/5121/5122 TrueAlert Power Supply Installation Instructions
|
|
- Myles Edwards
- 5 years ago
- Views:
Transcription
1 /5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies (TPS). These supplies provide auxiliary power, a battery charger, and three Signaling Line Circuits (SLC). Each of which provides control and power to the full range of TrueAlert appliances. The TrueAlert power supplies are identical to each other with the following exceptions: Domestic (US) version, requires a 120 VAC power source Canadian version, requires 120 VAC power source and provides battery cutout option. After installing a , refer to Enabling Low Battery Cutout Option in the ES Panel Programmer s Manual ( ) for information on enabling this option International version, uses a 220/240 VAC power source. If you are wiring Class A circuits, you need to install a Class A Adapter Card onto the TrueAlert Power Supply before installing the power supply. Refer to Document # for more information. This product is compatible with the 4100U and 4100ES Fire Alarm Control Panel (FACP). IMANT: Verify FACP System Programmer, Executive, and Slave Software compatibility when installing, or replacing system components. Refer to the Technical Support Information and Downloads website for compatibility information. In this Publication This publication discusses the following topics: Topic See Page # Cautions and Warnings 2 Introduction to the TPS 3 Mounting 6 Configuring the TPS 7 Power Distribution Module/Battery Connections 9 Compatible TrueAlert Devices 10 General Wiring Guidelines 12 Wiring Class A Circuits 14 Wiring Class B Circuits 17 Wiring AUX Power 20 Troubleshooting SimplexGrinnell LP. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice. Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license Rev. K
2 Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier. ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier. STATIC HAZARD - Static electricity can damage components. Handle as follows: Ground yourself before opening or installing. Prior to installation, keep components wrapped in anti-static material at all times. EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device. FCC RULES AND REGULATIONS PART 15 - This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. 2
3 Introduction to the TPS Overview The features of the TrueAlert Power Supply are: Three Signaling Line Circuits. The TPS provides uninterruptible power and control to three separate channels of TrueAlert addressable notification appliances. Each channel is referred to as a Signaling Line Circuit (SLC) and is power limited, power limited is defined in NFPA 70 (National Electric Code). The SLCs can be either Class B (Style 4) or Class A (Style 6). Class A requires the installation of a Class A adapter board. All SLCs are monitored for short and open circuits. 24VDC AUX Power. Provides up to 2 A of 24 VDC auxiliary power for use by the option cards. Internal Battery Charger. Charges up to 50 Ah (ULC-S527) or 110 Ah (UL-864 Listing) batteries connected to the power supply. The charger circuitry provides status monitoring of battery connection, input power, and Earth faults. SLC 1 SLC 2 SLC 3 Trouble Scroll Push Button LEDs 1, 2, and 3. Each Corresponds to an SLC DIP Switches SW1 to SW8 Battery Terminals LEDs A to E AUX Power Earth Fault Jumper Figure 1. Overview of TPS Continued on next page 3
4 Introduction to the TPS, Continued Additional Features Full TrueAlert Operation. TrueAlert addressable notification appliances are individually addressed and receive power, supervision, and control signals over the SLC. Horns sound with selectable high or low output, using a temporal, march time (60 or 120 beats per minute), or continuous pattern. Horns are controlled separately from visible appliances installed on the same two-wire circuit. (Combination speaker/strobe TrueAlert appliances receive audible control from separate audio circuit wiring.) Extensive Diagnostic Capabilities. LEDs on the TPS flash codes that identify the nature of trouble conditions. The TPS also monitors for short and open circuits and positive and negative Earth fault status. Depleted Battery Cutout (Canadian Version Only). When AC Power fails, the Depleted Battery Cutout feature disconnects a battery from the panel when its voltage is approximately 18 VDC. Visual Synchronization. A maximum of 46 MultiCandela addressable visuals may be synchronized per SLC. All SLCs are synchronized across a TPS. All TPSs are synchronized across the FACP. Input/Output/Battery Specifications The following table summarizes the AC Input, DC Output, and Battery Charger specifications of the TPS. Table 1. AC Input, DC Output, Battery Charger Specifications / Aux Power and Each SLC Input Voltage Range Output Voltage High Voltage Output Output Current Limit 4 A Maximum Hz AC Input Specifications 2 A Maximum 220/230/ or 60 Hz DC Output Specifications Minimum: 19 VDC Maximum: 32 VDC Ripple: 2 VDC, peak to full load (9A) Battery Charger Specifications VDC 27.4 VDC ± F (20 C), temperature compensated at 24 mv / deg. C A 1.4 A (For Ah battery) 3.3 A (Default for Ah battery [Canada]; Ah battery [United States]) Continued on next page 4
5 Introduction to the TPS, Continued TPS Current Consumption Table 2 lists the battery standby requirements for the TPS. The voltage is 24 VDC, which is the rated battery voltage for lead-acid type batteries. Table 2. Battery Standby Conditions Standby no alarms, SLCs normal Standby 3 SLCs ON Class A option (Standby or Alarm) Current 88 ma 100 ma 10 ma Environmental Requirements The TPS operates normally within the following temperature range: 32 F (0 C) and 120 F (49 C). Humidity: 90 F (32 C) degrees at 93% Relative Humidity (non-condensing). Note: Add auxiliary and card power currents to standby current. For each TrueAlert appliance, add 0.2 ma standby current. The maximum auxiliary current is 2A. The maximum card power is 2A. Deduct card power and auxiliary currents from 9A total power supply capacity. Maximum power supply alarm capacity is 9A. 5
6 Mounting Overview The TPS mounts onto the right side of an expansion box, and connects to the Power Distribution Interface (PDI). Mounting Procedure 1. Slide the two tabs on the bottom of the TPS into the rightmost two slots on the expansion bay. 2. Push the TPS assembly against the back of the expansion bay. a. Connect to the PDI, as shown below. b. Three PDI headers, shown below, must be pushed through the three open slots in the back of the TPS assembly. c. Align the two screw holes at the top of the TPS assembly with the holes in the cabinet backplane. 3. Use two #6 torx screws to secure the assembly to the expansion bay. Figure 2. TPS Mounting 6
7 Configuring the TPS Setting Earth Fault Enable/Disable Jumper The Earth Fault Enable/Disable jumper allows you to enable or disable positive and negative Earth Fault detection. Place the jumper block on Pins 1 and 2 to enable Earth fault detection. Place the jumper block on Pins 2 and 3 to disable Earth fault detection. See below. FigureTag FD Disabled Enabled Note: When one or more TPS unit resides in a system sharing a common 0V with any other type power supply (SPS/RPS/XPS), jumper only one of the TPS units to enable Earth Fault Detection. All other power supplies must be jumpered to disable Earth Fault Detection. Ensure that the Slave Exec firmware, later than Revision 1.04, is loaded on this TPS. Setting Address Switch The TPS device address is set via DIP switch SW1, which is a bank of eight switches. From left to right (see figure below), these switches are designated as SW1-1 through SW1-8. The function of these switches is as follows: SW1-1. This switch sets the baud rate for the internal FACP communications line running between the card and the FACP CPU. Set this switch to ON. SW1-2 through SW1-8. These switches set the card s address within the FACP. Note: You must set these switches to the value assigned to the card by the Programmer. FigureTag FD Comm. Baud Rate. Switch (SW1-1) Must Be Set to ON DIP Switches SW1-2 through SW1-8 set the Card Address. Figure shows an Address of 3. ON OFF Figure 3. DIP Switch SW1 Continued on next page 7
8 Configuring the TPS, Continued Setting Address Switch Table 3. Card Addresses Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW ON ON ON ON ON ON OFF 61 ON OFF OFF OFF OFF ON OFF 2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON 3 ON ON ON ON ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF 4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON 5 ON ON ON ON OFF ON OFF 65 OFF ON ON ON ON ON OFF 6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON 7 ON ON ON ON OFF OFF OFF 67 OFF ON ON ON ON OFF OFF 8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON 9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF 10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON 11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF 12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON 13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF 14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON 15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF 16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON 17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF 18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON 19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF 20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON 21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF 22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON 23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF 24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON 25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF 26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON 27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF 28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF 32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON 33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF 34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON 35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF 36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON 37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF 38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON 39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF 40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON 41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF 42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON 43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF 44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON 45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF 46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON 47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF 48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON 49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF 50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON 51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF 52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON 53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF ON ON ON OFF 54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON 55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF ON ON OFF OFF 56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON 57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF 58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON 59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF 60 ON OFF OFF OFF OFF ON ON 8
9 Power Distribution Module/Battery Connections Overview The TPS gets its power from the Power Distribution Module (PDM). The PDM takes power directly from a dedicated AC line and the two backup batteries, and distributes power to each bay in the cabinet. Power Distribution Module Connections The Power Distribution Module (PDM) connects to every power supply in each back box. Connect the Harness from the top connector on the PDM to the TPS. 1. Wire 120 VAC to the PDM, keeping AC wires at least one inch away from all other wires. AC power must be kept to the right side of the cabinet, in the non-power-limited area. 2. Connect batteries to P5 on the PDM using Harness Connect the PDM to the TPS using Harness Connect the separate Red and Black wires (with Yellow female terminations) to Plugs P5 (Black) and P4 (Red) on the TPS. Connect the White and Black wires, which terminate together in a White snap-on connector, to the bulkhead connector at the bottom of the TPS assembly, as shown below. 220/230/240V PART NUMBERS APPEAR IN ITALICS. Figure 4. PDM/Battery Connections 9
10 Compatible TrueAlert Devices Compatible TrueAlert Devices The following table lists compatible TrueAlert devices. All devices are rated one unit load, with the exception of the Isolator Module ( ) that is rated three unit loads. Note: If you are connecting devices to the (Canadian) TPS, you must only attach TrueAlert compatible, ULC listed devices. Table 4. Compatible TrueAlert Devices Device PID Installation Document # Horn -- Red Horn White Strobe (15 cd) Red Strobe (15 cd) White Strobe (75 cd) Red Strobe (75 cd) White Strobe (110 cd) Red Strobe (110 cd) White Strobe (15 cd), Ceiling Red Strobe (15 cd), Ceiling White Strobe (75 cd), Ceiling Red Strobe (75 cd), Ceiling White Strobe (110 cd), Ceiling Red Strobe (110 cd), Ceiling White A/V (15 cd) Red A/V (15 cd) White A/V (75 cd) Red A/V (75 cd) White A/V (110 cd) Red A/V (110 cd) White A/V (15 cd), Ceiling White A/V (75 cd), Ceiling White A/V (110 cd), Ceiling White Isolator Module V/70V Speaker /V (15 cd) Red V/70V Speaker /V (15 cd) White V/70V Speaker /V (75 cd) Red V/70V Speaker /V (75 cd) White V/70V Speaker /V (110 cd) Red V/70V Speaker /V (110 cd) -- White Continued on next page 10
11 Compatible TrueAlert Devices, Continued Compatible TrueAlert Devices Table 4. Compatible TrueAlert Devices (continued) Device PID Installation Document # Strobe Multi-Candela (15, 30, 75, 110) Red Strobe Multi-Candela (15, 30, 75, 110) White Strobe Multi-Candela (15, 30, 75, 110) Ceiling Red Strobe Multi-Candela (15, 30, 75, 110) Ceiling White A/V Multi-Candela (15, 30, 75, 110) Red A/V Multi-Candela (15, 30, 75, 110) White A/V Multi-Candela (15, 30, 75, 110) Ceiling Red A/V Multi-Candela (15, 30, 75, 110) Ceiling White Speaker/V Multi-Candela (15, 30, 75, ) Red Speaker/V Multi-Candela (15, 30, 75, ) White Speaker/V Multi-Candela (15, 30, 75, ) Ceiling White Amber Strobe Multi-Candela (15, 30, 75, ) Red Amber Strobe Multi-Candela (15, 30, 75, ) White Amber Strobe Multi-Candela (15, 30, 75, 110) Ceiling White
12 General Wiring Guidelines General Wiring Guidelines Use only copper conductors for all wiring applications. All equipment must be installed in accordance with the manufacturer s recommendations and the specifications and standards of the authority having jurisdiction (AHJ). The installation of all wiring, cable, and equipment must be in accordance with NFPA 70 and the National Electrical Code (NEC), specifically Article 760 (Fire Alarm Systems), Article 800 (Communications Circuits). If applicable, the installation must be in accordance with the Canadian Building Code, and any provincial and/or local requirements. Each TrueAlert channel is limited to 0.60uF maximum capacitance. This includes conductor to conductor and conductor to shield capacitance (if shield wire is used). TPS wiring must use ferrite beads in order to comply with the RF Immunity test specified in UL864 If shielded wire is used, the following must be observed. Metallic continuity of the shield must be maintained and insulated throughout the entire length of the cable. The entire length of the cable must have a resistance greater than 1 Mega ohm to Earth. Underground wiring must be free of all water. Wiring other than that connected to elevator cabs must not be run in elevator shafts (reference NFPA 70, Article 620). Wiring in ducts, plenums, and other air handling spaces must be installed in accordance with NFPA 70, Article 300. Splicing is permitted in accordance with NFPA 70. All junctions must be insulated as soundly as the original jacket. Continuity of shields (where used) must be maintained. A system ground must be provided for Earth detection and lightning protection devices. This connection shall be made to an approved, dedicated Earth connection, per NFPA 70, Article 250. Only system wiring can be run in the same conduit. Field wiring circuits shall not leave the building of origin unless all of the following conditions are met. Circuits are protected from lightning by utilization of either the Model or the Model listed isolated loop circuit protectors. One isolated loop circuit protector is inserted into the circuit where the wiring leaves the building. A second isolated loop circuit protector is inserted into the circuit where the wiring enters the next building. Underground wiring circuits are run in a parallel wiring trough separate from any commercial power distribution wiring. Overhead circuit wiring is run in parallel with relation to the commercial power distribution wiring. Overhead circuit wiring is separated from the commercial power distribution wiring by a minimum distance equal to the maximum span between two adjacent poles of either the system s circuit or the commercial power distribution circuit, or 100 feet (30 m), whichever is greater. Outside plant wiring is limited to one contiguous property and the total wire length may not exceed 3,270 feet (997 m). Continued on next page 12
13 General Wiring Guidelines, Continued Power-Limited/Non- Power Limited Wiring Guidelines Adhere to these guidelines when wiring power limited and non-power limited wiring within the FACP. Non-power limited field wiring (AC power, batteries) must be installed and routed in the shaded areas shown in the figure below. Power-limited field wiring must be installed and routed in the non-shaded areas shown in the figure below. Excess slack should be kept to a minimum inside the back box enclosure. The wiring should be neatly dressed and bundled together using the wire ties provided with the equipment. Anchor power-limited wiring to tie points, as shown in the figure below. Tie the wiring located between bays to the internal wiring troughs, if applicable. When powering remote units or switching power through relay contacts, power for these circuits must be provided by a power-limited power supply that is UL listed for fireprotective signaling use. A UL listed EOL relay must be used to supervise the auxiliary power circuit. IMANT: If the TPS is powered up with zero devices connected, the TPS indicates channel failure for those channels that are programmed to support devices. The TPS does not sense devices as they are connected when the TPS has been powered up with zero devices connected. After at least one valid device is connected, the unit must be reset by toggling the DIP Switch SW1-1 OFF and then ON. The TPS then communicates with devices as they are added. Conduit Entrance for Power-Limited Wiring Conduit Entrance for Non-Power Limited Wiring Power-Limited Wiring Non-Power Limited Wiring (Route in Shaded Area Only) Tie Point (Location May Vary) Figure 5. Non-Power Limited/Power-Limited Wiring Locations 13
14 Wiring Class A Circuits Class A Guidelines Class A wiring requires purchase of Class A Adapter Module Only TrueAlert appliances and accessories ( devices ) are allowed on these signaling line circuit (SLC) channels. Refer to Table 4 for a list of compatible TrueAlert devices and to the TrueAlert device installation instructions for connection details. Maximum of 63 devices or 75 unit loads per channel. Refer to Table 4 for unit load ratings of TrueAlert compatible devices. The maximum number of visuals that can be synchronized on one circuit is 43 for fixed candela and 46 for multi-candela devices. The maximum resistance between any two visuals is 30 Ohms. All wiring is supervised and power limited. All wiring to be twisted pair. Wire must be minimum of 18 AWG (0.82 mm 2 ) and maximum 12 AWG (3.31 mm 2 ). If shielded pair is used, then the cable shield drain wire must be attached back to the ( ) Terminal at both Class A and Class B ends of this circuit. Only one wire per terminal position. Maximum alarm current is 3.0 A per SLC channel. Use alarm current for lowest rated appliance nameplate voltage. Total alarm current for all 3 channels plus all current draw from AUX power and option cards must not exceed 9 A. Supervisory current is 0.20 ma per unit load. Maximum length of all wire segments added together is 10,000 feet (3,048 m) per channel. Maximum wire length from panel to any device is 2,500 feet (762 m). T-Tapping is NOT allowed. Maximum wire distance from panel to appliance farthest from the panel is the smaller of the values obtained from Table 5 and Table 6. Add the alarm loads of all the devices on an SLC wire loop and apply to Table 5. Voltage rating is 24 VDC nominal, 2 V peak-to-peak ripple, maximum. Overvoltage suppressors are required when wiring leaves the building. Use Simplex Model for wire distances of up to 1,000 feet (305 m). Use Simplex Model for long wire distances and light alarm loads. Note that the 6 Ohm line resistance of Simplex Model will decrease the distances given in Table 5. Maximum two suppressors between any device and SLC channel terminals (A or B). See the previous General Wiring Guideline section for information regarding wiring that leaves a building. Continued on next page 14
15 Wiring Class A Circuits, Continued Class A Guidelines The table below shows the maximum SLC wire lengths based on wire gauge and appliance current load. Table 5. Maximum SLC Wire Length to Farthest Appliance Based on Appliance Current Load Distance in Feet (Meters) to the Last Appliance Alarm Current 18 AWG (0.82 mm 2 ) 14 AWG (2.08 mm 2 ) 12 AWG (3.31 mm 2 ) 0.11 A 638 ft (194 m) 1,614 ft (492 m) 2,500 ft (762 m) 0.25 A 281 ft (86 m) 710 ft (216 m) 1,129 ft (344 m) 0.60 A 117 ft (36 m) 296 ft (90 m) 471 ft (144 m) 0.80 A 88 ft (27 m) 222 ft (68 m) 353 ft (108 m) 1.0 A 70 ft (21 m) 178 ft (54 m) 282 ft (86 m) 1.3 A 137 ft (42 m) 217 ft (66 m) 2.2 A 81 ft (25 m) 128 ft (39 m) 3.0 A 113 ft (34 m) Distances based on 2.0 V line drop If notification appliances on a given circuit are to be used for multiple notification zones for partial evacuation (selective signaling), then either a Class A loop circuit configuration and isolators must be used, with isolators bounding any wire segment that services a notification zone; or, the NAC riser must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002 ED. Section 6.9.4, using one or more of the following: 2 hour rated cable assembly a 2 hour rated shaft or enclosure 2 hour rated stairwell in building fully sprinklered in accordance with NFPA 13 The table below shows the maximum SLC wire length based on wire type and supervision communications. Table 6. Maximum SLC Wire Length to Farthest Appliance Based on Supervision Communications Distance in Feet (Meters) to the Last Appliance Unit Load Range 18 AWG (0.82 mm 2 ) 14 AWG (2.08 mm 2 ) 12 AWG (3.31 mm 2 ) 1 to ft (93 m) 772 ft (235 m) 1,228 ft (374 m) 4 to ft (79 m) 657 ft (200 m) 1,046 ft (319 m) 8 to ft (65 m) 538 ft (164 m) 856 ft (261 m) 14 to ft (53 m) 444 ft (135 m) 706 ft (215 m) 21 to ft (43 m) 355 ft (108 m) 565 ft (172 m) 31 to ft (36 m) 296 ft (90 m) 471 ft (144 m) 41 to ft (30 m) 254 ft (77 m) 403 ft (123 m) 51 to ft (68 m) 353 ft (108 m) 61 to ft (57 m) 297 ft (91 m) Continued on next page 15
16 16
17 Wiring Class A Circuits, Continued Class A Wiring Diagram (No Isolators) FigureTag FD TRUEALERT APPLIANCE TRUEALERT APPLIANCE TRUEALERT APPLIANCE Ferrite Bead Ferrite Bead Figure 6. Class A Wiring, No Isolators Class A Wiring Diagram (With Isolators) FigureTag FD ISOLATOR TRUEALERT APPLIANCE 1 2 TRUEALERT APPLIANCE ISOLATOR 2 1 Ferrite Bead ISOLATOR 2 Ferrite Bead Figure 7. Class A Wiring, with Isolators 17
18 Wiring Class B Circuits Class B Guidelines Only TrueAlert appliances and accessories ( Devices ) are allowed on these SLCs. Refer to Table 4 for a list of compatible TrueAlert devices and to the TrueAlert Device Installation Instructions for connection details. Maximum 63 devices or 75 unit loads per channel, whichever comes first. See Table 4 for unit load details. The maximum number of visuals that can be synchronized on one circuit is 43 for fixed candela and 46 for multi-candela devices. The maximum resistance between any two visuals is 30 Ohms. All wiring is supervised and power limited. All wiring to be twisted pair minimum 18 AWG (0.82 mm 2 ), maximum 12 AWG (3.31 mm 2 ). If shielded pair is used, the cable shield drain wire from all connected branches and taps must attach back to the (--) terminal of the circuit. Maximum two wires per terminal position. Maximum alarm current is 3 A per SLC. Use alarm current for lowest rated appliance nameplate voltage. Total alarm current for all three SLCs plus all current draw from AUX power and option cards must not exceed 9 A. Supervisory current is 0.20 ma per unit load. Maximum length of all wire segments added together is 10,000 feet (3,048 m) per SLC. Maximum wire length from panel to any device is 2,500 feet (762 m). The maximum wiring capacitance is 0.6 uf per channel. If shielded wire is used, you must add the capacitance of the drain wire to the conductor. Voltage rating is 24 VDC, 2 V, peak-to-peak ripple maximum. Maximum of six isolators between any appliance and SLC terminals. Maximum 12 isolators per SLC. Maximum 30 devices connected directly to any isolator terminal pair. If notification appliances on a given Class B circuit are to be used for multiple notification zones for partial evacuation (selective signaling), then the NAC riser must be installed in accordance with the Survivability From Attack by Fire Requirements in NFPA 2002 ED. Section One or more of the following should be used: 2 hour rated cable assembly A 2 hour rated shaft or enclosure 2 hour rated stairwell in building fully sprinklered in accordance with NFPA 13 The table below shows the maximum wire branch lengths for various alarm loads. Table 7. Maximum SLC Wire Branch Length Based on Appliance Current Load Distance in Feet (Meters) to the Last Appliance Alarm Current 18 AWG (0.82 mm 2 ) 14 AWG (2.08 mm 2 ) 12 AWG (3.31 mm 2 ) 0.11 A 1,058 ft (322 m) 2,500 ft (762 m) 2,500 ft (762 m) 0.25 A 471 ft (144 m) 1,328 ft (405 m) 2,169 ft (661 m) 0.50 A 241 ft (73 m) 669 ft (204 m) 1,089 ft (332 m) 0.75 A 164 ft (50 m) 450 ft (137 m) 730 ft (223 m) 1.00 A 125 ft (38 m) 340 ft (104 m) 550 ft (168 m) 1.25 A 102 ft (31 m) 274 ft (84 m) 442 ft (135 m) 1.50 A 87 ft (27 m) 230 ft (70 m) 370 ft (113 m) 2.00 A 175 ft (53 m) 280 ft (85 m) 2.50 A 142 ft (43 m) 226 ft (69 m) Wire Distances Based on 2.0 V Line Drop 18
19 19 Continued on next page
20 Wiring Class B Circuits, Continued Class B Guidelines The table below shows the maximum SLC wire branch length based on supervision communications. Table 8. Maximum SLC Wire Branch Length Based on Supervision Communications Distance in Feet (Meters) to the Last Appliance Unit Load Range 18 AWG (0.82 mm 2 ) 14 AWG (2.08 mm 2 ) 12 AWG (3.31 mm 2 ) ft (201 m) 1,681 ft (512 m) 2,500 ft (762 m) 2 to ft (183 m) 1,536 ft (468 m) 2,500 ft (762 m) 4 to ft (157 m) 1,310 ft (399 m) 2,086 ft (636 m) 8 to ft (129 m) 1,073 ft (327 m) 1,709 ft (521 m) 14 to ft (107 m) 887 ft (270 m) 1,411 ft (430 m) 21 to ft (86 m) 712 ft (217 m) 1,131 ft (345 m) 31 to ft (72 m) 595 ft (181 m) 944 ft (288 m) 41 to ft (62 m) 511 ft (156 m) 811 ft (247 m) 51 to ft (55 m) 449 ft (137 m) 711 ft (217 m) 61 to ft (47 m) 379 ft (116 m) 600 ft (183 m) Class B Wiring Diagram (No Isolators) For Class B wiring with no isolators, T-Tapping is allowed. SLC wiring may be split multiple times to form SLC wiring branches. Maximum wire distance of each of these SLC branches from the panel to any device is the smaller of the values obtained from Table 7 and Table 8. Add the alarm loads of all of the devices on an SLC branch and apply to Table 7. Add the unit loads (see Table 4) of all the devices on an SLC branch and apply it to Table 8. Use of Table 7 and Table 8 requires all SLC wire branches join within 10 feet (3 m) of the panel. T-tap wire stubs are allowed on the SLC wire branches, but each tap must be less than 100 feet (30 m). FigureTag FD TRUEALERT APPLIANCE TRUEALERT APPLIANCE TRUEALERT APPLIANCE TRUEALERT APPLIANCE TRUEALERT APPLIANCE TRUEALERT APPLIANCE Ferrite Bead Figure 8. Class B Wiring, No Isolators 20 Continued on next page
21 Wiring Class B Circuits, Continued Class B Wiring Diagram (With Isolators) For Class B wiring with isolators, T-Tapping is allowed. SLC wiring may be split multiple times to form SLC wire branches. Maximum wire distance of each of these SLC branches from panel to any device is the smaller of the values obtained from Table 8 and the Equation 1 shown below. Add the alarm loads of all the devices on an SLC wire branch and apply to Equation 1. Add the unit loads (see Table 4 for unit loads) for all devices on an SLC wire branch and the number of isolators and apply to Table 8. Use of Table 8 requires that all SLC wire branches join within 10 feet (3 m) of the panel. T-tap wire stubs are allowed on the SLC wire branches, but each tap must be less than 100 feet (30 m). Equation 1: Maximum SLC Wire Branch Length Based on Appliance Alarm Current Load Feet = 10 + (2V (2.5A * 10 * 2 * (res/ft) * 0.1(#isolators)(branch alarm amps) 2 * (res/ft) * (branch alarm amps) FigureTag FD TO OTHER DEVICES TO OTHER DEVICES ISOLATOR ISOLATOR 2 1 APPLIANCE APPLIANCE APPLIANCE APPLIANCE APPLIANCE TO OTHER DEVICES ISOLATOR ISOLATOR 2 TO OTHER DEVICES Ferrite Bead Figure 9. Class B Wiring, with Isolators 21
22 Wiring AUX Power Wiring Diagram to Connect AUX Power to Power Limited Wiring Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be used to supervise the circuit. Refer to the figure below for wiring directions for the EOL relay. TO AUX POWER Note: The Relay is used as an example. Other UL Listed 24 VDC EOL relays can be used, depending on the application. RED END OF LINE RELAY BLACK YELLOW IDC LAST IDC DEVICE RESISTOR Figure 10. Auxiliary Power-to-Power Limited Wiring AUX Compatible Devices The AUX Power output is defined by UL as Special Applications, and is compatible with these devices: 2088-Series relays and door handlers 2098-Series four-wire smoke detectors 2190-Series monitor and signal ZAMs 4090-Series IDNet ZAMs 4098-Series four-wire smoke detectors and duct detectors Printer /9051, 4-20 ma ZAMs LCD Annunciator 22
23 Troubleshooting System Trouble Indicators (LEDs A through E) The system trouble indicators consist of a bank of five yellow LEDS (refer back to Figure 1 for their location on the TPS). These LEDs are used to signal various trouble conditions on the TPS and its SLCs. Only one trouble at a time is shown. You can step through all of the troubles present on the TPS or its SLCs using the Trouble Scroll Pushbutton. This pushbutton is shown in Figure 1 and is located just to the right of LEDs A through E. Notes: Any trouble indication that applies to a specific SLC channel has the corresponding LED (CH1 through CH3) for that channel lit. The Trouble Scroll Pushbutton allows an operator to scroll through multiple troubles. = On LED = Off LED SYSTEM CODES A B C D E AC Fail Low/Missing Battery Running on Depleted Battery Memory Checksum Error RUI Comm Fail Hardware Configuration Mismatch Channel Controller Trouble Negative Earth Positive Earth Hardware Configuration Error Memory Test Error Charger Trouble Field Power Overcurrent Battery Cutout SLC CHANNEL CODES Channel Fail Short Circuit Duplicate Device Missing Device Extra Device Class A Trouble Earth Trouble Isolator Trouble Bad Download Address Out of Range SLC Overcurrent 23
24 Rev. K
/9308 External Battery Chargers Installation Instructions
4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.
More informationPanel Remote Annunciators Installation Instructions
Panel Remote Annunciators Installation Instructions Introduction This publication describes the installation procedures for the following PIDs: 4100-9607 Remote Annunciator w/ Flexible User Interface Domestic
More information4100U City and Relay Cards Installation Instructions
4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting
More informationNetwork Display Unit Installation Instructions
Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the
More information/ XPS Interconnection Diagrams
4100-5153/4100-5154 XPS Interconnection Diagrams Introduction This publication provides interconnection diagrams for 4100-5153 (120 VAC) and 4100-5154 (220/240 VAC) 13 A Expansion Power Supplies (XPS).
More informationClass A and Expansion NAC Modules Installation Instructions
Class A and Expansion NAC Modules Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1245 Flex Amplifier Expansion NAC (XNAC) 4100-1246
More informationAddressable IDNet Isolator Installation Instructions
4090-9116 Addressable IDNet Isolator Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed
More informationAU MX Digital Loop Card Installation Instructions
4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed
More informationLifeAlarm Fire Alarm Controls
UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity
More informationCautions and Warnings. Introduction 4009 NAC POWER EXTENDER
Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately
More informationTrueAlert Addressable Notification Appliances
Fire Control ** IS NORMAL ** :0:pm Mon 9-Feb-9 SY S TE M AC SUPERVISORY TROUB LE SILENCED SUPV TROUBLE SILENCE RESET CONTROL DISC ON NEC T POW ER + V ZONE P WR + 0V ZONE P WR - +IDNE T IDC + - IDNE T IDC
More informationRev. B. TrueAlert Addressable Controller Application Manual
574-996 Rev. B TrueAlert Addressable Controller Application Manual This page intentionally blank Copyrights and Trademarks Copyright 000 Simplex Time Recorder Company, Westminster, MA 044-000. All rights
More information4009 Fiber Optic Link Option Installation Instructions
4009 Fiber Optic Link Option Installation Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton
More informationTrueAlert Addressable Notification
UL, ULC Approved* TrueAlert Addressable Notification 4009 IDNAC Repeater; Power and Distance Extender Features IDNAC Repeaters provide enhanced power delivery to TrueAlert/ TrueAlert ES addressable notification
More information4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual *05791102H* This page is intentionally blank Contents CONTENTS 1 Cautions, Warnings, and Regulatory Information...3 2 Overview...4 2.1 4007ES
More informationLifeAlarm Fire Alarm Control Panels
LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient
More informationBooster Power Supply Manual
Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation
More informationAddressable NAC Output Module D327A
Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,
More informationAL800ULADA. NAC Power Extender. Installation Guide
AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery
More informationInstallation Guide for AL800UL-ADA. NAC Power Extender. Rev
Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA
More informationPSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
More informationAL600ULADA. NAC Power Extender. Installation Guide
AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery
More informationXPS and XNAC Installation Instructions
XPS and XNAC Installation Instructions Introduction This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102 (220/230/240 VAC), and 4100-5103 (120 VAC with battery disconnect)
More informationRemote NAC Power Supply D7038
Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus
More informationTrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions
TrueAlert NonAddressable, MultiCandela Notification Appliances Installation Instructions PRODUCT IDENTIFICATION REFERENCE (See Page 4 for Detailed Product Specifications) Type Mount Model Color Operation
More information4007ES Fire Control Panels
UL, ULC, CSFM Listed; FM Approved* Features Flexible standard combination of addressable initiation and addressable notification 4.3 (109 mm) Diagonal color touchscreen display: Convenient and intuitive
More informationPublic Safety DAS Annunciator Panel
Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This
More informationModel PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual
Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview
More informationTrueAlert Addressable Notification Appliances
UL, ULC Listed* TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances; Multi-Tone Horn/Strobe with 520 Hz Output Features Individually addressed and controlled multi-tone
More informationTrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed, FM Approved TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances, Wall Mount Multi-Candela Horn/Strobe, Model Series 49AV Features Individually addressed
More informationSystem Accessories, LCD Annunciators
System Accessories, LCD Annunciators UL, ULC Approved* A4606 Series Color Touchscreen LCD Annunciators for 4007ES Fire Alarm Control Panels Features Fig 1: A4606-9202 LCD Annunciator with Red Trim Fig
More informationTrueAlert Notification Appliances
TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible
More informationSC-6 Six Supervised Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:
More informationRAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description The TYCO RAPID RESPONSE Model RCP-1 Residential
More informationZ-20 Fire Control Panels
MANUAL RELEASE SYSTEM ABORT PUSH AND HOLD - I D N E T I N + + ID N E T I N - RE D NAC+ N A C - BLK C O ILS U P E R V IS IO NM O D U L E ( 2A M P )2 0 8 1-9 0 4 6 IN S T A L L A T IO NIN S T R U C T IO
More informationDoc. No Part No Rev. U * T*
Doc. No. 430545 Part No. 579-357 Rev. U *0579357T* Blank Page- Back of Front Cover Copyrights and Trademarks 2005-2018 Johnson Controls. All rights reserved. Specifications and other information shown
More informationMR-2602 Two Zone Fire Alarm Control Panel
MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...
More informationOperator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B
Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
More informationTrueAlert Addressable Notification Appliances
UL, ULC Approved* TrueAlert Addressable Notification Appliances Audible Notification Appliances; Multi-Tone Horns with 520 Hz Output Features Individually addressed and controlled TrueAlert ES multi-tone
More informationTECHNICAL DATA OBSOLETE
Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)
More informationPanel Message Memory Expansion Cards Installation Instructions
Panel Message Memory Expansion Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1241 Audio Message Memory Expansion Card (4 Megabytes
More informationModels NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring
More informationRAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) SECTIONS General Description.... 1 Warnings.... 2 Technical
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationTrueAlert ES Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved* TrueAlert ES Addressable Notification Appliances Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO Features Individually addressed
More informationInstallation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp
More informationInstallation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.
More information- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.
140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC
More information30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
More information4007ES Fire Control Panels
UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* 4007ES Fire Control Panels 4007ES Hybrid, Fire Detection and Control Panel with Addressable and/or Conventional Initiation Features Satisfies a variety
More informationACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel
ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More informationInstallation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev
Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control
More informationFireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
More informationPrint Specification. Publication. Instructions. Specific requirements. General requirements
Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is
More informationSIGA-CC1 Single Input Signal Module Installation Sheet
SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality
More informationInstallation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control
More informationFCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply
One Fire-Lite Place Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE Field Charger/Power
More informationMODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description
MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationIDP-Zone-6 Six Zone Interface Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority
More informationAddressable Fire Alarm Control Panel
PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT
More informationTrueAlert Multi-Candela Notification Appliances
UL, ULC Approved* TrueAlert Multi-Candela Notification Appliances Non-Addressable Visible Only Amber Lens Strobes for Emergency Communications Features Visible only (V/O) 24 VDC wall mount notification
More informationAPS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES
APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED
More informationFor a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight
More informationFire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION
Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,
More informationInstallation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationFire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features
Fire Control Units UL, ULC Listed, FM Approved* Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254 addressable
More informationgood things in small packages
FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with
More informationFor a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight
More informationFireNET Fire Alarm Control Panel Installation Manual
FireNET L@titude Fire Alarm Control Panel Installation Manual Page 2 Contents Contents Contents 3 Glossary 9 Compliance Information 11 Section 1: Introduction 12 Technical Support 12 Return Material Authorization
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationTECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.
September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.
More informationasimplex 4020 Fire Alarm System Contractor Installation Instructions Technical Manuals Online! -
asimplex 4020 Fire Alarm System Contractor Installation Instructions 0 1995 Simplex Time Recorder Co FA4-21-400 (574-061) All specifications and other information shown were current as of publication and
More information4100ES Fire Alarm System
FIRE ALARM 4100ES Fire Alarm System Installation Guide 574-848 Rev. AD Cautions, Warnings, and Regulatory Information Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationData Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
More informationPS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option
Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).
More informationTrueAlarm Addressable Fire Alarm Control Panels
FIRE FIRE SUPERVISORY PREVIOUS MENU NEXT SUPV SUPERVISORY PREVIOUS MENU NEXT SUPV SILENCED SILENCE DISABLE ENABLE FUNCTION EXIT CLEAR ENTER SILENCED SILENCE DISABLE ENABLE FUNCTION EXIT CLEAR ENTER AC
More informationInstallation Manual CFP-105. Fire Alarm Control Panel. Version 1.0
CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability
More informationOperation and Installation Guide. Fire Alarm Control Panel
Operation and Installation Guide Fire Alarm Control Panel 2001 Radionics Page 2 P/N: 36958D Contents Contents 1.0 Notices... 5 1.1 FCC Compliance Notice... 5 1.2 Notice... 5 1.3 Installation Guidelines
More informationFire alarm system specification for multiple tenant retail buildings
Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:
More informationSimplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*
Simplex ES Network UL, ULC Listed* ES Net features ES Network (ES Net) is a high bandwidth (100 Mbps) IP based fire alarm network that supports up to 99 nodes and uses industry standard network technology
More informationRelease Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POWER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
More informationTECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel
CVENTIAL ALARM S Features: Description: The LF-CP Series Fire Alarm Control Panel is manufactured based on advanced technology while maintaining high quality during assembly. It is of solid state circuitry
More information4007ES Fire Control Panels
UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* Features Flexible standard combination of addressable initiation and addressable notification 4.3 (109 mm) Diagonal color touchscreen display: Convenient
More informationModel 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
More informationRPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev
RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed
More informationFire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved*
Fire Control Panels UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* Features Basic system includes: Capacity for up to 248 addressable devices, up to 127 VESDA SLI points, up to 2000 points of Annunciation
More information4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions
4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 574-052 Rev. F This page intentionally blank Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights
More informationSeries. Access Power Controllers. Installation Guide
Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse
More informationMS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels
R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationFIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -
FIRE FIRE 4100U Fire Alarm Operator's Manual 579-197 574-xxx Rev. Rev. B 4 Blank Page- Back of Front Cover Copyrights and Trademarks Copyright Simplex Time Recorder Co., 2001. All rights reserved. Printed
More informationNotification Appliance Circuit Module
Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance
More information