Installation and User Instructions

Size: px
Start display at page:

Download "Installation and User Instructions"

Transcription

1 Installation and User Instructions The Informant is a self-contained alarm and logging device that uses the cellular phone network. Text message alarms are sent up to five cell phones. Events are logged to a cloud server with easy user access. The following monitored and logged: Temperature Refrigerant Leak City Power Amps Humidity City Power On Auto Light Control Door Ajar Power Failure Battery Back-up Panic Button Panic Reset Daily Status Message Accessing Your Stored Web Data Temp: -8F No alarms Alarms: SMS Text Messages Logging to Cloud Server Your Informant unit is factory configured to begin logging data as soon as it is powered up. No special software is required, only a computer with an Internet browser, such as Explorer or Safari. Follow the steps below to see your graphs and logs: 1. Point your browser to: Do not use www. 2. Your user name is: 3. Your password is: 1

2 Contents Connections 3 User Controls 4 Sensors 4 Wiring Layout - Inputs, Power, Controls 5 Scrolling Menu on Internal Display (Top Menu) 6 Signal Strength Indicator 6 Use of Door Sensor and Panic Buttons 7 Antenna Recommendations 8 Summary of Menu Functions 9 Entering Cell Phone Numbers 10 Setting Contact On/Off Alarms and Delay 10 Setting Contact On/Off Alarms and Delay 11 Using Delays 11 Setting Temperature Alarm Limits and Delay 12 Set Password 13 Set Celsius or Fahrenheit 13 Sending Test Messages 13 Go To SubMenu Functions 13 City Power Alarm 14 Testing the City Power Alarm 14 Battery Low Alarm 14 Contact On/Off Setup 15 UDP (Cloud Server) Logging 15 SMS (Text Messaging) 15 Daily Message 16 Keypad Lock 16 Alarm Buzzer 16 Silent Mode 16 Maintenance Mode 16 Add Wired Sensors Menu 17 Revert to Factory Configuration 17 Accessing Graphs and Logs 18 2

3 Connections Facing the Connector Block (Connector #1 is lowest in control box) Relay Outputs Contact 1A Contact 1B Contact 2A Contact 2B Contact 3A Contact 3B To External Alarm Interior Lights Auxiliary Relay Ammeter Input 0-5vdc Ground Dry Contact Inputs Input One Input Two Input Three Ground Sensor Inputs Sensor 1 Sensor 2 Sensor 3 Sensor 4 Power 4vdc Ground Power 24vac Door Position Up to four inputs or any type sensor Panic Button Leak Detector Current Transducer Reset Button Combination Temperature & Humidity Sensor Three wires Temperature Sensor Two wires 24vac Transformer Antenna M Coaxial Cable 3 RDTConnections( )

4 User Controls Wall-Mounted Installation Conduit to Controls Display The backlit display has two modes: Normal: four data panels constantly scroll Command: the display shows responses to menu changes Alarm Horn Keypad Letter keys are used for commands Number keys are used to enter phone numbers and values such as temperature alarm settings Sensors Temperature Sensor: Two wire, observe polarity. Use 22awg, stranded wire. Up to four can be used. Has 24 leads. Up to 200. Combo Temperature and Humidity Sensor: Three wire, observe polarity. Use 22awg, stranded wire. Up to four can be used. Has 24 leads. Door Sensor: Magnetic security-type sensor, two wire. Use 22awg wire. Normally closed or normally open can be used. Leak Detector: Typical sensor shown. Use 22awg wire. Normally closed contact sensor. 4

5 Wiring Layout - Inputs, Power, Controls 120vac or 208vac mains supply Informant Power 24vac Transformer Leak Detector Power 9vdc Transformer Informant Relay Panic Reset Alarm Horn Connections to Informant Horn Lighting Door Position Sensor Refrigerant Leak Detector Door Switch Panic Switch (inside Cooler) Relay Output - Lighting Relay Output - Ext. Horn Panic Button Refrigerant Leak Detector Relay Output - Aux. Four Temperature Sensors Note: Not all 24vac power is shown on Relay Outputs. Power to all outputs must be furnished through customer supplied 24vac transformer. 5 Side View of Refrigerated Room

6 Use of Door Sensor and Panic Buttons Typical Wiring: Door Position Sensors,Panic Button and Panic Reset Door Sensor Panic Button Reset Inside Panic Button Interior Lighting Conduit and Junction Boxes Sensors or Switches Side View of Refrigerated Area The door sensor (magnetic switch) automatically controls the internal lighting. Once the door is opened an internal timer in the Informant starts running. If the door is closed promptly the lights are shut off. If the door is opened too long a series of events begins as described in the table below. Additionally, an internal panic button can over-ride the timer. The external Panic Button Resert cancels the Internal Panic Button. Lighting Sequence Table Door Position: Opens: Closes: Open Too Long: Panic Button Pressed: Panic Reset Button Pressed: Actions Lights go on. Door open timer starts running. (0-99 min.) Lights go out. Timer resets Alarm horn sounds. (Delay time exceeded.) Text message alerts sent. Alarm horn sounds. Interior lighting turns on. Text message alarm sounds. Alarm silenced. Text message sent Alarm cleared Lights go out. 6

7 Scrolling Menu on Internal Display (Top Menu) Curr Temp1: 34F Curr Temp2: 45F 85F Cell Signal: Temperature updated every five seconds Signal needs two bars for good performance No Alarms Up to five cell phone numbers can be entered. Only the first two are shown. High Alarm: 86F Low Alarm: -5F : : B C ( ) ( ) Alarm status is displayed. A buzzer can also signal alarm status locally. High and low alarm # Backspace points. The temperature must be above or below the trip point by one degree to alarm. Manual scrolling by pressing the B and C keys ( ) ( ) Signal Strength Indicator Unusable Signal Strength Marginal - but usable This device sends SMS text messages and sends data over the 2G data channel. This requires at least two solid black bars signal strength. If no black bars are present a remote antenna will be required. Excellent signal level 7 See page on remote antenna if signal is low.

8 Antenna Recommendations External Directional antenna Metal roof Metal walls >5 miles from cell tower Attic Omni-Directional Antenna Composition (wood) Roof <5 miles from cell tower Wooden, sheet rock, walls Since most Informant installations are wall-mounted to refrigeration rooms, an external antenna is required. Depending on the type of building, the antenna can be mounted above the conduit. In all-metal buildings, a roof-mounted antenna will be required. When the Informant will be more than five miles from the cell phone tower a directional antenna will likely be required. Typical directional antenna. (Yagi). Usually mounted outside building. Coaxial cable to antenna Conduit to ceiling (3/4 ) Walk-In Box Typical non-directional tenna (monopole) RDTAntenna( ).ai 8

9 Summary of Menu Functions To Access Menus Scrolling Data Mode A Press A Key and Scroll Keys Main Menu Functions: 1) Cell phone numbers. 2) Amp Alarms 3) Contact #1 delay. 4) Contact #2 delay. 5) Temperature Alarms 6) Temperature alarm delay. 7) Set Password 8) degf or degc. 9) Send Test Text Message. 0) More options ( zero key). 0 Press 0 Key To Access Sub-Menu Sub Menu Functions: 1. City Power Alarm. 2. Battery Low Alarm. 3. Contact 1 Alarm. 4. Contact2 Alarm. 5. UDP Logging. 6. SMS (Text) Alarms. 7. Daily Status Message. 8. Keypad lock. 9. Alarm Buzzer. 10. Silent Mode. 11. Maintenance Mode. 12. Wireless Temp Sensors. 13. Discover Wired Temp Sensors. 14. Factory Config Reset. Press D Key twice to return to scrolling menu D ScrollingMenuLong( ).ai 9

10 Entering Cell Phone Numbers Change Cell Phone Numbers #1 1)New 2)Del Send Test Message Send Test Message Select numbers 1-5 This screen permits five cell phone numbers to be entered, changed or deleted. In the event of an alarm, all the numbers are sent a text message alarm. Be sure to send a test message to every phone number entered. Setting Contact On/Off Alarms and Delay The on/off contact sensing is set up in the sub-menu. See page 5 for more info on setting those. However, the delay time before sending an alarm is set on this page. Set Contacts 1 and 2 Delay Time Contact1 dly 0 Contact2 dly Adjusting Delay Time (minutes) Contact1 dly 0 1) Change The two dry contacts frequently monitor freezer and refrigerator doors and alarm if the door is left open for a certain time. If the value is set to zero, there is no delay. A submenu function enables the contacts operation. The value is minutes until an alarm is activated. These devices frequently monitor refrigerator doors and alarm if the door is left open for a long time. If set to zero, there is no delay. A submenu function enables the contacts operation. 10

11 Setting Contact On/Off Alarms and Delay The on/off contact sensing is set up in the sub-menu. See page 13 for more info on setting those. However, the delay time before sending an alarm is set on this page. Set Contacts 1 and 2 Delay Time Contact1 dly 0 Contact2 dly Adjusting Delay Time (minutes) Contact1 dly 0 1) Change The two dry contacts frequently monitor freezer and refrigerator doors and alarm if the door is left open for a certain time. If the value is set to zero, there is no delay. A submenu function enables the contacts operation. The value is minutes until an alarm is activated. These devices frequently monitor refrigerator doors and alarm if the door is left open for a long time. If set to zero, there is no delay. A submenu function enables the contacts operation. Using Delays Many delays are used on switch and contact functions. Temperature: delay alarm to ignore defrost cycle. Typically minutes. Door Position: delay alarm to allow door to be open for a period. Typically 5 minutes. Refrigeration Leak: delay to assure that genuine leak is present. Typically 15 minutes. Set delays carefully. A short delay causes false alarms, a long delay may mask problems. 11

12 Setting Temperature Alarm Limits and Delay (Shortcut: Press A and scroll down to 5.) 5)Temp Alarms 6)Temp Alarm Delay This screen sets the trip values of temperature. To automatically cancel the alarm the value must be greater (or less) than the trip value by one degree. Set High/Low Alarm Values 1)Hi Temp1 Alarm 2)Lo Alarm Alarm Setting Negative Temperature Values High temp above 0? 1)Yes 2) No Note that the temperature sensors must be discovered (see page 8) in order for high/low limits to be set. Setting Negative Temperature Values Enter Hi Alarm: Press D for Done Set Delay Before Alarm Shortcut: Press A and 6 1) Temp 1 Delay 01 minutes Enter minutes 0 for no delay This function permits 0-99 minutes of delay before sending a text alarm. The primary purpose is to ignore defrost cycles where the temperature can routinely and briefly jump to 20degF higher than normal. Press D for Done 12

13 Set Password Set Password Enter key code The keypad is disabled if the password is not entered. CAUTION: if you forget your password, you will have to call tech support to have an upload of the firmware done. There is no back-door method. Set Celsius or Fahrenheit 1) >> Fahrenheit 2) Celsius Select the temperature portrayal of F or C. All alarms and logging will be displayed with that portrayal. Sending Test Messages Send Test Message Select numbers 1-5 A test Text Message can be sent to any of the five cell phone numbers. Go To SubMenu Functions Shortcut: Press A and 0 Options 13

14 City Power Alarm Informant Circuits City Power Loss of city power is a critical failure. The Informant contains two Lithium batteries that automatically keep the Informant running when city power fails. ack-up atteries R123) Auto Cutover Circuit 24vac Transformer When power fails, text message alarms are sent and the event is logged. There is a oneminute delay before alarming to ignore transient power spikes of black outs. Testing the City Power Alarm. Unplug the wall transformer from the power receptacle. The display should go dim as the unit starts to conserve battery power. After two minutes, you should receive a text message alarm. There are two internal batteries that keep the Freezer Alert running when city power is lost. The batteries last for 24 hours or more. When they are exhausted, they must be replaced with CR123A cells which are available at Walmart. Battery Low Alarm Battery Low Alarm Off 1) Enable When the device cannot receive ity ower, it reverts to long-live batteries (CR123 Lithium) If ity ower remains off for longer than 20 hours the unit will send an alarm that it will soon be completely inactive. 14

15 Contact On/Off Setup Set Contacts 1 and 2 Delay Time Contact1 dly 0 Contact2 dly Adjusting Delay Time (minutes) Contact1 dly 0 1) Change Off 1) Enable The two dry contacts frequently monitor freezer and refrigerator doors and alarm if the door is left open for a certain time. If the value is set to zero, there is no delay. A sub menufunction enables the contacts operation. The value is minutes until an alarm is activated. These devices frequently monitor refrigerator doors and alarm if the door is left open for a long time. If set to zero, there is no delay. A submenu function enables the contacts operation. UDP (Cloud Server) Logging UDP Logging Off 1) Enable Enabling this function starts the device sending hourly logs and alerts to a server database. Call Tech Support to se up your user name and password. SMS (Text Messaging) SMS Alarms Off 1) Enable The is the principal alarm method. This function is normally used when setting up a device and is otherwise left on. 15

16 Daily Message Daily Message Off 1) Enable This function lets you know that the device is in contact with a cell tower and can receive the system time from it. It will send a daily message at noon to confirm its operational status. Keypad Lock Keypad lock Off 1) Enable Use this mode to block accidental setting of passwords in the Main Menu. The default password to enable the keypad is 1. Alarm Buzzer Silent Mode Alarm Buzzer Off 1) Enable Silent Mode Turns off the alarm buzzer. The device beeps when sending logging data and SMS Alarms.Enabling this function stops the beeping. Maintenance Mode Maintenance Mode Off 1) Enable This mode permits alarms from being transmitted to all five cell phone numbers. In this mode, alarms are only sent to the first cell phone number. An hourly warning message is sent. After 8 hours, Maintenance Mode is automatically discontinued. 16

17 Add Wired Sensors Menu Up to four temperature sensors can be used. Each sensor has a unique (internal) address and must be discovered by the unit in order to be displayed. Without discovering the sensors, no data will appear. Add Wired Sensors? 1) Yes This menu starts the discovery function. Discovery Finished Found 4 Sensors Added sensors Sensors have been found. Logging begins after return to top menu. Press the D twice to return to the scrolling menu. Set tem limits for alarm functions. Revert to Factory Configuration Factory Config? 1) Yes Selecting this resets all limits and other variables to the factory final assemble test setting. 17

18 Accessing Graphs and Logs If UDP logging is enabled, the Informant sends hourly the high, low and latest values of all sensors and alarms. The data is sent to a Cloud server automatically. Several fields on the server can be customized. No special software is required. Steps to accessing your Informant s stored data: 1. Open a Internet browser connection using Explorer, Chrome, Firefox. 2. Type in the address panel. Do not use www 3. Enter your user name and password. Top Menu - Summary Graphs and Menu Red line: highest value Blue line: lowest value During logging period. This field can be changed. 18

19 Graph and Report Generator Sub Menu Report formats: Graphs Excel HTML (browser text) Spreadsheet (CSV) Typical Report (HTML format) 19

Cellular Monitoring System

Cellular Monitoring System Cellular Monitoring System Wireless Temperature Monitoring Installation and Operation User s Manual For Firmware Versions 4.01-5.12 Temperature Monitoring System used in: Temperature-controlled storage

More information

Cellular Monitoring System

Cellular Monitoring System Cellular Monitoring System Wireless Temperature Monitoring Installation and Operation User s Manual Temperature Monitoring System used in: Temperature-controlled storage rooms and facilities Medical and

More information

Fire Command Keypad. XR5 User s Guide

Fire Command Keypad. XR5 User s Guide Fire Command Keypad XR5 User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm depending on which type of keypad

More information

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014 Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

Operation Manual For model CM706E

Operation Manual For model CM706E Operation Manual For model CM706E www.temperatureguard.com The CM706E is an environmental monitor with built in Ethernet and Cellular alarming and reporting capabilities. This unit can monitor up to ten

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Ontech GSM 9040/50. Reference Manual English -1 -

Ontech GSM 9040/50. Reference Manual English -1 - Ontech GSM 9040/50 Reference Manual English -1 - Content Welcome... 5 This manual... 5 Text styles... 5 Support... 5 Disclaimer... 5 Overview... 6 Accessories... 6 External temperature sensor 9901... 7

More information

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V NO ONE DARES COME CLOSE O WNER S GUIDE M O D E L 7756V Congratulations Congratulations on the purchase of your state-of-the-art Directed Digital System. Reading this Owner s Guide prior to using your

More information

XRSuper6. User s Guide

XRSuper6. User s Guide XRSuper6 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. DISARM SILENCE. Select SILENCE to stop the bell or siren. This

More information

DYGIZONE GJD910 Lighting Controller & Enunciator

DYGIZONE GJD910 Lighting Controller & Enunciator DYGIZONE GJD910 Lighting Controller & Enunciator MASTER WIRING IDENTIFICATION Power up to the DygiZone and you will see: All the LED s (red,yellow,green and blue buttons) will flash All the LCD icons will

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

PiSector GSM Cellular Wireless Alarm System

PiSector GSM Cellular Wireless Alarm System PiSector GSM Cellular Wireless Alarm System User Manual ( GS08 ) Read manual fully before use. PiSector Inc., USA, www.pisector.com Welcome to PiSECTOR Thank you for choosing PiSECTOR. Everyone at PiSECTOR

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

Follett Performance Plus

Follett Performance Plus Follett Performance Plus touchscreen user guide The next level of control in undercounter refrigeration Controller Operation - Performance Plus touchscreen Use and care of the LCD Performance Plus touchscreen

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

Introduction. OM-THA2

Introduction. OM-THA2 Introduction. The OM-THA2 is a multi-function product that monitors Temperature, Humidity and Dew Point, provides alarms for out of range conditions, and continuously logs data. It consists of a base unit

More information

Rev Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual

Rev Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual 026-1503 Rev 0 3-20-03 Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319

More information

Sensaphone 400 Telemetry System Integration

Sensaphone 400 Telemetry System Integration Application Note 003 Version 001 07 Oct 2014 Sensaphone 400 Telemetry System Integration The Sensaphone Model 400 is an alarm dialer device that is capable of calling out to one or more telephone numbers

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

REMOTE MONITORING AND ALARM SYSTEM

REMOTE MONITORING AND ALARM SYSTEM FUNCTIONALITY A. The water and wastewater facilities remote monitoring, reporting and alarm notification system shall be comprised of a hosted, Web-based user-interface which communicates to remotely monitored

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

Application Manual Loop Water Controller

Application Manual Loop Water Controller Application Manual Loop Water Controller AM - LWC TABLE OF CONTENTS LIST OF FIGURES ii iii 1.0 SAFETY CONSIDERATION 1 1.1 Installation Recommendations 1 2.0 GENERAL DESCRIPTION 2 2.1 General Introduction

More information

G4S SMARTalarm User Guide

G4S SMARTalarm User Guide G4S SMARTalarm User Guide CONGRATULATIONS WITH YOUR NEW SECURITY SYSTEM! We are glad that you have chosen G4S SMARTalarm. G4S is the largest supplier of security solutions in the world. We have invested

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

BURGLAR ALARM PANEL BS-468

BURGLAR ALARM PANEL BS-468 BURGLAR ALARM PANEL BS-468 Contents 1. Description... 3 2. Instructions for the user... 4 2.1Basic operations... 4 Complete system.... 4 Split system.... 4 2.2 Armed system indication... 5 2.3 Advanced

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

DC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide

DC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide DC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide (These instructions are intended for use by a technician familiar with electronic products) Remote Monitoring and Control Unit Web Ready

More information

THX-DL Data Logger USER & INSTALLATION MANUAL V

THX-DL Data Logger USER & INSTALLATION MANUAL V THX-DL Data Logger USER & INSTALLATION MANUAL V1.2012 www.thermomax-refrigeration.com Contents PRESENTATION Summary of Features 2 INSTALLATION Safety Precautions 4 THX Unit 4 Sensors 4 Alarm Relay 4 Power

More information

Silencing an Alarm. When the alarm siren is sounding, enter your user code or present your card to a keypad during the Status List display.

Silencing an Alarm. When the alarm siren is sounding, enter your user code or present your card to a keypad during the Status List display. Silencing an Alarm When the alarm siren is sounding, enter your user code or present your card to a keypad during the Status List display. All/Perimeter or Home/Sleep/Away System CANCEL VERIFY displays.

More information

Macurco DVP-120 Detection and Ventilation Control Panel

Macurco DVP-120 Detection and Ventilation Control Panel Macurco DVP-120 Detection and Ventilation Control Panel User Instructions IMPORTANT: Keep these User Instructions for reference. TABLE OF CONTENTS 1 Introduction 4 1.1 General Information 4 1.2 Features

More information

Fire Command Center XR2500F. User s Guide

Fire Command Center XR2500F. User s Guide Fire Command Center XR2500F User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm. 1. Turn the keyswitch to enable

More information

Electronic Multi-Zone Environmental Alarm System Installation/Owner s Manual D

Electronic Multi-Zone Environmental Alarm System Installation/Owner s Manual D Electronic Multi-Zone Environmental Alarm System Installation/Owner s Manual D-011-0152 Limitations of the Alarm System or Device While your alarm system or device is reliable and sophisticated, it does

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

User s Information Guide R2A

User s Information Guide R2A Pi HSC505 Home Security Controller User s Information Guide R2A Page 1 of 15 of its development program. 1This document and product are copyrighted and all rights are reserved. Introduction Convention

More information

HOME AUTOMATION, INC. Lumina and Lumina Pro Lighting and Automation System. Quick-Start Installation Guide

HOME AUTOMATION, INC. Lumina and Lumina Pro Lighting and Automation System. Quick-Start Installation Guide HOME AUTOMATION, INC. Lumina and Lumina Pro Lighting and Automation System Quick-Start Installation Guide Document Number 44I00-1 Rev. 2.12 February, 2006 For complete operation and programming instructions,

More information

ThinkPro Security and Automation Panel User Guide

ThinkPro Security and Automation Panel User Guide ThinkPro Security and Automation Panel User Guide North America s Fastest Growing Alarm Company 1-855-768-4465 (1-855-76-THINK) V.1.1 Welcome to Think Protection Thank you for choosing a Think Protection

More information

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY Introduction.

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

Important information. Government Regulations and Safety information. Your Warranty. Replacement remote controls

Important information. Government Regulations and Safety information. Your Warranty. Replacement remote controls Congratulations Congratulations on the purchase of your state-of-the-art security and remote start system. Reading this Owner s Guide prior to using your system will help maximize the use of your system

More information

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren.

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren. XR20 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. The keypad displays DISARM SILENCE. Press the Select key under

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Fire Command Center. XR2400F User s Guide

Fire Command Center. XR2400F User s Guide Fire Command Center XR2400F User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm. 1. Turn the keyswitch to enable

More information

Advisor Advanced Mobile Application User Manual

Advisor Advanced Mobile Application User Manual Advisor Advanced Mobile Application User Manual Content Warnings and Disclaimers 2 Advanced Mobile 2 Contact information 2 Description 2 Screen navigation 4 Gestures 4 Menu 4 Help navigation 4 Login 5

More information

XTL/XTLN/XTLN-WiFi USER GUIDE

XTL/XTLN/XTLN-WiFi USER GUIDE XTL/XTLN/XTLN-WiFi USER GUIDE Silencing an Alarm When the alarm siren is sounding, enter your user code or present your card to a keypad during the Status List display. All/Perimeter or Home/Sleep/Away

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

CARETAKER PLUS: MOST FREQUESNTLY ASKED QUESTIONS. Which sensor programming group should I use for a wireless freeze sensor?

CARETAKER PLUS: MOST FREQUESNTLY ASKED QUESTIONS. Which sensor programming group should I use for a wireless freeze sensor? CARETAKER PLUS: MOST FREQUESNTLY ASKED QUESTIONS Which sensor programming group should I use for a wireless freeze sensor? Group 29 (Auxiliary Environmental) is the sensor group for freeze or water sensors.

More information

WHAT HAPPENS NEXT FOR ADT SMART BUSINESS CUSTOMERS

WHAT HAPPENS NEXT FOR ADT SMART BUSINESS CUSTOMERS WHAT HAPPENS NEXT FOR ADT SMART BUSINESS CUSTOMERS Below you will find information about your installation and what you can expect to happen next. There are also some important steps to follow to ensure

More information

SILENCING AN ALARM When the alarm bell or siren is sounding, enter your user code or present your SecuraProx fob to your keypad.

SILENCING AN ALARM When the alarm bell or siren is sounding, enter your user code or present your SecuraProx fob to your keypad. SYSTEM USER GUIDE SILENCING AN ALARM When the alarm bell or siren is sounding, enter your user code or present your SecuraProx fob to your keypad. IS THIS A FALSE ALARM? YES NO displays. REAL ALARM If

More information

HMS MODEL 800 Owner s Manual

HMS MODEL 800 Owner s Manual HMS MODEL 800 Owner s Manual OnQ Document Number 1307535 Rev A October, 2000 Copyright v 2000 HAI All Rights Reserved www.onqtech.com Contents INTRODUCTION... 1 Underwriter's Laboratories (UL) Listing...

More information

Mobeye CM2410 GSM fire alarm communicator

Mobeye CM2410 GSM fire alarm communicator PORTAL USER MANUAL Mobeye CM2410 GSM fire alarm communicator Accessory for Ei Electronics fire detector SW version 5.n Incl. CM2400 Attention! Very important This user manual contains important guidelines

More information

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Sensor Cloud User Manual

Sensor Cloud User Manual Sensor Cloud User Manual Table of Contents DEVICES TAB 4 1. DEVICE LIST 4 2. EXPAND ALL 4 3. EXPAND 4 4. STATUS 4 5. DEVICE 4 6. NAME 5 7. MONITORING INTERVAL 5 8. LAST ACTIVITY 5 9. VIEW 5 10. DELETE

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D ASCO 5350 The ASCO 5350 ATS Remote Annunciator is listed under the Underwriter s Laboratories Standard UL-1008 for Automatic Transfer Switch accessories. This stand-alone device provides individual status

More information

DX2002 OPERATING AND PROGRAMMING INSTRUCTIONS

DX2002 OPERATING AND PROGRAMMING INSTRUCTIONS DX2002 OPERATING AND PROGRAMMING INSTRUCTIONS The four pushbuttons located at the bottom right of the circuit board are used to do all programming. Each button has more than one function. Alternate Settings

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Silencing an Alarm Note: Area Systems What to do when a trouble tone is sounding

Silencing an Alarm Note: Area Systems What to do when a trouble tone is sounding Silencing an Alarm When the alarm bell or siren is sounding, enter your user code or present your card to a keypad or reader during the Status List display. IS THIS A FALSE ALARM? YES NO or CANCEL VERIFY

More information

Silencing an Alarm All/Perimeter and Home/Away Systems. Area Systems. What to do when a trouble tone is sounding

Silencing an Alarm All/Perimeter and Home/Away Systems. Area Systems. What to do when a trouble tone is sounding XR40 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems 1. While the alarm bell or siren is sounding, enter your user code. The keypad displays DISARM SILENCE. 2. Press the SELECT key

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

1126 Series Ceiling Mount PIR Motion Detector

1126 Series Ceiling Mount PIR Motion Detector Installation Sheet 1126 Series Ceiling Mount PIR Motion Detector Description The 1126 Series PIR (Passive Infrared) Motion Detectors are a compact wireless PIR. The 1126 Series offer 360, Wide Angle, or

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

780 Keypad Demonstrator Module

780 Keypad Demonstrator Module 780 Keypad Demonstrator Module Description The DMP 780 Keypad Demonstrator Module is a portable module that connects to any DMP 32-character, Icon Series, or 7800 Series Graphic Touchscreen keypad to demonstrate

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat:

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat: SM CAUTION Follow the Installation Instructions before proceeding. Set the thermostat mode to OFF prior to changing settings in setup or restoring Factory Defaults. This Explorer thermostat has the ability

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

Fire detection and alarm system Operating instructions

Fire detection and alarm system Operating instructions Fire detection and alarm system Operating instructions Operating instructions Table of Contents User responsibility - - - - - - - - - - - - 4 Daily - - - - - - - - - - - - - - - - - - - 4 Weekly - - -

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm Back Box 5 The Frame/Module

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

wireless. web-based. worthy of the name RACO.

wireless. web-based. worthy of the name RACO. wireless. web-based. worthy of the name RACO. reliable monitoring unequalled accessibility on-demand reporting wireless, web-based alarm detection and notification system from RACO designed specifically

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

ThermoControl 0 C - 10 C - 20 C - 30 C

ThermoControl 0 C - 10 C - 20 C - 30 C ThermoControl Product and Quality Reliability Alarm Functions & Documentation Global Monitoring 0 C - 10 C - 20 C - 30 C Global monitoring: global temperature measurement and real-time monitoring using

More information

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with 2000, 2100 controllers (Spa Owner s Manual insert) P.N. 7876B February 11, 2015 For Spas equipped with BP2000, BP2100 controllers and Spa Touch panel. Spa Touch Control Panel

More information

NextGen Home Security. Quick Reference Guide

NextGen Home Security. Quick Reference Guide TM NextGen Home Security Quick Reference Guide Fire Auxiliary Panic (not active) Stay Away Chime Reset Bypass To view the full user manual, go to www.bellaliant.net/homesecurity and select Support. Arming

More information

Electro-Sentry. Users Manual

Electro-Sentry. Users Manual Electro-Sentry Users Manual 2. To view an individual point, e.g. Speed just touch that point and it will display a graph showing the 45 min. of activity. Viewing a Leg: 1. Touch the desired leg, e.g. East

More information

DSC PowerSeries NEO Quick Start Guide

DSC PowerSeries NEO Quick Start Guide DSC PowerSeries NEO Quick Start Guide WE DO NOT RECOMMEND BEING IN ANY PROGRAMMING SECTION THAT IS NOT IN THIS GUIDE UNLESS YOU FULLY UNDERSTAND THE FUNCTION OF THAT SECTION. Doing so may cause problems

More information

O WNER S GUIDE M O D E L

O WNER S GUIDE M O D E L Vista, CA 92081 www.directed.com The company behind Viper Auto Security Systems is Directed Electronics. Since its inception, Directed Electronics has had one purpose, to provide consumers with the finest

More information

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor A1UL PERS Personal Emergency Response System TABLE OF CONTENTS 1. READ THIS FIRST... 1 2. SYSTEM OVERVIEW.. 1 3. COMPONENTS 2 4. UNIT OPERATION! Standby Mode.. 3! Emergency Activation. 3! Answering Incoming

More information

Grandstream Networks, Inc. GDS3710 Input/output Connection Guide

Grandstream Networks, Inc. GDS3710 Input/output Connection Guide Grandstream Networks, Inc. Table of Contents INTRODUCTION... 4 GDS3710 WIRING CONNECTION... 5 Powering and Connecting the GDS3710... 5 Power and Data PINs... 5 Alarm In and Alarm Out PINs... 6 DETECT AND

More information

XTL Series USER GUIDE

XTL Series USER GUIDE XTL Series USER GUIDE Silencing an Alarm When the alarm siren is sounding, enter your user code or present your card to a keypad during the Status List display. All/Perimeter or Home/Sleep/Away System

More information

USER MANUAL DexTempTM 1000 Temperature Monitor (P/N: IR-1001) DexTempTM 1000 USB Non-Contact Temperature Monitor. User Manual.

USER MANUAL DexTempTM 1000 Temperature Monitor (P/N: IR-1001) DexTempTM 1000 USB Non-Contact Temperature Monitor. User Manual. USER MANUAL DexTempTM 1000 Temperature Monitor (P/N: IR-1001) DexTempTM 1000 USB Non-Contact Temperature Monitor User Manual 8690 Rev B Update: 10/24/2013 1 Table of Contents 1 Introduction.. 3 2 Host

More information

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Operating instructions Vigilon panel and Network node Fire detection and alarm system Healthy 15:45 Fault Power Fault Vigilon Fire System GENT 2015 Designed to EN54 Pt 2 & 4 System Fault Operating instructions Vigilon panel and Network node Fire detection and alarm system Test Fire Fault/Dis

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

EZY SWITCH. SMS-IRR-4 System Monitor Installation Manual

EZY SWITCH. SMS-IRR-4 System Monitor Installation Manual EZY SWITCH SMS-IRR-4 System Monitor Installation Manual Table of Contents COMMANDS Getting Started Setting Up Initial User 7 Adding a User 8 Removing a User 8 Adding an Administrator 8 Removing the Administrator

More information

POWERBRICKALARM TCP/UDP IP Alarm Panel Installation and Operation Manual

POWERBRICKALARM TCP/UDP IP Alarm Panel Installation and Operation Manual POWERBRICKALARM TCP/UDP IP Alarm Panel Installation and Operation Manual Version 1.37a Firmware: 9.xx.xxx PowerBrick International PO Box 68-266 Newton, Auckland 1021 New Zealand Phone: +064 9 3094403

More information

HMS MODEL 925 OWNER'S MANUAL

HMS MODEL 925 OWNER'S MANUAL HMS MODEL 925 OWNER'S MANUAL Document Number 889150 Rev B November, 1999 Copyright 1999 HAI All Rights Reserved OnQ Technologies, Inc. i Contents INTRODUCTION...1 Underwriter's Laboratories (UL) Listing...1

More information

EW 40 Wireless Fan Control

EW 40 Wireless Fan Control Installation & Operating Manual EW 40 Wireless Fan Control USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

OnCommand. Automation. Operation Manual ONCOM ONCOM-ACT ONCOM-RC ONCOM-ACT-RC ONCOM-POD2 ONCOM-ACT-POD2

OnCommand. Automation. Operation Manual ONCOM ONCOM-ACT ONCOM-RC ONCOM-ACT-RC ONCOM-POD2 ONCOM-ACT-POD2 092442A RevC OnCommand Automation \ Operation Manual Contents Introduction...2 Operation...3 Troubleshooting...29 Warranty...34 ONCOM ONCOM-ACT ONCOM-RC ONCOM-ACT-RC ONCOM-POD2 ONCOM-ACT-POD2 Hayward Pool

More information

Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output. Model LFS108B

Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output. Model LFS108B Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output Model LFS108B Copyright 2018 - LLC. All rights reserved. Table of Contents Quick Start... 3 1- Introduction... 4 2-

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Thank you for choosing Ideal Security s Home Security System with Telephone Dialer.

Thank you for choosing Ideal Security s Home Security System with Telephone Dialer. SK618 WIRELESS ALARM SYSTEM WITH AUTO DIALER OWNER'S MANUAL Thank you for choosing Ideal Security s Home Security System with Telephone Dialer. If at any time during your installation you have any questions

More information