1 OLTS vs OTDR Tier-2 Expert; How far from Tier-1? Christian Till, Application Engineer 2016/12/09 1

2 Why this industry is exciting! Bandwidth grows like crazy Global DC traffic 5ZB now, 10.4ZB 2019 Hyperscale are going 100% SMF planning G intra-dc! MMF OM5 standard has been adopted SWDM4 transceivers rise 10 GbE (SFP) is OK at top-of-the rack switch, 40G/100G+ Leaf-Spine 2016: Year of 25 GbE (SFP) and 4x25G lane, 100G Serial duplex OR Parralel Mobile & Telco operators re-architecture their CO in Data Center (CORD) Existing infrastructure (LC/UPC patch panels) are more sensitive to back reflection What is the value of testing? 2

3 Standard Testing Requirements Tier-1 Certification Tests Normative Measurements Polarity (VFL) Insertion Loss (IL) Length Recommended Method LS/PM OLTS/Certifier Tier-2 Extended Tests & Troubleshooting Informative Measurements Polarity (VFL) Insertion Loss Length Connector and Splice Loss Connector Reflectance Recommended Method OTDR/iOLM 3

4 IEEE Standards (published or under development) IEEE 802.3bs 200/400G Fiber Includes MMF & SMF options SMF Duplex Series up to 500m/2Km/10Km MMF Parallel 16x25G. Source: Commscope 4

5 What fiber & connector types to choose? Serial Duplex LC connectors Parralel Optics - Multi-Fiber MPO/MTP Ceramic ferrule (zirconia) One fiber per connector Typically used in duplex (transmit & receive) Common types include LC Polymer ferrule Multiple fibers in linear array (8, 12, 24) High-density connectivity in single connector. Common type is MPO or MTP MMF (OM4, OM5) UPC versus SMF (OS1) / APC or UPC 5

6 Construction (Tier-1 test) Only OLTS (or LSPM) defined for Tier 1 testing 6

7 Troubleshooting (Tier-2 test) Copper (CAT) Fiber Mapping faults along the fiber requires the use of an iolm-otdr iolm-otdr is the only tool for: FIP FIP FIP Leaf Detect Macrobends Measure and validate proper return loss of connectors Serial Duplex Transceivers SMF or MMF FIP MTP/MPO trunks FIP Receive fiber iolm FIP Spine Detect excessive connector loss due to contamination, damage Identify the position of a fiber fault or issue Launch fiber 7

8 Move Add & Change (MAC) Transceivers Copper (CAT) Fiber OLTS and Fiber Inspection probe, because it s faster (3 sec.)! 1-Validate channel is Pass with OLTS Leaf 2-Clean & inspect connectors Serial Duplex Transceivers SMF or MMF FIP FIP MTP/MPO trunks FIP FIP OLTS FIP FIP Spine 3-Connect new transceivers/ link 4-Validate the link works properly 5-If not proper, transceiver is likely to be the issue. OLTS 8

9 OTDR for Tier-1 testing..? Can OTDR provides total fiber link attenuation/loss measurement as accurately as OLTS provides, in the field? 1. Slight variations of fiber geometry along the fiber under test induce some errors in the OTDR measurement when tested from a single direction. 2. When testing link attenuation, the local errors due to fiber geometry mismatch are not cumulative. The link attenuation error only depends on launch vs receive fiber geometry. 3. Averaging measurements performed from both ends remove these errors (bidirectional averaging). 9

10 Why Encircled Flux (EF) is Important LED VCSEL Ideal/ EF conditioned OFL/Mandrel Wrap per TIA A, Encircled Flux (EFL) TIA B, Annex A Source: Belden (2011) Optical loss testing in the field, not as simple as it seems 10

11 LSPM: Main uncertainty contributors MMF loss measurement using a 1-cord reference, at 850 nm for a link of 300 m, with a total loss of 1.6 db Uncertainty contributor Source of errors Value Comment Light source instability Test Equipment +/-0.05 db Typical instability of a light source as per IEC Light source wavelength Test Equipment/ FUT (spectral dependency) Spectral loss dependence for 300 mat 850 nm +/-30 nm Light source wavelength tolerance specified as per ISO/IEC (2016) MMF Launch condition Test Equipment +/- 10% x 1.6 db (850 nm) For Encircled Flux compliant source Mating reproducibility FUT +/- 0.1 db As per IEC Reference connector repeatability FUT +/ db As per IEC /-0.27 db (850 nm) total uncertainty ref. IEC TR (2016) (considers statistical addition of all contributors, weight dependent) 11

12 MMF: OLTS reference set-up OLTS measurement has been made in duplex (1-cord reference) EF compliant REF-Grade (3m) REF-Grade (3m) EF compliant Typical FUT: 12

13 MMF: OLTS attenuation (850 nm) Uncertainty of light-source / power meter measurement on a MMF link as per IEC TR (2016) +/ db Test conditions: 3 OLTS, TJ-REF Jumpers Reproductibility of the OLTS measurement is consistent with the expected measurement uncertainty (using three different OLTS). 13

14 OTDR - Main uncertainty contributors Uncertainty contributor Launch and receive test cord fiber geometry Comment Fiber geometry (mainly the core size and the numerical aperture of the fiber) influence the amount of backscatter signal that a fiber generates(source uncertainty in the measurement of individual connectors and splices loss with an OTDR). The uncertainty contribution due to fiber geometry mismatch is +/-0.19 db for SMF assuming a (fairly typical) fiber core specification of 9.2 +/-0.4 mm. Performing bidirectional OTDR measurement will remove this error. Loss spectral dependency of fiber OTDR trace noise Trace recovery Proper measurement of link loss Trace analysis/event detection robustness The fact that the LS and the iolm can have slightly different nominal wavelengths will cause some deviation in the measurements due to the spectral attenuation characteristics of the fiber (in general, connectors and splices losses have low dependencies on nominal wavelength, but not the fiber) OTDR is dependent on the right adjustment of OTDR test parameters (pulse length, distance range and averaging time). When a strong reflectance occurs close to the end of the link under test, it may cause some error on the measurement of the backscatter level on the receive test cord Minimum receive test cord length depends on worse case reflectance that is expected. In general, OTDR performances are highly dependent on the quality of the raw OTDR trace (clean trace, no distortion or artefacts) as well as the robustness of the algorithms performing trace analysis (event detection and characterization). 14

15 MMF: iolm reference set-up iolm IL measurement - In the iolm application, specify the Launch and Receive lengths - Launch an iolm acquisition and read the span loss. iolm SPSB-EF DUT SPSB-100m PM 15

16 MMF: iolm attenuation (850 nm) Consistent results over multiple instruments. Test conditions: 3 OTDRs, Launch & Receive fibers Reproductibility of the iolm measurementexhibitsvery good consistency (using three different iolm). EXFO is willing to share its procedure for comparison. 16

17 MMF: OLTS vs iolm attenuation (850 nm) Test conditions: 3 OTDRs, Launch & Receive fibers OLTS, TJ-REF Jumpers This bias is explained by the fundamental mechanism of backscattering which produces a slightly underfilled equivalent measurement (even if the iolm is conditioned for EF). iolm measures slightly lower attenuation than OLTS (average bias db) 17

18 SMF: iolm reference set-up (1310/ 1550 nm) Presented at TR meeting, Philadelphia OTDR 1310/1550 Polarization Scrambler Launch Fiber Power Meter P1 Attenuation REF = P1-P OTDR 1310/1550 Polarization Scrambler Launch Fiber FUT Receive Fiber Power Meter P2 A reference measurement is required to validate accuracy of OTDR method. The reference is done using Light Source (LS) and Power Meter (PM). The best possible conditions are set for the reference: LS is using OTDR source in CW mode to ensure same wavelength as OTDR measurement A Polarization scrambler is used to reduce PDL effects A high-linearity, cooled detector, Laboratory PM is used Ambient temperature is 23 C +/-1C Long warm-up are allowed (>30 minutes) before measurements This setup can provide an attenuation reference with 0.01 db uncertainty. OTDR settings (pulse, range, averaging duration) are appropriate to ensure a low-noise measurement. Launch and receive cords are of sufficient lengths. 18

19 SMF: Single Direction OTDR Measurement Test conditions: 5 +/ db OTDRs Launch fibers Receive fibers Launch & receive from same fiber type & manufacturer (to reduce uncertainty due to MFD mismatch) 19

20 SMF: Bi-directional OTDR Measurement Test conditions: 5 +/- 0.1 db OTDRs Launch fibers Receive fibers Bi-directional OTDR measurement: cancel out Backscatter characteristics between launch & receive fibers 20

21 Conclusions For SMF, only launch & tail cords backscatter characteristics are important for link attenuation. When launch & tail cords have the same backscatter characteristics, there is no error introduced in the link attenuation. For MMF, there is a slight bias between OTDR and LSPM due to the nature of the backscattering process. OTDR can provide extremely accurate fiber link attenuation measurements for SMF and fairly accurate for MMF. OTDR should be considered as a valid tool/method for Tier 1 characterization of SMF. For characterization of MMF, improvements are on the way. 21

22 22

23 Reflectance issues at the patch panel? Thresholds (customers): Standards (TIA D(2016, b.3), IEC (2010): SMF 35dB, MMF 20dB Direct modulation (CWDM4, PSM4, PAM4): -40 to -45dB CRC issues Coherent-based: -30dB = EDFA APR mode issue Strict correlation (clean vs. oil) Finger oil db average change (clean vs. oil) Source: EXFO Application Note 327 Touching on Failure: Sources of Singlemode Fiber Issues in the Data Center, December

24 MTP/MPO based links (Tier-1 & Tier-2) Parallel optics Pre-installation quality test Migration to 100G/ 200G/ 400G

25 Server to server communication inside a DC 25

26 Leaf Spine topology: Redundant, scalable Efficient use of most affordable components, QSFP28, switches Each servers in the data center is linked with all the other servers with the same number of hops. Can be configured in Layer 2 (switched) or Layer 3 (routed) 26

27 OM5 MMF Considerations (SWDM4) Source: Commscope Test parameter Attenuation ORL / Reflectance Dispersion (Chromatic and Modal) Test vendor advices Testing 850 nm worst case appears the best practice 850 nm presents higher attenuation than 950 or 1300 nm VCSEL is more sensitive to ORL than LED ORL is wavelength independent, not light source independent Expect the smallest differential mode delay (DMD) specs possible for WBMMF Unless stated otherwise by the fiber manufacturer, CD (chromatic) and modal dispersion shall be considered OK by design Source: EXFO 27

28 What are the main contributors of uncertainty? Light Source / Power Meter (OLTS) OTDR Light Source (LS) instability (warming time) LS wavelength drift after referencing Reference test jumpers conditions Multimode reference test jumpers launch condition Mating reproducibility Reference connector repeatability LSPM vs OLTS (coupler PDL) Ideal LSPM vs OTDR (samefor SM, slight difference for MM) OTDR loss linearity (vs loss uncertainty) Launch vs receive fiber geometry (different backscattering ratio) Noise on trace (vs pulse, vs averaging time) Trace recovery (vs reflectance, vs length of receive fiber) Echos Trace analysis/ event detection robustness Respect calibration period and change your test jumpers 1- Equipment variation (repeatability) 2- Product variation(fut variation) 28

29 UNCERTAINTY SPECIFICATIONS Source & Power meter-olts Specification (db) Typical Notes Link IL uncertainty 0.1 (0.2) PM/LS: Loss <46 db (OLTS: Loss <55 db) Single connector IL uncertainty N/A Reflectance uncertainty N/A Short link ORL uncertainty 0.5 (1) PM/LS: mandrel method (OLTS: Up to 55 db ORL for APC) USING SUITABLE REFERENCE CABLES OTDR -iolm Typical Specification (db) Notes Link IL uncertainty 0.1 Link loss for 3m<L<500m or <12 db. Single connector IL uncertainty m L <500m Reflectance uncertainty 0.75 From -45 to -65 db ForL<15 m. Includes two connectors and fibre loss Short link ORL uncertainty 1 uncertainties. Events may be merged. Specifications of FTB-730-iOLM testing of short span links (3m<Link<500m) Results valid at Results valid at 1310 and 1550 nm at 23±3 C Launch/ Receive (matched): 150m (for FUT <5 db IL) or 500m (for FUT <12 db IL) Reflectance specifications valid for L 15 m 29

30 Why Encircled Flux method is so important? LED VCSEL IDEAL (EF) EF ready, no external mode conditioner required EF ready, external mode conditioner required 10G+ fiber-optic testing, requires EF metric, launching condition to satisfy the required REPEATABILITY, REPRODUCIBILITY and OPTIMAL UNCERTAINTY 30

31 Is up to 30% uncertainty acceptable? TIA-568 C.3 : 3.5dB (OM1-OM4) IEEE 802.3ae 10GBASE-LX4 : 2dB (OM2-OM4) IEEE 802.3ba 40/100GBASE-SR4 : 1.5dB (OM4) OFL/Mandrel Wrap per TIA A, Encircled Flux (EFL) TIA B, Annex A Source: Belden (2011) Optical loss testing in the field, not as simple as it seems 31

32 OLTS/ PM-LS / certification TX RX LC-MTP MTP-LC (1G/10G) TX RX MAX-940-QUAD 100 m OM4, 2km OS1 <3 seconds, 2 wavelengths Duplex, bi-directional, EF testing OLTS IL = 1.27 db TIA-568-C.3 ISO/IEC = 3.5 db IEEE802.3.ba 40/100GBASE-SR4 (4x25) = 1.9 db Two evolutive tabletinspired Platforms Expert guidance, every step of the way On-board multistandar d Certification Reduced cost of ownership 32

33 Is MMF dead? I think not: WBMMF (SWDM4) 2 fibers / 850 nm 880 nm 910 nm 940 nm Wideband Multimode Fiber (WBMMF) Source: Commscope Test parameter Test vendor advices Attenuation Testing 850 nm worst case appears the best practice 850 nm presents higher attenuation than 950 or 1300 nm ORL / Reflectance VCSEL is more sensitive to ORL than LED ORL is wavelength independent, not light source independent Chromatic Dispersion Dispersion (Chromatic and Modal) Expect the smallest differential mode delay (DMD) specs possible for WBMMF Unless stated otherwise by the fiber manufacturer, CD (chromatic) and modal dispersion shall be considered OK by design Modal Dispersion Pulse spreading Source: EXFO 33

34 Questions, checklist & test objectives # Checklist Prerequisite Note Important: Test instruments calibration and reference test jumpers Changetest jumpers each connections or if they are scratched. Measurement uncertainty depends on these factors. Input:Multimode or Singlemode fiber Keep in mind the 150 m reach limitation for MMF (OM4/WBMMF). Input:What volume orcounts of fiber to test Decision:Test tools, testing time & test procedures 1 Contaminantson the connector endfaces 2 Masteringtest repeatability, uncertainty What is the test task:fiber certification, troubleshooting, warranty registration OLTS helps screen suspect links (ORL) OTDR maps fault and connectors RL Clean& inspect, first time right. Multimode fiber, EncircledFlux compliant equipment & procedure. Tighter budgetfor 40G& 100G over OM4 MMF/ WBMMF, SMF more $ Set your objectives carefully. Testinstruments alone do not solve everything! Ultimate baseline for an effectiveand efficient optical testing! Respect calibration and test jumpers quality! 3 Testdata valorization Documentation system and processes Bestpractices to speed up future trouble shooting. 4 Managing10G to 100G+ migration: connectors RL impact RL can kill a network at 25Gbps line rate 25/50 Gbps more demandingthan 10 Gbps 34

35 OLTS vs iolm-otdr / RL, BR, ORL Tier-1 & 2 Return loss(rl) is thelossof power in the signal returned/reflected by a discontinuityin a transmission line or optical fiber. This discontinuity can be a mismatch with the terminating load or with a device inserted in the line (also called Reflectance or back reflection ). Optical Return Loss (ORL) is a measure taken from one end of the total energy reflected back to the source by all the interfaces due to a variation of the index of refraction (IOR), breaks, voids, backscatter, etc., created inside a component or along a link. iolm iolm -OTDR Launch Receive LC LC End-to-end OLTS FasTest Simplex 35

36 EXAMPLE 36

37 OLTS/ ORL: screening & link certification MAX-945iCERT-QUAD MAX-945iCERT-QUAD 500 ft. (150 m) Targeted applications 1- OLTS 1- OLTS 2- FIP 3- iolm 1- OLTS 2- iolm Move, Add and Changes (MACs) of pluggables optics Construction, certification of total loss budget (tier-1) 37

38 iolm OTDR single fiber 100G-SWDM4 IDA LC patch panel SPSB-EF-30m Launch LC Patch panel Standard OM3 30m Receive ToR MDA 1.5 db / 150 m (OM4) DCI WDM OTDR-iOLM positions faults, loss, reflectance and provide link loss and ORL. Threshold and standard certification-based Pass/Fail. 38

39 iolm OTDR software interface OTDR-iOLM positions faults, loss, reflectance and provide link loss and ORL. Threshold and standard certification-based Pass/Fail. 39

40 Testing MPO 40

41 MTP/MPO cable configurations (polarity, types) 41

42 Adapter MPO Pinned (Male) MPO Unpinned (Female) MPO Guiding pins MPO Guiding holes 42

43 Physical Contact The Physical Contact area is the critical joining point in the fiber network. If no clean physical connection, the light path is disrupted and the connection is compromised. Multiple connects-disconnectscan create fiber misalignments (loose pin/ hole or memory shape related issues) 43

44 LC serial duplex MTP/MPO trunk catastrophic 44

45 FIP MTP/ MPO inspection auto-center / focus MTP12 MTP24 (MM/SM) High mag view (400X): Highest Magnification on the market Auto-center + Auto Focus FIP controls: Low mag view PIP (100X): Allows to see which fiber is being inspected in High magnification AutoCenter AutoFocus Capture Analysis 45

46 10G MTP/ MPO trunk test Step 1: Pre-installation quality test Step 2: End to end LC-LC permanent link test 46

47 47

Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team

Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team INTRODUCTION The OTDR is a very efficient tool for characterizing the elements on

More information

TESTING HIGH SPEED FIBER LINKS

TESTING HIGH SPEED FIBER LINKS TESTING HIGH SPEED FIBER LINKS Rodney Casteel, RCDD, DCDC, NTS, OSP - CommScope, Chair TIA FOTC Tyler Vander Ploeg - Viavi Solutions Jamie Humphreys - EXFO Rob Gilberti - AFL Jim Davis - Fluke Networks

More information

VTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links

VTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links VTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links TB Number 004 This bulletin is supplied for information only and is intended to provide

More information

FTB-7400E Metro/CWDM OTDR METRO/CORE AND CWDM NETWORK FIBER CHARACTERIZATION

FTB-7400E Metro/CWDM OTDR METRO/CORE AND CWDM NETWORK FIBER CHARACTERIZATION METRO/CORE AND CWDM NETWORK FIBER CHARACTERIZATION i OLM R E A D Y GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD High-resolution OTDR covering longer metro distances and ITU-based

More information

ENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING

ENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING ENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING Tier-1/2 solutions with controlled source launch conditions

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication ISO/IEC 14763-3 CONSOLIDATED VERSION Edition 2.1 2018-08 colour inside Information technology Implementation and operation of customer premises cabling Part 3: Testing of optical fibre cabling INTERNATIONAL

More information

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING Provided by www.aaatesters.com FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP

More information

ENCIRCLED FLUX (EF) TEST SOLUTIONS

ENCIRCLED FLUX (EF) TEST SOLUTIONS ENCIRCLED FLUX (EF) TEST SOLUTIONS Tier-1/2 solutions with controlled source launch conditions for maximum accuracy and repeatability designed to remove uncertainty from multimode fiber testing. KEY FEATURES

More information

Fibre Characterisation and FTTx New challenges

Fibre Characterisation and FTTx New challenges Fibre Characterisation and FTTx New challenges Broadband Technology Event Rotterdam, November 10th, 2009 Nicolas CARLIER France & Benelux RSM nicolas.carlier@exfo.com What is Fiber Characterisation when

More information

Ensuring Cabling Performance in the Customer-Owned Outside Plant

Ensuring Cabling Performance in the Customer-Owned Outside Plant Ensuring Cabling Performance in the Customer-Owned Outside Plant Needs to be able to qualify the installation to validate bandwidth requirements are met Future high bandwidth applications Future Proof

More information

The Rise of Tier 2 Testing

The Rise of Tier 2 Testing The Rise of Tier 2 Testing Why enterprises today demand better visibility into their fiber infrastructure Unprecedented demand for more bandwidth, faster network speeds, lower latency, and improved data

More information

EXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME

EXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME 10 /0 /100Gb/s transmission links are typically shared by a vast number of application and users. EXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME Claiming that they are most of the

More information

Certified Fibre Optic Specialist - Testing

Certified Fibre Optic Specialist - Testing Certified Fibre Optic Specialist - Testing COURSE DESCRIPTION: This training program is designed to introduce the student to the process of fibre optic network testing. It is intended for those looking

More information

AS/NZS ISO/IEC :2012

AS/NZS ISO/IEC :2012 AS/NZS ISO/IEC 14763.3:2012 (ISO/IEC 14763-3:2011, MOD) Australian/New Zealand Standard Telecommunications installations Implementation and operation of customer premises cabling Part 3: Testing of optical

More information

MTTplus Modular Test Platform

MTTplus Modular Test Platform MTTplus-410 Fiber Optics Test Module 2017 MTTplus Modular Test Platform The Fiber Optics module for the VeEX MTTplus supports a full range of test functions including OTDR, OPM, Light Source and VFL. Geo

More information

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications Ensuring Cabling Performance in the Customer-Owned Outside Plant Keith Foord Product Manager Greenlee Communications Introduction: Outside plant fiber networks require low reflectance terminations for

More information

Fiber Tes)ng 101 Essen)als Every Network Analyst Needs to Know. David S(llwell BCNET Oscar Rondon BCNET Gwenn Amice - EXFO

Fiber Tes)ng 101 Essen)als Every Network Analyst Needs to Know. David S(llwell BCNET Oscar Rondon BCNET Gwenn Amice - EXFO Fiber Tes)ng 101 Essen)als Every Network Analyst Needs to Know David S(llwell BCNET Oscar Rondon BCNET Gwenn Amice - EXFO Workshop format The Workshop is going to start with three short lecture style power

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO/IEC 14763-3 First edition 2006-06 Information technology Implementation and operation of customer premises cabling Part 3: Testing of optical fibre cabling Reference number ISO/IEC

More information

FTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD

FTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD FTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD 157 APPLICATION NOTE Mario Simard, Product Manager, Optical Business Unit The purpose of any fiber-optic network is to perform high-speed,

More information

FTBx-740C-DWC TUNABLE OTDR C-BAND DWDM METRO ETHERNET LINK CHARACTERIZATION

FTBx-740C-DWC TUNABLE OTDR C-BAND DWDM METRO ETHERNET LINK CHARACTERIZATION C-BAND DWDM METRO ETHERNET LINK CHARACTERIZATION GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD NEW OTDR GENERATION Tunable DWDM OTDR for testing through MUX/DEMUX channels to provide

More information

infrastructure for 10, 40 and 100Gbits/s readiness

infrastructure for 10, 40 and 100Gbits/s readiness Field Testing of fiber optic infrastructure for 10, 40 and 100Gbits/s readiness Christian Schillab Product Manager Media Test Fluke Networks Europe Member BritishStandards Institute Working Group TCT 7/

More information

FTB-730 PON FTTx/MDU OTDR OPTIMIZED FOR ACCESS FIBER DEPLOYMENTS AND TROUBLESHOOTING

FTB-730 PON FTTx/MDU OTDR OPTIMIZED FOR ACCESS FIBER DEPLOYMENTS AND TROUBLESHOOTING OPTIMIZED FOR ACCESS FIBER DEPLOYMENTS AND TROUBLESHOOTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The perfect tool for field technicians who need to seamlessly

More information

Fibre (TIA) Field Test Specification

Fibre (TIA) Field Test Specification This document has been prepared to aid consultants or engineers in developing contractual specifications covering the testing of duplex fibre optic cabling installations. It is offered as a general guide.

More information

FTB-720C LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

FTB-720C LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING FTB-720C LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD NEW OTDR GENERATION The ideal

More information

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation.  or (800) , (603) Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Industry leading TruEvent analysis Short dead zones provide precise testing of closely spaced events Front Panel and

More information

FLX380-30x FlexTester OTDR

FLX380-30x FlexTester OTDR Features 3rd generation hand-held, all-in-one OTDR, Source, Power Meter, VFL Icon-based LinkMap display with pass/fail for easy network analysis Patented in- or out-of-service testing from a single port

More information

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing.

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing. 3.4 TESTING OF FIBER OPTICS CABLING A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing. B. General: In the event

More information

CHALLENGE OF THE NEW OPTICAL FIBRE TECHNOLOGIES

CHALLENGE OF THE NEW OPTICAL FIBRE TECHNOLOGIES THE CHALLENGE OF THE NEW OPTICAL FIBRE TECHNOLOGIES 17th September 2002 Botanical Gardens Birmingham The Way We Were 1GbE and 10GbE OF Categories Channel Design Cleaning SFF Connecting Hardware Testing

More information

MT-RJ Optical Fiber System Field Testing

MT-RJ Optical Fiber System Field Testing MT-RJ Optical Fiber System Field Testing Table of Contents INTRODUCTION... 3 TEST JUMPERS... 4 LAUNCH CONDITIONS... 4 MT-RJ TEST KITS... 5 MT-RJ SYSTEM TESTING: Fixed transmit and receive (SC or ST-style)

More information

Fiber Optics for Todays Industry Applications

Fiber Optics for Todays Industry Applications Hands-On Fiber Optics for Todays Industry Applications (A Non-Telephone Company Course) Course Description This Hands-On course is designed to provide technicians with a practical understanding and Hands-On

More information

M310 Data Center OTDR

M310 Data Center OTDR Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone

More information

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture

More information

LAN/WAN OTDR FTB-7200 FTTx Access/Metro OTDR FTB-7200/7300 Metro/Long-Haul OTDR FTB-7400/74000 Long-Haul OTDR FTB-7500

LAN/WAN OTDR FTB-7200 FTTx Access/Metro OTDR FTB-7200/7300 Metro/Long-Haul OTDR FTB-7400/74000 Long-Haul OTDR FTB-7500 OTDR MODULE SERIES LAN/WAN OTDR FTB-7200 FTTx Access/Metro OTDR FTB-7200/7300 Metro/Long-Haul OTDR FTB-7400/74000 Long-Haul OTDR FTB-7500 NETWORK TESTING OPTICAL Platform Compatibility First-class benefits

More information

M700-Series Multifunction OTDR

M700-Series Multifunction OTDR M700-Series Multifunction OTDR Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Test Modes Full Auto OTDR Normal (point-to-point) fiber cable construction testing and fault location

More information

OPTICAL TIME DOMAIN REFELECTOMETER (OTDR): PRINCIPLES

OPTICAL TIME DOMAIN REFELECTOMETER (OTDR): PRINCIPLES OPTICAL TIME DOMAIN REFELECTOMETER (OTDR): PRINCIPLES Why Test Fiber with an OTDR? Single ended test that......characterizes fiber from end-to-end...locate and measure each event...provides a detailed

More information

FG-750 Client API SDN-READY INTELLIGENT OTDR

FG-750 Client API SDN-READY INTELLIGENT OTDR SDN-READY INTELLIGENT OTDR 4G Northbound API Any controller platform Southbound API REST Client API REST Client API REST Client API REST Client API Fiber monitoring device ready to be integrated with Open

More information

Kingfisher KI-3800 Light Source. Inexpensive handheld source for testing and commissioning optical fibre networks. Compact and rugged,

Kingfisher KI-3800 Light Source. Inexpensive handheld source for testing and commissioning optical fibre networks. Compact and rugged, TEST EQUIPMENT POWER METERS, LIGHT SOURCES Kingfisher KI-9800 Light Source Kingfisher KI-3800 Light Source Inexpensive handheld source for testing and commissioning optical fibre networks. Compact and

More information

FTB-735C Metro/PON FTTx/MDU OTDR

FTB-735C Metro/PON FTTx/MDU OTDR OPTIMIZED FOR METRO/CORE AND FTTX/MDU FIBER DEPLOYMENTS AND TROUBLESHOOTING i OLM R E A D Y GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD NEW OTDR GENERATION High-resolution OTDR designed

More information

M210 Multifunction Micro OTDR

M210 Multifunction Micro OTDR Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Features 30 db dynamic range single-mode 16-hour battery life Remote display capable Touch and Test intuitive user interface New

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61280-4-1 Edition 2.0 2009-06 Fibre-optic communication subsystem test procedures Part 4-1: Installed cable plant Multimode attenuation measurement IEC 61280-4-1:2009(E) THIS

More information

OTDR II. Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling

OTDR II. Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling The OTDR II is the first tablet

More information

FTB/FTBx-740C-CWDM Tunable OTDR 18-WAVELENGTH CWDM OTDR FOR METRO ETHERNET AND C-RAN LINK CHARACTERIZATION

FTB/FTBx-740C-CWDM Tunable OTDR 18-WAVELENGTH CWDM OTDR FOR METRO ETHERNET AND C-RAN LINK CHARACTERIZATION 18-WAVELENGTH CWDM OTDR FOR METRO ETHERNET AND C-RAN LINK CHARACTERIZATION NEW OTDR GENERATION A single and compact OTDR unit that covers all 18 CWDM ITU channels for testing through MUX/DEMUX channels,

More information

A Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification

A Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification A Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing Vol. 2 Tier 2 Certification Notice Copyright Every effort was made to ensure that the information in this document

More information

Intelligent Optical Link Mapper (iolm)

Intelligent Optical Link Mapper (iolm) Intelligent Optical Link Mapper (iolm) AUTOMATED, EXPERT-LEVEL SINGLEMODE FIBER TESTING Available on: FTB-700 OTDR Series FTB-7000 OTDR Series Powered by T E C H N O L O G Y Patent protection applies to

More information

Fibre Optic Connector and Component Standards Developments & Key Issues in IEC & CENELEC. Philip C Longhurst Corporate Fibre Optic R & D Manager

Fibre Optic Connector and Component Standards Developments & Key Issues in IEC & CENELEC. Philip C Longhurst Corporate Fibre Optic R & D Manager Fibre Optic Connector and Component Standards Developments & Key Issues in IEC & CENELEC Philip C Longhurst Corporate Fibre Optic R & D Manager Outline CENELEC TC86BXA work programme IEC SC86B WG 6 and

More information

OTDR. Optical Time Domain Reflectometer. User Guide

OTDR. Optical Time Domain Reflectometer. User Guide OTDR Optical Time Domain Reflectometer User Guide Copyright 2013 2015 EXFO Inc. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form,

More information

FTBx-750C Metro/Long-Haul OTDR LONG-DISTANCE FIBER CHARACTERIZATION AND FIBER UPGRADES

FTBx-750C Metro/Long-Haul OTDR LONG-DISTANCE FIBER CHARACTERIZATION AND FIBER UPGRADES LONG-DISTANCE FIBER CHARACTERIZATION AND FIBER UPGRADES GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD NEW OTDR GENERATION High dynamic range combined with high resolution for highly

More information

A Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification

A Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification A Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing Vol. 2 Tier 2 Certification A Quick Start Guide to Fiber-to-the-Antenna enna (FTTA) Installation and Maintenance Testing

More information

Field Test Procedure for Optical Fibre Link Measurements

Field Test Procedure for Optical Fibre Link Measurements Application Notes Field Test Procedure for Optical Fibre Link Measurements Issued April 2014 Abstract After fiber optic cables are installed, spliced and terminated, they must be tested. For every fiber

More information

palmotdr Series Handheld OTDR

palmotdr Series Handheld OTDR palmotdr Series Handheld OTDR Most Compact High-Performance OTDR Comprehensive fiber applications, ideal for LAN/WAN/FTTx certification & trouble-shooting: SM: 1310/1490/1550, 1625/1650nm (with filter),

More information

THE ENTRY-LEVEL SOLUTION DESIGNED FOR ALL YOUR TESTING NEEDS

THE ENTRY-LEVEL SOLUTION DESIGNED FOR ALL YOUR TESTING NEEDS THE HANDHELD OTDR... REINVENTED. The MAX-700B/C Series is the first tablet-inspired OTDR line that is handy, lightweight and rugged enough for any outside plant environment. With a 7-inch, outdoor-enhanced

More information

The True Value of Connector Inspection: New Challenges and Best Practices

The True Value of Connector Inspection: New Challenges and Best Practices The True Value of Connector Inspection: New Challenges and Best Practices Vincent Racine Product Line Manager August 2011 1 Table of contents 1 Best Practices 2 Connector Inspection Tools 3 Connector Inspection

More information

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation.  or (800) , (603) Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry

More information

M210 Multifunction Micro OTDR

M210 Multifunction Micro OTDR Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Features 30 db dynamic range single-mode 16-hour battery life Remote display capable Touch and Test intuitive user interface New

More information

Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010

Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010 Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010 Adrian Young Sr. Customer Support Engineer Foreword Reflectance is measured using an Optical

More information

Acceptance Requirements. Fibre Optic Systems. Revised 12/2017. December 5th, Alexander Kölbel

Acceptance Requirements. Fibre Optic Systems. Revised 12/2017. December 5th, Alexander Kölbel December 5th, 2017 Acceptance Requirements Fibre Optic Systems Revised 12/2017 Alexander Kölbel +49 6190 8880-40 alexander.koelbel@datwyler.com Dätwyler Cables GmbH, Auf der Roos 4-12, 65795 Hattersheim,

More information

Event dead zone: 0.8 m. Attenuation dead zone: 4 m. Dynamic range: up to 50 db. Platform compatibility. FTB-200 Compact Platform

Event dead zone: 0.8 m. Attenuation dead zone: 4 m. Dynamic range: up to 50 db. Platform compatibility. FTB-200 Compact Platform OTDR MODULE SERIES FTB-7000 OTDR Series NETWORK TESTING OPTICAL Powerful OTDRs covering all network testing applications Event dead zone: 0.8 m Attenuation dead zone: 4 m Dynamic range: up to 50 db FTTx

More information

Optical Return Loss Measurement by Gregory Lietaert, Product Manager

Optical Return Loss Measurement by Gregory Lietaert, Product Manager White Paper Optical Return Loss Measurement by Gregory Lietaert, Product Manager Introduction With the increasing frequency of high-speed transmission systems and DWDM deployment, optical return loss (ORL)

More information

FastReporter 2 DATA POST-PROCESSING SOFTWARE

FastReporter 2 DATA POST-PROCESSING SOFTWARE DATA POST-PROCESSING SOFTWARE Consolidated data management and post-processing tool designed to increase the reporting productivity for connector endface inspection and all types of optical-layer testing:

More information

Extensive range of models covering all telecom testing applications. Flexible design, allowing up to three wavelengths in a single module

Extensive range of models covering all telecom testing applications. Flexible design, allowing up to three wavelengths in a single module 7000 OTDR MODULE SERIES NETWORK TESTING The all-new FTB-7000D: first-class benefits 1 m event dead zone: shortest in the industry Testing time: four times shorter than industry standard FTTx ready: passive

More information

ACCESS Master MT9085 Series. Product Introduction

ACCESS Master MT9085 Series. Product Introduction ACCESS Master MT9085 Series Product Introduction Strengthen of MT9085 Series: 1/5 All Optical Fiber Evaluation Functions in One Tester The ACCESS Master MT9085 series is an all-inone tester with OTDR,

More information

Universal Connectivity Platform A Modular Approach to Infrastructure Design

Universal Connectivity Platform A Modular Approach to Infrastructure Design A Modular Approach to Infrastructure Design TE Connectivity s Universal Connectivity Platform (UCP) provides a fully modular approach to designing data centers and telecommunications rooms. This patch

More information

M700-Series OTDRs. or (800) , (603)

M700-Series OTDRs.  or (800) , (603) Features M700 Compact QUAD OTDR M700 OTDR with DFS1 Digital FiberScope Integrated OPM and VFL (650 nm) Inspection capable with the DFS1 FiberScope Full Auto, Expert, and Real-Time OTDR test modes Automatic

More information

Accelerating NBN fiber testing. Tom Ronan Marketing Lead Fiber Optics Melbourne

Accelerating NBN fiber testing. Tom Ronan Marketing Lead Fiber Optics Melbourne Accelerating NBN fiber testing and workforce Performance. Tom Ronan Marketing Lead Fiber Optics Melbourne Agenda Network Elements and Parameters Distributed Fiber Network (DFN) Construction Network Activation

More information

intelligent Optical Link Mapper (iolm)

intelligent Optical Link Mapper (iolm) OTDR-BASED APPLICATION MAKING EXPERT-LEVEL FIBER TESTING ACCESSIBLE TO ANYONE Powered by T E C H N O L O G Y Available on: MaxTester 700B/C OTDR Series FTB-700C OTDR Series FTBx-700C OTDR Series FTB-7000E

More information

VIEW500 USER-FRIENDLY STANDARD OTDR

VIEW500 USER-FRIENDLY STANDARD OTDR USER-FRIENDLY STANDARD OTDR SOLA (Smart Optical Link Analyzer) 7 Touch Screen with Smart GUI 8GB Internal Storage with Internal SD Card & External USB Memory Built-In VFL, Light Source and OPM Fast Booting

More information

FTBx-730C PON FTTx/MDU OTDR OPTIMIZED FOR FTTx/MDU FIBER DEPLOYMENTS AND TROUBLESHOOTING

FTBx-730C PON FTTx/MDU OTDR OPTIMIZED FOR FTTx/MDU FIBER DEPLOYMENTS AND TROUBLESHOOTING OPTIMIZED FOR FTTx/MDU FIBER DEPLOYMENTS AND TROUBLESHOOTING i OLM R E A D Y GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD NEW OTDR GENERATION The perfect tool for field technicians

More information

Benefits of Enhanced Event Analysis in. Mark Miller

Benefits of Enhanced Event Analysis in. Mark Miller Benefits of Enhanced Event Analysis in Data Center OTDR Testing Mark Miller Dr. Fang Xu AFL/Noyes Test & Inspection Overview Challenges Topics Techniques and Improvements Benefits of enhanced event analysis

More information

palmotdr Series Handheld OTDR

palmotdr Series Handheld OTDR palmotdr Series Handheld OTDR Most Compact High-Performance OTDR Comprehensive fiber applications, ideal for LAN/WAN/FTTx certification & trouble-shooting: SM: 1310/1490/1550, 1625/1650nm (with filter),

More information

OPX-BOX. Platform Highlights. Software Support. Key Features

OPX-BOX. Platform Highlights. Software Support. Key Features Ultra Compact, Highly Versatile OTDR with Bluetooth Wireless and USB Control The VeEX is an ultra-compact, OTDR designed to operate remotely using Fiberizer software. The unit can be controlled via USB

More information

FX150 OTDR. Platform Highlights. Key Features

FX150 OTDR. Platform Highlights. Key Features Mini OTDR for FTTx and Metro fiber networks FX150 mini OTDR is designed for the installation, maintenance and troubleshooting of FTTx, Mobile FrontHaul/BackHaul and Metro fiber networks. The compact, lightweight

More information

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech Course Description This Hands-On 3-day course has been customized to provide technicians with a practical understanding of fiber optic theory and fiber

More information

OptiFiber Pro OTDR Built for the enterprise

OptiFiber Pro OTDR Built for the enterprise OptiFiber Pro OTDR Built for the enterprise As enterprise networks and datacenter architectures evolve, IT infrastructure administrators demand better OTDR technology to maintain fiber network performance.

More information

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling Hands-On Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling Certification Course Description This Hands-On course is customized to give Technicians the confidence and skills to maintain Fiber

More information

Noyes OFL 250B Specs Provided by

Noyes OFL 250B Specs Provided by Noyes OFL 250B Specs Provided by www.aaatesters.com OFL 250 Handheld OTDR The Noyes OFL 250 from AFL Telecommunications is a single-mode OTDR with an integrated Optical Power Meter (OPM), Source (OLS),

More information

VIEW500 FASTEST STANDARD OTDR

VIEW500 FASTEST STANDARD OTDR FASTEST STANDARD OTDR SOLA, Simplify The OTDR Test Process 7 Touch Screen with Smart GUI 8GB Internal Storage with Internal SD Card & External USB Memory Built-In VFL, Light Source and OPM Fast Booting

More information

IDEAL INDUSTRIES, INC. USER MANUAL IDEAL OTDR

IDEAL INDUSTRIES, INC. USER MANUAL IDEAL OTDR IDEAL INDUSTRIES, INC. USER MANUAL IDEAL OTDR Revision: March 31, 2016 Copyright 2013 2016 EXFO Inc. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or

More information

FastReporter 2 DATA POST-PROCESSING SOFTWARE

FastReporter 2 DATA POST-PROCESSING SOFTWARE DATA POST-PROCESSING SOFTWARE Consolidated data management and post-processing tool designed to increase the reporting productivity for connector endface inspection and all types of optical-layer testing:

More information

AV6416 OTDR. Product Overview: Main Features:

AV6416 OTDR. Product Overview: Main Features: AV6416 OTDR Product Overview: AV6416 OTDR is a test instrument designed for FTTx. It s mainly used to measure the physical characteristics of optical fiber & cables, including length, transmission loss

More information

FlexScan OTDR With SmartAuto and LinkMap

FlexScan OTDR With SmartAuto and LinkMap FlexScan OTDR With SmartAuto and LinkMap Quick Reference Guide Test & Inspection Controls, Display, Interfaces 1 2 4 8 1. Power button 2. Power jack (5 VDC) 3. Charge/AC indicator 4. USB ports 5. OTDR/source

More information

Flexibility, scalability andsecurity

Flexibility, scalability andsecurity THE OF INFORMATION TECHNOLOGY SYSTEMS An Official Publication of BICSI January/February 2014 l Volume 35, Number 1 data center Flexibility, scalability andsecurity plus + The Next Five Years in AV + Measuring

More information

FLX380-30x FlexTester3 OTDR

FLX380-30x FlexTester3 OTDR Features 3rd generation hand-held, all-in-one OTDR, OLS, OPM, VFL Patented in- or out-of-service testing from a single port 42/42 db dynamic range @ 1310/1550 nm; test up to 1x128 PON Industry-leading

More information

GAMMA OTDR application consists of main window and menu. Using menu user can operate in different modes of application.

GAMMA OTDR application consists of main window and menu. Using menu user can operate in different modes of application. GAMMA OTDR Introduction...1 Using GAMMA OTDR...1 Application main window...1 Menu description...2 file...2 instrument...2 mode...5 events...9 view...11 Introduction GAMMA OTDR is the first Android application

More information

MINI2. Inno Mini 2 Specs Provided by MOST ACCURATE COMPACT OTDR

MINI2. Inno Mini 2 Specs Provided by  MOST ACCURATE COMPACT OTDR Inno Mini 2 Specs Provided by www.aaatesters.com MOST ACCURATE COMPACT OTDR SOLA (Smart Optical Link Analyzer) 5 Touch Screen with Smart GUI 8GB Internal Storage with Internal SD Card & External USB Memory

More information

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis Experience designing cable and network testers has enabled a breakthrough

More information

OptiFiber Pro OTDR Built for the enterprise

OptiFiber Pro OTDR Built for the enterprise OptiFiber Pro OTDR Built for the enterprise As enterprise networks and datacenter architectures evolve, IT infrastructure administrators demand better OTDR technology to maintain fiber network performance.

More information

Optical Multitester 500 450 OTDR EMEA & APac Edition Issue 1 Page 1 of 10 Description The 450 OTDR is a PC based state-ofthe-art OTDR designed for field applications. It is a dedicated OTDR which offers

More information

Fibre Specification Standards

Fibre Specification Standards Fibre Specification Standards User Manual The most important thing we build is trust Cobham Wireless - Coverage Table of Contents 1. Single-mode Fibre to ITU-T Recommendation G.652 3 2. SC/APC Mated Pair

More information

MINI2 MOST ACCURATE COMPACT OTDR

MINI2 MOST ACCURATE COMPACT OTDR MOST ACCURATE COMPACT OTDR SOLA, Simplify The OTDR Test Process 5 Touch Screen with Smart GUI 8GB Internal Storage with Internal SD Card & External USB Memory Built-In VFL and Light Source Fast Booting

More information

Securing optical network physical layer with Fiber Monitoring and Management Vratislav Blažek Regional Sales Manager

Securing optical network physical layer with Fiber Monitoring and Management Vratislav Blažek Regional Sales Manager Securing optical network physical layer with Fiber Monitoring and Management Vratislav Blažek Regional Sales Manager 2/3/2016 Remote and Centralized OTDR Testing Challenges How can I know if the fiber

More information

Refurbished EXFO Instruments

Refurbished EXFO Instruments The following list of available refurbished EXFO instruments is only updated daily. Consequently, it may not reflect recent changes in the inventory. Once an order is placed ofr a refurbished unit, the

More information

Optical Fiber Monitor (OFM) Whitebox WB-OFM-1262-DC

Optical Fiber Monitor (OFM) Whitebox WB-OFM-1262-DC Optical Fiber Monitor (OFM) Whitebox WB-OFM-1262-DC www.lumentum.com Data Sheet The Lumentum Optical Fiber Monitor (OFM) Whiteboxes reduce network downtime with automated fault location. Detecting and

More information

M-Series Compact OTDRs User s Guide

M-Series Compact OTDRs User s Guide M-Series Compact OTDRs User s Guide Limited Warranty One Year Limited Warranty All Noyes products are warranted against defective material and workmanship for a period of one year from the date of shipment

More information

FTS500 Series. Handheld OTDR Test Set.

FTS500 Series. Handheld OTDR Test Set. www.opwill.com OTDR Tester is entirely new pad product released by OPWILL. It has rapid start technology and supports automatic and realtime test mode, which can guarantee engineers to examine and detect

More information

OPX-BOXe Rugged, Pocket-sized Mini OTDR

OPX-BOXe Rugged, Pocket-sized Mini OTDR OPX-BOXe Rugged, Pocket-sized Mini OTDR Highly Versatile OTDR with Wireless and USB Control The VeEX OPX-BOXe is an ultra-compact, OTDR designed to operate remotely using Fiberizer software. The unit can

More information

STAND OUT FROM THE CROWD. Bisham Abbey, 14th May 2002 INTRODUCTION. Work Smart FIA. The Fibreoptic Industry Association STAND OUT FROM THE CROWD

STAND OUT FROM THE CROWD. Bisham Abbey, 14th May 2002 INTRODUCTION. Work Smart FIA. The Fibreoptic Industry Association STAND OUT FROM THE CROWD INTRODUCTION Work Smart FIA STAND OUT FROM THE CROWD 14th May 2002, Bisham Abbey Mike Gilmore 2002 Fibreoptic Industry Association Work Smart www.it-cabling.com www.e-readybuilding.com PO Box MT65, LEEDS,

More information

Remote fiber testing to improve SLA s

Remote fiber testing to improve SLA s Remote fiber testing to improve SLA s Presented by : Kamel SOUILAH System Sales Engineer kamel.souilah@exfo.com 2010 EXFO Inc. All rights reserved.. 1 EXFO is the leader in the test and measurement solutions

More information

TRM 2.0 Test Results Manager All-In-One Comprehensive Analysis and Reporting Software

TRM 2.0 Test Results Manager All-In-One Comprehensive Analysis and Reporting Software TRM 2.0 asic Software Features Generate professional acceptance reports including: OTDR traces Certification loss results/opm loss results Connector Inspection Results Create certification results and

More information

AE2200 FTTx Multi-Function Meter

AE2200 FTTx Multi-Function Meter AE2200 FTTx Multi-Function Meter Key Benefits Future-proof, all-in-one solution includes optical, cable TV analysis, and metallic testing for verifying the installation of FTTx, RFoG and RF PON networks

More information

Intelligent Optical Link Mapper (iolm)

Intelligent Optical Link Mapper (iolm) Intelligent Optical Link Mapper (iolm) AUTOMATED, EXPERT-LEVEL SINGLEMODE AND MULTIMODE FIBER TESTING Available on: MAX-700B OTDR Series FTB-700 OTDR Series FTB-7000E OTDR Series Powered by T E C H N O

More information