FIRE PREVENTION EXHIBIT GUIDELINES
|
|
- Walter Bruce
- 5 years ago
- Views:
Transcription
1 FIRE PREVENTION EXHIBIT GUIDELINES Exhibit booth construction shall meet all building requirements. All means of entrance and exit must be clear and free from obstruction at all times. No storage of any kind is allowed behind booths or near electrical service. A one-day supply of product is permitted within but cannot be stored behind the booth. Fire extinguishers and emergency exits must be visible and accessible at all times. Should this equipment be within a booth or exhibit due to the layout of floor space, additional signage indicating fire equipment location(s) (extinguisher, - etc.) will be necessary, along with accessibility being maintained at all times. Compressed gas cylinders, including LPG, and all flammable or combustible liquids are prohibited inside the building. Any other exceptions require prior approval by the Convention Services Manager and the Fire Prevention Office. ( Kimberly Pires at kpires@iecshows.com if you plan to use gas of any kind in your booth.) Only Freeman has authorization for use of motorized equipment (forklifts, man lifts, boom lifts, etc.) in support of the Show. All booths greater than 1000 square feet must be submitted to Show Management to be passed on to the LVCC at least 45 days prior to the start of the event. AHR Booth layout approval form: ahrexpo. com/ahr-booth-layout-approval/ The travel distance within a booth, to an exit access aisle shall not exceed 50 feet. Exhibitors who plan to demonstrate fuel-burning appliances in the Las Vegas Convention Center must have approval from the Convention Services Manager 60 days prior to the event. Apply for approval through Show Management online at: Enclosed fireplaces must be approved for burning by the Las Vegas Convention Center Fire Prevention Department. Apply for approval through Show Management online at: Exhibit design directly around the fireplace and installation of the fireplace must meet the requirement/code for permanent fireplace installation.
2 COVERED EXHIBITS DEFINITIONS Multi-level Any occupied second story or greater area which is accessible by an approved means of egress. Covered Area Any area that covers the exhibit space and prevents the building fire sprinkler system from discharging water unobstructed to the floor. This will include single story exhibits with ceilings, upper deck exhibits, roof, overhead lighting installations, and any materials hanging or installed overhead that are not recognized as acceptable for use under fire sprinkler systems by fire code. Means of Egress An approved stairway or ramp constructed to the specifications of the code used for access and exiting. BOOTH PLAN REGULATIONS & APPROVAL All multiple-level exhibits and any single level exhibit over 1000 square feet or exceeding 300 square feet of contiguous covered area must submit a booth plan to the Las Vegas Convention Center Fire Prevention office for approval (via AHR Show Management) 45 days prior to the show. Plans must be submitted in.dwf,.dwg or.pdf format online at: ahrexpo.com/ahr-booth-layout-approval/ Previously approved plans must be resubmitted each year. Multi-level or covered contiguous areas in excess of 1,000 square feet are required to have a fire sprinkler system installed by a Nevada State licensed fire sprinkler contractor under the entire area and every level of a multi-level exhibit only when the following conditions apply. - The exhibit contains display vehicles. - The exhibit contains open flame. - The exhibit contains hot works. Any upper deck area to be occupied must have an approved plan with a State of Nevada engineered stamp. Multi-level areas that are greater than 300 square feet or which will occupy more than nine persons shall have at least two means of egress. Spiral stairways are not an approved means of egress. Multi-level, covered or roofed areas exceeding 300 square feet in size will require the installation of battery operated smoke detectors that will emit an audible alarm that can be heard outside of the area. Any covered area that is also enclosed, regardless of the size of the area, will require the installation of battery operated smoke detectors that will emit an audible alarm that can be heard outside of the area.
3 COVERED EXHIBITS (continued) PLAN REVIEW CHECKLIST Dimensions: All plans must indicate the dimensions for the booth and structure. Double Deck Booth Less Than 300 Square Feet (28 Square Meters): Maximum occupancy for a deck with a single staircase is nine (9) persons, which must be posted in plain view near the base of the staircase. Double Deck Booth 300 Square Feet (28 Square Meters) or larger: Must be equipped with two (2) remote staircases, minimum. Definition of Remote Stairs: The upper landings of remote staircases must be separated by at least one-half (1/2) the distance of the longest measurement of the upper deck, measured diagonally from corner to opposite corner for square or rectangular shaped decks. (Consult with the LVCVA Fire Prevention Office for the remote calculations on irregularly shaped decks.) Note: Limiting occupancy to nine (9) persons is not an acceptable alternative in lieu of this Life Safety Code requirement for remote staircases. Engineer Wet Stamp: Booth plans submitted shall be accompanied by an engineer s wet stamp to verify the integrity of the structure, per regional requirements -- or the documentation must be made available for review during onsite inspection of the exhibit on the show floor. Live-Load Rating: Booth plans submitted shall also include the live-load rating for the deck (minimum: 100 psf or 3.50 KN/m2) -- or the documentation must be made available for review during onsite inspection of the exhibit on the show floor. Fascia / Toe Boards: Are required so that loose objects cannot easily fall or be kicked over the edge of the deck onto persons below. Fascia / toe boards must raise four inches (4 / 12.5 cm), minimum, above the outer edge of decks not having walls. Guard Requirements: Minimum height of guard is 42 inches (107 cm). With guard openings up to 34 inches (86 cm), a four inch (4 / 10 cm) sphere must not be able to pass between the rails; above 34 inches (86 cm) an eight inch (8 / 20 cm) sphere must not be able to pass between the rails. Guards must be able to absorb a concentrated load of 200 pounds (91 kilograms), minimum. Staircase Requirements: Width of staircase is a minimum of 36 inches (91 cm) as measured between the protruding hand rails; staircase landings may not be less than the width of the staircase served; and staircase handrail height is 34 (86 cm) to 38 (97 cm) from the nose of the stair or ramp surface. Spiral Staircases: Are not allowed as ingress/egress pathways may be used for display purposes, only. Curved Staircases: Will be evaluated by the Fire Prevention Office on a case-by-case basis.
4 COVERED EXHIBITS (continued) No Combustible Storage Under Staircases: Unless the under stair area is equipped with a temporary automatic fire sprinkler system, no storage of combustible materials is allowed. Exception: No sprinklers are required whenever the under stair storage area is completely devoid of any electrical wires or equipment, or such electrical items are separated from the storage area in a manner approved by the Fire Prevention Office. Fire Extinguisher Requirements for Double Deck Booth: Five-pound (5 lb.) ABC fire extinguishers shall be mounted in plain view, per manufacturer s specs, on the ground level and upper deck level. The actual travel distance from any point within the booth to a mounted fire extinguisher must be no more than 75 (23 meters). In-house fire extinguishers may be factored into the distance equation for the ground floor only. At least one (1) fire extinguisher must be provided for each level. Any additional fire extinguishers that are required must be provided by the exhibitor. Fire Extinguisher Requirements for Covered Booths and Booths Exceeding 299 Square Feet (28 Square Meters): Five-pound (5 lb.) ABC fire extinguishers shall be mounted in plain view, per manufacturer s specs. The actual travel distance from any point within the booth to a mounted fire extinguisher must less than 75 (23 meters). In-house fire extinguishers may be factored into the distance equation for the ground level, only. Battery-Operated Smoke Detectors: Must be provided below double-decks and inside any fully-enclosed rooms or closets. (Mounted per manufacturer s specs) Certificate of Flame Retardancy: Required for all fabrics, decorations and other applicable materials. Certificates must be made available during onsite inspection(s). Field-testing, per code specifications, may be approved in lieu of a certificate. Onsite application of the required retardant may also be approved through a final field-test. 18 Inch Separation Between Booths: Each booth must grant a minimum of nine inches (9 / 23 cm) easement (only at the applicable side(s) of the booth usually the back or where the resident contractor supplied electrical lines are routed) to accommodate access to show electrical service. This easement must be totally clear of miscellaneous objects and all combustible storage. Not required for in-booth branch lines. No Combustible Storage Allowed: Behind booths or on or near electrical cords and appliances. Linear Halogen Lighting Prohibited: Linear halogen bulbs (including uncovered MR 11/MR16, line voltage and low voltage bi-pin bulbs) on LVCVA premises have been prohibited since January 1, Please refer to LVCVA Halogen Lighting Policy for addition information (Building Users Manual). Final Approval of Booth Plan: As always, final approval is contingent upon a routine inspection(s) of the exhibit area by members of the LVCVA Fire Prevention Office. Note: Approved plans that have later been revised must be resubmitted to the LVCVA FIRE WATCH Under certain circumstances the Fire Prevention Office may require a fire watch for an exhibit.
5 VEHICLES ON DISPLAY INDOORS Any vehicle on the show floor must abide by the following: Fuel tank openings shall be locked or sealed in an approved manner to prevent escape of vapors. Fuel tanks shall not contain more than one-quarter their capacity or more than five gallons of fuel, whichever is less. Batteries must be disconnected. Auxiliary batteries not connected to engine starting system may be left connected. External power is recommended for demonstration purposes. Battery charging is not permitted inside the building. Combustible/flammable materials must not be stored beneath display vehicles. Fueling or de-fueling of vehicles is prohibited. Vehicles shall not be moved during the show and will remain off while freight doors are closed. 36 of clear access or aisles must be maintained around the vehicle. Vehicles must be a minimum of 20 feet from exit of door or exit pathway. Vehicles placed in lobbies and meeting rooms must have approval of the CSM and leak protection.
EXHIBITOR KIT TABLE OF CONTENTS
EXHIBITOR KIT TABLE OF CONTENTS Aerosol Cans 2 Anchoring Machinery/Equipment 2 Animals 2 Balloons 2 Booth Set-up 2 Business Center 3 Chemicals 3 Contractor & Vendor Requirements 3 Emergency Procedures
More informationMcCormick Place Fire Safety Regulations
CANDLES AND OTHER OPEN FLAME DISPLAYS Any open flame devices used for illumination or decoration, such as candles, gelled alcohol fuel fire bowls, firepots or fireplaces must comply with the following:
More informationDear Exhibitor, To assist in th. and safety issues that you may encounter with your booth.
Dear Exhibitor, The Phoenix Convention Center and the Phoenix Fire Department have partnered to assist you in both a safe and successful experience in our facility. To facilitate this, the Phoenix Convention
More informationMULTI-LEVEL & COVERED BOOTH CONDITIONS
MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the
More informationAll orders are governed by the GES Payment Policy and GES Terms & Conditions of Contract as specified in this Exhibitor Services Manual.
Fire Regulations G-8 All orders are governed by the GES Payment Policy and GES Terms & Conditions of Contract as specified in this Exhibitor Services Manual. Automechanika Chicago McCormick Place April
More informationEXHIBITOR KIT TABLE OF CONTENTS
EXHIBITOR KIT TABLE OF CONTENTS Aerosol Cans 2 Anchoring 2 Animals 2 Balloons 2 Booth Set-up 3 Business Center 3 Chemicals 3 Contractor & Vendor Requirements 3 Drones/Unmanned Aerial Vehicles 4 Emergency
More informationFACILITY REGULATIONS
FACILITY REGULATIONS (Excerpt from Service Ordering Guide) Animals and Pets Domestic animals: If you plan to use a domestic animal (i.e., cat or dog) in your exhibit, be sure to contact your Show Manager
More informationFACILITY REGULATIONS
FACILITY REGULATIONS Animals and Pets Domestic animals: If you plan to use a domestic animal (i.e., cat or dog) in your exhibit, be sure to contact your Show Manager for approval. An insurance disclaimer
More informationNON-DOMESTICATED ANIMALS
ANIMALS DOMESTICATED ANIMALS Service animals are always welcome. Please refer to the ADA American Disabilities Act portion of this manual for the ADA s definition of a service animal. Permission for any
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 2017 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD SPECIAL EVENT PUBLIC ASSEMBLY PURPOSE This standard is applicable to any public event, exhibit space, booth, festival or any other similar
More informationEXHIBITOR KIT TABLE OF CONTENTS
EXHIBITOR KIT TABLE OF CONTENTS Aerosol cans 2 Animals 2 Balloons 2 Booth Set-up 3 Business Center 3 Chemicals 3 Contractor & Vendor Requirements 3 Drones/Unmanned Aerial Vehicles 3 Emergency Procedures
More informationATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS
ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS DALLAS FIRE-RESCUE DEPARTMENT Inspection and Life Safety Education Division Special Events Section 1551 Baylor Street, Suite 400, Dallas,
More informationhowever no company branding will be allowed above the height limitations must
A. Exhibitor s display booth(s) shall conform to the following specifications: 1. The maximum height of a display booth at the backwall, including any form of lighting system, signage, or header shall
More informationFOOD PREPARATION WITHIN EXHIBITS
FOOD PREPARATION WITHIN EXHIBITS Whenever food is prepared within an exhibit, an Application for Food Preparation within Exhibits form should be completed and forwarded to your Convention Services Manager
More informationPALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE
PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE FIRE DEPARTMENT REGULATIONS For Additional Information
More informationVENUE (LACC) GUIDELINES
VENUE (LACC) GUIDELINES FIRE & SAFETY REGULATIONS (Updated 09.01.14) The following are the Los Angeles City Fire Department's minimum requirements for shows and exhibits in the LACC. No variance or alternate
More informationTownship of Upper Providence Office of the Fire Marshal
Township of Upper Providence Office of the Fire Marshal Convention Center Fire Safety Regulations 1286 Black Rock Road P.O. Box 406 Oaks, Pa 19456 9 610N933N9179 JULY 2010 REVISION www.uprovnmontco.org
More informationEXHIBITOR KIT Error! Bookmark not defined.
EXHIBITOR KIT TABLE OF CONTENTS AEROSOL CANS... 2 ANIMALS... 2 BALLOONS... 2 BOOTH SET-UP... 3 BUSINESS CENTER... 3 CHEMICALS... 3 CONTRACTOR & VENDOR REQUIREMENTS... 3 FOOD AND BEVERAGE... 4 PREPARATION
More informationREGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES
REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES DATE: January 6, 2014 INFORMATION BULLETIN: F-14-002 APPROVED BY: W. Schellhous 2013 California Fire Code (CFC) and Riverside Municipal
More informationWashington State Convention Center Fire Safety Guidelines
Washington State Convention Center Fire Safety Guidelines ROLE OF THE SEATTLE FIRE DEPARMENT A Seattle Fire Department (SFD) Public Assembly Permit is required for exhibits, registration areas, any proposed
More informationRiverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)
Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group
More informationFamily Foster Home Fire Safety Evaluation Checklist Instructions
Family Foster Home Fire Safety Evaluation Checklist Instructions Please read these instructions prior to commencing your inspection. This checklist is provided to specific Foster Family Homes for the purpose
More informationFor additional information regarding R-3.1 residential care facilities please contact (951)
Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationDEPARTMENT OF FIRE AND EMERGENCY SERVICES
MASHANTUCKET PEQUOT TRIBAL NATION DEPARTMENT OF FIRE AND EMERGENCY SERVICES A Guide to SAFE EXHIBITS, EXPOSITIONS, EVENTS and DECORATIONS PREVENTION IS OUR INTENTION 0 Table of Contents Introduction:.
More informationTo provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified
More informationSeptember 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal
M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and
More informationConvention Center Rules & Regulations
Mandalay Bay Convention Center Level 1 Bayside E&F Las Vegas, NV Convention Center Rules & Regulations AMERICAN DISABILITIES ACT (ADA) The Mandalay Bay Convention Center was designed and constructed to
More informationFire Safety Guidelines and Requirements CenturyLink Field and Event Center June 2015
Fire Safety Guidelines and Requirements CenturyLink Field and Event Center June 2015 The Seattle Fire Department is required to review and enforce all issues relating to public safety in assembly occupancies
More informationFire and Life Safety Review Form
Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from
More informationPolicies - Building Rules and Regulations
Policies - Building Rules and Regulations The following regulations will be enforced during KEC events. It is your responsibility to inform your exhibitors, attendees and service contractors of these regulations.
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationBusiness License Pre-inspection Checklist
Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements
More informationEXCELSIOR FIRE DISTRICT
EXCELSIOR FIRE DISTRICT Minnesota State Fire Code and the Excelsior Fire District Inspection Fire Safety & Code Requirements TENTS OVER 200 SQUARE FEET The following codes set fourth by the Minnesota State
More informationBurien/Normandy Park Fire Department 900 SW 146 th ST PO Box Burien, WA BP (206) Fax (206)
Burien/Normandy Park Fire Department 900 SW 146 th ST PO Box 66029 Burien, WA 98166 BP (206) 242-2040 Fax (206) 433-6042 HOME DAYCARE SELF-INSPECTION CHECKLIST ` Complete the following daycare checklist,
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More information4. Distances to property line, buildings, other tents, parked vehicles and engines;
Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) Tent Requirements SafetyNet #: 554 Tent permit applications SHALL include all of the following before plans will be approved.
More informationGENERAL STAND BUILDING REGULATIONS AND INFORMATION
GENERAL STAND BUILDING REGULATIONS AND INFORMATION There are two types of stand available to exhibitors at Euro Attractions Show 2016 a shell scheme stand where the structure is purchased from the official
More informationFIRE PREVENTION STANDARDS
DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationCONVENTION AND VISITORS AUTHORITY ANIMALS
CONVENTION AND VISITORS AUTHORITY ANIMALS Permission for any domesticated animal (cats, dogs, etc.) to appear in a show or booth must first be approved by show management then by the Convention Services
More informationSTANDARD DETAILS & SPECIFICATIONS Spec No _SI _ Rev. Date 10/20/11
EST. 1947 STANDARD DETAILS & SPECIFICATIONS Spec No _SI- - - 4_ Rev. Date 10/20/11 SUBJECT: HAUNTED HOUSES/GHOST WALKS Eff. Date 08/23/90 Approved By Page 1 of 6 SCOPE These regulations shall apply to
More informationOrange County Fire Rescue Department Office of the Fire Marshal 7079 University Blvd. Winter Park, FL Phone: Fax:
Office of the Fire Marshal 7079 University Blvd. Winter Park, FL 32792 Phone: 407-836-0004 - Fax: 407-836-8310 Trade Show & Conventions Permit Application Process With the recent upgrade to our Mobile
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.14 Control Number: A.0 Effective Date: 9/14/11 TITLE:
More informationTENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE
SCOPE Revised 1/1/17 These provisions shall apply to any tent or temporary membrane structure having an area in excess of 400 square feet. The following information shall be submitted with each permit
More informationcomprised the facility Cables Candles be placed
Overall Fire Safety Regulations Floor plans, exhibits, and decorative materials must meet thee requirements of the Code of Massachusetts Regulations 780 CMR EIGHT EDITION (Building Code). The 8th edition
More informationDenver Fire Department Fire Prevention Division
/A 505.1 505.1 Address: Clearly marked from street, Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Address identification characters shall contrast with their background. Each
More informationCity of Cleveland. Division of Fire Fire Prevention Bureau 1645 Superior Avenue Cleveland, Ohio Standard Operating Procedure 18
City of Cleveland Division of Fire Fire Prevention Bureau 1645 Superior Avenue Cleveland, Ohio 44114 216.664.6664 Standard Operating Procedure 18 Cleveland Fire Prevention Fire Safety Regulations for Displays
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationSEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS
CITY OF SEMINOLE BUILDING DEPARTEMENT/FIRE DEPARTMENT 9199 113 th Street N. SEMINOLE, FL 33772 Phone: (727) 392-1966 - FAX (727) 319-6583 NO SMOKING UNDER THE TENT(S) Tents may be erected in any zoning
More informationCITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS
CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS Last Updated: April 28, 2008 FIRE REGULATIONS The purpose of fire regulations is to maintain an acceptable level of fire safety within CGS facilities.
More informationTents and Temporary Membrane Structures Packet
Tents and Temporary Membrane Structures Packet Tents and Temporary Membrane Structures Permit Procedure VERSION 1.0 12/2015 SCOPE: These provisions shall apply to any tent or temporary membrane structure
More informationFraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.
Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents
More informationFIRE & SAFETY REGULATIONS (Updated )
FIRE & SAFETY REGULATIONS (Updated 09.01.14) The following are the Los Angeles City Fire Department's minimum requirements for shows and exhibits in the LACC. No variance or alternate method of compliance
More informationTents and Temporary Membrane Structures Permit Procedure
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 E. Hillsdale Blvd. Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 Tents and Temporary Membrane Structures
More informationPLACES OF ASSEMBLY CHAPTER 17
CHAPTER 17 PLACES OF ASSEMBLY SECTION 1701 GENERAL 1701.1 Scope. Places of assembly, including trade shows and exhibitions, outdoor assembly events, outdoors mazes, special amusement buildings and special
More informationFIRE MARSHAL REGULATIONS
Cooking Information A Cooking/Open Flame Agreement form must be obtained prior to any on-site cooking, and/or food warming activities on the premises. Cooking/Open Flame Agreement forms can be obtained
More informationExhibits and Trade Shows Permit Application
Applicant Information: Exhibits and Trade Shows Permit Application Organization: Name: First Last Application Date: Position or Title: Address: Street Address / / City State Zip Phone: Primary Number Other
More informationSCOUT HALL INSPECTION CHECKLIST
Scouts Australia NSW Level 1, Quad 3 102 Bennelong Parkway Sydney Olympic Park 2127 P O Box 125 Lidcombe NSW 1825 Ph: 02 9735 9000 Fax: 02 9735 9001 SCOUT HALL INSPECTION CHECKLIST Please complete all
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.34 Control Number: A.1 Revision Date: TITLE: SCOPE: PURPOSE:
More informationCHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE
CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5609 is amended, to read as follows, with the entire section being an addition to the Fire Code: SECTION 5609. FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE
More informationCHILD CARE CENTER INSPECTION CHECKLIST 06C
CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS
More informationResidential Care Facilities Having 6 or Fewer Clients Classified in the California Building Code as R-3.1 Occupancies
Building Permits & Inspection Division General Information: (916) 875-5296 www.building.saccounty.net Full Service Center 827 7th Street, Room 102 Sacramento, CA 95814 M-F 8:30am - 4:30pm Bradshaw Center
More informationConvention Center Rules and Regulations
Mandalay Bay Convention Center - South Pacific Ballroom Las Vegas, NV Convention Center Rules and Regulations Americans with Disabilities Act: The Mandalay Bay Convention Center was designed and construction
More informationUC Irvine Environmental Health & Safety TITLE: Special Events Program
SECTION: UC Irvine Environmental Health & Safety TITLE: Special Events Program INITIATOR: Steven Eros REVISION DATE September 14, 2011 1. Program Description 2. Scope 3. Definitions 4. Responsibilities
More informationNew Facilities. Minimum Requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationFIREDEPARTMENT REGULATIONS AND GUIDELINES
FIREDEPARTMENT REGULATIONS AND GUIDELINES FIRE DEPARTMENT REGULATIONS Safety, for our guests and vendors, is our number one priority at the Spokane Convention Center. Please familiarize yourself with the
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.13 Effective Date: Revision Date: TITLE: SCOPE: EXHIBITS
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationFIRE SAFETY GUIDELINES
FIRE SAFETY GUIDELINES Assembly Events PRINCE WILLIAM COUNTY FIRE MARSHAL S OFFICE 5 County Complex Ct Prince William, Virginia 22192 TELEPHONE: 703-792-6360 The following fire safety guidelines have been
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationChapter Nursing Homes
Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of
More informationDEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIVISION OF ADULT FOSTER CARE LICENSING ADULT FOSTER CARE FACILITIES
DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIVISION OF ADULT FOSTER CARE LICENSING ADULT FOSTER CARE FACILITIES (By authority conferred on the department of social services by section 9 of Act No. 380
More informationFIRE SAFETY PRACTICES AND PROCEDURES
FIRE SAFETY PRACTICES AND PROCEDURES One of the most costly and destructive causes for loss of life and property that the City could experience would be from a major fire. Reporting Fires All employees
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationMinimum Information Required to Process your Special Occasion Application. Parking area Access to site
FIRE CODE PERMIT SPECIAL OCCASION APPLICATION YAKIMA COUNTY FIRE MARSHAL S OFFICE International Fire Code 128 N. 2nd Street, 4th floor, Yakima, WA 98901 - (509) 574-2300 FORM: BFS45A 6/5/18 Minimum Information
More information2012 International Fire Code Errata (Portions of text and tables not shown are unaffected by the errata)
1 st PRINTING (8-30-12) CHAPTER 2 - DEFINITIONS [B] CARE SUITE. A group of treatment rooms, care recipient sleeping rooms and their associated support rooms or spaces and circulation space within Group
More informationOCFEC Fire Marshal Summary Report
OCFEC Fire Marshal Summary Report Fire Marshal report (Correction Notices received on 6/1/2018) OC FAIR & EVENT CENTER Maintenance Restrooms 1. CCR Title 19 Section 3.28 Plans and Specifications : Submit
More informationFire/General Safety Review Program Key Performance Indicators Environmental Health and Safety
Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire and CO Detection Systems Fire alarm pull station obstructed. Annunciation panel obstructed. Lack of approved
More informationSTATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL
STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988
More informationFIRE PREVENTION GUIDELINE
Title: Fire Escapes Number: FPG-07 Effective Date: 01/01/2008 Revised Date: 03/01/2009 Code References: California Fire Code (CFC), California Code of Regulations (CCR) Title 19, Merced Municipal Code
More informationShort-Term & Accessory Short-Term Rental Safety Certification
Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need
More informationTable of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME
Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationCertificate of Inspection CHECKLIST
Neptune Township Code Enforcement 25 Neptune Boulevard Neptune, NJ 07753 732-988-5200 X211 Inspections@neptunetownship.org Rev. 05/23/18 Certificate of Inspection CHECKLIST For Residential & Commercial
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More information30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY
AP # Permit # Cost Revised 12/31/17 Page 1 of 2 Check # Receipt # 30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY 6 TH EDITION (2017) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE FLORIDA
More informationLevel I Chapter 1 Worksheet
Chapter 1 Worksheet 1. When the present code requires certain safety to life requirements for existing buildings, those requirements shall. a. be void b. apply c. be approved d. be grand-fathered 2. The
More informationClark County Department of Building & Fire Prevention 4701 West Russell Road, Las Vegas, NV (702) FAX (702)
Clark County Department of Building & Fire Prevention 4701 West Russell Road, Las Vegas, NV 89118 (702) 455-7316 FAX (702) 455-7347 Ronald L. Lynn Director/Building & Fire Official Samuel D. Palmer, PE.,
More informationGeneral Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin
The purpose of a monthly self-inspection program is to identify unsafe conditions in the work environment and unsafe employee actions. Management can then correct these safety hazards, reducing the potential
More informationGeneral Safety Requirements
PART II General Safety Requirements Chapter 3: General Precautions against Fire Chapter 4: Emergency Planning and Preparedness 41 CHAPTER 3 General Precautions against Fire The general safety requirements
More informationCity of Leduc Fire Services Indoor Special Event Requirements
City of Leduc Fire Services Indoor Special Event Requirements 0 Table of Contents Contents Definitions... 2 Indoor Special Event... 3 Special Event Approval... 3 Event Information Sheet Requirements...
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationFIRE DEPARTMENT PERMIT GUIDELINES
FIRE DEPARTMENT PERMIT GUIDELINES SPECIAL EVENT PUBLIC ASSEMBLY (EACH EVENT) The Special Event Assembly Permit is applicable to any public event, exhibit space, booth, festival or any other similar event
More information