1 Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are fully operational to perform when needed. These systems, such as automatic sprinkler systems, are effective at reducing damage from fire and smoke as well as the potential for injury or death to building occupants. When such a system is out of service due to a planned or emergency repair, human error, or a malicious act, a fire can grow unchecked, resulting in substantial property loss or personal injury. A fire protection impairment program can be used to manage these situations in order to reduce the threat to property and personnel. The program accomplishes this through the following: limiting the time and scope of unavailable fire protection, controlling hazards, establishing alternate fire detection and alarm activation methods, providing substitute fire suppression systems, and ensuring that response to a fire, should one occur during the impairment, is swift and appropriate. Impairments Impairment can be described as the condition when at least one aspect of fire protection is out of service. While any number of conditions could cause impairment to protection systems, impairments are typically grouped into three types: planned, emergency, and hidden. Planned Impairment A planned impairment is when a fire protection system is out of service due to work, such as maintenance, scheduled repairs, or new construction. To reduce the potential for loss, it is best to schedule maintenance and repair work so that only a part of the system is impaired during the repair or maintenance work. Emergency Impairment An emergency impairment occurs when a fire protection system is taken out of service unexpectedly. Emergency impairments can be caused by numerous occurrences, such as a ruptured pipe or activation of a sprinkler head. Hidden Impairment Impairments are sometimes not readily apparent and are often discovered by accident or during routine inspection, testing, or maintenance of the fire protection system or equipment. A closed sprinkler system control valve is one of the most common of these hidden impairments. When discovered, these impairments should be treated in the same manner as an emergency impairment. Systems and Equipment The scope of an impairment program goes beyond automatic fire sprinkler systems. A thorough impairment management program will also include alarm systems, water supplies, special extinguishing systems, and other equipment. An impairment management program should include all aspects of fire protection including: Fire sprinkler systems Fire pumps Water supplies, including public and private water systems and underground supply piping Fire alarm systems Smoke and fire detection systems Life safety systems, such as evacuation alarms and voice notification systems Special extinguishing systems, such as carbon dioxide, foam, water mist, and chemical extinguishing systems Fire hydrants, fire department connections, and standpipe and hose systems Impairment Management Organizations should develop a documented impairment program, which outlines management s expectations. It should follow many of the guidelines that are introduced in the remainder of this document. In order to ensure that impairments are identified and preventive measures promptly enacted, management should designate an impairment coordinator who is responsible for administering the impairment management program. The impairment coordinator should have sufficient authority to be able to expedite repairs and suspend hazardous operations. Before an Impairment Prior to a planned impairment or immediately after an emergency impairment has been discovered, the following procedures should be followed:

2 Suspension of Hazardous Operations During impairments, hazardous operations should be stopped until fire protection is fully restored. Such operations can include spray painting, flammable liquid operation, and hot work operations (e.g., cutting and welding). This includes strictly enforcing no smoking rules. If possible, the impairment should be scheduled to occur during idle periods when no ignition sources are present. Control the fuel load in the area of impairment. Minimize or eliminate, if possible, all combustible and other hazardous materials; ensure good housekeeping practices are in place. Notifications Notify the following entities of the impairment: Local fire department being aware of the impaired fire protection system will allow them to respond to an alarm with additional units and resources. The impaired fire protection may also require them to alter their plan of attack. A good pre-plan should consider fires that occur during common impairments. Philadelphia Insurance Companies notifying PHLY allows us to understand the scope of the outage and degree of increased risk. We can review the implemented precautions and provide guidance on any additional ones needed. Finally, it provides another level of reminders to return the fire protection system to full service. Please contact us via at phlyrms@phly.com. Facility emergency response team (ERT) Alarm monitoring company Affected employees Use Impairment Permits/Tags The fire protection impairment permit should be filled out as a record of the impairment. One impairment tag should be filled out and attached to the impaired valve or piece of fire protection equipment. Finally, a second tag should be attached to the affected fire department connection. The reason for the latter is that it provides prominent notice of the impairment to the responding fire department if called. The permit and tags provide reminders of the impaired state of the system and the necessity to return to full service once the reason for the impairment is no longer present. The person requesting the impairment is responsible for filling out the permit, tags, and obtaining an authorized signature. See PHLY Impairment Permit & Tags associated with this document for these items. For additional information and guidance, see PHLY Fire Protection Impairment Management at the end of this document, which provides a checklist of things to be addressed during impairment. Compartmentalization When fire protection systems are out of service, the last line of defense between fire control and a significant loss may be the fire doors. Whenever possible, fire doors should be closed until fire protection is restored. Therefore, it is important that fire doors are properly maintained and in working order. See Fire Protection Report FP-43-01, Fire Doors, for additional information on this topic. Temporary Fire Protection The facility emergency organization and/or emergency response team (ERT) must be informed. This organization may need to provide alternate fire protection equipment, such as portable extinguishers and charged fire hoses, in the event of an emergency and should maintain a heightened sense of awareness during the impairment. Temporary fire protection measures to be taken include, but are not limited to, the following: Hydrants hooked up to sprinkler riser Hose line(s) charged Extra fire extinguishers distributed throughout the facility Extra security or fire watch patrols provide a means to quickly notify proper authorities in event of fire The use of sectional control valves, whenever possible, to minimize the area without fire protection When possible, place somebody at or near the closed (impaired) control valve(s) so that they can open them in the event of a fire See Fire Protection Report FP-45-20, Emergency Response Teams (ERT), for additional information on this topic. Expeditious Repairs The shutdown can be minimized if repair crews are authorized to work continuously overnight and through weekends. Ideally, the work should be done without interruption until the job is complete. For work that involves a large area, the planned repair or extension should be done in sections, where possible, to minimize the area without fire protection. Additional considerations include: No planned impairment should start until all supplies are present - this will reduce the impairment time A timetable should be employed to allow management to keep track of repair progress During the Impairment During the impairment, the repair crew and their progress should be periodically checked. Temporary protection, such as charged hose lines, should be checked on a regular basis to ensure their status has not changed. The suspension of hazardous operations requirements should be continued. Additional considerations include: Establishing a 24-hour fire watch - this can be done by extending employee hours or hiring a temporary guard service When possible, assigning personnel to reopen fire protection valves in case of a fire Assigning personnel to transmit fire alarms to the occupants and the fire department when the building alarm system is impaired Strictly enforcing no smoking rules

3 After the Impairment (Restoration) After the impairment, restoration of fire protection must be verified. This is done by performing a main drain test on a sprinkler system or by other methods appropriate for the fire protection system. The impairment coordinator should ensure that all systems are back in service and properly secured. After the fire protection is verified to be back in service, the entities, such as the fire department and Philadelphia Insurance Companies, that were notified of the impairment need to be notified that the fire protection had been restored to full service. Ensure that all copies of the impairment tags are collected, completed, and filed. If the impairment was of a hidden nature, investigate its cause so that its recurrence can be prevented in the future.

4 Fire Protection Impairment System impaired: Area protected by impaired system Date Hazardous operations in impaired area Halt hazardous operations that could cause or increase size of fire Remove or reduce fuel load as much as practical Schedule impairment during idle period Maintain good housekeeping practices Smoking is prohibited Notifications made Local fire department Philadelphia Insurance Companies Facility management and impairment coordinator Facility emergency response team Alarm monitoring company Affected employees Permit and tags Impairment permit filled out and displayed with copy in office Tag filled out and affixed to impaired control valve or applicable part of system Tag filled out and affixed to fire department connection Compartmentalization Fire doors in impaired area are closed Work planning No planned impairment until all supplies and equipment needed for project are in place Timetable to track progress has been developed and displayed Work done in sections so the area of impaired protection is minimized Interim fire protection measures Hydrant hooked up to sprinkler riser Hose lines placed in impaired area and charged Extra fire extinguishers are provided throughout facility as needed 24-hour fire watch established with means to quickly alert authorities of a fire Sectional control valves utilized where possible Individual posted at or near impaired control valve for ready opening if needed

5 Restoration after impairment Fire protection system restoration is verified (via main drain or other applicable test) Alarm devices have been restored Make notifications to previously notified parties that system has been restored Restore fire doors Release interim fire protection measures Remove posted permit and tags, and file in office as record of impairment Return to normal operations Ed

Management Practices: Fire Protection Impairments November 2015

Management Practices: Fire Protection Impairments November 2015 RiskTopics Management Practices: Fire Protection Impairments November 2015 When business capital is invested in fire protection, it is difficult to explain any fire protection outage that allows a fire

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire

More information

Fire System Impairment Policy

Fire System Impairment Policy Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,

More information

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit) DUQUESNE UNIVERSITY Fire Protection System Impairment Program (Red etag Permit) Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Exceptions 2 Definitions

More information

Impairments to Fire Protection Equipment

Impairments to Fire Protection Equipment Impairments to Fire Protection Equipment INTRODUCTION Buildings and equipment are provided with fire protection and/or detection systems to reduce property damage and interruption to business in the event

More information

2010 FIRE CODE OF NEW YORK STATE

2010 FIRE CODE OF NEW YORK STATE 2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,

More information

UNIVERSITY. Facilities Management

UNIVERSITY. Facilities Management EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

Builders Risk - Fire Prevention Inspection Checklist

Builders Risk - Fire Prevention Inspection Checklist Builders Risk - Fire Prevention Inspection Checklist Use our inspection checklist tool to help you identify and monitor risk related to builders risk of fire on the job site. Inspection Details: Inspector

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites

More information

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

OXNARD FIRE DEPARTMENT Fire Watch Guidelines OXNARD FIRE DEPARTMENT Fire Watch Guidelines What is a Fire Watch? A Fire Watch is a temporary measure intended to ensure continuous and systematic surveillance of an activity, building or portion thereof

More information

Managing Fire Protection System Impairment

Managing Fire Protection System Impairment Managing Fire Protection System Impairment Can your company afford to lose US$3.2 million in assets? Forgetting to restore an impaired sprinkler or other fire protection system at your facility could cost

More information

Renovation Program. Renovation Program GENERAL

Renovation Program. Renovation Program GENERAL Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services

More information

Freezing of Water-Based Fire Protection Systems

Freezing of Water-Based Fire Protection Systems Risk Solutions Freezing of Water-Based Fire Protection Systems Freezing of water in fire protection piping can seriously compromise a property s fire protection. This report provides information on methods

More information

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope 1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements

More information

Procedure DESCRIPTION/OVERVIEW

Procedure DESCRIPTION/OVERVIEW Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety

More information

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES BACKGROUND INFORMATION Alberta Fire Code 2014: FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES Alberta Fire Code (AFC) 2014, Division B, Section 5.6. requires a Fire Safety Plan for

More information

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY PURPOSE The fire prevention plan provides information and procedures to minimize the occurrence of an accidental fire at the job site or office, and an efficient

More information

Emergency Action Fire Prevention Plan

Emergency Action Fire Prevention Plan Emergency Action Fire Prevention Plan Table of Contents Section Title Page 1.0 Purpose 2 2.0 Scope and Application 2 3.0 Responsibilities 2-3 University Safety Coordinator 2-3 Department Heads, Supervisors

More information

FIRE PREVENTION PLAN EMERGENCY ACTION

FIRE PREVENTION PLAN EMERGENCY ACTION FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces

More information

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS Note: For information on OOS Fire Alarms please see Inspectional

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

BURN NOTICE: KEEP THE HEAT AWAY!

BURN NOTICE: KEEP THE HEAT AWAY! BURN NOTICE: KEEP THE HEAT AWAY! 2019 MHEC MPP LOSS CONTROL WORKSHOP MARCH 8, 2019 Jared Stolin Property Risk Consultant, Marsh Risk Consulting Mike Fairfield Sr. Risk Engineering Consultant, Zurich Objectives

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the

More information

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue Xavier Field Office for Xavier Field Office 1601 Dana Avenue Xavier University January 30, 2012 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace

More information

Evacuation Fire Safety Program

Evacuation Fire Safety Program Evacuation Fire Safety Program Emergency Procedures Provisions must be made for prompt medical attention in case of serious injury. The location and phone number of emergency service providers will be

More information

Fire Protection System Impairment Procedure

Fire Protection System Impairment Procedure Fire Protection System Impairment Procedure June 2017 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance and Responsibility Notification

More information

Fire Prevention Plan for Alter Hall 3743 Ledgewood Drive

Fire Prevention Plan for Alter Hall 3743 Ledgewood Drive Administrative Office and Classroom Building for Alter Hall 3743 Ledgewood Drive Xavier University October 2, 2006 Page 1 3/3/2016 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace

More information

OUTLINE FOR FIRE PREVENTION ACTIVITY

OUTLINE FOR FIRE PREVENTION ACTIVITY OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion

More information

Fire Prevention Plan for Campus Services Building 1630 Musketeer Drive

Fire Prevention Plan for Campus Services Building 1630 Musketeer Drive Application Services and Technology Support Mailing Services for Campus Services Building 1630 Musketeer Drive Xavier University October 31, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...

More information

SCALES NW EMERGENCY ACTION PLAN

SCALES NW EMERGENCY ACTION PLAN Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.

More information

Iowa State Fire Marshal

Iowa State Fire Marshal Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards

More information

FIRE PROTECTION PROGRAM

FIRE PROTECTION PROGRAM Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

Fire Prevention Plan for Residence Life 1625 Musketeer Drive

Fire Prevention Plan for Residence Life 1625 Musketeer Drive Residence Life for Residence Life 1625 Musketeer Drive Xavier University November 14, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

Written Fire Safety Plans

Written Fire Safety Plans Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize

More information

What are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number:

What are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number: What are the Contents of an Effective Fire Safety Plan? A study of fire safety plans that have already been produced illustrates that one size does not fit all. Depending upon the complexity of a given

More information

IIPP. Injury & Illness Prevention Program Hartog Drive San Jose CA Responsibilities. Workplace Hazards. Training. Incident Investigations

IIPP. Injury & Illness Prevention Program Hartog Drive San Jose CA Responsibilities. Workplace Hazards. Training. Incident Investigations Injury & Illness Prevention Program Responsibilities Training Workplace Hazards IIPP Recordkeeping Incident Investigations Employee Communications 1876 Hartog Drive San Jose CA 95131 Page 1 of 23 IIPP

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.

More information

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed. REQUIREMENT 2. HOT WORK OPERATIONS 1.0 PURPOSE 1.1 To establish a requirement with responsibilities for any hot work operations during all phases of construction, renovation and routine maintenance work

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

Hot Work Policy and Procedures

Hot Work Policy and Procedures Environmental Health & Safety Office of the Fire Marshal Hot Work Policy and Procedures In Accordance With New Jersey Fire Code And National Fire Protection Association 505 Ramapo Valley Road, Building

More information

RISK ENGINEERING GUIDELINE.

RISK ENGINEERING GUIDELINE. RISK ENGINEERING GUIDELINE. IMPAIRMENT OF FIRE PROTECTION SYSTEMS HDI Risk Consulting Property www.hdi.global An impairment of fire protection systems increases the risk. In order to reduce the risk of

More information

Chapter 18 Welding Table of Contents

Chapter 18 Welding Table of Contents Chapter 18 Welding Table of Contents 18.1 Foreword 18.2 Introduction 18.3 Applicability of Standard 18.4 Other Policies that Might Apply 18.5 Approved Areas for Welding and Cutting 18.6 Other Areas 18.7

More information

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days. Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure

More information

HOT WORK PERMIT PROCEDURES

HOT WORK PERMIT PROCEDURES HOT WORK PERMIT PROCEDURES 1. An approved YYC Hot Work Permit is required when any cutting, grinding, welding, or soldering work is being done. As well, any work that creates a dust cloud which can set

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

Fire Prevention Plan for St. Barbara Hall 3904 Winding Way

Fire Prevention Plan for St. Barbara Hall 3904 Winding Way Military Science Department for St. Barbara Hall 3904 Winding Way Xavier University November 16, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace

More information

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES Last Updated: July 18, 2013 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3 1. Facility Hot Work

More information

Fire Prevention Plan for

Fire Prevention Plan for Kuhlman Hall for Kuhlman Hall 3824 Ledgewood Avenue Xavier University November 9, 2006 Steve Owen Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire Hazards...

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for

More information

Stillwater Area Community Services Center Inc.

Stillwater Area Community Services Center Inc. Fire Prevention Plan 1. Purpose The purpose of this Fire Prevention Plan is to eliminate the causes of fire, prevent loss of life and property by fire, and to comply with the Occupational Safety and Health

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community. CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All

More information

Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities. Regulation Explanation Document Reference

Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities. Regulation Explanation Document Reference Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities Mandatory Immediate Notifications to NJDHSS 8:39-9.4(e)1 8:39-9.4(e)4 Interruption for 3 or more hours of physical

More information

POLICY NUMBER ISSUE DATE REVISED DATE REVIEW DATE

POLICY NUMBER ISSUE DATE REVISED DATE REVIEW DATE POLICY NAME: IMPLEMENTATION OF INTERIM LIFE SAFETY MEASURES, FIRE SYSTEM IMPAIRMENTS, AND FIRE WATCH (formerly Implementation of Interim Life Safety Measures) POLICY NUMBER: S06-10 ISSUE DATE: FEBRUARY

More information

IRVING FIRE DEPARTMENT EMERGENCY PLANS

IRVING FIRE DEPARTMENT EMERGENCY PLANS IRVING FIRE DEPARTMENT EMERGENCY PLANS INTERNATIONAL FIRE CODE, Selected Sections from 404.2-406.3 404.2 Where required. An approved fire safety and evacuation plan shall be prepared and maintained for

More information

Fire Prevention Plan Program

Fire Prevention Plan Program Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure

More information

Progressive Safety Services LLC 2

Progressive Safety Services LLC 2 Progressive Safety Services LLC 2 Oxygen - to sustain combustion Heat - to raise material to ignition temperature Fuel or combustible material Chemical - exothermic reaction Progressive Safety Services

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

Fire Prevention Plan for Cintas Center 1624 Musketeer Drive

Fire Prevention Plan for Cintas Center 1624 Musketeer Drive Athletics Xavier Dining Cintas Center Operations Xavier Leadership Center for Cintas Center 1624 Musketeer Drive Xavier University November 1, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...

More information

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80 Established 1995 Preparing the future High Rise Building Fire Safety Directors Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness

More information

FIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES

FIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES Effective Date: April 1 st, 2016 WICHITA AIRPORT AUTHORITY FIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES APPLICATION AND PERMIT FOR CUTTING, WELDING OR HOT WORK PROCESSES USING ELECTRIC ARCS

More information

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this

More information

Fire Prevention Plan for Bellarmine Parish Center 3832 Ledgewood Avenue

Fire Prevention Plan for Bellarmine Parish Center 3832 Ledgewood Avenue Bellarmine Parish for Bellarmine Parish Center 3832 Ledgewood Avenue Xavier University October 20, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY Origination Date: July 1 st 2009 1. PURPOSE The purpose of this policy is to create a safe environment for faculty, staff, students and visitors by applying

More information

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Indiana University Northwest Environmental Health & Safety Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Applies to: Issue Date: Latest

More information

Fire Inspection & Prevention Initiative. Fire Safety Plan Documentation Guide. Part 3 (of 3) Format Guide Edition. (December 5, 2014)

Fire Inspection & Prevention Initiative. Fire Safety Plan Documentation Guide. Part 3 (of 3) Format Guide Edition. (December 5, 2014) Fire Inspection & Prevention Initiative Fire Safety Plan Documentation Guide Part 3 (of 3) Format Guide 2012 Edition (December 5, 2014) FSP Documentation Guide - Part 3: Format Guide Fire Safety Plan Documentation

More information

BCIT FIRE SAFETY PROGRAM

BCIT FIRE SAFETY PROGRAM BCIT FIRE SAFETY PROGRAM February 2018 This page intentionally blank 2 TABLE OF CONTENTS 1. INTRODUCTION 4 2. RESPONSIBILITIES 4 3. LEGISLATIVE COMPLIANCE 6 4. FIRE PREVENTION 6 5. OCCUPANCY 7 6. FIRE

More information

Fire Safety Plan Information. For Construction and Demolition Sites

Fire Safety Plan Information. For Construction and Demolition Sites Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions

More information

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION

More information

British Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY

British Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY BCIT Safety Manual Contents 1. Purpose... 2 2. Definitions... 2 3. Reference Materials... 5 4. Roles & Responsibilities... 5 4.1 BCIT Employees, Students, Contractors and Visitors... 5 4.2 Supervisors...

More information

Fire Prevention Program

Fire Prevention Program Fire Prevention Program Updated February 2010 REGULATORY AUTHORITY California Code of Regulations, Title 8, Section 3221, Title 19 (19CCR) and Title 24 (24CCR), along with National Fire Protection Association

More information

The Social Accountability International (SAI) Fire Safety Checklist

The Social Accountability International (SAI) Fire Safety Checklist The Social Accountability International (SAI) Fire Safety Checklist Introduction The Social Accountability International (SAI) Fire Safety Checklist is a guidance tool prepared for SA8000 & BSCI Auditors

More information

HOT WORK SAFETY PROGRAM:

HOT WORK SAFETY PROGRAM: HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.

More information

FIRE SAFETY FOR OFFICE WORKERS

FIRE SAFETY FOR OFFICE WORKERS 2746 FIRE SAFETY FOR OFFICE WORKERS Leader s Guide ERI Safety Videos FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

Statement of Policy. Fire Extinguisher Use Policy #: SMS-041

Statement of Policy. Fire Extinguisher Use Policy #: SMS-041 Statement of Policy Fire Extinguisher Use Policy #: SMS-041 Controlling Office: Director of Health, Safety, Education and Training Effective Date: May 1, 2013 Applies to CAMTS: Ninth Edition 04.02.01-E

More information

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing

More information

State of North Carolina Department of Environment and Natural Resources Division of Waste Management. Safety and Risk Management Program

State of North Carolina Department of Environment and Natural Resources Division of Waste Management. Safety and Risk Management Program State of North Carolina Department of Environment and Natural Resources Division of Waste Management Safety and Risk Management Program Revised: January 5, 2015 FOREWORD This North Carolina Division of

More information

Property Conservation Essentials

Property Conservation Essentials Property Conservation Essentials Define Property Conservation Discuss the Purpose of a Property Conservation Program Review Property Conservation Implementation Strategies Explain the Common Exposures

More information

Training Toolbox Series. ICA11v1.0 Information, Digital Media & Technology

Training Toolbox Series. ICA11v1.0 Information, Digital Media & Technology Vocational Education and Training Training Toolbox Series ICA11v1.0 Information, Digital Media & Technology Cert I, II and III Classroom Handouts 2 Section 10 Emergency Planning, Accident Reporting and

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

FIRE SAFETY. This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are:

FIRE SAFETY. This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are: FIRE SAFETY This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject that it addresses.

More information

Structural Firefighting Policy

Structural Firefighting Policy Section Policy Number Effective Date C C1 09/01/2015 Policy Issued As Reference Policy # B1-B4, B6, C2-C10, C12, D1, and TBD Subject Approval: Policy Donald Norman, Fire Chief PURPOSE The purpose of this

More information

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES 10 FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Demonstrate procedures for assuming and transferring command at an emergency scene, utilizing an incident management system. REFERENCE: NFPA 1001,

More information

Fire Emergency Response Procedure

Fire Emergency Response Procedure Contents 1. Purpose & Scope... 3 2. Procedure... 3 2.1 General Requirements... 3 2.2 Fire Response Procedure... 3 2.3 Evacuation Routes... 3 2.4 Fight fire ONLY if... 4 2.5 Fire Extinguishers... 4 3. Responsibilities...

More information

Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems.

Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems. RiskTopics Management practices Cold weather freeze-ups August 2015 Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems. Introduction

More information

FIRE SAFETY INSPECTIONS

FIRE SAFETY INSPECTIONS FIRE SAFETY INSPECTIONS RCG002 (E)-v2-01/2017 Page 1 2017 Royal & Sun Alliance Insurance plc Introduction Most of us give little thought to our surroundings until an accident occurs. Who left the power

More information