YO3 - YO4 / YL4 - YO5 / YL5
|
|
- Maud Logan
- 5 years ago
- Views:
Transcription
1 C l i f f o r d & S n e l l YO3IS YO4IS DIMENSIONS mm 81(3.2 ) 90(3.5 ) YO3 - YO4 / YL4 - YO5 / YL5 Intrinsically Safe Audible and Visual Alarms ATEX YO5IS YL4IS YL5IS 90(3.5 ) 81(3.2 ) MAIN FEATURES BASEEFA approved 2 stage alarm Rugged construction 32 selectable tones meeting international regulations Meets PFEER sound signals recommended by UKOOA Enclosure made from ABS flame retardant plastic Monitoring facility High sound output Stainless steel fixings Continuously rated Sound selection via DIL switch C Mounting: Via internal fixing holes E D 180(7.1 ) Model YO4 Models Y03 and YO5 Dim. For YO3 For YO5 Dim A 118 (4.7 ) 169 (6.7 ) Dim B 102 (4.0 ) 153 (6.0 ) Dim C 89 (3.5 ) 134 (5.3 ) Dim D 85 (3.4 ) 128 (5.0 ) Dim E 18 (0.7 ) 23 (0.9 ) Dim F 6 (0.2 ) 8 (0.3 ) CONFIGURATOR Unit Type Sounder YO3 A B C All dimensions quoted are approximate only and subject to change without notice as are technical features resulting from continual development and improvement. Sounder YO4 Sounder YO5 Combination Unit - YL4 European Approved Barriers (See application notes) Opto-coupled Temp Classification 57.5(2.3 ) Combination Unit - YL5 276(10.9 ) Model YL4IS 88(3.5 ) 88(3.5 ) 9(0.4 ) Model YL5 (dimensions not shown same as for YO5) Mounting: Via external lugs 2 x Ø F fixing holes M20 Cable mounting hole at Dim E TECHNICAL SPECIFICATION Relative humidity 40 deg C Weight: YO3is 0.40Kg YO4is 0.49Kg YO5is 0.85Kg For use in zones 0,1,2 IP55 rated YO3, YO4 and YL4 IP56 rated YO5 and YL5 Volume control fitted on T4 class only Operating voltage 12Vdc, 18Vdc or 24Vdc via barriers Sound output YO3/4 1 mtr Max YO5 1 mtr Max European models ISC & ISD Operating temp 25deg C to 40deg C II 1G Ex.ia IIC, T4 or T6 YO3,YO4 and YO5 II 1G Ex.ia IIC, T4 YL4 and YL5 Voltage upper limit controlled by barrier D7277 Operating & Installation Instructions YO3,YO4 and YO5 D7441 Operating & Installation Instructions I.S. Beacons The PFEER sound signals recommended by UKOOA are: General Alarm Sound Signal 15 Interrupted tone 1000 Hz PAPA Sound Signal 31 Reverse Sweep Hz Toxic Gas Sound signal 11 Continuous Tone 1000 Hz APPROVAL SPECIFICATION European Standards Baseefa Certificate No. BAS02ATEX1190X YO3, YO4 and YO5 Baseefa certificate No. Baseefa08ATEX0194X YL4 and YL5 EN :2006 EN :2007 Lens Colour Red Flame Base Colour Red Normal (YL4 only) White (YL4 only) T4 Only YL4 YO3/4 YL5 YO5 YL4 YL5 YO3 YO4 YO5 YO5/YL5 YO3/YO4/YL4 Clifford & Snell - Member of the R.STAHL Technology Group Page 1 D
2 THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE CARRYING OUT ANY WORK ON THESE INTRINSICALLY SAFE ALARMS AN ATEX APPROVED APPROPRIATE BARRIER MUST BE USED BEFORE CONNECT- ING THESE UNITS TO ANY POWER SUPPLY THESE ALARMS SHOULD ONLY BE INSTALLED BY COMPETENT PERSONNEL These alarms are ATEX approved. Certification No: Baseefa08ATEX0194X CE0158 EX II 1 G - EEx ia IIC T4 No alteration to the unit i.e. PCB or pressure unit is allowed. In case if the unit becomes faulty, It must be returned to the factory. This equipment is designed and manufactured to protect against other hazards as defined in paragraph of Annex II of the ATEX Directive 94/9/EC. SPECIAL CONDITION FOR SAFE USE: The apparatus has plastic enclosures which constitute a potential electrostatic hazard. The enclosures must be cleaned only with a damp cloth. Location: A suitable location must be selected with regard to the area to be covered by the sound signal and the beacon. The surface should be flat in the area of the fixings and the material suitable to carry the weight of the alarm. The case of the sounder shouldn t be put under any stress. Installation: The sounder and beacon must be independently wired with an individual ATEX approved appropriate barrier. Sounder Setup Sound Signal Selection: Sound signal selection is made by the setting of a PCB mounted DIL switch, located between the input and output terminals, as shown in diagram below: SOUND SELECTION SWITCH OPEN=0, CLOSE=1 VOLUME CONTROL Volume Control: A volume control giving approximately 15dB(A) adjustment is located besides the DIL switch on alarms with a T4 temperature classification. Page 2 D
3 SOUND SIGNALS, SOUND OUTPUT AND SUPPLY CURRENT First Sound Frequency Rept. Rate 2nd Stage Sound Output Input Stage Description Hz Signal Switches db(a) Current Signal ma 1 alt. two tone / Cont.tone In. tone / / Int.fast,rising fast siren rising cons /40/ iso 8201 evac as std fast whoop slow whoop reverse sweep siren NOTES: The above sound output levels, switching rate and current consumption values relate to a typical YL5 sounder connected to 24Vdc supply via a suitable ATEX approved 28 Volts 300 Ohm d.c shunt diode For other Intrinsically Safe models i.e. YL4 the sound output is typically reduced by 2dB(A). For the same sounder connected to an 18 Volts or 12 Volts d.c supply via a 22 Volts 150 Ohm barrier respectively, the sound output level and current consumption figures will be reduced by 1-2.5dB(A), mA for 18Volts and dB(A), mA for 12 Volts supplies. Connection of two sounders in parallel to a single 24 volts d.c supply will reduce the sound output level by approximatly 3dB(A) and an input voltage tolerance to 10%. The recommended PFEER sound signals by UKOOA are as follows: General Alarm 1000Hz at 1.0 second intervals Signal number 15 PAPA Reverse sweep Hz Signal number 31 Toxic Gas 1000Hz Continuous Note Signal number 12. Page 3 D
4 Sounder Connection Details and Line Monitoring An End Of Line (E.O.L) Resistor is required for Line Monitoring and it should be wire wound or metal film type with a resistance value of not less than 750 ohms, and power rating not less than 2 Watts, or not less than 4700 ohms, with power rating of not less than 0.4 Watts. The line monitoring facility allows the integrity of the line to the sounder to be monitored through the barrier to the control system fault detection and indication circuits. Two same type sounders can be connected in parallel. 1. Monitoring via Reverse Polarity Single Stage Alarm: 2nd Stage Alarm with a third wire: 2. Monitoring via Threshold (applied voltage <1V) 1st Stage: 2nd Stage: Page 4 D
5 Beacon Connection Details and Line Monitoring For a 24 Volts source, connect the unit via a suitable ATEX approved 28 Volts 300 Ohm dc shunt diode For an 18 Volts source, connect the unit via a suitable ATEX approved 22 Volts 150 Ohm dc shunt diode For a 12 Volt s source, connect the unit via a suitable ATEX approved 15 Volts 100 Ohm dc shunt diode Note: - Connection of two or more beacons in parallel to a single supply (via a suitable barrier) will slightly reduce the light output. Line Monitoring. An End Of Line Resistor (EOLR) is required for Line Monitoring. This should be of the wire wound or metal film type with a resistance value of not less than 750 Ohms and a power rating not less than 2 Watts or not less than 4700 Ohms with a power rating not less than 0.4 Watts. The Line Monitoring facility allows the integrity of the line to the beacon to be monitored through the barrier to the control system fault detection and indication circuits. Two or more, same type, beacons can be connected in parallel. FIRST UNIT SECOND UNIT FINAL UNIT 0V Ve EOLR ATEX approved BARRIER INTERMEDATE UNITS A GROUP OF R. STAHL, WALDENBURG, GERMANY R. STAHL (P) LTD., 2/397, MOOKAMBIKA NAGAR KATTUPAKKAM, CHENNAI , INDIA TEL: / FAX: web: Page 5 D
OPERATING AND INSTALLATION
A division of Signature Ind. Ltd YO6 YL6 V6 DIMENSIONS (mm) 280mm 11 OPERATING AND INSTALLATION INSTRUCTIONS FOR (UL & ATEX) YODALEX FLAMEPROOF AUDIBLE AND VISUAL ALARMS D7292 OPERATING CLASS 1 DIVISION
More informationYodalarm. Sounders. Pg Y03 Y04/YL4 Y05/YL5 Y08/YL8/Y08 SUPER/ YL8 SUPER V4 V6/Y06/YL6 Carillon
Sounders Y03 Y04/YL4 Y05/YL5 Y08/YL8/Y08 SUPER/ YL8 SUPER V4 V6/Y06/YL6 Carillon Pg 185 186 187 188 189 190 191 Y03 1YA030207 1YA030203 1YA030205 YL030/24 A1:2002 YL030110/230 UL464 C22.2 No. M1983 BS
More information4) Intrinsic Safety Certification
INSTRUCTION MANUAL Minialert Intrinsically Safe Round Combined Unit Section Volume Control Tone Generator S2 S3 Tone Selection Switches Fig 1 Simplified block diagram The combined unit is CE marked for
More informationDB5 Intrinsically Safe Sounder Type DB-5
Operating Instructions RTK Instruments Limited DB5 Intrinsically Safe Sounder Type DB-5 Description The DB5 Sounder is a strong, lightweight warning sounder, CENELEC certified to Ex II 1G EExia IIC T4
More informationE2S Datasheet v10a. The IS-mA1 is suitable for all intrinsically safe signalling applications including fire, security and process control.
E2S Datasheet 1.2.1 v10a ISmA1 ISminialarm The ISmA1 is a compact, 100dB(A) alarm sounder. Approvals include ATEX, IECEx and GOSTR for Zone 0 applications and FM approval for Class I Division 1 and Class
More informationE2S Datasheet v10a
E2S Datasheet 1.2.3 v10a ISmC1 ISminialert The ISmC1 is a compact combined 100dB(A) alarm sounder and L.E.D. beacon only one Zener barrier or galvanic isolator required to run both sounder & beacon or
More informationINSTRUCTION & SERVICE MANUAL
INSTRUCTION & SERVICE MANUAL D2xC1 ALARM HORN AND STROBE For Use In Hazardous Locations 3) Ratings and Markings 3.1 ATEX / IECEx certification The D2xC1 Alarm Horn and Strobe complies with the following
More informationINSTRUCTION MANUAL (ATEX)
INSTRUCTION MANUAL (ATEX) ISmA1M Minialarm Intrinsically Safe Round ISmA1M Volume Control Tone Generator S3 Tone Selection Switches Fig 1 Simplified block diagram The ISmA1M sounder is CE marked for compliance
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MANUAL (ATEX / IECEx) BExS110D and BExS110D-R Sounder For use in Flammable Gas and Dust Atmospheres BExS110D BExS110D-R 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT
More informationExplosion Proof Combination Signal db (A) / 5 Joule
Explosion Proof Combination Signal - Operating instructions Additional languages www.r-stahl.com General information Contents 1 General information...2 1.1 Manufacturer...2 1.2 Information regarding the
More informationINSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon
INSTRUCTION MANUAL Minialite Intrinsically Safe Round LED This instruction sheet describes installations which conform to EN60079:Part14:2008 Electrical Installation in Hazardous Areas. When designing
More informationGRP Flameproof Combination Signal db(a) / 5 Joule Series YL6S
www.stahl.de > Corrosion resistant omnidirectional high output sounder > Integrated Ex d enclosure > Extreme temperature range > 3 stage alarm with independant tone selection for V DC systems > IP66 IP67
More informationMANUAL CALL POINT Intrinsically Safe (EExia), Weatherproof BG3 Range ATEX
MAUAL CALL POIT Intrinsically Safe (EExia), Weatherproof BG3 Range ATEX ow Chinese Certified Introduction This manual fire alarm call point is designed in accordance with the latest draft European Call
More informationINSTRUCTION & SERVICE MANUAL
INSTRUCTION & SERVICE MANUAL D1xC COMBINED RADIAL HORNS & STROBES For Use In Hazardous Locations - Gas 3) Ratings and Markings The D1xC1 and D1xC2 combined alarm horns and strobes comply with the following
More informationProduct Manual Standard Asserta Sounder Range
Product Manual Standard Asserta Sounder Range Document Structure: Steve Martin - 18/09/08 Technical Information: Chris Anderson - 14/10/08 Cooper Fulleon Ltd Llantarnam Park Cwmbran South Wales NP44 3AW
More informationVTG-32E Spatial Sounder 24Vdc EN54 part 3 approved
The VTG32E family of sounders have been designed to cover a wide spectrum of applications. The 24 volt EN543 approved version is for use with conventional fire alarm systems including SAVWIRE two wire
More informationED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR
ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk
More informationINSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres
INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres 1) Introduction The BExBG05D-SIL is a flameproof beacon which is certified
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MANUAL (ATEX / IECEx) BExTS110D Flameproof Sontel 1) Introduction The BExTS110D is a flameproof Sontel telephone sounder which is certified to the meet the requirements of the ATEX directive
More informationDICTATOR Hold-Open Systems for Hazardous Areas
DICTATOR for Hazardous Areas Products to be used in hazardous areas obviously have to meet special demands. The European ATEX directives (first the EN 94/9/EG and then the directive 2014/34/ EU) brought
More informationVIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm
VIMPEX Sounder Range Fire Alarms Banshee Electronic Sounders FlashDome EN 54-3 Evacuation Audible Alarm BS 5839-1 Beacons The range of sounders, beacons, sounder beacons and accessories represents the
More informationDSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor
DSF xx15.xx xhv Ex-Atex Product ID Type # Product # Drawing # DSF 1215.01 SHV Ex-atex (5m) 304Z-05197 113216 DSF 1415.01 AHV Ex-atex S148 304Z-05256 113351 DSF 1615.01 SHV Ex-atex (5m) 304Z-05196 113214
More informationINSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas
INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas UL 1203 CSA C22.2 NO. 30-M1986 The D1xS1 and D1xS2 Alarm Horns also comply with the following standards for signaling
More informationDB1 Range - HORNS - Up to 103 db(a)
DB1 Range - HORNS - Up to 103 db(a) Explosion-proof, Weatherproof Features UL listed Class I, Div. 1, Groups C & D. Class 1, Zone 1. ATEX approved. NEMA 4x, IP66. Certified temperature: 13 F to +158 F.
More informationExplosion Proof Combination Signal db (A) / 5 Joule Series YL60
www.stahl.de Explosion Proof Combination Signal - 110 db (A) / 5 Joule > Omnidirectional high output sounder 110 db (A) / 1 m > 5 Joule xenon strobe > 2 stage alarm, independently selectable 2nd stage
More informationINSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder
INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder 1) Introduction The Appello tone and speech annunciation sounder has three different styles in AC and DC. A105NAPPX
More informationFIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF
DETECTOR TYPE ED816 ZE 1 ZE 2 ZE 3 ZE 4 ZE 5 ZE 6 ZE 7 S ZE 8 CIRCUIT 1 ZE 9 ZE 10 ZE 11 ZE 12 ZE 13 ZE 14 ZE 15 ZE 16 CIRCUIT 1 POWER POWER SUPPLY GENERAL MENT DC GENERAL SYSTEM ALARM DELAYED ALARM RESOUND
More informationINSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder
AUTHORIZED DISTRIBUTOR ControlSystemsUSA.com Houston, Texas USA sales@controlsystemsusa.com 832-615-3588 INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder
More informationTX6831 Data Sheet. Features. Benefits
Audio/Visual Alarm Combined audible and visual alarm signalling, for use with sensors and monitoring systems Environments: Mining Tunnelling Machine monitoring Features TX6831 For use with sensors and
More informationTechnical Manual for the Horn - DB1PUL DB1HP UL
Technical Manual for the Horn - DB1PUL DB1HP UL Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or
More informationFire Signalling. Signalling Solutions
Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.
More informationTechnical Manual for the Horn DB1P UL DB1HP UL
Technical Manual for the Horn DB1P UL DB1HP UL Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or expense
More informationMAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL
MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...
More informationPATROL SOUNDERS 110/120 db(a) PA 10 / PA 20
PRODUCTS AUDIBLE SIGNALING DEVICES PATROL SOUNDERS 110/120 db(a) PA 10 / PA 20 PATROL the new generation of sounders. Three dimensional innovation. Safe; an incorrect installation is virtually impossible.
More informationINSTRUCTION MANUAL (ATEX/IECEx/SIL2)
INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExS110D-SIL Flameproof Sounders For use in Flammable Gas Atmospheres BExS110D-SIL 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN
More informationPATROL SOUNDERS 100/105 db(a) PA 1 / PA 5
PRODUCTS AUDIBLE SIGNALING DEVICES PATROL SOUNDERS 100/105 db(a) PA 1 / PA 5 PATROL the new generation of sounders. Three dimensional innovation. Safe; an incorrect installation is virtually impossible.
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MANUAL (ATEX / IECEx) BExBG15E and BExBG10E Flameproof / Increased Safety Xenon Beacons For use in Flammable Gas and Dust Atmospheres 1) Introduction The BExBG15E and BExBG10E beacons are flameproof
More informationFire Signalling. Signalling Solutions
Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.
More informationATEX. IECEx. culs GOST-R. VdS
1. Hazardous Area Signalling 1.11 Intrinsic safety: Visual 1.12 Intrinsic safety: Audible 1.13 Intrinsic safety: Combination 1.14 Intrinsic safety: Manual Call Points 1.21 Explosion / flame proof: Visual
More informationL+T GASETECHNIK. Klöpper-Waldmann GmbH & Co. K G. Alarm unit LSG4
Areas of application The LSG4 alarm unit is used for monitoring industrial systems, e.g. in the following areas: Alarm and hazard stati in production e.g. for monitoring temperature and pressure in reactors
More informationstandards: standards:
INSTRUCTION MANUAL D2xB1LD2 LED Beacons For use in Hazardous Locations 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING HAZARD
More informationX10 Mini, Midi & Maxi
Industrial Sounder, Sounder Beacon X0 Mini, Midi & Maxi Installation Manual EAT X0 Mini, Midi & Maxi Installation Manual (90F) Contents Overview and purpose... Product assembly... Select wiring method......
More informationCONTENTS NBM-06 Bell (6") Page 1
CONTENTS NBM-06 Bell (6") - - - Page 1 NBM-08 Bell (8") - - - Page 1 LFB-24 Sounder Banshee - Page 2 VCT--NT Base Version Sounder Page 2 VCT--NT Wall Version Sounder Page 2 VRS1-R or W Bedhead Sounder
More informationINSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations
INSTRUCTION MANUAL E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING
More informationSOUNDERS Up to 113 db(a) EExd, Weatherproof DB1 Range
SOUNDERS Up to 113 db(a) EExd, Weatherproof DB1 Range ATEX GOST Now UL & GOST Listed Introduction This range of light weight, flameproof Sounders has been designed with a high weatherproof rating to cope
More information14300 MAINS SEPARATOR ALARM MANUAL
Conder Environmental Solutions 14300 MAINS SEPARATOR ALARM MANUAL Separator and Alarm provided by: Alarm Installation, Commissioning & Servicing Support Please contact: www.envirotank.com.au www.envirotank.co.nz
More informationMultiple Status Indicators Series MEXE, MS25, MS35, MS45, MS55
www.stahl.de > Pre-wi ready-to-use multi-signalling unit > Corrosion resistant > Suitable for offshore / onshore harsh environments > Incorporates the FX15 GRP beacon YA90 for visual audible notification
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MNUL (TEX / IECEx) ExG21D Flameproof Xenon eacon For use in Flammable Gas and Dust tmospheres 1) Introduction The ExG21D is a flameproof beacon certified to meet the requirements of the TEX
More informationFire Signalling. Signalling Solutions
Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.
More informationNexus 120 DC Sounder Nexus 120 DC Sounder with 5J Xenon Beacon Nexus 120 DC Sounder with LED Beacon
Nexus 120 DC Sounder Nexus 120 DC Sounder with 5J Xenon Beacon Nexus 120 DC Sounder with LED Beacon Technical Specification 1. Sounder Supply Voltage Range 10-60V DC Current 0.12 0.55A* (Typ. 0.5A @ 24V,
More informationWeb: LGM Products Ltd.
Hazardous Area Product Brochure Email: sales@lgmproducts.com Web: www.lgmproducts.com 2015 LGM Products Ltd. About us Formed in 1988, we are proud to be an independent service orientated company. LGM Products
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 50 mm non-flush Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 50 mm Installation non-flush Output polarity NAMUR
More informationPRODUCT ATEX IECEx UL ULC CSA Inmetro CUTR CQST ABS SIL IP Rating Page DB7 66 / DB12 66 / DB15 66 / DB1 DB3 DB3V DB3B
Horns and Sounders The MEDC range of horns and sounders are suitable for a wide variety of applications and feature a variety of tone settings and traditional bells. Sounders and Horns are used to warn
More informationExcel-EN Conventional Fire Control Panel
Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs
More informationRT FLOW RATE TOTALISER
Universal Mount Series RT FLOW RATE TOTALISER I N S T R U C T I O N M A N U A L S U P P L E M E N T for I N T R I N S I C A L L Y S A F E F L O W R A T E T O T A L I S E R ATEX & IECEx approvals The name
More informationBT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL
BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4
More informationZIOU/230 - MAINS IO INSTRUCTION MANUAL
Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel
More informationXP95 Sounder VAD Base
PP2478/2016/Issue 5 XP95 Sounder VAD Base FUNC TION The XP95 Sounder Visual Alarm Device (VAD) Bases incorporates a standard mouting base with a loop-powered sounder VAD. It is used to signal a fire alarm
More informationAP200 SERIES INTELLIGENT ALARM DEVICES
Tech Data Sheet D0170GB Fire Detection /01 AP00 SERIES INTELLIGENT ALARM DEVICES Intelligent AP00 series alarm devices for FX fire detection system The intelligent AP00 series alarm devices are used in
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm non-flush Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 15 mm Installation non-flush Assured operating distance s a 0...
More informationFlameproof Manual Call Points
Operating instructions Additional languages www.r-stahl.com CS & Clifford & Snell Contents General Information.... Manufacturer.... Information regarding the operating instructions.... Further documents....
More informationConventional Fire Detection
SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct
More informationAnnubar Flowmeter Series
Reference Manual Appendix B Approvals Annubar Flowmeter Series Hazardous Locations Installations.................. page B-1 Rosemount 3051SFA Product Certifications.......... page B-1 Rosemount 3095MFA
More informationDSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor
Product ID Type # Product # Drawing # DSF 1210.00 SHV Ex-atex (2m) 374Z-05066 110428F1 DSF 1210.00 SHV Ex-atex (5m) 374Z-05176 110428F1 DSF 1210.00 SHV Ex-atex (10m) 374Z-05590 110428F1 DSF 1410.00 SHV
More informationSegnalatori acustici AW-ETH12MD AW-ETH12MD audible warning
Segnalatori acustici audible warning devices I segnalatori acustici, sono utilizzati in ambienti a basso rumore di fondo, ove sia presente una potenziale atmosfera esplosiva. Sono dotati di circuito a
More informationSegnalatori acustici AW-ETH20MD Audible warning devices
Segnalatori acustici Audible warning devices I segnalatori acustici sono utilizzati in ambienti aperti ad alto rumore di fondo, ove sia presente una potenziale atmosfera esplosiva. Sono dotati di circuito
More informationMANUAL Overflow sensor NVF-104/34-PF
PROCESS AUTOMATION MANUAL Overflow sensor NVF-104/34-PF ISO9001 0102 Overflow sensor NVF-104/34-PF With regard to the supply of products, the current issue of the following document is applicable: The
More informationEmerald 3000 MK3 GJD010 Lighting Controller
Emerald 3000 MK3 GJD010 Lighting Controller SPECIFICATION SUPPLY: 230 Vac 50Hz via ELCB/MCB - unit fused at 13A 12VDC@ 100mA: GJD Opal XL (6mA) or Elite Detectors (10mA) Optional external 12VDC piezo sounder
More informationSignaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.
Signaling Devices Acoustic Signaling Devices 28 Optical Signaling Devices 30 26 Signaling Devices Acoustic Signaling Devices Acoustic Signaling Devices MSS300-SA SG 200 DS 10 LSN/GLT GLT GLT GLT Operating
More informationRTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ
Operating Instructions RTK Instruments Limited Telephone: 44 (0)1423 580500 Facsimile: 44 (0)1423 580501 DA135 Intrinsically Safe LED Beacon Introduction This manual provides the information necessary
More informationEN54-23 Beacons & Sounder Beacons
EN54-23 Beacons & Sounder Beacons In a fire, everyone matters. Sonos Pulse and Nexus Pulse fire beacons ensure that all personnel are notified of fire emergencies. With Pulse Alert Technology, buildings
More informationTechnical Data. General specifications. Rated operating distance s n 5 mm
0102 Model Number Features 5 mm non-flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance s n 5 mm
More informationUser manual. Explosion-safe window air conditioning system Type series AR-054. II 3 G Ex ic nac h IIC T3 Gc
User manual Explosion-safe window air conditioning system Type series AR-054 II 3 G Ex ic nac h IIC T3 Gc 1. Safety Instructions The window air conditioning series AR-054 is an explosion-safe product suitable
More informationPower Supply Display Module PSDM. Installation and Operation Manual
Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious
More informationSnifter ATEX22 VERSION. User Manual. Distributor
Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5
More informationIGD. O p e r a t i o n a n d M a i n t e n a n c e V International Gas Detectors. Triton House Crosby Street Stockport SK2 6SH England
TOC-70 SERIES 2-WIRE ANNUNCIATORS O p e r a t i o n a n d M a i n t e n a n c e V 1. 3 0 OLIVER Triton House Crosby Street Stockport SK2 6SH England IGD Tel: +44 (0)161 483 141 Fax: +44 (0) 161 484 234
More informationINSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder
INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder 1) Introduction The Appello tone and speech annunciation sounder has three different styles in AC and DC. A105NAPPX
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
0102 Model Number Features 5 mm non-flush Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 5 mm Installation non-flush
More informationFlameproof Manual Call Points Series MCP
> Light weight glass reinforced polyester (GRP) Ex d enclosure > Weather resistant high performance red paint finish as standard > Break glass version supplied with test key > Push button version supplied
More informationAP200 SERIES INTELLIGENT ALARM DEVICES
Tech Data Sheet D017GB1 Fire Detection /01 AP00 SERIES INTELLIGENT ALARM DEVICES Intelligent AP00 series alarm devices for FX NET fire detection system The intelligent AP00 series alarm devices are used
More informationEX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN TECHNICAL MANUAL
PRODUCT NAME: SD-100-1- WEATHER-PROOF SOUNDER/HORN DOC NO.: EX-TECH SIGNALLING SAS-12-SD100-1-TM REV03 WEATHERPROOF SOUNDER/HORN IP66 SD-100 SERIES EX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN
More informationTank Gauging System Special Safety Instruction
Tank Gauging System www.rosemount-tg.com Rosemount TankRadar REX Table of Contents Contents SPECIAL SAFETY INSTRUCTION........................ 1-1 1. GENERAL REQUIREMENTS....................... 1-2 1.1
More informationAnalogue addressable devices
Apollo XP95 Analogue addressable devices from Channel Safety Systems Apollo XP95 Analogue addressable devices The XP95 range of analogue addressable fire detectors is advanced in design, improved in performance
More informationIntellia Sounder Bases and Sounder Beacon Bases
Intellia Bases and Beacon Bases The Base and Beacon Base are a local-area alarm devices designed for indoor use. They can be connected only to detection systems using Intellia detectors and FX control
More informationRE-PR3-E-27 3-Phase Panel Mount 27kW
Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting
More informationCrowcon Gasmaster. 1 to 4 channel gas detection control panel. Installation, Operation and Maintenance Manual
1 to 4 channel gas detection control panel Installation, Operation and Maintenance Manual M070010 Issue 2 October 2014 The equipment described in this manual may have mains voltages applied to it. Ensure
More informationINSTRUCTION MANUAL A131 High Level Audible Warning System
Weight: 1.5kg single AC unit 2.9kg four way AC unit Marking: 3) Installation Requirements 1) Introduction The A131 high level audible warning system is an effective wide area warning alarm system and can
More informationSOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon
SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon alarm devices For fire detector and extinguishing systems Loud alarm signal clearly recognizable as a danger signal even in noisy environments
More informationWARNING FIRE DOOR CLOSING
PRODUCT INSTRUCTIS Stock Code: 088 FCP - Lite Floats Road, Wythenshawe Manchester, M 9WB Tel: + (0) 9 Fax: + (0) 9 Doc No PI - 88 Iss:.0 WARNING FIRE DOOR CLOSING STOP Contents ) Blank ) Features and
More informationFire & Security Products. Siemens Building Technologies Group
Fire & Security Products Siemens Building Technologies Group . 1 Brief overview.................................................... 1 1.1 Characteristics....................................................
More informationINSTRUCTION MANUAL. D2xB1XH1 & D2xB1XH2 Xenon Beacons For use in Hazardous Locations
INSTRUCTION MANUAL D2xB1XH1 & D2xB1XH2 Xenon Beacons For use in Hazardous Locations synchronization requirements of UL1971 & UL1638 / CAN/ULCS526. 2.2 NEC & CEC Class / Division Ratings for US / Canada
More information1510 Side Mounted Level Switch
1510 Side Mounted Level Switch General Instructions The SOR 1510 Level Switch mounts into the side of a vessel. Electric switching action is provided by the float moving a magnet into the field of a hermetically
More informationIndustrial Signalling
Industrial Signalling Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place. Product Range
More informationUniversal Tank Alarm Type Installation, Operation & Maintenance
Universal Tank Alarm Type 14400 Installation, Operation & Maintenance Universal Tank Alarm Type 14400 Contents Declaration of Conformity 3 IMPORTANT 3 General Description 4 General Operation 4 Installation
More informationEmergi-Lite Orbis detectors
Emergi-Lite Orbis detectors Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire systems. Non-addressable (conventional) smoke and heat sensors respond
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 4 mm
0102 Model Number Features 4 mm non-flush Accessories BF 12 Mounting flange, 12 mm Technical Data specifications Switching element function NAMUR, NO Rated operating distance s n 4 mm Installation non-flush
More informationGas leak detectors. We measure it. For a quick overview. testo testo testo testo gas detector testo 316-Ex.
Gas leak detectors For a quick overview testo 317-2 testo 316-1 testo 316-2 testo gas detector testo 316-Ex CH 4 C 3 H 2 Gas leak testing Over and over again, devastating explosions and fires are caused
More informationSOUNDER CONTROL MODULE SCM-AS4
1 of 9 INTRODUCTION DESCRIPTION The forms part of the Nittan (UK)'s SENSORTEC-ANALOGUE range of Analogue Addressable Devices. This module is designed to control a group of bells or sounders from the detection
More informationInstallation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels
CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power
More informationBattery Powered Separator Alarm Type Standalone Unit. Installation, Operation & Maintenance
Battery Powered Separator Alarm Type 17200 Standalone Unit Installation, Operation & Maintenance Battery Powered Separator Alarm Type 17200 Contents Declaration of Conformity 3 IMPORTANT 3 General Description
More information