1 Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are fully operational to perform when needed. These systems, such as automatic sprinkler systems, are effective at reducing damage from fire and smoke as well as the potential for injury or death to building occupants. When such a system is out of service due to a planned or emergency repair, human error, or a malicious act, a fire can grow unchecked, resulting in substantial property loss or personal injury. A fire protection impairment program can be used to manage these situations in order to reduce the threat to property and personnel. The program accomplishes this through the following: limiting the time and scope of unavailable fire protection, controlling hazards, establishing alternate fire detection and alarm activation methods, providing substitute fire suppression systems, and ensuring that response to a fire, should one occur during the impairment, is swift and appropriate. Impairments Impairment can be described as the condition when at least one aspect of fire protection is out of service. While any number of conditions could cause impairment to protection systems, impairments are typically grouped into three types: planned, emergency, and hidden. Planned Impairment A planned impairment is when a fire protection system is out of service due to work, such as maintenance, scheduled repairs, or new construction. To reduce the potential for loss, it is best to schedule maintenance and repair work so that only a part of the system is impaired during the repair or maintenance work. Emergency Impairment An emergency impairment occurs when a fire protection system is taken out of service unexpectedly. Emergency impairments can be caused by numerous occurrences, such as a ruptured pipe or activation of a sprinkler head. Hidden Impairment Impairments are sometimes not readily apparent and are often discovered by accident or during routine inspection, testing, or maintenance of the fire protection system or equipment. A closed sprinkler system control valve is one of the most common of these hidden impairments. When discovered, these impairments should be treated in the same manner as an emergency impairment. Systems and Equipment The scope of an impairment program goes beyond automatic fire sprinkler systems. A thorough impairment management program will also include alarm systems, water supplies, special extinguishing systems, and other equipment. An impairment management program should include all aspects of fire protection including: Fire sprinkler systems Fire pumps Water supplies, including public and private water systems and underground supply piping Fire alarm systems Smoke and fire detection systems Life safety systems, such as evacuation alarms and voice notification systems Special extinguishing systems, such as carbon dioxide, foam, water mist, and chemical extinguishing systems Fire hydrants, fire department connections, and standpipe and hose systems Impairment Management Organizations should develop a documented impairment program, which outlines management s expectations. It should follow many of the guidelines that are introduced in the remainder of this document. In order to ensure that impairments are identified and preventive measures promptly enacted, management should designate an impairment coordinator who is responsible for administering the impairment management program. The impairment coordinator should have sufficient authority to be able to expedite repairs and suspend hazardous operations. Before an Impairment Prior to a planned impairment or immediately after an emergency impairment has been discovered, the following procedures should be followed:
2 Suspension of Hazardous Operations During impairments, hazardous operations should be stopped until fire protection is fully restored. Such operations can include spray painting, flammable liquid operation, and hot work operations (e.g., cutting and welding). This includes strictly enforcing no smoking rules. If possible, the impairment should be scheduled to occur during idle periods when no ignition sources are present. Control the fuel load in the area of impairment. Minimize or eliminate, if possible, all combustible and other hazardous materials; ensure good housekeeping practices are in place. Notifications Notify the following entities of the impairment: Local fire department being aware of the impaired fire protection system will allow them to respond to an alarm with additional units and resources. The impaired fire protection may also require them to alter their plan of attack. A good pre-plan should consider fires that occur during common impairments. Philadelphia Insurance Companies notifying PHLY allows us to understand the scope of the outage and degree of increased risk. We can review the implemented precautions and provide guidance on any additional ones needed. Finally, it provides another level of reminders to return the fire protection system to full service. Please contact us via at phlyrms@phly.com. Facility emergency response team (ERT) Alarm monitoring company Affected employees Use Impairment Permits/Tags The fire protection impairment permit should be filled out as a record of the impairment. One impairment tag should be filled out and attached to the impaired valve or piece of fire protection equipment. Finally, a second tag should be attached to the affected fire department connection. The reason for the latter is that it provides prominent notice of the impairment to the responding fire department if called. The permit and tags provide reminders of the impaired state of the system and the necessity to return to full service once the reason for the impairment is no longer present. The person requesting the impairment is responsible for filling out the permit, tags, and obtaining an authorized signature. See PHLY Impairment Permit & Tags associated with this document for these items. For additional information and guidance, see PHLY Fire Protection Impairment Management at the end of this document, which provides a checklist of things to be addressed during impairment. Compartmentalization When fire protection systems are out of service, the last line of defense between fire control and a significant loss may be the fire doors. Whenever possible, fire doors should be closed until fire protection is restored. Therefore, it is important that fire doors are properly maintained and in working order. See Fire Protection Report FP-43-01, Fire Doors, for additional information on this topic. Temporary Fire Protection The facility emergency organization and/or emergency response team (ERT) must be informed. This organization may need to provide alternate fire protection equipment, such as portable extinguishers and charged fire hoses, in the event of an emergency and should maintain a heightened sense of awareness during the impairment. Temporary fire protection measures to be taken include, but are not limited to, the following: Hydrants hooked up to sprinkler riser Hose line(s) charged Extra fire extinguishers distributed throughout the facility Extra security or fire watch patrols provide a means to quickly notify proper authorities in event of fire The use of sectional control valves, whenever possible, to minimize the area without fire protection When possible, place somebody at or near the closed (impaired) control valve(s) so that they can open them in the event of a fire See Fire Protection Report FP-45-20, Emergency Response Teams (ERT), for additional information on this topic. Expeditious Repairs The shutdown can be minimized if repair crews are authorized to work continuously overnight and through weekends. Ideally, the work should be done without interruption until the job is complete. For work that involves a large area, the planned repair or extension should be done in sections, where possible, to minimize the area without fire protection. Additional considerations include: No planned impairment should start until all supplies are present - this will reduce the impairment time A timetable should be employed to allow management to keep track of repair progress During the Impairment During the impairment, the repair crew and their progress should be periodically checked. Temporary protection, such as charged hose lines, should be checked on a regular basis to ensure their status has not changed. The suspension of hazardous operations requirements should be continued. Additional considerations include: Establishing a 24-hour fire watch - this can be done by extending employee hours or hiring a temporary guard service When possible, assigning personnel to reopen fire protection valves in case of a fire Assigning personnel to transmit fire alarms to the occupants and the fire department when the building alarm system is impaired Strictly enforcing no smoking rules
3 After the Impairment (Restoration) After the impairment, restoration of fire protection must be verified. This is done by performing a main drain test on a sprinkler system or by other methods appropriate for the fire protection system. The impairment coordinator should ensure that all systems are back in service and properly secured. After the fire protection is verified to be back in service, the entities, such as the fire department and Philadelphia Insurance Companies, that were notified of the impairment need to be notified that the fire protection had been restored to full service. Ensure that all copies of the impairment tags are collected, completed, and filed. If the impairment was of a hidden nature, investigate its cause so that its recurrence can be prevented in the future.
4 Fire Protection Impairment System impaired: Area protected by impaired system Date Hazardous operations in impaired area Halt hazardous operations that could cause or increase size of fire Remove or reduce fuel load as much as practical Schedule impairment during idle period Maintain good housekeeping practices Smoking is prohibited Notifications made Local fire department Philadelphia Insurance Companies Facility management and impairment coordinator Facility emergency response team Alarm monitoring company Affected employees Permit and tags Impairment permit filled out and displayed with copy in office Tag filled out and affixed to impaired control valve or applicable part of system Tag filled out and affixed to fire department connection Compartmentalization Fire doors in impaired area are closed Work planning No planned impairment until all supplies and equipment needed for project are in place Timetable to track progress has been developed and displayed Work done in sections so the area of impaired protection is minimized Interim fire protection measures Hydrant hooked up to sprinkler riser Hose lines placed in impaired area and charged Extra fire extinguishers are provided throughout facility as needed 24-hour fire watch established with means to quickly alert authorities of a fire Sectional control valves utilized where possible Individual posted at or near impaired control valve for ready opening if needed
5 Restoration after impairment Fire protection system restoration is verified (via main drain or other applicable test) Alarm devices have been restored Make notifications to previously notified parties that system has been restored Restore fire doors Release interim fire protection measures Remove posted permit and tags, and file in office as record of impairment Return to normal operations Ed
Management Practices: Fire Protection Impairments November 2015
RiskTopics Management Practices: Fire Protection Impairments November 2015 When business capital is invested in fire protection, it is difficult to explain any fire protection outage that allows a fire
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationSubject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees
Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire
More informationFire System Impairment Policy
Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,
More informationDUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)
DUQUESNE UNIVERSITY Fire Protection System Impairment Program (Red etag Permit) Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Exceptions 2 Definitions
More informationImpairments to Fire Protection Equipment
Impairments to Fire Protection Equipment INTRODUCTION Buildings and equipment are provided with fire protection and/or detection systems to reduce property damage and interruption to business in the event
More information2010 FIRE CODE OF NEW YORK STATE
2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,
More informationUNIVERSITY. Facilities Management
EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationUNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
More informationBuilders Risk - Fire Prevention Inspection Checklist
Builders Risk - Fire Prevention Inspection Checklist Use our inspection checklist tool to help you identify and monitor risk related to builders risk of fire on the job site. Inspection Details: Inspector
More informationI. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018
Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationOXNARD FIRE DEPARTMENT Fire Watch Guidelines
OXNARD FIRE DEPARTMENT Fire Watch Guidelines What is a Fire Watch? A Fire Watch is a temporary measure intended to ensure continuous and systematic surveillance of an activity, building or portion thereof
More informationManaging Fire Protection System Impairment
Managing Fire Protection System Impairment Can your company afford to lose US$3.2 million in assets? Forgetting to restore an impaired sprinkler or other fire protection system at your facility could cost
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationFreezing of Water-Based Fire Protection Systems
Risk Solutions Freezing of Water-Based Fire Protection Systems Freezing of water in fire protection piping can seriously compromise a property s fire protection. This report provides information on methods
More informationHot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope
1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More informationFIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES
BACKGROUND INFORMATION Alberta Fire Code 2014: FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES Alberta Fire Code (AFC) 2014, Division B, Section 5.6. requires a Fire Safety Plan for
More informationCHAPTER 15: FIRE PREVENTION & AWARENESS POLICY
CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY PURPOSE The fire prevention plan provides information and procedures to minimize the occurrence of an accidental fire at the job site or office, and an efficient
More informationEmergency Action Fire Prevention Plan
Emergency Action Fire Prevention Plan Table of Contents Section Title Page 1.0 Purpose 2 2.0 Scope and Application 2 3.0 Responsibilities 2-3 University Safety Coordinator 2-3 Department Heads, Supervisors
More informationFIRE PREVENTION PLAN EMERGENCY ACTION
FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces
More informationTEN STEP PROCESS PREPARING FIRE SAFETY PLANS
TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF
More informationFIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition
More informationBUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS
BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS Note: For information on OOS Fire Alarms please see Inspectional
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationFire Prevention Plan
Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........
More informationBURN NOTICE: KEEP THE HEAT AWAY!
BURN NOTICE: KEEP THE HEAT AWAY! 2019 MHEC MPP LOSS CONTROL WORKSHOP MARCH 8, 2019 Jared Stolin Property Risk Consultant, Marsh Risk Consulting Mike Fairfield Sr. Risk Engineering Consultant, Zurich Objectives
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the
More informationXavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue
Xavier Field Office for Xavier Field Office 1601 Dana Avenue Xavier University January 30, 2012 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationEvacuation Fire Safety Program
Evacuation Fire Safety Program Emergency Procedures Provisions must be made for prompt medical attention in case of serious injury. The location and phone number of emergency service providers will be
More informationFire Protection System Impairment Procedure
Fire Protection System Impairment Procedure June 2017 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance and Responsibility Notification
More informationFire Prevention Plan for Alter Hall 3743 Ledgewood Drive
Administrative Office and Classroom Building for Alter Hall 3743 Ledgewood Drive Xavier University October 2, 2006 Page 1 3/3/2016 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationOUTLINE FOR FIRE PREVENTION ACTIVITY
OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion
More informationFire Prevention Plan for Campus Services Building 1630 Musketeer Drive
Application Services and Technology Support Mailing Services for Campus Services Building 1630 Musketeer Drive Xavier University October 31, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...
More informationSCALES NW EMERGENCY ACTION PLAN
Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.
More informationIowa State Fire Marshal
Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards
More informationFIRE PROTECTION PROGRAM
Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationFire Prevention Plan for Residence Life 1625 Musketeer Drive
Residence Life for Residence Life 1625 Musketeer Drive Xavier University November 14, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationWritten Fire Safety Plans
Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize
More informationWhat are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number:
What are the Contents of an Effective Fire Safety Plan? A study of fire safety plans that have already been produced illustrates that one size does not fit all. Depending upon the complexity of a given
More informationIIPP. Injury & Illness Prevention Program Hartog Drive San Jose CA Responsibilities. Workplace Hazards. Training. Incident Investigations
Injury & Illness Prevention Program Responsibilities Training Workplace Hazards IIPP Recordkeeping Incident Investigations Employee Communications 1876 Hartog Drive San Jose CA 95131 Page 1 of 23 IIPP
More informationTo: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard
SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an
More informationTitle: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015
Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.
More information1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.
REQUIREMENT 2. HOT WORK OPERATIONS 1.0 PURPOSE 1.1 To establish a requirement with responsibilities for any hot work operations during all phases of construction, renovation and routine maintenance work
More informationUC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION
SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions
More informationHot Work Policy and Procedures
Environmental Health & Safety Office of the Fire Marshal Hot Work Policy and Procedures In Accordance With New Jersey Fire Code And National Fire Protection Association 505 Ramapo Valley Road, Building
More informationRISK ENGINEERING GUIDELINE.
RISK ENGINEERING GUIDELINE. IMPAIRMENT OF FIRE PROTECTION SYSTEMS HDI Risk Consulting Property www.hdi.global An impairment of fire protection systems increases the risk. In order to reduce the risk of
More informationChapter 18 Welding Table of Contents
Chapter 18 Welding Table of Contents 18.1 Foreword 18.2 Introduction 18.3 Applicability of Standard 18.4 Other Policies that Might Apply 18.5 Approved Areas for Welding and Cutting 18.6 Other Areas 18.7
More informationThis policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.
Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure
More informationHOT WORK PERMIT PROCEDURES
HOT WORK PERMIT PROCEDURES 1. An approved YYC Hot Work Permit is required when any cutting, grinding, welding, or soldering work is being done. As well, any work that creates a dust cloud which can set
More informationFire Prevention Plan
Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........
More informationFire Prevention Plan for St. Barbara Hall 3904 Winding Way
Military Science Department for St. Barbara Hall 3904 Winding Way Xavier University November 16, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationJohn Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES
John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES Last Updated: July 18, 2013 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3 1. Facility Hot Work
More informationFire Prevention Plan for
Kuhlman Hall for Kuhlman Hall 3824 Ledgewood Avenue Xavier University November 9, 2006 Steve Owen Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire Hazards...
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationStillwater Area Community Services Center Inc.
Fire Prevention Plan 1. Purpose The purpose of this Fire Prevention Plan is to eliminate the causes of fire, prevent loss of life and property by fire, and to comply with the Occupational Safety and Health
More informationFIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures
FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE
More informationPurpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.
CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All
More informationRegulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities. Regulation Explanation Document Reference
Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities Mandatory Immediate Notifications to NJDHSS 8:39-9.4(e)1 8:39-9.4(e)4 Interruption for 3 or more hours of physical
More informationPOLICY NUMBER ISSUE DATE REVISED DATE REVIEW DATE
POLICY NAME: IMPLEMENTATION OF INTERIM LIFE SAFETY MEASURES, FIRE SYSTEM IMPAIRMENTS, AND FIRE WATCH (formerly Implementation of Interim Life Safety Measures) POLICY NUMBER: S06-10 ISSUE DATE: FEBRUARY
More informationIRVING FIRE DEPARTMENT EMERGENCY PLANS
IRVING FIRE DEPARTMENT EMERGENCY PLANS INTERNATIONAL FIRE CODE, Selected Sections from 404.2-406.3 404.2 Where required. An approved fire safety and evacuation plan shall be prepared and maintained for
More informationFire Prevention Plan Program
Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure
More informationProgressive Safety Services LLC 2
Progressive Safety Services LLC 2 Oxygen - to sustain combustion Heat - to raise material to ignition temperature Fuel or combustible material Chemical - exothermic reaction Progressive Safety Services
More informationFIRE SAFETY AND PREVENTION POLICY
Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has
More informationFire Prevention Plan for Cintas Center 1624 Musketeer Drive
Athletics Xavier Dining Cintas Center Operations Xavier Leadership Center for Cintas Center 1624 Musketeer Drive Xavier University November 1, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...
More informationNY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80
Established 1995 Preparing the future High Rise Building Fire Safety Directors Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness
More informationFIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES
Effective Date: April 1 st, 2016 WICHITA AIRPORT AUTHORITY FIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES APPLICATION AND PERMIT FOR CUTTING, WELDING OR HOT WORK PROCESSES USING ELECTRIC ARCS
More informationINTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES
INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this
More informationFire Prevention Plan for Bellarmine Parish Center 3832 Ledgewood Avenue
Bellarmine Parish for Bellarmine Parish Center 3832 Ledgewood Avenue Xavier University October 20, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationChapter 4: Fire Protection Systems
Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system
More informationCAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY
CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY Origination Date: July 1 st 2009 1. PURPOSE The purpose of this policy is to create a safe environment for faculty, staff, students and visitors by applying
More informationTitle: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)
Indiana University Northwest Environmental Health & Safety Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Applies to: Issue Date: Latest
More informationFire Inspection & Prevention Initiative. Fire Safety Plan Documentation Guide. Part 3 (of 3) Format Guide Edition. (December 5, 2014)
Fire Inspection & Prevention Initiative Fire Safety Plan Documentation Guide Part 3 (of 3) Format Guide 2012 Edition (December 5, 2014) FSP Documentation Guide - Part 3: Format Guide Fire Safety Plan Documentation
More informationBCIT FIRE SAFETY PROGRAM
BCIT FIRE SAFETY PROGRAM February 2018 This page intentionally blank 2 TABLE OF CONTENTS 1. INTRODUCTION 4 2. RESPONSIBILITIES 4 3. LEGISLATIVE COMPLIANCE 6 4. FIRE PREVENTION 6 5. OCCUPANCY 7 6. FIRE
More informationFire Safety Plan Information. For Construction and Demolition Sites
Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationBritish Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY
BCIT Safety Manual Contents 1. Purpose... 2 2. Definitions... 2 3. Reference Materials... 5 4. Roles & Responsibilities... 5 4.1 BCIT Employees, Students, Contractors and Visitors... 5 4.2 Supervisors...
More informationFire Prevention Program
Fire Prevention Program Updated February 2010 REGULATORY AUTHORITY California Code of Regulations, Title 8, Section 3221, Title 19 (19CCR) and Title 24 (24CCR), along with National Fire Protection Association
More informationThe Social Accountability International (SAI) Fire Safety Checklist
The Social Accountability International (SAI) Fire Safety Checklist Introduction The Social Accountability International (SAI) Fire Safety Checklist is a guidance tool prepared for SA8000 & BSCI Auditors
More informationHOT WORK SAFETY PROGRAM:
HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.
More informationFIRE SAFETY FOR OFFICE WORKERS
2746 FIRE SAFETY FOR OFFICE WORKERS Leader s Guide ERI Safety Videos FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationStatement of Policy. Fire Extinguisher Use Policy #: SMS-041
Statement of Policy Fire Extinguisher Use Policy #: SMS-041 Controlling Office: Director of Health, Safety, Education and Training Effective Date: May 1, 2013 Applies to CAMTS: Ninth Edition 04.02.01-E
More informationWELDING, CUTTING, AND BRAZING SAFETY PROGRAM
WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing
More informationState of North Carolina Department of Environment and Natural Resources Division of Waste Management. Safety and Risk Management Program
State of North Carolina Department of Environment and Natural Resources Division of Waste Management Safety and Risk Management Program Revised: January 5, 2015 FOREWORD This North Carolina Division of
More informationProperty Conservation Essentials
Property Conservation Essentials Define Property Conservation Discuss the Purpose of a Property Conservation Program Review Property Conservation Implementation Strategies Explain the Common Exposures
More informationTraining Toolbox Series. ICA11v1.0 Information, Digital Media & Technology
Vocational Education and Training Training Toolbox Series ICA11v1.0 Information, Digital Media & Technology Cert I, II and III Classroom Handouts 2 Section 10 Emergency Planning, Accident Reporting and
More informationH&S Forum. Fire Safety Policy Glascote Academy
Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote
More informationFIRE SAFETY. This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are:
FIRE SAFETY This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject that it addresses.
More informationStructural Firefighting Policy
Section Policy Number Effective Date C C1 09/01/2015 Policy Issued As Reference Policy # B1-B4, B6, C2-C10, C12, D1, and TBD Subject Approval: Policy Donald Norman, Fire Chief PURPOSE The purpose of this
More informationFIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES
10 FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Demonstrate procedures for assuming and transferring command at an emergency scene, utilizing an incident management system. REFERENCE: NFPA 1001,
More informationFire Emergency Response Procedure
Contents 1. Purpose & Scope... 3 2. Procedure... 3 2.1 General Requirements... 3 2.2 Fire Response Procedure... 3 2.3 Evacuation Routes... 3 2.4 Fight fire ONLY if... 4 2.5 Fire Extinguishers... 4 3. Responsibilities...
More informationCold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems.
RiskTopics Management practices Cold weather freeze-ups August 2015 Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems. Introduction
More informationFIRE SAFETY INSPECTIONS
FIRE SAFETY INSPECTIONS RCG002 (E)-v2-01/2017 Page 1 2017 Royal & Sun Alliance Insurance plc Introduction Most of us give little thought to our surroundings until an accident occurs. Who left the power
More information