Water Leak Detector - Four Zone with open/short-circuit detection. Product overview
|
|
- Lynne Norton
- 5 years ago
- Views:
Transcription
1 Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must be used with one of the AX-WLDF-Cx or AX-WLDF-P range of sensor types. The AX-WLDF can have a total of 200m of cable connected to each input. Relay outputs provide alarm signals for each individual zone, together with a combined alarm relay. A multiplexed analogue 0-10V output signal indicates zone status. The input sensitivity of each zone is adjustable to ensure false returns are not given. A total of 200m cable on each zone Detects open or short circuit sensors Mixed sensor types can be used Audible alarm with mute contacts LED indication of each zone alarm sensitivity adjustable for each zone Relay output to BMS or Alarm annunciator Analogue output provides zone status indication Supply Voltage: WLDF-24 50Hz ±10% and 24Vdc ±10% at 150mA max. Common Alarm Relay: Individual Alarm Relays: Sensor s / Types: Cable Length per : Analogue Output: Sensor LEDs: Alarm LED: Audible Alarm Output: Mute input: Electrical Connections: Dimensions / Weight: Ambient Temperature Range: AX-WLDF-24 WLDF Hz ±15% SPCO rated 250Vac resistive. NO Contact closed when OK SPNO rated 250Vac resistive. Contact closed when OK Cable or Point (Polarity independent) 200m (including header cable) maximum 0-10V at 5mA maximum 1 for each zone. Solid green = OK Flashing green = zone disabled (pot adjusted fully-anticlockwise) Solid red = water detected Flashing red = fault detected (open or short circuit) Red when fault detected 10cm Volt free contact (switching 5V at 1mA) Rising cage terminals for mm² cable 82 x 45 x 47mm / 155gms -10 to +50 C, 0 90% RH condensing Four zone water leak detection module 24V AX-WLDF-230 Four zone water leak detection module 230Vac Compatible Sensors Refer to pages 4 and 5 Issue 1.0 (16/08/16) Page 1 of 5
2 SAFETY NOTE Ensure all installations are in compliance with applicable electrical codes and that the installation is carried out by qualified installers familiar with the relevant standards and proper safety procedures for high voltage installations. Never rely on status indication on any device to determine if power is present. Mounting The AX-WLDF clips easily on to standard DIN Rail. If it is necessary remove the module from the DIN rail, ensure to use a flat bladed screwdriver to release the DIN clip. Connections AX-WLDF-230 only Live 230Vac Neutral Alarm LED Common General Alarm NO NC Channel 4 Alarm VFC Channel 3 Alarm VFC Channel 2 Alarm VFC Channel 1 Alarm VFC V Supply 0V Supply AX-WLDF-24 only 0V Mute VFC 0-10V Out Channel 4 Channel 3 Channel 2 Channel 1 The relays are shown in the power-off condition. When power is applied, and zones are fault free (or disabled), then the relays will be in the opposite state. Operation Disable zone To disable a zone turn the relevant sensitivity preset fully anticlockwise. The zone LED will flash green every two seconds. The zone alarm relay will remain in the OK state and the 0-10V output will show the zones as OK. Page 2 of 5
3 Sensitivity Within 30 seconds of applying power to the AX-WLDF, with the cable connected, adjust the sensitivity potentiometers on each input by turning clockwise (increasing sensitivity) until the zone LED illuminates red, and then anti-clockwise (reducing sensitivity) until the zone LED goes off. Less sensitivity may be needed when long runs of cable are used. If the input is not used it should be disabled, see Disable zone. Testing To test the installation, after the sensitivity has been set, put a wet cloth over the cable to simulate a water leak, the indicator zone LED will illuminate solid red. Remove the cloth, short across the mute input, and if the cable is dry the zone LED will be solid green. Audible alarm output If the unit is in alarm and there is no mute switch in use, the alarm can be silenced by shorting across the mute terminals. If the audible alarm is not required the mute terminals can be permanently shorted. Alarm relay outputs and alarm LED Only when the fault is removed and the mute contacts closed will the alarm relay contacts return to normal, and the Alarm LED extinguish. Cable fault The unit monitors the cable for open and short circuit conditions. Only 1 cable or sensor should be connected to each zone input. Connecting two cables or sensor to one zone input will interfere with the cable fault detection and unit sensitivity. When a fault is detected the the Zone relay and General relay will go into the alarm state, the 0-10V will show an alarm for the zone and the zone LED will flash red. Analogue 0-10V output: The table below indicates the output voltage for each fault condition (Alarm = water detected, open circuit or short circuit) (OK = No alarm or input disabled): Channel 1 Channel 2 Channel 3 Channel 4 Analogue Output OK OK OK OK 10.00V OK OK OK ALARM 9.33V OK OK ALARM OK 8.67V OK OK ALARM ALARM 8.00V OK ALARM OK OK 7.33V OK ALARM OK ALARM 6.67V OK ALARM ALARM OK 6.00V OK ALARM ALARM ALARM 5.33V ALARM OK OK OK 4.67V ALARM OK OK ALARM 4.00V ALARM OK ALARM OK 3.33V ALARM OK ALARM ALARM 2.67V ALARM ALARM OK OK 2.00V ALARM ALARM OK ALARM 1.33V ALARM ALARM ALARM OK 0.67V ALARM ALARM ALARM ALARM 0V Page 3 of 5
4 Technical overview The AX-WLDF-Cx range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction with the AX-WLDF range of detection modules. The cable excitation used from the AX-WLDF is an isolated AC signal which ensures the detectors will not be subject to oxidation or erosion over time, avoiding the degradation problems associated with DC systems. This cable sensor must only be used with the AX-WLDF range of modules, in order to detect open and short circuit conditions. Easy to Lay Detects Closed and Open Circuits Detects water along length of sensor Will not oxidise or erode as with DC Systems PVC Twisted pair with stainless 316 elements Response Time: Typically <1 sec after exposure Dimension: 3.5mm diameter Maximum Cable Run: 200m (including header cable) 1. Fit cable sensors to the floor, using suitable fixings 2. Connect the 2-core leader cables to the AX-WLDF alarm module (polarity independent). 3. Power the AX-WLDF, and adjust the relevant potentiometers on the module clockwise until the relevant red LED illuminates, and then anti-clockwise until the LED extinguishes. 4. Test the cables by placing a damp cloth over each of the cables to simulate a water leak, the relevant red LED will illuminate. Remove the cloth, short across the mute input, and if the cable is dry the red LED will extinguish. AX-WLDF-C2 Water Cable Sensor Premium for AX-WLDF, 2m cable & 1m leader cable AX-WLDF-C5 Water Cable Sensor Premium for AX-WLDF, 5m cable & 3m leader cable AX-WLDF-C10 Water Cable Sensor Premium for AX-WLDF, 10m cable & 3m leader cable AX-WLDF-C15 Water Cable Sensor Premium for AX-WLDF, 15m cable & 3m leader cable AX-WLDF-C20 Water Cable Sensor Premium for AX-WLDF, 20m cable & 3m leader cable AX-WLDF-Cxx Customer spec Water Cable Sensor Premium for AX-WLDF, Specify cable & leader cable Page 4 of 5
5 Technical overview The AX-WLDF-P water leak point sensor is used to detect water at a localised point. It is perfect for use with drip trays for alarm indication when the level reaches a pre-determined height. The unit can detect open and closed circuit along the length of the cable, and can even be cut to a desired length without issue. Additional features include a robust housing with slotted lugs for easy mounting, stainless steel probes and IP65 protected internals for impressive durability. Slotted lugs for easy installation Detects open / closed circuit along the entire length Cable can be cut to suit application. Robust housing 2m and 5m variants IP65 protection Housing Cable Length: Dimensions: Protection: Probes: Dimensions: Black ABS 2m 67 x 35 x 20mm (mounting slots 3.5mm wide on 57.8mm centres) IP65 Stainless Steel 13mm x 3mm diameter 1. Fix the AX-WLDF-P in the location where water detection is required. 2. The AX-WLDF-P is fitted with a 2m leader cable that can be terminated at a junction box. This can then be lengthened to a maximum of 200m to the AX-WLDF alarm module. 3. Connect the 2-core leader cable to the relevant sensor input on the alarm module (polarity independent). 4. Power the AX-WLDF, and adjust the relevant potentiometer on the module clockwise until the relevant red LED illuminates, and then anti-clockwise until the LED extinguishes 5. Test the sensor by placing a damp cloth over the stainless steel probes to simulate a water leak, the relevant red LED will illuminate. Remove the cloth, short across the mute input, and if the cable is dry the red LED will extinguish. AX-WLDF-P2 AX-WLDF-P5 Water Point Sensor Premium & 2m Cable Water Point Sensor Premium & 5m Cable Page 5 of 5
WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.
Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction
More informationWater Detection Controllers
Page 1 of 5 Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation or erosion
More informationGasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.
Gasflag Single Channel Control Panel Alarm Only Apparatus Installation, operating and maintenance instructions, M07225 Issue 2 1/07/05 Crowcon Detection Instruments Ltd 2 Blacklands Way Abingdon Business
More informationLEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL
LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water
More informationLEAKSTOPPER 1 Single zone water leak detection system
LEAKSTOPPER 1 Single zone water leak detection system WHAT DOES THE PRODUCT DO? The LeakStopper 1 detects the presence of water in environments where it is not supposed to be. Should water be detected
More informationLEAKSTOPPER RANGE Multizone water leak detection systems
LEAKSTOPPER RANGE Multizone water leak detection systems WHAT DOES THE PRODUCT DO? The LeakStopper detects water leaks and instantly triggers an alarm to warn you. It is capable of monitoring between 2
More informationPublic Safety DAS Annunciator Panel
Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This
More informationSYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System
SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing
More informationtcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual
tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual This manual covers operation of the tcm100 and tcm101 Series Temperature Control Modules.
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationZIOU/230 - MAINS IO INSTRUCTION MANUAL
Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel
More informationGas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller
Gas Safety Products Installation, operating and maintenance 11/18/2015 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply....
More informationOperating Instructions. For. Alarm Control Module. Model SSR 500
SSR 500 LEVEL CONTROL RELAY MODULE Operating Instructions For Alarm Control Module Model SSR 500 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:
Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1
More informationLC2200 Level Controller Installation and Maintenance Instructions
4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%
More information1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER
Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where
More informationDoor Release Power Supply
www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation
More informationLD1000 ARCHITECT AND ENGINEER SPECIFICATIONS. RLE TECHNOLOGIES Rev
LD1000 ARCHITECT AND ENGINEER SPECIFICATIONS RLE TECHNOLOGIES Rev. 1.0 110063 1. GENERAL SPECIFICATION 1.1 The contractor shall provide RLE Technologies SeaHawk LD1000 Alarm Panel (hereinafter referred
More informationHydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)
Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front
More informationMBCE-110/230UV Flame Sensor Module
MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a
More informationIntegrated PIR detectors
EBMINT - Product Guide Integrated PIR detectors Overview The EBMINT series of miniature PIR (passive infrared) presence detectors provide automatic control of lighting loads with optional manual control
More informationExcellence in Level Measurement
Technical Data Sheet No. Novaflo 2000 'Fail-Safe' Level Alarm System Excellence in Level Measurement Afriso Eurogauge Ltd Imberhorne Lane, East Grinstead West Sussex. RH19 1RF Tel: 01342 323641 Fax: 01342
More informationModels NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring
More informationED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR
ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016
Gas Safety Products Installation, operating and maintenance 05/10/2016 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Mains Supply...
More informationLEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL
LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone
More informationTBR 40 1 GD Blood Refrigerator Instruction Manual. for BLOOD STORAGE REFRIGERATORS MODEL TBR 40 1 GD. (40 x 500ml Blood Bag Capacity)
for BLOOD STORAGE REFRIGERATORS MODEL TBR 40 1 GD (40 x 500ml Blood Bag Capacity) REVISION 10/10/07 PLEASE READ CAREFULLY BEFORE OPERATION Thermoline Scientific Equipment Pty. Ltd. ABN 80 000 859 129 9
More informationGas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1
Gas Safety Products Merlin CT1650+ Gas Interlock System Installation, operating and maintenance 09/05/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel
More informationInstallation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels
Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:
Gas Safety Products Merlin 1500S Gas Interlock System Installation, operating and maintenance Rev: 03 Date: 08-01-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting....
More informationFireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds
Fireray 2000 pplication and FETURES Installation Guide Range 10-100 metres 12V to 24V dc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or automatic reset
More informationEmerald 3000 MK3 GJD010 Lighting Controller
Emerald 3000 MK3 GJD010 Lighting Controller SPECIFICATION SUPPLY: 230 Vac 50Hz via ELCB/MCB - unit fused at 13A 12VDC@ 100mA: GJD Opal XL (6mA) or Elite Detectors (10mA) Optional external 12VDC piezo sounder
More informationAFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION
968 AFMS AFMS TECHNICAL SPECIFICATION 08/07 Ref B ATV-ELEKTRONIK GMBH WIENER STRASSE 228 A-4030 LINZ +43 732 301600 FAX. +43 732 301600 21 Page 2 Table of contents General Introduction...3 Overview...3
More informationFlostop TS D7E and A8E. Operation Manual
Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany
More informationTraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM
TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.
More informationTable of Contents. Page Quick Set-up Instructions 1. Theory of Operation 2. Specifications 3. TM 1003W Controls and Connections 4
Table of Contents Page Quick Set-up Instructions 1 Theory of Operation 2 Specifications 3 TM 1003W Controls and Connections 4 1. Power Source Connector 5 2. Alarm Output Connector 5 3. Variation Detection
More informationRTD TEMPERATURE SENSING SYSTEM
General Overview RTD TEMPERATURE SENSING SYSTEM The Prime Technology RTD Temperature System 9219-00-0002 is a three-channel temperature measuring system that utilizes two RTD Temperature Sensor inputs
More informationRectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English
Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed
More informationProduct Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1
Gas Safety Products Merlin GDP2 Installation, operating and maintenance 23/08/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting..... 3 2.2 Mains
More informationGas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1
Gas Safety Products Merlin CT1250 Gas Interlock System Installation, operating and maintenance 28/10/2015 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.....
More informationGL-CO-RFG Channel Gas Leak Alarm System
Four Elms Road Edenbridge Kent TN8 6AB UK Features & Benefits Remote sensors for natural gas, LPG and CO 1 x SPST relay outputs DIN-rail as standard, panel mounting kit available Adjustable alarm thresholds
More informationINSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06
INSTRUCTION MANUAL 8100 & 8200 Monitor Manual Issue 06 ** This page is intentionally left blank ** Table of Contents 1 Introduction... 4 1.1 Manual Conventions... 4 1.2 Version 4 PCBA's... 4 1.3 Product
More informationMBCE-110/230FR Flame Sensor Module
MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion
More informationModel A1600 Series Annunciator
Seekirk Model A1600 Series Annunciator Applications: For usage in all types of process industries, electric generation, transmission and distribution, gas and water utilities. Features: The Seekirk model
More informationITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual
ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,
More informationDMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 DMWD 1 to 4 Zone Water Detection with Distance to Leak Measurement Installation and Operation Manual
More informationAlarm Panel Operating Instructions
Alarm Panel Operating Instructions 1.0 Introduction The Gascon Systems G8850 alarm panel is designed to be used with gas reticulation systems. It is available in single, twin and triple input channel models.
More informationTOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions
TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions Approvals / Certifications Hazardous Locations Class I, Division 2 Groups A, B, C, D Touch 1500-HAZ-CPU and Touch 1500-HAZ-TS
More informationTX6831 Data Sheet. Features. Benefits
Audio/Visual Alarm Combined audible and visual alarm signalling, for use with sensors and monitoring systems Environments: Mining Tunnelling Machine monitoring Features TX6831 For use with sensors and
More informationOPERATION AND INSTALLATION MANUAL
EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in
More information, ,
796-2028, 796-2021, 796-2025 Batten mount PIR detectors Overview This series of miniature PIR (passive infrared) presence detectors provide automatic control of lighting loads with optional manual control
More informationUSER MANUAL FOR OPERATING SYSTEM
P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177
More informationAnalogue Dimming Microwave Presence/Absence Detector
Product Guide MWS3A-AD Analogue Dimming Microwave Presence/Absence Detector Contents Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Wiring & Fixing 3 4 Installation 3
More informationAIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)
AIS750 Series Alarm Annunciator User Manual (Ver 23 / JUNE 2014) 3-350 John Street, Thornhill, tario L3T 5W6 Phone: 289 597 APEX (2739) Fax: 289 597 2200 Toll Free: 1 866 776 2943 Email: mail@annunciatorca
More informationPTE0705 Electric Fence Monitor
PTE0705 Electric Fence Monitor The JVA logo is a registered trademark of JVA Technologies. JVA Technologies. TABLE OF CONTENTS DESCRIPTION... 2 QUICK START GUIDE... 3 FEATURES... 4 EXPLANATION OF TERMS...
More informationEBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC
Product Guide EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM-VFC PIR (passive infrared) presence detector provides automatic control of lighting loads
More informationSENSA MRE DDM MR
96239831 SENSA MRE DDM MR Contents Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Wiring and fixing 3 4 Programming 6 5 Wiring diagrams 8 6 Detection pattern diagrams
More informationDec Wirsbo CoSy Radio. Installation and Operating Instructions
Dec. 2002 Wirsbo CoSy Radio Installation and Operating Instructions Contents 1. Overview... 3 2. Room thermostat... 3 2.1 Thermostat models... 3 2.2 Function... 4 2.3 Positioning... 4 2.4 Setting and limiting
More informationTTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS
TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must
More informationMWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features
Product Guide MWS5 Miniature Microwave Presence Detector (standalone) Overview The MWS5 series of miniature microwave presence detectors provide automatic control of lighting loads with optional manual
More informationFeatures. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign
Features DATASHEET Connects to multiple sensing instruments One/Two Channel Device Bright solid state LED Alarm Display Audible Alert (internal and external) High reliability, fully dual redundant alarm
More informationFlopurge TS. Operation Manual
Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com
More informationAPPLICATION DATA SHEET
APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors
More informationPNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel
PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum
More informationConventional Fire Alarm System 2014 V1.2
Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel
More informationCellarSafe. Carbon Dioxide and Oxygen Safety Monitor
CellarSafe Carbon Dioxide and Oxygen Safety Monitor Installation and operating instructions for the CellarSafe Monitor and the CellarSafe Calibration Unit M07234 May 2008 Issue 6 Warning Please take care
More informationESP TECHNOLOGIES LIMITED
Alarm Technology ESPAN-01 Series Annunciator System Combination type User Manual (Rev. 1) ESP TECHNOLOGIES LIMITED www.esptechno.com Content Page Introduction 2 General Description 2 Overview - Annunciator
More informationHALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL
HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. Tem p. Range 1 - = > 60 o F 2 - = 40-60 o F 3 - = < 40 o F G as Type 1 - R-11 2 - R-12 3
More informationTHERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16
TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and
More information20 Light Remote Annunciator
Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator
More informationMODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS
MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS OPERATES ON 12 OR 24 VOLTS AC/DC, AUTO VOLTAGE SENSING FULLY PROGRAMMABLE FROM THE KEYPAD
More information360 Surface Mount Ceiling PIR Light Controller
360 Surface Mount Ceiling PIR Light Controller Model: SLW360L Installation & Operating Instructions 1 1. General Information These instructions should be read carefully and retained for further reference
More informationFTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS
QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.
More informationGUARDIAN CX10 PRIORITY/EVACUATION INTERFACE USERS MANUAL
GUARDIAN CX10 PRIORITY/EVACUATION INTERFACE USERS MANUAL General information The CX10 provides a priority input into an audio system of up to 10 channels in a 19 1RU package. The CX10 may be used with
More informationQuickheat 30 weather compensated boiler control
Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The
More informationLDRA6 ARCHITECT AND ENGINEER SPECIFICATIONS. RLE TECHNOLOGIES Rev
LDRA6 ARCHITECT AND ENGINEER SPECIFICATIONS RLE TECHNOLOGIES Rev 1.0 110062 1. GENERAL SPECIFICATION 1.1 The contractor shall provide RLE Technologies SeaHawk LDRA6 Multi-Functional Alarm Panel (hereinafter
More informationLC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV
LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998
More informationMEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.
WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM
More information2704 Controller Melt Pressure Controller
2704 Controller Melt Pressure Controller A. SUPPLEMENT 2704 MELT PRESSURE CONTROLLER. 2 A.. INTRODUCTION...2 A.2. WHAT IS THE MELT PRESSURE CONTROLLER?...2 a.3. INSTALLATION...3 a.4. WIRING CONNECTIONS...3
More informationOperating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm
Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm
More informationSolid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10
Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10 DESCRIPTION FEATURES PRODUCT DATA Solid and Split Core Vdc Output Current Transmitters. Fast Response Time. Integral
More informationInstallation and user manual for the BiWire / Conventional Repeater Panel
Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....
More informationReflective Optical Beam Smoke Detector User Guide
Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating
More informationELECTROPROJECT GTV-A POWER SUPPLY FOR DOOR MAGNETS
ELECTROPROJECT POWER SUPPLY FOR DOOR MAGNETS Innovative and carefully thought out Always the right drive ELECTROPROJECT AANDRIJFTECHNIEK ElectroProject has evolved over the last 75 years from a technical
More informationSentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.
Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...
More informationLMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS
G LMS 188 4P BMS August, 2018 LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS! WARNING: This product can expose you to chemicals including lead, which is known
More informationTOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design
TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup
More informationSensepoint XCL Fixed Gas Detector
Gas Detec on Sensepoint XCL Fixed Gas Detector Quick Start Guide Sensepoint XCL Fixed Gas Detector Quick Start Guide Read and understand the Sensepoint XCL Operating Instructions before installing, operating
More informationAnalog Room Pressure Monitor RPC Series
Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the
More informationPRODUCT DATA AND INSTALLATION SHEET MWS5-SA STAND ALONE MINIATURE CEILING MOUNTED MICROWAVE PRESENCE DETECTOR
8. SPECIFICATION LOAD 6 Amps fluorescent and incandescent lighting. 3 Amps compact fluorescent lighting. 3 Amps low energy lighting. 3 Amps low voltage lighting (switch primary of transformer). Switch
More informationThe most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation
The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of
More informationAddressable Detectors & Bases
Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously
More informationInstallation, Operation and Maintenance Manual
ECO-1 (AT-EL-1) Single Zone Leak Detection Alarm Panel Installation, Operation & Maintenance Manual ECO-1 (AT-EL-1) Single Zone Leak Detection Alarm Panel Installation, Operation and Maintenance Manual
More informationTHA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY Introduction.
More informationPower Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses
BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF
More informationHALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL
HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL S E R I A L N O. M O D E L N O. T e m p. R a n g e 1 - = > 6 0 o F 2 - = 4 0-6 0 o F 3 - = < 4 0 o F - G a s T y p e 1 - R -1 1 2
More informationGAS SUPRESSION CONTROL PANEL:
GAS SUPRESSION CONTROL PANEL: MODEL NAME: COMPANY: DELTA 437/2, Main Road, Mandwali Fazalpur, Delhi-110092 Page 1 ABOUT THE PRODUCT ASES is very proud of to introduce DELTA the completely digital microprocessor
More informationPre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit
Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design N56 W16665 Ridgewood Drive Menomonee Falls, WI 53051 SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where
More information2604 Controller Melt Pressure Controller
2604 Controller Melt Pressure Controller A. SUPPLEMENT 2604 MELT PRESSURE CONTROLLER. 2 A.. INTRODUCTION...2 A.2. WHAT IS THE MELT PRESSURE CONTROLLER?...2 a.3. INSTALLATION...3 a.4. WIRING CONNECTIONS...3
More informationHALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL
HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL SERIAL NO. MODEL NO. Temp. Range - = > 0 o F - = 0-0 o F - = < 0 o F No. of Sensors/Gas Type A - R- B - R- C - R- Outputs D - R-a - x A
More information