MLCFC HMI NAVIGATION MANUAL

Size: px
Start display at page:

Download "MLCFC HMI NAVIGATION MANUAL"

Transcription

1 MLCFC HMI NAVIGATION MANUAL MOTIVAIR CORPORATION 85 WOODRIDGE DRIVE AMHERST, NY Phone# Fax#

2 MAIN MENU 20:55 10/09/12 M0 Water inlet 12,0 C Water outlet 7,0 C U1 ANTIFREEZE ALARM MENU Press to enter in ALARM MENU U:1 AL00 No alarms detected Press or to scroll the active alarm Press to reset the alarm a-maitenance MENU Press MENU Press LIST to return in MAIN MENU LIST to enter in MENU Press or to scroll the menu Press Press or to scroll the maintenance menu parameter to enter in MENU a-maintenance -> i-input/output k-clock s-setpoint p-user c-manufacturer h-summer/winter m-on_off unit q-history u-unit change Carel S.p.A. Ah Code: FLSTDMMSBE-H Ver.:3.5 11/02/12 Press to return in MENU LIST i-input/ OUTPUT MENU Press or to scroll the input/output Info Digital Inputs I1 OOOOOOOOOOOOOO Digital Outputs OOOOOCOCOOOOOO Press to return in MENU LIST

3 Press or to scroll the clock Info Press to return in MENU LIST k-clock MENU s-setpoint MENU Press or to enter in setpoint changing mode Clock config. Time 15:24 Date 10/09/12 Day Monday Actual setpoint S0 7,0 C Press to change the setpoint Press or to increase or decrease setpoint Press to confirm new setpoint Press to return in MENU LIST p-user MENU Press or to insert the user password Insert user password P Press to confirm the user password Press or to scroll the user parameter Press to return in MENU LIST c-manufacturer MENU Press or to insert the manufacturer password Press to confirm the manufacturer password Press or to scroll the manufacturer submenu Press to enter in the submenu Press or to scroll the submenu parameter Summer temperat. P1 Setpoint limits Low 5,0 C High 25,0 C Insert manufacturer password Z CONFIGURATION -> Parameters Carel EXV Drivers Timig Unit conf.: 02 C1 WATHER/AIR CHILLER+FREECOOLING Press to return in the submenu Press to return in MENU LIST

4 If the unit is OFF Press If the unit is ON Press m-on_off MENU to switch ON to switch OFF u-unit CHANGE MENU Unit Status 01 M1 ANTIFREEZE - Press ENTER to - - Switch on - Unit address: 1 M3 Press or to set the unit address to switch Switch to Unit: 2 Press to switch

5 CIRCUIT# 1 AND CIRCUIT# 2 MAIN SCREEN

6 SCREEN OPTIONS - DEPRESSING THE PROGRAM BUTTON

7 MAINTENANCE VIEW ONLY - MASTER

8 MAINTENANCE VIEW ONLY - MASTER

9 MAINTENANCE VIEW ONLY - MASTER

10 MAINTENANCE VIEW ONLY - SLAVE

11 MAINTENANCE VIEW ONLY - SLAVE

12 INPUT/OUTPUT VIEW ONLY - MASTER

13 INPUT/OUTPUT VIEW ONLY - MASTER

14 INPUT/OUTPUT VIEW ONLY - MASTER

15 INPUT/OUTPUT VIEW ONLY - MASTER

16 INPUT/OUTPUT VIEW ONLY - SLAVE

17 INPUT/OUTPUT VIEW ONLY - SLAVE

18 INPUT/OUTPUT VIEW ONLY - SLAVE

19 SET POINT SCREENS

20 CHILLER ON/OFF AND CIRCUIT CHANGE SCREENS

21 MAINTENANCE PARAMETERS - MASTER DESCRIPTION SCREEN MASK Input Maintenance Password A3 Duty hours thresholds for evaporator pump 1 A4 Reset duty hours thresholds for evaporator pump 1 A4 Duty hours thresholds for compressor A6 Reset compressor duty hours A6 Adjustment of probe B1 A7 Adjustment of probe B2 A7 Adjustment of probe B3 A7 Adjustment of probe B4 A7 Adjustment of probe B5 A8 Adjustment of probe B7 A8 Adjustment of probe B8 A8 0-10V FC Valve manual forcing Actual Value Av 0-10V FC Valve manual forcing Manual position. Av Enable compressor 1 A9 Enable compressor 2 A9 Enable compressor 3 A9 Enable compressor 4 A9 Delete Alarm Log Aa Manual release of Driver 1 at start-up Ab Adjustement mode for driver 1 valve Ad Number of steps for manual opening of Driver 1 valve Ad Input New Maintenance Password Af

22 MAINTENANCE PARAMETERS - SLAVE DESCRIPTION Input Maintenance Password Duty hours thresholds for compressor Reset compressor duty hours Adjustment of probe B4 Adjustment of probe B7 Adjustment of probe B8 alarm log delete Manual release of Driver 1 at start-up Adjustement mode for driver 1 valve Number of steps for manual opening of Driver 1 valve Input New Maintenance Password SCREEN MASK A3 A6 A6 A7 A8 A8 Aa Ab Ad Ad Af

23 CLOCK PARAMETERS - MASTER DESCRIPTION Enter clock password Enter clock password Enter New Clock Password SCREEN MASK K2 K6 K7

24 USER PARAMETERS - MASTER DESCRIPTION Input User Password Minimum limit of summer set point Maximum limit of summer set point Selection of control probe Outlet regulation force off (Delta) : Summer (-) Outlet regulation force off (Delta) : Winter (+) Control band Request time between steps: power-on Request time between steps: power-off Delayed power up between pump and compressors Delayed power down of main pump Enable remote On/Off Type of remote ON-OFF (MASTER) Enable On/Off from supervisor Alarm relay logic Enable summer / winter selection from digital input Enable summer / winter selection from supervisor Enable language mask start-up Type of freecooling control Integral time for freecooling management Freecooling offset on set-point Minimum freecooling delta Maximum freecooling delta Freecooling differential Compressors delay in freecooling Minimum threshold for freecooling valve start Maximum threshold for freecooling valve opening Board identification number for supervision network Card communication speed for supervision network Selection of communication serial network Type of unit measurement Input New User Password SCREEN MASK P0 P1 P1 P3 P5 P5 P6 Po Po P8 P9 Pa Pa Pl Pl Pb Pb Pc Pd Pd Pd Pe Pe Pe Pe Pf Pf Pj Pj Pj Pm Pk

25 USER PARAMETERS - SLAVE DESCRIPTION Input User Password Minimum limit of summer set point Maximum limit of summer set point Request time between steps: power-on Request time between steps: power-off Enable remote On/Off Enable On/Off from supervisor Alarm relay logic Enable language mask start-up Minimum freecooling delta Maximum freecooling delta Freecooling differential Compressors delay in freecooling Board identification number for supervision network Card communication speed for supervision network Selection of communication serial network Input New User Password SCREEN MASK P0 P1 P1 Po Po Pa Pl Pl Pc Pe Pe Pe Pe Pj Pj Pj Pk

26 MANUFACTURER PARAMETERS - MASTER Input Manufacturer Password Z0 CONFIGURATION Unit configuration C1 Type of compressors Cb Number of steps per compressor Cb Refrigerant Cb Number of drivers present Ca Number of compressors present Ca Compressor rotation Ca # of Evaporator pumps Cc Enable probe B1 C2 Enable probe B2 C2 Enable probe B3 C2 Enable probe B4 C2 Enable probe B5 C2 Enable probe B6 C2 Enable probe B7 C2 Enable probe B8 C2 Generic probe lower limit C4 Generic probe upper limit C4 Probe types for analogue inputs 1 and 2 (for pco1 cards only) C5 Type of delivery temperature probe C6 High pressure probe lower limit C7 High pressure probe upper limit C7 Low pressure probe lower limit C8 Low pressure probe upper limit C8 Enable double set-point C9 Solenoid Valve Configuration CY Enable step 1 special management Ch Stage 1 CR1 Cd Stage 1 CR2 Cd Stage 1 CR3 Cd Stage 2 CR1 Ce Stage 2 CR2 Ce Stage 2 CR3 Ce Stage 2 CR1 Cf Stage 2 CR2 Cf Stage 2 CR3 Cf Stage 2 CR1 Cg Stage 2 CR2 Cg

27 MANUFACTURER PARAMETERS - MASTER Stage 2 CR3 Enable pump down Minimum pump - down time Configuration of compressor power level in case of forced capacity control. Enable condensation Type of condensation control ID14 Config. Compressor Enable From ID14 Output config:. ECO valve Output config. FC OnOff valve Cg Cp Cp Cq Cr Cr Cn Cm Cm PARAMETERS Enable high pressure prevention Type of high condensation prevention Condensation set-point High condensation differential Enable delivery prevention Antifreeze prevention set point Antifreeze prevention differential Condensation set-point Condensation differential Inverter max. speed Inverter min. speed Maximum speed time Enable serious alarm Enable phase monitor alarm Enable evaporator flow-switch alarm Enable condenser flow-switch alarm Alarm set-point for delivery temperature probe Alarm differential for delivery temperature probe High pressure probe alarm set-point High pressure probe alarm differential Low pressure probe alarm set-point Low pressure probe alarm differential Low differential pressure alarm Alarm set-point: difference between high and low pressure Ritardo alla partenza allarme diff. tra pressioni Antifreeze set point Antifreeze differential Pump status in case of antifreeze alarm Pump status in the event of evaporator or condenser flow swich alarm Solenoid-valve management set-point Solenoid-valve management differential Stop F.C. / Antifreeze heater set point Antifreeze heater differential Cycle reversing valve logic Type of freecooling control Antifreeze temperature Economiser: Delta P. ECO Off Freecooling: Activation mode ChillBooster: Function ChillBooster: CH DetP.ON ChillBooster: Diff.(OFF) ChillBooster: FC SetP.OFF ChillBooster: Diff.(ON) ChillBooster: Min. ON time G1 G1 G1 G1 G2 G3 G3 G4 G4 G5 G5 G5 G6 G6 G7 G7 G8 G8 G9 G9 Ga Ga Gb Gb Gb Ge Ge Gf Gk Gg Gg Gh Gh Gi Gi Gi Gm Gn Gp Gp Gp Gq Gq Gq CAREL EXV DRIVERS: System EVD parameters Activation of driver battery Type of valve Select bidirectional valve F0 F2 F2

28 MANUFACTURER PARAMETERS - MASTER Custom valve: stand by steps minimum value of S1 pressure sensor maximum value of S1 pressure sensor Delay low superheat alarm Delay high temperature intake alarm Delay LOP alarm Delay MOP alarm Capacity required from driver with step 1 active (stepped capacity control ) or with continuous capacity control Capacity required from driver with step 2 active Capacity required from driver with step 3 active Capacity required from driver with step 4 active F7 F8 F8 F9 F9 Fa Fa Fc Fc Fd Fd CAREL EXV DRIVERS: Autosetup Installation of parameters of default Percentage ratio between fridge power and driver power type of compressor or unit Type of capacity control Type of cold mode exchanger Type of heat mode exchanger Threshold for LOP protection during chiller operation Threshold for MOP protection during chiller operation Superheat high alarm threshold Fs Ft Fu Fu Fv Fv Fw Fx Fy CAREL EXV DRIVERS: Advance setting Percentage ratio between fridge power and driver power in chiller function Proportional gain in chiller function Integral time during chiller operation Superheat set point during chiller operation Threshold for superheat protection during chiller operation Superheat dead band derivative time Integral time for superheat low protection Threshold integral time for LOP protection during chiller operation Threshold integral time for LOP protection during chiller operation Delay in MOP protection departure Dynamic proportional enabling factor Protection threshold for high temperature condensantion Integral time for high temperature condensation Fe Ff Ff Fg Fg Fn Fn Fo Fo Fp Fp Fq Fr Fr TIMINGS Delayed start due to evaporator flow-switch alarm Delayed steady state operation due to evaporator flowswitch alarm Delayed start due to low pressure alarm Delayed steady state operation due to low pressure alarm Delayed start due to oil differential alarm Delayed steady state operation due to oil differential Alarm Starting PW Starting Compressor minimum ON Time Compressor minimum OFF time Time between power-ups of different compressors Time between thrusts of same compressor Time between solenoid/ capacity control 1 Time between capacity controls 1 and 2 Time between capacity controls 2 and 3 Time between capacity controls 3 and 4 CR4 period Maximum operative time out with the operative limit T0 T0 T2 T2 T3 T3 T4 T4 T5 T5 T6 T6 T7 T7 T7 T7 T9 T9

29 MANUFACTURER PARAMETERS - MASTER Delay at start up of the high of suction pressure alarm Delay to reach to normal working Unloader time Slide valve reset (time from 100%) in power off Slide valve reset (time from 100%) in power on Freecool. On-Off valve kick : Pulse period Kick test Prev,high cond. 2nd action delay T9 Te Te Tz Tz Tf Tf Tp INITIALIZATION Deletion of memory and installation of default values. Input New Manufacturer Password V0 V1

30 MANUFACTURER PARAMETERS - SLAVE DESCRIPTION Input Manufacturer Password SCREEN MASK Z0 CONFIGURATION Enable probe B1 Enable probe B2 Enable probe B3 Enable probe B4 Enable probe B5 Enable probe B6 Enable probe B7 Enable probe B8 Generic probe lower limit Generic probe upper limit Probe types for analogue inputs 1 and 2 (for pco1 cards only) Type of delivery temperature probe High pressure probe lower limit High pressure probe upper limit Low pressure probe lower limit Low pressure probe upper limit Solenoid Valve Management Enable step 1 special management Enable pump down Minimum pump - down time Configuration of compressor power level in case of forced capacity control. Enable condensation Type of condensation control ID14 Config. Compressor Enable From ID14 Output config:. ECO valve Output config. FC OnOff valve C2 C2 C2 C2 C2 C2 C2 C2 C4 C4 C5 C6 C7 C7 C8 C8 CY Ch Cp Cp Cq Cr Cr Cn Cm Cm PARAMETERS Enable high pressure prevention Type of high condensation prevention Condensation set-point High condensation differential Enable delivery prevention Condensation set-point Condensation differential Inverter max. speed G1 G1 G1 G1 G2 G4 G4 G5

31 MANUFACTURER PARAMETERS - SLAVE Inverter min. speed Maximum speed time Enable serious alarm Enable phase monitor alarm Enable evaporator flow-switch alarm Enable condenser flow-switch alarm Alarm set-point for delivery temperature probe Alarm differential for delivery temperature probe High pressure probe alarm set-point High pressure probe alarm differential Low pressure probe alarm set-point Low pressure probe alarm differential Low differential pressure alarm Alarm set-point: difference between high and low pressure Delayed start due to low pressure difference alarm Solenoid-valve management set-point Solenoid-valve management differential Economiser: Delta P. ECO Off G5 G5 G6 G6 G7 G7 G8 G8 G9 G9 Ga Ga Gb Gb Gb Gg Gg Gm CAREL EXV DRIVERS: System EVD parameters Activation of driver battery Type of valve Select bidirectional valve Custom valve: stand by steps minimum value of S1 pressure sensor maximum value of S1 pressure sensor Delay low superheat alarm Delay high temperature intake alarm Delay LOP alarm Delay MOP alarm Capacity required from driver with step 1 active (stepped capacity control ) or with continuous capacity control Capacity required from driver with step 2 active Capacity required from driver with step 3 active Capacity required from driver with step 4 active F0 F2 F2 F7 F8 F8 F9 F9 Fa Fa Fc Fc Fd Fd CAREL EXV DRIVERS: Autosetup Installation of parameters of default Percentage ratio between fridge power and driver power type of compressor or unit Type of capacity control Type of cold mode exchanger Type of heat mode exchanger Threshold for LOP protection during chiller operation Threshold for MOP protection during chiller operation Superheat high alarm threshold Fs Ft Fu Fu Fv Fv Fw Fx Fy CAREL EXV DRIVERS: Advance setting Percentage ratio between fridge power and driver power in chiller function Proportional gain in chiller function Integral time during chiller operation Superheat set point during chiller operation Threshold for superheat protection during chiller operation Superheat dead band derivative time Integral time for superheat low protection Threshold integral time for LOP protection during chiller operation Threshold integral time for LOP protection during chiller operation Delay in MOP protection departure Dynamic proportional enabling factor Fe Ff Ff Fg Fg Fn Fn Fo Fo Fp Fp Fq

32 MANUFACTURER PARAMETERS - SLAVE Protection threshold for high temperature condensantion Integral time for high temperature condensation Fr Fr TIMINGS Delayed start due to low pressure alarm Delayed steady state operation due to low pressure alarm Delayed start due to oil differential alarm Delayed steady state operation due to oil differential Alarm CR4 period Maximum operative time out with the operative limit Delay at start up of the high of suction pressure alarm Prev,high cond. 2nd action delay T2 T2 T3 T3 T9 T9 T9 Tp INITIALIZATION Deletion of memory and installation of default values. Set new Manufacturer Password V0 V1

Standard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve

Standard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve Application program for pco¹ pco² pco 3 Standard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve 1.1 09 / 11 / 2006 version of manual Program code: FLSTDmMSBE We wish to save you

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

Standard Rooftop 1/2 compressors

Standard Rooftop 1/2 compressors Application program for pco 2, pco¹, pco C and pco XS Standard Rooftop 1/2 compressors Manual version: 1.1 dated 06/05/04 Program code: FLSTDMRT0E We want to save you time and money We can assure you

More information

Service control manual Smart HP. Application FLBB0mHPGU

Service control manual Smart HP. Application FLBB0mHPGU Service control manual Smart HP Application FLBB0mHPGU 1 Summary 1. INTRODUCTION...3 1.1 Purpose of the manual...3 2. SYSTEM ARCHITECTURE...4 2.1 Main control components...4 3. USER INTERFACE...5 3.1 Terminal...5

More information

OPERATION AND MAINTENANCE MANUAL

OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE MANUAL Prg Sel line alarm on on/off alarm enter Clear EMIpro MICROPROCESSOR CONTENTS 1 GENERAL CHARACTERISTICS Page 2 1.1 General description Page 2 2 EMIPRO USER INTERFACE Page

More information

Standard Air Handling Units

Standard Air Handling Units Application software for pco² - pco XS Standard Air Handling Units Program code: FLSTDMAHUA We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee

More information

Index. 1. General description of the application Types of units controlled Types of regulation Condensation...

Index. 1. General description of the application Types of units controlled Types of regulation Condensation... LCS pco ADVANCED MICROPROCESSOR USER MANUAL GB Index 1. General description of the application... 4 1.1. Types of units controlled...4 1.2. Types of regulation...4 1.3. Condensation...4 1.4. Safety devices

More information

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12 CAREL ir33 Quick reference Handbook Pag.1/12 MAIN FEATURES OF THE INSTRUMENT USER INTERFACE 1. ON/OFF switch button UP button to increase temperature values 2. DOWN button to decrease values - Activates/deactivates

More information

User manual. pco 1 AQUA 4. Polyvalent air cooled heat pump kw AQUA4-CMA-1405-E. lennoxemeia.com

User manual. pco 1 AQUA 4. Polyvalent air cooled heat pump kw AQUA4-CMA-1405-E. lennoxemeia.com User manual pco 1 AQUA 4 Polyvalent air cooled heat pump 50 330 kw AQUA4-CMA-1405-E lennoxemeia.com TABLE OF CONTENTS 1 GENERAL DESCRIPTION OF THE APPLICATION... 2 2 CONTROL LOGIC 2.1 CONTROL OF INLET

More information

Operation manual. Rooftop Packaged Unit

Operation manual. Rooftop Packaged Unit Operation manual Rooftop Packaged Unit odels: UATYQ20ABAY1 UATYQ25ABAY1 UATYQ30ABAY1 UATYQ45ABAY1 UATYQ50ABAY1 UATYQ55ABAY1 UATYQ65ABAY1 UATYQ75ABAY1 UATYQ90ABAY1 UATYQ110ABAY1 UATYQ115ABAY1 UATYQ20AFC2Y1

More information

MCX ELECTRONIC CONTROLLER

MCX ELECTRONIC CONTROLLER WATER - AIR UNITS: CHILLERS y HEAT PUMPS User Manual Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

User Manual Ichill 200 L/D (Firmware version 1.7)

User Manual Ichill 200 L/D (Firmware version 1.7) User Manual Ichill 2 L/D (Firmware version 1.7) Pag. 1 of 142 INDEX 1. GENERAL FEATURES...8 1.1 Main Function... 8 2. ICHILL 2L/D TABLE OF THE FEATURES...1 3. USER INTERFACE...11 4. REMOTE KEYBOARD...15

More information

User manual for reversible heat pump

User manual for reversible heat pump User manual for reversible heat pump Heat pump system integrated in Geniox, DV or TIME air handling unit Manual version 1.01.14 Part number of this manual 90925374 Contents DECLARATION OF CONFORMITY EXAMPLE...2

More information

MCX ELECTRONIC CONTROLLER

MCX ELECTRONIC CONTROLLER WATER - AIR UNITS: CHILLERS y HEAT PUMPS Installer Manual Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

IPC108D - IPC108E (V.2.0)

IPC108D - IPC108E (V.2.0) IPC108D - IPC108E (V.2.0) APPLICATION GUIDE INDEX 1. IMPORTANT RECOMMENDATIONS 6 1.1 PRODUCT DISPOSAL (WEEE) 7 2. GENERALITIES 8 3. AVAILABLE APPLICATION CONFIGURATIONS 8 3.1 MAIN FUNCTIONS 9 4. SUPERVISION

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

ENERGY 200 Electronic Control for mono & bi- Compressor CHILLERS. User Manual

ENERGY 200 Electronic Control for mono & bi- Compressor CHILLERS. User Manual Electronic Control for mono & bi- Compressor CHILLERS User Manual 2/55 1 CONTENTS 1 Contents...3 2 How to use this manual...5 3 Introduction...6 3.1 Components...6 3.1.1 Basic module...6 3.1.2 Keyboards...6

More information

High Density Cooling Systems

High Density Cooling Systems OPERATION MANUAL Close Control Units Controller for Row-DENCO High Density Cooling Systems Table of Contents Controller for Row-DENCO 1 Safety and User Information... 4 1.1 Availability of the operation

More information

Products no longer available

Products no longer available Technical data sheet MONICO-.. Turnkey automation station MONICO-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Completely wired controller in matching control

More information

IC200L Series User manual

IC200L Series User manual IC2L Series User manual DIXELL INDEX 1 GENERAL ADVICE 7 2 GENERAL FEATURES 8 2.1 MAIN FUNCTION 8 3 IC2 L TABLE OF THE FEATURES 1 4 USER INTERFACE 11 4.1 FUNCTION OF THE LEDS OF THE KEY BUTTONS 11 4.2 USE

More information

Multi-zone Standard air-conditioning units

Multi-zone Standard air-conditioning units Application program for pco¹ and pco 2 Multi-zone Manual version 1.1 15 April 2004 Program code: FLSTDEMARE To save time and money! The thorough reading of this manual will ensure proper installation

More information

QUICK REFERENCE GUIDE SERIES IC100CX FW 1.8 (rel. 1.0)

QUICK REFERENCE GUIDE SERIES IC100CX FW 1.8 (rel. 1.0) QUICK REFERENCE GUIDE SERIES IC1CX FW 1.8 (rel. 1.) INDEX 1. General Advices 3 2. User Interface 4 3. Remote Keyboard VICX61 5 4. Display visualization 6 5. Silencing the Buzzer 6 6. First Installing

More information

WRL AFTER SALES SERVICE - REGULATION MANUAL. SOFTWARE UPDATE CAREL μpc vers. up to 2.6.3

WRL AFTER SALES SERVICE - REGULATION MANUAL. SOFTWARE UPDATE CAREL μpc vers. up to 2.6.3 AFTER SALES SERVICE - REGULATION MANUAL WATER / WATER CHILLER WATER COOLED REVERSIBLE CHILLER WATER/WATER HEAT PUMP WRL SOFTWARE UPDATE CAREL μpc vers. up 2.2.2 to 2.6.3 EN edition February 2013 Pag. 2/76

More information

Air-condensed water chillers and heat pumps YLCA / YLHA 100, 120 and 150

Air-condensed water chillers and heat pumps YLCA / YLHA 100, 120 and 150 Air-condensed water chillers and heat pumps YLCA / YLHA 100, 120 and 150 User manual Ref.: N-40291_EN 1110 Index Index 1 User manual...1 1.1 General description of the unit...2 1.1.1 Models available and

More information

DFZ. In Cab Control Description and Operation

DFZ. In Cab Control Description and Operation DFZ In Cab Control Description and Operation Index 1. Description of the control unit 1.1. Switching on the control unit 1.2. Diesel operation setting-up 1.3. Setting-up of the operation set point 1.4.

More information

DFZ. Cabin Control Description and operation

DFZ. Cabin Control Description and operation I DFZ Cabin Control Description and operation Index 1. Description of the control unit 1.1. Switching on the control unit 1.2. Diesel operation setting-up 1.3. Setting-up of the operation set point 1.4.

More information

CLIMATIC 60 User manual

CLIMATIC 60 User manual CLIMATIC 60 User manual ECOLEAN NEOSYS Air cooled chiller CL60 AC-CHILLER-IOM-0512-E TABLE OF CONTENTS CLIMATIC 60 AIR COOLED CHILLER CONTROL MANUAL Ref : INTRODUCTION CLIMATIC 60 controller Compatibility

More information

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller 339,95 195,85 0 2 89,35 14,15-1 Four Steps Chiller Heat Pump Controller 1 CONTENTS 1 Contents...2 2 How to use this manual...4 3 Introduction...5 3.1 Components...5 3.1.1 Basic Module...5 3.1.2

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

1/4 compressor modular Chiller-HP for ALCO Driver

1/4 compressor modular Chiller-HP for ALCO Driver plan application program plan 1/4 compressor modular Chiller-HP for ALCO Driver Manual version: 1.2 - July 22, 2000 Program code: EPSTDEMCHC ef.: 110EM &QWHQWV APPLICATIONS AND FUNCTIONS CAIED OUT BY THE

More information

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17 Q-SMART MODBUS KIT Modbus Protocol & Parameters Cod.001085120EN rev.a ed.08/2018 Q-SMART Software Version AE17 Index 1 Modbus Protocol on Q-SMART... 4 1.1 Broadcasting... 4 1.2 Data Protection... 4 1.3

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november

Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november Service Manual Chiller unit MQH R 410A Release Date Rev Review Date november 2008 ----- ----- MQH R410A ELECTRONIC CONTROL CONTROL PANEL The control panel allows the user to carry out all the operations

More information

XC1008D -XC1011D- XC1015D and VGC810

XC1008D -XC1011D- XC1015D and VGC810 Electronic Controller for Compressor Racks XC1008D -XC1011D- XC1015D and VGC810 Instructions Manual INDEX 1. GENERAL WARNING 4 1.1 PLEASE READ BEFORE USING THIS MANUAL 4 1.2 SAFETY PRECAUTIONS 4 2. WIRING

More information

CWB CHILLERS. User Maintenance Manual Cooling Capacity from 40 to 160 tons Scroll compressors-r410 Refrigerant. CWB-R Air-cooled water chillers

CWB CHILLERS. User Maintenance Manual Cooling Capacity from 40 to 160 tons Scroll compressors-r410 Refrigerant. CWB-R Air-cooled water chillers CWB CHILLERS BY FRIULAIR CWB-R Air-cooled water chillers User Maintenance Manual Cooling Capacity from 40 to 160 tons Scroll compressors-r410 Refrigerant Dear Customer, Thank you for the trust you have

More information

User manual CLIMATIC 50 - CHILLERS

User manual CLIMATIC 50 - CHILLERS User manual CLIMATIC 50 - CHILLERS Providing indoor climate comfort CL50-CHILLERS-IOM_0808-E INTERNAL USE LENNOX TECHNICIANS VERSION Climatic 50 CHILLER & HEAT PUMP INCLUDING NEOSYS RANGE USER MANUAL Ref:

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

Air-to-water scroll chillers

Air-to-water scroll chillers Air-to-water scroll chillers Model CGA 040 to 115 Cooling capacity: 14-40 kw CG-PRC031B-GB Table of Contents Technical specifications...4 Standard configuration... 4 Hydraulic version... 4 Casing... 4

More information

MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This chiller has been factory run tested to the specified water pressure

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

DC 60 & DM 60 displays

DC 60 & DM 60 displays USER MANUAL DC 60 & DM 60 displays BALTIC FLEXAIR ENERGY AIRCOOLAIR COMPACTAIR FLATAIR (& Inverter) AQUALEAN DC60-DM60-IOM-1310-E www.lennoxemea.com Summaries 1 Display DC60 1.1 Introduction... 2 1.2

More information

Configurator Commercial code/product Codes and accessories... 6 Architecture... 7

Configurator Commercial code/product Codes and accessories... 6 Architecture... 7 Pag. 1/76 Pag. 1/76 Table of contents Configurator 0200-0750... 4 Configurator 0800-1800... 5 1.1.1 Commercial code/product Codes and accessories... 6 Architecture... 7 2 Inputs/outputs... 8 2.1 pco3 large

More information

MasterCase. User Manual

MasterCase. User Manual MasterCase User Manual PRELIMINARY VERSION 24 January 2003 CONTENTS 1. Introduction...5 1.1 Main characteristics of the MasterCase...5 2. Layout of the hardware...7 2.1 Meaning of the inputs and outputs...7

More information

NA G µair CONNECT 2

NA G µair CONNECT 2 NA 9.41 G 7-216 µair CONNECT 2 Control manual EN CONTENTS PAGE 1. GENERAL INFORMATION 2 2. COMPONENTS 3 2.1 On the front: 3 2.2 On the rear: 4 3. MENU TREE 7 4. ACCESS LEVEL (menu 8) 1 5. CONFIGURING

More information

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration

More information

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

µc 2 SE for process chiller electronic control User manual

µc 2 SE for process chiller electronic control User manual µc SE for process chiller electronic control User manual IMPORTANT WARNINGS CAREL bases the development of its products on several years experience in the HVAC field, on continuous investment in technological

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Standard Air-conditioners Application program for pco 1, pco 2, pco 3, pco xs

Standard Air-conditioners Application program for pco 1, pco 2, pco 3, pco xs Standard Air-conditioners Application program for pco 1, pco 2, pco 3, pco xs User manual Manual version: 2.6 dated 11/02/2016 Program code: FLSTDMCZ0E We wish to save you time and money! We can assure

More information

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running Climaveneta Technical Bulletin BRH_0011_0121_201211_EN BRH r HFC R-410A 0011-0121 5,5-35,1 kw Water-cooled liquid chillers (The photo of the unit is indicative and may change depending on the model) Versatile

More information

ERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135

ERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135 ERV-24 Technician Settings & Operating Manual Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135 1 Introduction brief description General The ERV-24-HC11

More information

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS REFRIGERATORS OPERATING INSTRUCTIONS

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS REFRIGERATORS OPERATING INSTRUCTIONS COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS REFRIGERATORS OPERATING INSTRUCTIONS CONTENTS 1. Transportation Positioning Installation 3 2. Starting up 3 3. Safety instructions 4 4. Temperature regulation

More information

Controller User Guide. For chillers and heat pumps with IPro controller

Controller User Guide. For chillers and heat pumps with IPro controller Controller User Guide For chillers and heat pumps with IPro controller April 2018 PROD-SVU001A-GB Table of Contents GENERAL INFORMATION... 3 1. ADVANCED CONTROL... 4 2. CONTROL HARDWARE ARCHITECTURE...

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

Quick reference guide

Quick reference guide F IC2CX Series Quick reference guide INDEX GENERAL ADVICE 6 2 IC2 CX TABLE OF THE FEATURES 7 3 USER INTERFACE 8 3. DISPLAY CONFIGURATION 8 3.2 Icons Meaning 8 3.3 Meaning / Functionning of the bottom display

More information

30XA/30XW. PRO-DIALOG Control 30XA 30XW. Operation and maintenance instructions

30XA/30XW. PRO-DIALOG Control 30XA 30XW. Operation and maintenance instructions 30XA/30XW PRO-DIALOG Control 30XA 30XW Operation and maintenance instructions Contents 1 - SAFETY CONSIDERATIONS... 3 1.1 - General...3 1.2 - Avoid electrocution...3 2 - GENERAL DESCRIPTION...3 2.1 - General...3

More information

YST PRE START-UP CHECKLIST

YST PRE START-UP CHECKLIST STEAM TURBINE CENTRIFUGAL LIQUID CHILLERS START-UP CHECKLIST Supersedes 160.67-CL1 (1108) Form 160.67-CL1 (114) YST PRE START-UP CHECKLIST OFFICE LOCATION TECHNICIAN S NAME UNIT MODEL NUMBER YORK CONTRACT

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls User s manual Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING Table of Contents Introduction p. 3 Configuring the host

More information

5-stage compressor racks + 2 converter outputs

5-stage compressor racks + 2 converter outputs GB 1454H502 Ed.02 AKO-14545 AKO-14545-C 5-stage compressor racks + 2 converter outputs User Manual Contents Page 1.- Precautions...3 2.- Versions and part numbers...3 3.- Description...3 3.1.- Keypad functions...3

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

Standard Instructions For MC-2000/3000/4000 Controllers

Standard Instructions For MC-2000/3000/4000 Controllers Standard Instructions For MC-2000/3000/4000 Controllers Manual Update: 09/12/11 Version: 3.10 1 1 QUICK REFERENCE GUIDE 1.1 NAVIGATING THE DISPLAY Interacting with the AboveAir Technologies unit is accomplished

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

ULTRA-SAFE Explosion-proof Duct Heaters

ULTRA-SAFE Explosion-proof Duct Heaters Standard Construction Heat Exchanger has copper tubes with integral aluminum fins. Each unit undergoes hydrostatic testing at 350 psig, five times the pressure relief valve setting of 70 psig. Heat Transfer

More information

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors Product sheet SN1.402 Type CDR-AL CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors CDR-AL sensors are designed to detect carbon dioxide concentration and temperature in the room spaces. The units

More information

MT Alliance Refrigeration Technician s Manual

MT Alliance Refrigeration Technician s Manual MICRO THERMO TECHNOLOGIES MT Alliance Refrigeration Technician s Manual Document No. 71-MTA-1007-R3.1 V4.1 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in

More information

50AZ/UZ. for rooftop units. 50 Hz. Installation, operation and maintenance instructions

50AZ/UZ. for rooftop units. 50 Hz. Installation, operation and maintenance instructions 50AZ/UZ PRODIALOG for rooftop units Control 50 Hz Installation, operation and maintenance instructions 1 CONTENTS 1 SAFETY CONSIDERATIONS...3 1.1 General... 3 1.2 Avoid electrocution... 3 2 GENERAL DESCRIPTION...3

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

Standard air-conditioning units Manual version: /09/97

Standard air-conditioning units Manual version: /09/97 Application program for pco Standard air-conditioning units Manual version: 1.0-14/09/97 Program code: EPSTDECZUA Rif.: 36 EM CONTENTS: 1. INTRODUCTION TO THE REGULATION SYSTEM:...2 1.1. FUNCTIONS CARRIED

More information

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS CAREL CONTROLLER Programming Instructions The Carel controller has a two-level menu system for programming the operation of the case. Level 1 program settings are the most frequently accessed parameters.

More information

CAREL IR33+ CONTROLLER

CAREL IR33+ CONTROLLER CAREL IR33+ CONTROLLER Programming Instructions The Carel IR33+ controller has a two-level menu system for programming the operation of the case; Level 1 and Level 2 program settings. Unlike IR33, the

More information

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98 Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw Scroll Compressors Series: SCAEY-FC Leaflet: DE 98 Issue: 04/11 Supersedes: 12/10 Identification code Index Index... pag. 2 Identification code...»

More information

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option The MC4000 has 2 stages of cooling control available for each connected air conditioner. It is

More information

4Danfoss Turbocor. Increased Non Standard Part Load Value

4Danfoss Turbocor. Increased Non Standard Part Load Value MAKING MODERN LIVING POSSIBLE MCX Turbocor Compound Capacity Controller user manual Your entire chiller system is fully optimized with only one MCX controller Increased Non Standard Part Load Value of

More information

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller PB_ER65-DRW_ 202 ER65-DRW Controller Heating Applications Product Bulletin The controller is a digital device for domestic or residential heating units. It covers water and air heating applications. All-in-one

More information

SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER

SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER Models: HR58APA HR58APB Part of the Bard Free Cooling Unit System NOTE: LV1000 Controller is required for operation when multiple HR58AP* units

More information

INSTALLATION AND OPERATION MANUAL COOLING DISTRIBUTION UNIT

INSTALLATION AND OPERATION MANUAL COOLING DISTRIBUTION UNIT INSTALLATION AND OPERATION MANUAL COOLING DISTRIBUTION UNIT For use with Motivair Chilled Doors Motivair Corporation 85 Woodridge Drive Amherst, NY 14228 716-691-9222 (Ph) 716-691-9229 (fax) www.motivaircorp.com

More information

Owner s Guide and Installation Instructions

Owner s Guide and Installation Instructions Owner s Guide and Installation Instructions Rheem IQ TM Tariff Intelligent Controller Version 1.1 This Tariff Controller must be installed and serviced by a qualified person. Please leave this guide with

More information

Capacity controller for water chiller AK-CH 650

Capacity controller for water chiller AK-CH 650 Capacity controller for water chiller AK-CH 650 Menu operation via AKM Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

TE809-Ats Instructions Manual

TE809-Ats Instructions Manual TE809-Ats Instructions Manual Project: v2.0 PREFACE Thanking you for preference, TECNOELETTRA SRL hopes that the use of this equipment could be a reason of satisfaction. This manual is designed to put

More information

Capacity controller AK-PC 651

Capacity controller AK-PC 651 User Guide Capacity controller AK-PC 651 ADAP-KOOL Refrigeration Control System Introduction Application The controller is used for capacity regulation of compressors and condensers in small refrigeration

More information

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document CONTROLS MANUAL CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF Original document Contents 1. General description....5 2. Set-up... 6 2.1. micropc control board... 6 2.2. TCO user

More information

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature EVCO S.p.A. EV3B24 Data sheet ver. 1.0 Code 1043B24E104 Page 1 of 6 PT 12/15 EV3B24 Basic controller for low temperature bottle coolers, cabinets, refrigerated cabinets, tables and pizza counters, with

More information

Blue Box Epsilon Echos +

Blue Box Epsilon Echos + Blue Box Epsilon Echos + 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Packaged version in 5 sizes Nominal cooling capacity (A35;W7): 6 26 kw Nominal heating

More information

TYPE APPROVAL CERTIFICATE

TYPE APPROVAL CERTIFICATE TYPE APPROVAL CERTIFICATE Certificate No: TAA0000120 Revision No: 1 This is to certify: That the Programmable Controller with type designation(s) Fail-safe Programmable Logic Controller and Fail-safe Modules

More information

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173) Evco S.p.A. Code 104K204E05 page 1/5 EVK204 Digital controller for ventilated refrigerating units, with HACCP and Energy Saving functions version 1.05 GB ENGLISH 1 PREPARATIONS 1.1 Important Please read

More information

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N DPC-1 Programmable digital thermostat with communication Versión 2.0 Ref: N-27360 1108 Technical Information I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España, S.L. is participating in the

More information

ECH 985. Electronic controller for heat pumps used in residential hot water application

ECH 985. Electronic controller for heat pumps used in residential hot water application ECH 985 Electronic controller for heat pumps used in residential hot water application Introduction General Description ECH 985 is a heat pump for the following kinds of applications: water-water water-air

More information

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw Multifunction chillers for indoor installation. Cooling Capacity: 22 222 Heating Capacity: 25 236 Scroll compressors EC Plug Fans Plate type heat exchangers EER up to 3,12 COP up to 3,84 ESEER up to 4,01

More information

SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER

SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER Models: HR36APA HR36APB HR58APA HR58APB Part of the Bard Free Cooling Unit System NOTE: LV1000 Controller is required for operation when multiple

More information

General information. Technical data...2 General information...2. Description. Installation

General information. Technical data...2 General information...2. Description. Installation user manual Table of contents Technical data Technical data...2 General information...2 Installation...3 Navigation...3 First run...4 Main screen...6 Main menu...6 Time...7 Date...7 Calendar...7 Language...10

More information

Regulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL

Regulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL Regulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL WARNINGS SAFETY WARNINGS Read this manual carefully before installation and/or use of the equipment and keep it in an accessible place. The Manufacturer

More information