupancy sensors Overview The CM Series of ceiling mount occupancy sensors provide a range sensor solutions for applications with finished ceilings (e.g., ceiling tiles, sheetrock,

More information

Arrow Hart. Universal Dimmers and Sensors. Eaton s Arrow Hart. Reliable lighting control for commercial installations

Arrow Hart. Universal Dimmers and Sensors. Eaton s Arrow Hart. Reliable lighting control for commercial installations Eaton s Arrow Hart Commercial lighting controls Eaton s Arrow Hart Universal Dimmers and Sensors Reliable lighting control for commercial installations Arrow Hart Eaton s s and dimmers are cost -effective

More information

TENOCHCA HALL - FAN COIL UNITS, RESTROOM AND FINISH RENOVATION PROJECT NO

TENOCHCA HALL - FAN COIL UNITS, RESTROOM AND FINISH RENOVATION PROJECT NO SECTION 26 09 43 - DISTRIBUTED DIGITAL LIGHTING CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Digital Lighting Controls 2. Relay Panels 3. Emergency Lighting Control Related Sections:

More information

LIGHTING CONTROLS

LIGHTING CONTROLS 260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance

More information

Model #: RC3 Model #: RC3D Model #: RC3DE SAFETY INSTRUCTIONS

Model #: RC3 Model #: RC3D Model #: RC3DE SAFETY INSTRUCTIONS gate Installation Instructions l #: RC l #: RCD l #: RCDE l #: RC-PL l #: RCD-PL l #: RCDE-PL l #: RCD-PL-CP l #: RCDE-PL-CP l #: RC-PL-N l #: RCD-PL-N l #: RCDE-PL-N l #: RCD-PL-N-CP l #: RCDE-PL-N-CP

More information

Reduce lighting energy costs with controls

Reduce lighting energy costs with controls Reduce lighting energy costs with controls Reduce energy costs. Support sustainability Get control of your lighting. Upgrading lighting systems to next-generation lighting technologies can deliver energy

More information

2025 Lavoisier, #135 Quebec, Quebec G1N 4L6 T F E. cristalcontrols.

2025 Lavoisier, #135 Quebec, Quebec G1N 4L6 T F E. cristalcontrols. 2025 Lavoisier, #135 Quebec, Quebec G1N 4L6 T. 418 681-9590 1 800 681-9590 F. 418 681-7393 E. info@cristalcontrols.com cristalcontrols.com TM Index Quick Selection...3-4 Which Technology to use...4 Retrofit

More information

Stellar Panelboard Dimming Systems

Stellar Panelboard Dimming Systems create a new dimension in lighting control. While lighting systems consume energy, Stellar dimming panels conserve and redirect energy into the atmosphere of your facility. The panel s universal dimmers

More information

GE TLC Softwired Contactor TM Guideform Specification

GE TLC Softwired Contactor TM Guideform Specification GE TLC Softwired Contactor TM Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative, or call the GE Lighting

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

, ,

, , 796-2028, 796-2021, 796-2025 Batten mount PIR detectors Overview This series of miniature PIR (passive infrared) presence detectors provide automatic control of lighting loads with optional manual control

More information

Specifications Occupancy/Vacancy Sensors CSI ASHRAE AIA Division 16 Section 16950

Specifications Occupancy/Vacancy Sensors CSI ASHRAE AIA Division 16 Section 16950 1 Specifications Occupancy/Vacancy Sensors CSI 26.09.23. ASHRAE 90.1-2010 AIA Division 16 Section 16950 1. PART 1 - General 1.1 Overview 1.1.1 Provide Occupancy/Vacancy sensors as shown on the plans and

More information

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton

More information

Integrated PIR detectors

Integrated PIR detectors EBMINT - Product Guide Integrated PIR detectors Overview The EBMINT series of miniature PIR (passive infrared) presence detectors provide automatic control of lighting loads with optional manual control

More information

1. Section [ Lighting Control Panel Boards:] Lighting panels (switching) controlled by ControlKeeper

1. Section [ Lighting Control Panel Boards:] Lighting panels (switching) controlled by ControlKeeper SECTION 260923 EATON DISTRIBUTED LOW-VOLTAGE POWER SYSTEM This specification was updated June 1, 2017 and supersedes all previous DLVP specifications. This section includes editing notes. These notes are

More information

Infrared Ceiling Mount Sensor

Infrared Ceiling Mount Sensor Infrared Ceiling Mount Sensor 69655c 0.07. The LOS-CIR Series passive infrared ceiling-mount sensors can integrate into LutronR systems or function as stand-alone controls using a LutronR power pack. The

More information

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors Product sheet SN1.402 Type CDR-AL CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors CDR-AL sensors are designed to detect carbon dioxide concentration and temperature in the room spaces. The units

More information

PRODUCT DATA AND INSTALLATION SHEET MWS5-SA STAND ALONE MINIATURE CEILING MOUNTED MICROWAVE PRESENCE DETECTOR

PRODUCT DATA AND INSTALLATION SHEET MWS5-SA STAND ALONE MINIATURE CEILING MOUNTED MICROWAVE PRESENCE DETECTOR 8. SPECIFICATION LOAD 6 Amps fluorescent and incandescent lighting. 3 Amps compact fluorescent lighting. 3 Amps low energy lighting. 3 Amps low voltage lighting (switch primary of transformer). Switch

More information

Vive PowPak Fixture Controls

Vive PowPak Fixture Controls Vive 369918g 1 03.12.18 The PowPak wireless fixture control is a radio-frequency (RF) device that controls either the Lutron EcoSystem or 0 10 V- electronic fluorescent ballasts and LED drivers (depending

More information

Devices for Special Applications

Devices for Special Applications Overview AP 2/11 UP 2/12 N 26/02 UP 28/11 UP 28/21 N 342 AP24/02 GE 22 GE 23 GE 24 UP 2 AP 2 Control Integrated constant light level control 1-channel 3-channel -- -- -- 1-channel -- -- 1-channel -- 1-channel

More information

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features Product Guide MWS5 Miniature Microwave Presence Detector (standalone) Overview The MWS5 series of miniature microwave presence detectors provide automatic control of lighting loads with optional manual

More information

POWER FLEXIBILITY ECONOMY

POWER FLEXIBILITY ECONOMY POWER FLEXIBILITY ECONOMY WattStopper lighting control panels offer the convenience of scheduled control combined with the flexibility to suit any application. Lighting Integrator (LI) provides a range

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

EBMHS (standard & slim-line PSU)

EBMHS (standard & slim-line PSU) Product Guide EBMHS (standard & slim-line PSU) Miniature HS PIR Presence Detector (luminaire fitting) Overview The EBMHS series of miniature PIR (passive infrared) presence detectors provide automatic

More information

AHAC-DT MicroSet dual tech low/line voltage ceiling sensors

AHAC-DT MicroSet dual tech low/line voltage ceiling sensors s Ceiling sensors description The dual technology sensor s combination of ultrasonic and passive infrared technologies offers the most complete sensing equipment available today. MicroSet self-adjusting

More information

Wireless High Bay Sensor (WHS100) Installation Instructions

Wireless High Bay Sensor (WHS100) Installation Instructions Installation Instructions The Daintree Networks WHS100 Wireless High Bay Sensor is a line powered control component within the ControlScope wireless building controls platform. It enables wireless control

More information

IP65 High Bay Dual Sense Sensor

IP65 High Bay Dual Sense Sensor IP65 High Bay Dual Sense Sensor TM and, Daylight Harvest with Remote Control Technical Data Input Characteristics Sensor Data Model No. Model No. Mains voltage 220-240VAC 50/60Hz Sensor principle High

More information

TEC1100 Series Thermostats

TEC1100 Series Thermostats Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a

More information

Integrated Classroom Control System. Installation and Operation Manual

Integrated Classroom Control System. Installation and Operation Manual Integrated Classroom Control System Installation and Operation Manual 1 Table of Contents Introduction... 3 Installation... 4 Operation... 8 Notes: Daylighting Configuration... 14 Appendix A Open Loop

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Wireless Plug Load Control

Wireless Plug Load Control General Specification Wireless Plug Load Control Model No.: PL20R & PLBPC Description:Enerlites Wireless Plug Load Controller is designed with simplicity, and helps to make plug load control requirements

More information

The Power To Supply... All Your Electrical Products

The Power To Supply... All Your Electrical Products ENERGY EFFICIENT RETROFIT SOLUTIONS The Power To Supply... All Your Electrical Products www.cef.co.uk All products are subject to availability and are correct at the time of print. Errors and omissions

More information

HIGH BAY APPLICATIONS

HIGH BAY APPLICATIONS STAIRWELLS The IIS Inverter can operate multiple fixtures in a building s stairwell and can be wired to bypass dimmers or occupancy sensors...keeping your egress corridors lit without sacrificing your

More information

CONTENTS SENSOR SWITCH

CONTENTS SENSOR SWITCH FOCUS ON LIGHTING CONTROL With each product or new technology we develop, our objective is to continually achieve greater energy savings with outstanding user convenience. Our particular focus on lighting

More information

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver EBDSPIR-HB-DD Product Guide High bay PIR presence detector DALI / DSI dimming Overview The EBDSPIR-HB-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional

More information

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features Product Guide PIR/INT & PIR/INT-D Batten mount PIR detectors Overview The PIR/INT & PIR/INT-D miniature PIR (passive infrared) presence detectors provide automatic control of lighting loads with optional

More information

Agenda. Company Background Product Overview Applications Flexibility Wrap Up / Q&A

Agenda. Company Background Product Overview Applications Flexibility Wrap Up / Q&A LCM Series Agenda Company Background Product Overview Applications Flexibility Wrap Up / Q&A Company Background Company Background PLC Multipoint Founded in 1972 by Fred Blake as Multipoint Inc Purchased

More information

VIENTO MEDIUM AREA & SITE LED LUMINAIRE OPTICS

VIENTO MEDIUM AREA & SITE LED LUMINAIRE OPTICS PROJECT INFORMATION Project Name Date VIENTO MEDIUM Catalog # APPLICATIONS Auto Dealership Sales Lots Parking Lots Educational/Business Campuses Type Parks & Recreation Areas Security Areas Mall & Retail

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver Product Guide EBDSPIR-HB-AD High bay PIR presence detector 1-10V dimming Overview The EBDSPIR-HB-AD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional manual

More information

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR 5/9/18 Procurement Towson University 8000 York Road Towson, MD 21252-0001 t. 410 704-2171 f. 410 704-8233 Ladies and Gentlemen:

More information

Installation Instructions

Installation Instructions Specifications PW-100 PW-200 PW-100/PW-100-347/PW-200/PW-200-347 v3 Passive Infrared Wall Switch Occupancy Sensor PW-100-347 PW-200-347 Voltages: PW-100 & PW-200................ 120/277VAC, 50/60Hz PW-100-347

More information

Education Title Solutions

Education Title Solutions Education Solutions Design Guide Crestron Electronics, Inc. Contents About 1 Design Guide Information 1 Code Standards 2 Classroom 4 Zūm... 4 GLPP... 5 Higher Education Classroom 6 Zūm... 6 GLPAC... 7

More information

Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group. Technical Product Information

Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group. Technical Product Information Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group Technical Product Information DCL with DEMANDflex DEMANDflex ballasts are high efficiency

More information

Tualatin Valley Fire & Rescue Finance Department SW 70 th Ave., Tigard, OR Phone: , Fax:

Tualatin Valley Fire & Rescue Finance Department SW 70 th Ave., Tigard, OR Phone: , Fax: Tualatin Valley Fire & Rescue Finance Department 11945 SW 70 th Ave., Tigard, OR 97223 Phone: 503-259-1157, Fax: 503-649-5347 SOLICITATION NO: ITB 13-0002 AMENDMENT NO. 2 General Contractor Construction

More information

FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR

FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR INNOVATION AND RELIABILITY THAT SPANS OVER 120 YEARS.

More information

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Code. LIT-1900896 Issued February 17, 2017 TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Description The TEC3000 Series Thermostat

More information

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM SECTION 260943.13 DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM PART 1 - GENERAL 1.1 SUMMARY LED Lighting Upgrade 26 00 00 1 Digital Network Lighting Controls A. The following

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

STANDARD FEATURES SPECIFICATIONS

STANDARD FEATURES SPECIFICATIONS MAG LOCK P/N 300768 STANDARD FEATURES Holding Force: 1500 lbs.(675 Kg.) Easy Installation: Versatile mounting bracket for new and existing doors and frames. Sensor: Built-in Hall effect crystal affected