A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.
|
|
- Lorin Lewis
- 5 years ago
- Views:
Transcription
1 DIVISION 26 ELECTRICAL SECTION PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets required for auxiliary systems shall be specified under those Sections or as shown on the Drawings. C. All devices shall be ganged together where shown grouped on the Drawings. D. All normal power devices shall be the same color QUALITY ASSURANCE A. All equipment shall be UL listed and labeled and in accordance with applicable NEMA and ANSI Standards. B. All wiring devices and plates shall be furnished by one of the Manufacturers listed. No mixing of Manufacturer's products shall be permitted unless otherwise noted herein or on the Drawings SUBMITTALS A. For Review: 1. Product data sheets for wiring devices and plates B. To be included in Record and Information Manuals: 1. One (1) copy of each approved submittal 1.04 MANUFACTURERS A. Wiring Devices (except dimmers) and Plates 1. Cooper 2. Pass and Seymour 3. Hubbell 4. Leviton B. Dimmers and Plates 1. Lutron 2. Leviton C. Cover Assemblies 1. TayMac Corporation 2. Intermatic Inc. 3. Carlon Electrical Products 13-HC
2 D. Occupancy/Vacancy Sensors 1. Watt Stopper Inc. 2. Leviton 3. Sensorswitch SECTION E. Emergency Lighting Switch Bypass Device 1. Bodine 2. WattStopper PART 2 PRODUCTS 2.01 SWITCHES A. Switches shall conform to NEMA Heavy Duty Standards and shall be Specification Grade, general use AC quiet type, 20 Ampere, volt, back and side wired with white handles, unless noted otherwise. B. Pilot light switches shall be Specification Grade, general use AC quiet type, 20 Ampere, volt, back and side wired with clear handle DIMMERS A. LED Dimmers 1. Local manual dimmers for LED loads shall be solid state, thin profile, slide type with square law dimming, power failure memory, gangable with side sections intact. Color shall be white. There shall be no visible screws or fins from the front. Dimmers shall be single location or two location (using standard 3 way wiring) as noted on the Drawings. Dimmers shall be tested and approved for LED loads. B. Fluorescent Dimmers 1. Local manual dimmers shall be solid state, Lutron Nova T Hi-lume Series, white color. Control module shall be model NTF Series. 2. Dimming controls shall regulate lighting level via linear slide and have no side sections, screws, or other fasteners visible on the front of the unit. Dimming controls shall mount in a standard single-gang switch box and be gangable without derating capacity. 3. Light output shall be uniform throughout a controlled circuit of lamps, and be free from flicker and striations throughout the dimming range. Dimming shall be smooth and continuous from 100% to minimum light level. 4. The dimming control and the fixture pack/lamp combination shall be totally inaudible at 27 db room ambient throughout the dimming range. 5. The system shall be voltage regulated to minimize the effects of line voltage fluctuations. 6. The fixture pack combinations shall require standard bi-pin lamp sockets; special disconnect sockets shall not be required RECEPTACLES A. All convenience and power receptacles shall conform to NEMA Heavy Duty Standards and shall be Specification Grade, grounding type HC1-033
3 B. Hospital grade convenience duplex receptacles shall be 20 Ampere, 125 volt, back and side wired, 3 wire grounding, UL listed as complying with the requirements of NEC 517 and NEMA 5-20R configuration. C. Hospital grade ground-fault circuit-interrupting duplex receptacles shall be 20 Ampere, 125 volt "Feed-through" type, UL listed as comparing with the requirements of NEC 517, and NEMA 5-20R configuration. D. Hospital grade isolated ground receptacles shall be the same as convenience receptacles, except a solid barrier of insulation insulates the receptacle grounding circuit from the mounting strap. Color shall be orange. E. Hospital grade tamper resistant duplex receptacles shall be 20 Ampere, 125 volt, 3 wire grounding, UL listed as complying with the requirements of NEC 517 and NEMA 5-20R configuration. F. Weatherproof Duplex Receptacles shall be 20 Ampere, 125 volt or 250 volt, UL listed as weather resistant type per NEC 406. G. All receptacles shall be white, unless on emergency power or circuited to CP panels, in which case receptacles shall be red. H. Refer to the Drawings for specification of specialty receptacles PLATES A. Plates for flush devices in interior partitions shall be stainless steel. B. Plates for flush devices on concrete block walls shall match others but be "Jumbo" plates. C. Plates for voice/data communication boxes shall match wiring device plates in material, and be as specified in Section , "Voice/Data Communication Raceway System" or Section , "Voice/Data Communication Wiring System." D. Plates for devices in surface fittings shall be cadmium plated steel surface covers. Covers shall fit without overlap and have round corners. E. Plates for specialty receptacles required for auxiliary systems shall be satin stainless steel, furnished and specified with the device. F. Plates for future system outlets shall be blank plates matching device plates in quality and finish COVER ASSEMBLIES A. Wiring devices in wet locations shall have hinged, gasketed cast aluminum coverplates of a color matching adjacent wall finish. 13-HC
4 B. Wiring devices subject to wet locations while in use shall be provided with NEMA 3R cover assemblies UL listed for wet locations while in use. Cover assemblies shall use a vertically-lifting "canopy" to protect the wiring device(s). Cover assemblies shall be standard size, one (1) or two (2) gang as required with gaskets between the hinged cover and mounting plate/base to assure proper seal OCCUPANCY/VACANCY SENSORS A. Ceiling mounted low voltage 360 degree dual technology sensors shall contain both PIR and ultrasonic technologies, adjustable 15 second to 15 minute time delay, integrated adjustable light level sensor, adjustable sensitivities, LED indicator for both technologies, isolated relay, 24 VDC operable, 277 volt power pack, 1200 square feet - wide angle coverage. Watt Stopper DT-300. Provide minimum one (1) power pack for every room. B. Ceiling mounted corridor low voltage ultra sonic occupancy sensor shall be solid state, adjustable 15 seconds to 15 minute time delay LED indicator, 24 VDC operable, 277 volt power pack. Watt Stopper W2000H. Provide minimum one (1) power pack for every room. C. Ceiling mounted low voltage passive infrared occupancy sensor shall be user adjustable from 30 seconds to 30 minutes, sensitivity adjustment and LED indicator. Watt Stopper WPIR. Provide minimum one (1) power pack for every room. D. Wall mounted line voltage passive infrared occupancy sensor shall have adjustable 30 second to 30 minute time delay, manual on switches for bilevel lighting control, integrated adjustable light level sensor, adjustable sensitivity, LED indicator, 900 square feet degree coverage. Color shall be white. E. Wall mounted line voltage passive infrared vacancy sensor shall have adjustable 30 second to 30 minute time delay, manual on switches for bilevel lighting control, integrated adjustable light level sensor, adjustable sensitivity, LED indicator, 900 square feet degree coverage. Color shall be white. F. Power packs shall be dual voltage 120/277 volt primary with self contained transformer and 20 Ampere relay contacts. Watt Stopper BZ100. G. Slave packs shall be 277 volt primary with 120 volt, 20 Ampere relay contacts. Watt Stopper S-120/277E. PART 3 EXECUTION 3.01 APPLICATION A. Provide outlets as noted on the Drawings and herein described. B. Provide GFCI type outlets in all bathrooms, anywhere within 6 feet of sinks, lavatories, mop basins, in pool and pool equipment rooms, and in all exterior locations. C. Provide GFCI type outlets for all 120 volt devices located in food preparation rooms HC1-033
5 D. Provide tamper resistant hospital grade devices in all pediatric areas such as patient rooms, bathrooms, playrooms, daycare, activity rooms, etc., in accordance with NEC 517. E. Provide 30 ma GFCI type outlets for heat trace type or ice melting gutter heating tape INSTALLATION A. Install wiring devices as indicated, in compliance with the Manufacturer's written instructions, applicable requirements of NEC and NECA's "Standard of Installation," and in accordance with recognized industry practices to fulfill project requirements. B. Coordinate installation of wiring devices with other work, including painting, electrical box and wiring work, as necessary. C. Install wiring devices only in electrical boxes, which are clean, free from excess building materials, dirt and debris. D. All devices shall be connected to conductors using the side wiring terminal screw connections. Devices with voltages higher than 120 volt shall have two (2) layers of electrical tape applied over the exposed side terminals. Provide electrically continuous, tight grounding connections for wiring devices, as required by NEC Article 250. E. Delay installation of wiring devices and wall plates until after painting work is completed. Wiring devices may be installed prior to painting where protective plastic covers are used. All wiring devices and covers shall be clean and free of paint upon completion of work. F. Upon installation of wall plates and receptacles, advise other Contractors regarding proper and cautious use of convenience outlets. At time of Contract Completion, replace those items which have been damaged, including those burned and scored by faulty plugs. G. Install matching device plates on all devices. Devices shown grouped on the Drawings shall be ganged together with one plate. H. Ceiling mounted occupancy/vacancy sensors shall not be installed within 3 feet of an HVAC diffuser. Provide lens shields as required to prevent nuisance operation of occupancy sensors. Locate or aim sensors so they sense all areas of the room, but not out the doorway. I. Install engraved flush switch plates at all locations indicating function of switches for special applications and at every location where more than two switches are ganged together. Engraved switch plates shall have 1/8 inch black filled letters. J. Provide permanently installed barriers between switches ganged in outlet boxes where the voltage between adjacent switches exceeds 300 volts. K. Run neutral conductor to all dimmers. L. Receptacle plates shall be labeled with permanent marker on the back with panelboard and circuit number. M. All unused outlet boxes shall have blank coverplates installed. 13-HC
6 N. Wiring from ground-fault circuit-interrupters shall not occupy the same raceways with wiring from non-ground-fault interrupting type devices. O. Occupancy/vacancy sensors to be initially set at 75% maximum sensitivity and 5 minute time delay. Locate all occupancy sensor power packs and slave packs above lay-in ceiling at room entry location. P. Tamper resistant duplex receptacles shall have their coverplates attached with tamper proof screws. Q. Wiring devices shall be installed with grounding pin on top OCCUPANCY/VACANCY SENSOR OPERATION VERIFICATION A. Contractor shall verify proper operation of every occupancy sensor in building at completion of project. Provide appropriate masking on sensor where line-of-site extends out of room and causes nuisance operation when room is vacant SPARE PARTS A. Furnish spare occupancy sensors in a quantity of 5% of total (of each type) used in building (minimum of two (2) of each type). B. Division 26 Contractor shall include in his/her bid an allowance for furnishing and installing five (5) additional occupancy sensors of each type (with average length of conduit and wire) at completion of the project as directed by the Architect. If all are not used, remaining value shall be credited to the Owner or turned over to the Owner as additional spares per Owner's discretion. C. Two screwdrivers for any specialty fasteners used TESTING A. Prior to energizing circuitry, test wiring devices for electrical continuity, short circuits, and proper polarity connections. B. Verify that occupancy sensors are turning off lighting when spaces are unoccupied. Each sensor shall be tested for proper operation with HVAC system operational. END OF SECTION HC1-033
Job No A. Submit the following equipment, materials and products, including all fittings and accessories:
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationLIGHTING CONTROL DEVICES
SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More information1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND
More informationSECTION (16140) - WIRING DEVICES
SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -
More informationA. This Section includes the following lighting control devices:
SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationA. This Section includes the following lighting control devices:
Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationA. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire
More informationB. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationC. Pigtail: Short lead used to connect a device to a branch-circuit conductor.
SECTION 26 27 26 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationIN2 Lighting Control Devices
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationSECTION LIGHTING CONTROL DEVICES
SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationEmery County Senior Center Green River 06/07
SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS
SECTION 26 09 23 LIGHTING CONTROL DEVICES AND CONTROL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Remote control lighting relays. 2. Lighting contactors. 3. Switches. 4. Switch plates.
More informationSECTION LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS
SECTION 260923 LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Wall box mounted, wall/corner
More informationPrinceton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors
Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationLIGHTING CONTROLS
260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance
More informationSECTION ISOLATED POWER SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationSECTION LIGHTING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationDIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system
More informationTechnology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2
Passive Infrared Sensors (PIR) Using a patented fresnel lens which minimizes optical aberrations, each Legrand/Pass & Seymour PIR sensor breaks its coverage area into zones. Upon detecting an infrared
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,
More informationLeviton Combination Switch And Tamper Resistant Outlet Wiring Diagram
Leviton Combination Switch And Tamper Resistant Outlet Wiring Diagram Leviton SmartLockPro 15 Amp Tamper-Resistant Combination GFCI Duplex Outlet and Switch - White-R02-X7299-00W - The Home Depot. From
More informationEast Central College
SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationWINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016
SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,
More informationSECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.
SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT
More informationSECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationA. This Section provides requirements and specifications for wiring devices, wiring device accessories, and wiring device assemblies including:
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. This Section provides requirements and specifications for wiring devices, wiring device accessories, and wiring device assemblies including:
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationInstallation Instructions
DT-300 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On features Specifications Voltage................18-28VDC/VAC, half wave rectified AC Current Consumption...............................43mA
More informationSECTION ENCLOSED CONTROLLERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,
More informationSECTION LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationApplied Lighting Controls
Better Buildings By Design 2010 Applied Lighting Controls Steven Mesh, LC, IESNA Senior Lighting Program Coordinator Pacific Energy Center (Pacific Gas & Electric) 851 Howard Street, San Francisco, CA
More informationPART GENERAL 1.01 SECTION INCLUDES
Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,
More informationCS1200 WHT Pir Ceiling Mount Occupancy Sensor
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 Catalog Number Manufacturer Description Weight per unit Product Category Features Area Coverage Field of View Load Type
More information.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.
Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code
More informationSECTION EXTERIOR LIGHTING
SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26
More informationv3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature
DT-300 v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature Specifications Voltage...18-28VDC/VAC, half wave rectified AC Current Consumption...25
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSPECIFICATION SUBMITTAL
SPECIFICATION SUBMITTAL The dimmer with remote control One tap on to selected light level/off; two taps full bright;press & hold for 10-second fade-tooff Press rocker to adjust light level Front accessible
More informationProduct Specifications Dialog Room Controller* (*patent pending)
1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018
SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationMaestro 0 10 V Dimmer Sensor
NEW Maestro 0 10 V Dimmer Sensor Setting the new standard for 0 10 V control 0 10 V Dimmer Sinking control for 0 10 V fluorescent and LED fixtures Passive Infrared (PIR) Sensor Fine motion detection with
More informationCHAPTER 20 SERVICE EQUIPMENT
SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE
More informationTaxonomies, Classifications, and Categories Residential dimmers, motion sensors, controls, & photo cells Rotary dimmer, single-pole
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 C2000WH 2000W SP WH Rotary Lutron Catalog Number Manufacturer Description Weight per unit Product Category Features actuator
More informationSECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.
SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning
More informationVESICA LINEAR SUSPENDED VES L
PROJECT INFORMATION Project Name Catalog # VESICA LINEAR SUSPENDED APPLICATIONS Office Spaces Conference Rooms Municipal Facilities Medical Facilities Type Date Financial Institutions Retail Spaces Hospitality
More informationCeiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1
Occupancy and Vacancy Sensors ENERLITES offers a wide variety of lighting sensors. They are designed to bring convenience to your life and business while helping to reduce energy consumption in commercial,
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationSECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL
SECTION 265100 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4.
More informationRAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS
RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including
More informationEG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G
E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5
More informationSECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES
SECTION 26 50 00 INTERIOR AND EXTERIOR LIGHTING FIXTURES PART 1: GENERAL 1.1 WORK INCLUDED: A. Interior lighting fixtures and accessories B. Exterior lighting fixtures and accessories C. Emergency battery
More informationRESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS
RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationHMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3
HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.
More informationLS-CM Series. Overview. Applications. Features & Benefits. Datasheet. Ceiling mount occupancy sensors
Datasheet Ceiling mount occupancy sensors Overview The CM Series of ceiling mount occupancy sensors provide a range sensor solutions for applications with finished ceilings (e.g., ceiling tiles, sheetrock,
More informationDIVISION 16 ELECTRICAL
DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment
More informationPANELBOARDS & BUILDING DISTRIBUTION
262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic
More informationSensors and Detectors
12/12/2017 Sensors and Detectors - Clipsal by Schneider Electric Sensors and Detectors Add sensors and detectors to make an environment smarter and more efficient. C-Bus sensors and detectors allow environmental
More informationHi-lume 3D Overview. Fluorescent Dimming Ballasts Hi-lume 3D Architectural Dimming
Fluorescent Dimming s Hi-lume 3D Architectural Dimming Hi-lume 3D Overview 369-280f 1 03.08.12 Hi-lume 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements.
More informationSECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS
SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS PART - 1 GENERAL 1 SYSTEM DESCRIPTION A. The distributed lighting control system as specified herein shall be comprised
More informationWVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL
265100 INTERIOR LIGHTING PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. AHJ Authority Having
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)
SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill
More informationKINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION
SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationHi-lume 3D Overview. Fluorescent Dimming Ballasts
Fluorescent Dimming s Overview 1 architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of
More informationCADDY CORPORATION. Utility Distribution Systems
Food Service Equipment Air Systems Utility Distribution Systems page 1 of 2 Equipment Specifications General Specifications Caddy Corporation of America Energy Distribution and Management System, which
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationCommercial Grade Lighting Controls Collection
Product Specifications Commercial Grade Lighting Controls Collection VZI06-1L / VZ00R-1L VZ00R-10 VZE06 VZS15 / VZ0SR-1L VZ0SR-10 KEY PRODUCT FEATURES Efficient construction with consistent form factor,
More informationSECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationPSC-ID-x-CM Series Ceiling Mount Occupancy Sensor
TECHNICAL SPECIFICATIONS PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor Basic Features Line voltage version: 120-277VAC, 60Hz Low voltage version: 24VDC, requires separate class 2 power supply PIR sensor
More informationFR-A180 FR-A360. Occupancy detector. Use
5 488 Occupancy detector with daylight sensor Occupancy detector with integral daylight sensor for demand-based control of HVAC systems and lighting. Adjustable switch-on and switch-off delay Adjustable
More informationA. This Section includes transfer switches rated 600 V and less, including the following:
SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION NURSE CALL SYSTEM
NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system
More informationSENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification
This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing piping heat tracing for freeze prevention, domestic hot-water-temperature maintenance, and
More informationFROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR
FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR INNOVATION AND RELIABILITY THAT SPANS OVER 120 YEARS.
More informationCustom Duct Heaters. Special Applications
Special Applications Air Conditioning & Air Handling Units For more than 55 years, INDEECO has been supplying special heaters for use in air handling and air conditioning equipment (Figure 49). A wide
More informationB. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).
SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover
More informationTABLE OF CONTENTS. Division 16 Electrical
TABLE OF CONTENTS Division 16 Electrical 16050 Basic Electrical Materials and Methods 16110 Conduits, Raceways, Boxes, Fittings 16120 Conductors and Connectors 16140 Wiring Devices and Plates 16195 Identification
More informationVive PowPak Fixture Controls
Vive 369918g 1 03.12.18 The PowPak wireless fixture control is a radio-frequency (RF) device that controls either the Lutron EcoSystem or 0 10 V- electronic fluorescent ballasts and LED drivers (depending
More informationCIRRUS CEILING WALL GRAZER WITH REMOTE POWER
0.9" (2.3cm) 0.13" (0.3cm) CIRRUS WALL GRAZER (ACTUAL SIZE) 0.9" (2.3cm) CIRRUS WALL GRAZER LENS (ACTUAL SIZE) DESCRIPTION Cirrus Ceiling Wall Grazer is a linear LED fixture that offers direct light in
More informationCeiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions
Ceiling-Mounted Motion Detector 752/CD, 752/CP, 752/CU and 752/Cx180 Installation Instructions Contents 1.0 Description...3 1.1 Contents of the Box...3 2.0 Safety...4 3.0 Coverage Patterns...4 3.1 PIR
More informationSpecifications Occupancy/Vacancy Sensors CSI ASHRAE AIA Division 16 Section 16950
1 Specifications Occupancy/Vacancy Sensors CSI 26.09.23. ASHRAE 90.1-2010 AIA Division 16 Section 16950 1. PART 1 - General 1.1 Overview 1.1.1 Provide Occupancy/Vacancy sensors as shown on the plans and
More informationArrow Hart. Universal Dimmers and Sensors. Eaton s Arrow Hart. Reliable lighting control for commercial installations
Eaton s Arrow Hart Commercial lighting controls Eaton s Arrow Hart Universal Dimmers and Sensors Reliable lighting control for commercial installations Arrow Hart Eaton s s and dimmers are cost -effective
More informationSECTION ELECTRICAL IDENTIFICATION
SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationWireless Plug Load Control
General Specification Wireless Plug Load Control Model No.: PL20R & PLBPC Description:Enerlites Wireless Plug Load Controller is designed with simplicity, and helps to make plug load control requirements
More information