1 Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation

2 Introduction and Scope This Fire Risk Assessment is designed to highlight all the relevant fire safety issues appertaining to your premises. The extent of the survey undertaken is dependent on levels of access to various parts of the building. It is not always practical to assess areas such as ceiling voids and wall cavities but where there are concerns that further special assessment of these areas is required, this will be highlighted within the report. In this report: Where relevant facts in relation to the premises were not visually apparent on the date of our inspection, we have relied on the information and/or responses provided by or on behalf of the Employer or other Responsible Person. We have assumed that all relevant building regulations were complied with in the construction of the premises, including any extension(s), conversion(s), renovation(s) and refurbishment(s). Unless otherwise stated, we have assumed that at the premises (I) all fire safety equipment, including fire doors and fire resistant partitions and (ii) all servicing of fire safety equipment has been installed or carried out (as the case may be) by persons competent to do so and in accordance with all applicable standards. We have not looked in roof spaces or other hidden areas in the premises except where there was an obvious fire hazard, which reasonably required further investigation. We have assumed that information and documentation supplied to us by or on behalf of the Employer or other Responsible Person who has a bearing on this Fire Risk Assessment is current, true, accurate and not misleading. The term Responsible Person has the meaning given to it in The Regulatory Reform (Fire Safety) Order This report reflects the circumstances found at the time of the inspection and does not take away the duties imposed on the Responsible Person for ensuring effective fire safety management within the premises on a day-to-day basis. Page 2

3 INTRODUCTION AND SCOPE... 2 IN THIS REPORT:... 2 GENERAL INFORMATION The Premises The Occupants Occupants Especially At Risk From Fire Fire Loss Experience Other Relevant Information Relevant Fire Safety Legislation... 6 FIRE HAZARDS AND THEIR ELIMINATION OR CONTROL Electrical Sources of Ignition Smoking Arson Portable Heaters and Heating Installations Cooking & Catering Lightning Housekeeping Hazards Introduced by Outside Contractors and Building Works Dangerous Substances Other Significant Fire Hazards That Warrant Consideration Including Process Hazards That Impact on General Fire Precautions FIRE PROTECTION MEASURES Fire Protection Measures Means of Escape From Fire Reasonable Distances Travelled Structural Means of Escape External Staircase and Escape Routes Emergency Escape Lighting Fire Safety Signs and tices Means of Giving Warning in Case of Fire Manual Fire Extinguishing Appliances Relevant Automatic Fire Extinguishing Systems Fire Fighter Safety Access & Water Supplies Management of Fire Safety Procedures and Arrangements Procedures Arrangements Contractors Training & Drills Drills Testing & Maintenance Maintenance & Routine Checks Records ACTION PLAN Appendix REGULATORY REFORM (FIRE SAFETY) Page 3

4 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Responsible person (e.g. employer) or persons having control of the premises: Name: Position: Premises name / Employer: Address of Premises RP Name RP Position ABC Car Workshop ABC Car Workshop, ABC Road, ABC County, A123 ABC Premises contact number: Person/s consulted if not 'Responsible Person' Name: Position: Date of fire risk assessment: Details of previous assessment: Date of previous fire risk assessment: Suggested date for review: This fire risk assessment should be reviewed by a competent person by the date indicated above or at such earlier time as there is reason to suspect that it is no longer valid, or if there has been a significant change in the matters to which it relates, or if a fire occurs 1 year The purpose of this report is to provide an assessment of the risk to life from fire in these premises, and, where appropriate, to make recommendations to ensure compliance with fire safety legislation. The report does not address the risk to property or business continuity from fire. Assessor: (Assessor s Name) Signature: Date: 24/07/17 Page 4

5 General Information 1. The Premises 1.1 Total number of floors, including basement floors in the building: What are the total number of floors included in the risk assessment: Approximate floor area in m2 of the footprint of the building Approximate total floor area in M2 of all floors surveyed: Number of occupiers in the building Description of property The property is a detached building of two floors consisting of a warehouse for car storage and workshop with first floor office area. 1.7 Brief details of construction The building is of modern construction with concrete floors and stairs. 1.8 Use of premises Workshop with warehouse. 1.9 Details: The premises are currently unoccupied. 2. The Occupants 2.1 Approximate maximum number in the premises: Estimated initially 10 persons. 2.2 Approximate number of employees in the premises at any one time: As above. 2.3 Maximum number of members of public at any one time: Estimated Associated times/hours of occupation: to Monday to Friday. 2.5 Approximate number of people who sleep in the premises: Number of persons in the premises who require special assistance i.e. children, language barriers etc.: When used as a place of public assembly, the maximum number of persons admitted should not exceed: 3. Occupants Especially At Risk From Fire 3.1 Sleeping occupants: ne 3.2 Disabled occupants: ne 3.3 Occupants in remote areas and lone workers: ne 3.4 Young persons: ne 3.5 Others: ne Page 5

6 4. Fire Loss Experience Date: Reported by: Location Details There has been no known fire loss experience. Probable cause Assessors recommendations 5. Other Relevant Information 5.1 The building is currently unoccupied and undergoing refurbishment 6. Relevant Fire Safety Legislation 6.1 The following fire safety legislation applies to these premises: Regulatory Reform (Fire Safety) Order The above legislation is enforced by: Region: Enforcer: London. London Fire Brigade. 6.3 Other legislation that makes significant requirements for fire precautions in these premises (other than the Building Regulations 2010): The Smoke Free (Premises & Enforcement) Regulations Furniture and Furnishings (Fire) (Safety) Regulations 1988 (as amended 1988 and 1993). Health and Safety (Safety Signs and Signals) Regulations The legislation referenced above is enforced by: Other 6.5 Comments and observations Page 6

7 Fire Hazards and Their Elimination or Control 7. Electrical Sources of Ignition 7.1 Are fixed electrical circuits periodically inspected and tested? See comments 7.2 Name of the company maintaining the system: See comments 7.3 Date of last test: Unknown 7.4 Has portable appliance testing (where appropriate) been carried out? See comments 7.5 Tested by: 7.6 Date of last test: N/a 7.7 Suitable policy regarding the use of personal electrical appliances? 7.8 Suitable limitation of trailing leads and adapters? Yes 7.9 Are there any other measures required to prevent fires of electrical origin? 7.1 It could not be confirmed when the main electrical circuits were last tested. 7.4 There were no portable appliances at the time of assessments 7.8 At the time of the survey the use of adaptors and extension leads appeared satisfactory 7.9 At the time of the survey no other measures were considered necessary to prevent fires of electrical 8. Smoking 8.1 Is smoking prohibited in the premises? Yes 8.2 Is the appropriate signage displayed? 8.3 Suitable arrangements for those who wish to smoke? 8.4 This policy appeared to be observed at time of inspection? Yes 8.5 Are there any other measures required to prevent fires in relation to smoking? 8.1 It was confirmed that smoking is not allowed in the premises. 8.2 The necessary " smoking" signs are not currently displayed. 8.3 Smoking is currently permitted outside the building. 8.4 At the time of the survey the no smoking policy was being complied with. 8.5 There are no other comments to make in relation to smoking. Page 7

8 9. Arson 9.1 Does basic security against arson by outsiders appear reasonable? - Reasonable only in the context of this fire risk assessment. If specific advice on security (including security against arson) is required, the advice of a security specialist should be obtained. 9.2 Is there an absence of unnecessary fire load in close proximity to the premises or available for ignition by outsiders? Yes Yes 9.3 Are there internal security arrangements in place? 9.4 Have there been any recent arson occurrences, deliberate ignition or vandalism? 9.5 Are there any other measures required to prevent deliberate fires? 9.1 The RP stated that internal CCTV and an Intruder Alarm are provided 9.2 There are currently no arrangements for the disposal of rubbish 9.4 There have been no reported incidents of arson. Whilst no premises can be excluded from the possibility of arson, the site was not considered to be a high arson risk. 9.5 There are no other comments to make in relation to arson 10. Portable Heaters and Heating Installations 10.1 Is the use of portable heaters avoided as far as practicable? 10.2 Is the use of the more hazardous type (e.g. radiant bar fires or lpg appliances) avoided? 10.3 Are suitable measures taken to minimize the hazard of ignition of combustible materials by heaters? 10.4 Are fixed heating installations subject to regular maintenance? See comments 10.5 Name of the company maintaining the system: 10.6 Date of last test: Are there any other measures required to prevent fires involving heaters or heating? 10.1 There were no portable heaters in evidence at the time of assessments 10.2 See comments above 10.3 See comments above 10.4 The premises is heated by a new domestic combination boiler, commissioning certificates have yet to be provided by the installer 10.6 There are no other comments to make in relation to heaters or heating. Page 8

9 11. Cooking & Catering 11.1 Are domestic type catering facilities provided e.g. tea, coffee, microwave, or toaster? 11.2 Are cookers, deep fat fryers or hobs in use? 11.3 Filters changed and ductwork cleaned regularly? 11.4 Are appropriate cut off switches provided? 11.5 Suitable extinguishing appliances available? 11.6 Are there any other measures required to prevent fires involving cooking? 11.1 There are no catering facilities in the building at present 11.2 There are no cookers or deep fat fryers in use in the building 11.6 There are no other comments to make in relation to cooking. 12. Lightning 12.1 Does the premises have a lightning protection system? 12.2 Name of Company carrying out the test: Date of last test: 12.3 Are there any other measures required to prevent fires involving lightning? 12.1 Lightning protection is not normally required for low rise buildings 12.3 There are no other comments to make in relation to lightning protection. Page 9

10 13. Housekeeping 13.1 Is the standard of housekeeping adequate? Yes 13.2 Combustible materials appear to be separated from ignition sources? Yes 13.3 Avoidance of unnecessary accumulation of combustible materials or waste? Yes 13.4 Appropriate storage of hazardous materials? Yes 13.5 Avoidance of inappropriate storage of combustible materials? Yes 13.6 Are there excessive display materials on walls and corridors or in protected routes? 13.7 Are there any other measures required to prevent fires involving combustible materials? 13.2 At the time of the survey all combustible materials were separated from ignition sources There appeared to be good management and control of combustibles and waste materials The escape routes were clear of display materials There are no other comments to make in relation to combustible materials in the building. Page 10

11 14. Hazards Introduced by Outside Contractors and Building Works 14.1 Are fire safety conditions imposed on outside contractors? Yes 14.2 Is there satisfactory control over works carried out on the premises by outside contractors (including hot work permits)? 14.3 If there are in-house maintenance personnel, are suitable precautions taken during hot work, including use of hot work permits? 14.4 Are there any other measures required to prevent fires when building works are being carried out or contractors are working on site? Yes It is understood that ABC monitor contractors while on site. 15. Dangerous Substances 15.1 Are the general fire precautions adequate to address the hazards associated with dangerous substances used or stored within the premises? 15.2 If 15.1 applies, has a specific risk assessment been carried out, as required by the Dangerous Substances and Explosive Atmospheres Regulations 2002? 15.3 Are all flammable liquids cleaning products and chemicals stored in suitable areas and in containers away from potential sources of ignition? 15.4 Are there any other measures required to prevent fires involving chemicals or flammable materials? Yes 15.1 At the time of the survey there were no dangerous substances identified. Page 11

12 16. Other Significant Fire Hazards That Warrant Consideration Including Process Hazards That Impact on General Fire Precautions 16.1 Are there any hot processes other than cooking taking place in the premises? 16.2 Are there any chemical agents stored or used in the premises? 16.3 Are there any factory processes carried out in the premises? 16.4 Are there any other hazards that should be noted? 16.1 At the time of the survey there were no significant hot processes being carried out. There are no other comments to make in relation to significant fire hazards in the building. Page 12

13 Fire Protection Measures 17. Fire Protection Measures Means of Escape From Fire 17.1 It is considered that the premises are provided with reasonable means of escape in case of fire. Yes 17.2 Adequate design of escape routes? Yes 17.3 Adequate provision of exits? Yes 17.4 Exits easily and immediately openable where necessary? Yes 17.5 Fire exits open in direction of escape where necessary? 17.6 Are electronic securing devices fitted on any doors forming part of the means of escape appropriately fitted and tested? 17.7 Avoidance of sliding or revolving doors as fire exits where necessary? Yes 17,8 Are the external escape routes satisfactory? Yes 17.9 Are there any other measures required in relation to the fire exit routes? 17.1 The number, distribution and widths of emergency routes and exits have been assessed for the use of the buildings and likely numbers of occupants. It is considered that the number and width of emergency exits are suitable for the likely number of occupants The design and layout of the escape routes were satisfactory The provision of exits is considered appropriate All doors inspected during the survey were fitted with push bar devices or turn button lock release The final staircase exit door opened inwards. As this door serves less than 60 people and is not directly at the bottom of a staircase this is considered acceptable There are no electronic securing devices in the premises 17.7 There are no sliding or revolving doors on the escape routes The external escape routes appeared satisfactory 17.9 There are no other comments to make in relation to fire protection measures in the building. Page 13

14 Reasonable Distances Travelled Where there is a single direction of travel? Yes Where there are alternative means of escape? Yes Suitable fire precautions for all inner rooms? Yes Are escape routes unobstructed? It is considered that the premises are provided with reasonable arrangements for means of escape for disabled people Are there any other measures required in relation to travel distances? At the time of the survey the single direction means of escape and travel distances were considered suitable and sufficient At the time of the survey the means of escape and travel distances were considered suitable and sufficient At the time of the survey it was noted that the escape route was obstructed There are no disabled persons on site. Page 14

15 Structural Means of Escape Are the escape routes provided with the necessary level of fire protection? Yes Do all fire-resisting doors appear to comply with BS476? Are the fire doors held or wedged in the open position by irregular means? Yes Are any approved hold open devices fitted to fire doors properly fitted and suitably signed? Are there any other measures required in relation to the structural means of escape? In the areas inspected during the survey the protected routes appeared to provide the necessary level of fire protection Any timber fire-resisting door that protects an escape route is required to be fitted with approved cold smoke seals and intumescent strips to the top and both vertical edges of the door or door frame in order to prevent the passage of smoke and fire, which can put persons and premises at risk. The fitted cold smoke seals must touch the adjacent frame or door edge to create the necessary seal. It was noted that there are fire doors of this type which are not fitted with these items. The fire door to the store room between the warehouse and stair was fitted with a vent. This vent appeared not to be the type that resists fire and smoke. The staircase door to the lobby did not close onto its rebate. The double rebated warehouse doors require a leaf selector to be fitted. The ground floor store door leading onto the protected staircase did not appear to be fire resisting There were no hold open devices in the premise There are no other comments to make in relation to the structural means of escape. Page 15

16 External Staircase and Escape Routes Is the external staircase suitable and sufficient and in good condition? Are any doors or windows (other than toilet windows), which open onto or are adjacent to, external staircases, balconies, and gangways, which are used for means of escape purposes, or are within 1.8 metres horizontally or 9 metres vertically of it, fire resisting? Are external staircases, balconies and gangways examined by a competent person at least every three years? Are the external escape staircases clear of obstructions or any other hazards? Is the external escape route from the building considered satisfactory? Yes Are there any other measures required in relation to the external escape routes from the building? There are no external escape stairs or balconies associated with the building The external escape routes from the building to the assembly point are suitable and sufficient for persons escaping from the building There are no other comments to make in relation to the structural means of escape. Page 16

17 18. Measures to Limit Fire Spread and Development 18.1 Is compartmentation of a reasonable standard? Yes Based on visual inspection of readily accessible areas, with a degree of sampling where appropriate Reasonable limitation of linings that might promote fire spread. Yes 18.3 As far as can reasonably be ascertained, fire dampers are provided as necessary to protect critical means of escape against passage of fire, smoke and combustion products in the early stages of a fire? A full investigation of the design of HVAC systems is outside the scope of this fire risk assessment Are there any other measures required in relation to fire separation or compartmentation 18.1 At the time of the survey all areas of compartmentation inspected appeared satisfactory The wall linings for this size of premises appeared satisfactory There are no HVAC systems associated with the building There are no other comments to make in relation to the fire separation or compartmentation. Page 17

18 19. Emergency Escape Lighting 19.1 Reasonable standard of emergency escape lighting system provided? Yes Based on visual inspection, but no test of luminance levels or verification of full compliance with relevant British Standards carried out Is the system tested to comply with BS ? 19.3 Is the system serviced to comply with BS ? 19.4 Name of Company carrying out the test: Date of last test: 19.5 Are there any other measures required in relation to emergency lighting 19.2 It could not be confirmed that the existing emergency lighting system is being tested each month in accordance with the recommendations of the current British Standard 5266: Part At the time of the survey, no records of the servicing, testing and maintenance of the emergency lighting system were available There are no other comments to make in relation to the emergency lighting. 20. Fire Safety Signs and tices 20.1 Is there a reasonable standard of fire exit signage? Yes 20.2 Reasonable provision of other fire safety signs and notices? Yes 20.3 Do the signs comply with the Health & Safety (Signs & Signals) Regulations 1996 or British Standard :2014? Yes 20.4 Are there suitable and sufficient Fire Action notices? 20.5 Is the assembly point suitably signed? 20.6 Are there any other measures required in relation to fire safety signs and notices? 20.4 There was a lack of fire procedure notices in the building The designated fire assembly point is not provided with an appropriate sign There are no other comments to make in relation to fire safety signs and notices. Page 18

19 21. Means of Giving Warning in Case of Fire 21.1 Is there a satisfactory means of raising the alarm in the event of a fire? 21.2 Reasonable manually operated electrical fire alarm system provided? 21.3 Is the fire alarm system tested on a weekly basis? 21.4 Is the system serviced on an annual basis to comply with BS 5839? 21.5 Name of Company carrying out the test: Date of last test: 21.6 Automatic fire detection provided? 21.7 Extent of automatic fire detection generally appropriate for the occupancy and fire risk? 21.8 Remote transmission of alarm signals? 21.9 Is a fire alarm zone plan provided adjacent to the fire alarm panel? Are there any other measures required in relation to the means of giving warning in case of fire? 21.1 There is currently no fire alarm provision. Occupiers would not be aware of a fire situation in the building. An electrical fire alarm to B25839 Part 1 category L5/M as an accepted minimum will be required There are no other comments to make in relation to the means of giving warning in case of fire. Page 19

20 22. Manual Fire Extinguishing Appliances 22.1 Reasonable provision of portable fire extinguishers? 22.2 Hose reels provided? Yes 22.3 Are all fire extinguishing appliances readily accessible? 22.4 Are all extinguishers fitted on wall brackets or provided with floor stands? 22.5 Are there any dry powder extinguishers in the building? 22.6 Are all extinguishers tested in accordance with British Standard 5306? 22.7 Name of the company maintaining the system: Date of last test: 22.8 Are there any other measures required in relation to fire extinguishing appliances? 22.1 There was no portable firefighting provision Hose reels are provided in the warehouse area and were last serviced by ABC Fire Control in January At the time of the survey no powder extinguishers were noted inside the building There are no other comments to make in relation to the fire extinguishing appliances. Page 20

21 23. Relevant Automatic Fire Extinguishing Systems 23.1 Other Relevant Type of Fixed Systems And Equipment Yes 23.2 Name of the company maintaining the system: Date of last test: Are there any other measures required in relation to fire extinguishing appliances? See comments in 22.2 above. 24. Fire Fighter Safety Access & Water Supplies 24.1 Are access roads for Fire & Rescue Service vehicles satisfactory Yes 24.2 Is there good access to the building for fire-fighters Yes 24.3 Are there adequate and local water supplies available Yes 24.4 Is there an Emergency Folder with sufficient information and plans for fire-fighters? 24.5 Is there external signage to warn fire-fighters of significant hazards? 24.6 Is there suitable provision of fire-fighters switches for high voltage luminous tube signs, etc Is the responsible person aware of any environmental issues as a consequence of a fire in the building 24.8 Are there any other measures required in relation to fire-fighter access or water supplies? 24.1 There is good access to the building for F&RS vehicles There is good access to the building for fire fighters There is an adequate provision of hydrants in close proximity to the building Due to the size and use of the building an emergency folder is recommended External signage should be considered There is no requirement for fire fighters switches The content of the premises and the building construction are such that in the event of fire there should be low environmental impact There are no other comments to make in relation to fire-fighter access or water supplies. Page 21

22 25. Management of Fire Safety Procedures and Arrangements 25.1 Fire safety is managed by: RP 25.2 Competent person(s) appointed to assist in undertaking the preventive and protective measures (i.e. relevant general fire precautions)? 25.3 Is there a suitable record of the fire safety arrangements? Specifically, policy arrangements for the planning, organising, controlling, monitoring and reviewing of the fire safety arrangements? 25.4 Where the premises forms part of a building with other premises, or the landlord has responsibility for common areas, have arrangements been made to cooperate and coordinate others regarding risks? Fire Marshall 25.5 Are there any other measures required in relation to management issues? Comments: 25.3 Fire Safety Policy documentation was not available at the time of the survey The building is not shared with other occupiers There are no other comments to make in relation to fire safety management. Page 22

23 Procedures 25.6 Appropriate fire procedures in place? 25.7 Are procedures in the event of fire appropriate and properly documented? 25.8 Are there suitable arrangements for summoning the fire and rescue service? 25.9 Are there suitable arrangements to meet the fire and rescue service on arrival and provide relevant information, including that relating to hazards to fire-fighters? Are there suitable arrangements for ensuring that the premises have been evacuated? Is there a suitable fire assembly point(s)? Are there adequate procedures for evacuation of any disabled people who are likely to be present? Are there any other measures required in relation to the fire procedures? Comments: 25.6 At the time of the survey there was no formal fire evacuation procedure for the safe evacuation of the building There are no documented fire procedures for the actions to be taken in the event of a fire. Simple detailed Fire action tices are considered sufficient for initial occupation. This should be reviewed and a more detailed Fire Emergency Procedure should be developed At the time of the survey there was no procedure in place to ensure that the fire & rescue service is called in an emergency At the time of the survey there were no arrangements in place to meet the fire service on their arrival and to pass on all relevant information to them. Arrangements should be put in place to provide all relevant information regarding the building, including any hazards to fire-fighters See 25.6 Page 23

24 Arrangements Persons nominated and trained to use fire extinguishing appliances? Persons nominated and trained to assist with evacuation, including evacuation of disabled people? Appropriate liaison with fire and rescue service (e.g. by fire and rescue service crews visiting for familiarisation visits)? Routine in-house inspections of fire precautions (e.g. in the course of health and safety inspections)? Are there any other measures required in relation to the fire arrangements? Comments: See comments in 25.6 above A Fire Service familiarisation visit will be at the discretion of the fire authority Routine fire precautions inspections should be carried out upon occupation. Contractors When the employees of another employer work in the premises is their employer given appropriate information (e.g. on fire risks and general fire precautions)? When the employees of another employer work in the premises are they provided with adequate instructions and information? Yes Yes Are there any other measures required in relation to the management of contractors? Comments: It is understood that on site contractors are managed centrally and furnished with adequate instruction and information in relation to the existing fire precautions Page 24

25 26. Training & Drills 26.1 Are all staff given adequate fire safety instruction and training on induction? 26.2 Are all staff given adequate periodic refresher training at suitable intervals? 26.3 Does all staff training provide information, instruction or training appropriate to their responsibilities and applicable to their role? Including: Fire risks in the premises, The fire safety measures on the premises, Action in the event of fire, Action on hearing the fire alarm signal, Method of operation of manual call points, Location and use of fire extinguishers, Means for summoning the fire and rescue service, Identity of persons nominated to assist with evacuation, Identity of persons nominated to use fire-extinguishing appliances Are staff with special responsibilities given additional training? 26.5 Are there any other measures required in relation to training? Comments: See comments in 25.6 There are no other comments to make in relation to training Drills 26.6 Are fire drills carried out at appropriate intervals? 26.7 Date of last fire drill: 26.8 Are there any other measures required in relation to fire drills? Comments: 26.6 Fire drill procedure should be reviewed to ensure employees are prepared in the event of an evacuation There are no other comments to make in relation to fire drills. Page 25

26 27. Testing & Maintenance 27.1 Weekly testing and periodic servicing of fire detection and alarm system? 27.2 Monthly and annual testing routines for emergency escape lighting? 27.3 Annual maintenance of fire extinguishing appliances? 27.4 Periodic inspection of external escape staircases and gangways? 27.5 Six-monthly inspection and annual testing of rising mains? 27.6 Weekly and monthly testing, six-monthly inspection and annual testing of firefighting lifts? 27.7 Weekly testing and periodic inspection of sprinkler installations? 27.8 Are there any other measures required in relation to testing and maintenance? Comments: 27.2 At the time of the survey, no records of the servicing, testing and maintenance of the emergency lighting system were available. See comments in Section 19. Page 26

27 Maintenance & Routine Checks 27.9 Routine checks of final exit doors and/or security fastenings? Adequate maintenance of premises? Yes Are suitable systems in place for reporting and subsequent restoration of safety measures that have fallen below standard? Are there any other measures required in relation to routine maintenance or checks? Are there any other relevant inspections or tests? 28. Records Appropriate records of fire drills? Appropriate records of fire training? Appropriate records of fire alarm tests? Appropriate records of emergency escape lighting tests? Appropriate records of maintenance and testing of other fire protection systems? Are there any other measures required in relation to the maintenance of records? Comments: 28.6 There are no other comments to make in relation to the maintenance of records. Page 27

28 Fire Risk Assessment Methodology The following simple fire risk level estimator is based on a commonly used health and safety risk level estimator. Likelihood of Fire Potential Consequences of Fire Slight harm Moderate harm Extreme harm Low Trivial risk Tolerable risk Moderate risk Medium Tolerable risk Moderate risk Substantial risk High Moderate risk Substantial risk Intolerable risk Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (likelihood of fire) at these premises is: Low Medium High X In this context, a definition of the above terms is as follows: Low Medium High Unusually low likelihood of fire as a result of negligible potential sources of ignition. rmal fire hazards (e.g. potential ignition sources) for this type of occupancy with fire hazards generally subject to appropriate controls (other than minor shortcomings). Lack of adequate controls applied to one or more significant fire hazards, such as to result in significant increase in likelihood of fire. Taking into account the nature of the premises and the occupants, as well as the fire protection and procedural arrangements observed at the time of this fire risk assessment, it is considered that the consequences for life safety in the event of fire would be: Slight harm Moderate harm X Extreme harm In this context, a definition of the above terms is as follows: Slight harm Moderate harm Extreme harm Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a room in which a fire occurs). Outbreak of fire could foreseeably result in injury (including serious injury) of one or more occupants, but it is unlikely to involve multiple fatalities. Significant potential for serious injury or death of one or more occupants. Page 28

29 Accordingly, it is considered that at the time of the survey the risk to life from fire at these premises is: Trivial Tolerable Moderate X Substantial Intolerable A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one that has been advocated for general health and safety risks: Risk level Trivial Tolerable Moderate Substantial Intolerable Action and timescale action is required and no detailed records need be kept. major additional fire precautions required. However, there might be a need for reasonably practicable improvements that involve minor or limited cost. It is essential that efforts are made to reduce the risk. Risk reduction measures, which should take cost into account, should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Considerable resources might have to be allocated to reduce the risk. If the premises are unoccupied, it should not be occupied until the risk has been reduced. If the premises are occupied, urgent action should be taken. Premises (or relevant area) should not be occupied until the risk is reduced. (te that, although the purpose of this section is to place the fire risk in context, the above approach to fire risk assessment is subjective and for guidance only. All hazards and deficiencies identified in this report should be addressed by implementing all recommendations contained in the following action plan. The fire risk assessment should be reviewed regularly.) Page 29

30 ACTION PLAN It is considered necessary that all recommendations in the Action Plan be implemented in order to reduce fire risk to, or maintain it at, the following level: Priority Trivial Tolerable X INTOLERABLE risks will be notified at the time of inspection and should be cleared immediately. If this is not possible the premises Fire Safety Manager will be contacted and advised of the serious risk and the need for immediate action. SUBSTANTIAL risks are set as a HIGH priority within the action plan and action should be taken to rectify them within 1 month MODERATE risks are set as MEDIUM priority within the action plan and action should be taken to rectify them within three months, or to be reduced in severity to a tolerable risk until the defect can be rectified. TOLERABLE risks have a LOW priority within the action plan and action should be taken to rectify them within six months. TRIVIAL risks will be included as advisory action with no time period for completion. The time for rectification is judged reasonable for the risk category but the rectification should be as soon as possible and within the time set by the company s policy on such matters. Action Priority Action by whom Date action taken 7.1 It should be confirmed that all electrical installations and fixed wiring have been tested by a competent electrical engineer within the last 5 years. Ensure that an Electrical Installation Condition Report has been issued, and that any recommendations are being dealt with. Moderate 8.2 At least one legible no-smoking sign must be displayed at the premises in accordance with the duty imposed by virtue of The Smoke-free (Signs) Regulations Moderate The side escape route from the warehouse was partially obstructed with tyres which should be removed Moderate All fire doors should be upgraded with three hinges, intumescent strips and cold smoke seals. Moderate The fire door to the storeroom between the warehouse and stair door vent should be of a type that prevents the passage of smoke and fire. Intumescent and mechanical fire dampers are available to achieve this. Moderate The staircase to lobby door fire door should receive maintenance to ensure that it closes fully onto its rebate Substantial Page 30

31 The rebated double-leaf fire-resisting doors from the warehouse to the office area ground floor need to be fitted with an effective selector device to ensure that the door leaves close in the correct sequence Substantial The ground floor store door leading onto the protected staircase should be upgraded or replaced to comply with the current British Standard BS 476, 30 minute fire resisting. It should have intumescent strips that incorporate cold smoke seals on the top edge and both vertical edges of the door or door frame and have three hinges with a melting point above 800ºC. If the door is not used as a cupboard or storeroom door it should be fitted with an effective self-closing device Substantial 19.2 It is recommended that tests (flick tests) are carried out by management on the existing emergency lighting system by the simulation of a failure of the power supplies. Any failure should be recorded and arrangements made to provide the necessary repairs. Emergency lighting should be tested in accordance with the current British Standard 5266: Part 8, i.e. monthly and the results entered in the fire log book recommended. Additionally, regular inspections of the luminaries should be conducted to identify any that are physically damaged or those that are not showing an illuminated battery charging light. Moderate 19.3 It is recommended that the existing emergency lighting is serviced in accordance with the recommendations in BS 5266 Moderate 20.4 Printed FIRE ACTION tices complying with the current British Standard BS 5499 and British Standard BS ISO 7010 should be displayed at conspicuous positions in the premises. They must state in concise terms the essentials of the action to be taken upon discovering a fire and on hearing the fire alarm. The notices must be permanently fixed and suitably protected to prevent loss or defacement. They should be located in prominent positions, such as staff notice boards, tea rooms and canteens, and immediately adjacent to all fire alarm call points when installed Substantial 20.5 The nominated fire assembly point should be indicated by the appropriate graphical sign of adequate size complying with the current British Standard BS 5499 and British Standard BS ISO Moderate 21.1 An electrical fire alarm should be installed to BS5839 Part 1 category L5 with call points adjacent to all final exit doors including the warehouse. Substantial 22.1 Water and CO2 fire extinguishers should be provided. Page 31

32 They should be hung from wall brackets at a convenient height or placed within floor stands which are fixed to the walls, and sited adjacent to all final exits. Substantial 22.2 The existing hose reels in the warehouse should be serviced. Moderate 25.3 A Fire Safety Policy document is required to demonstrate effective arrangements for planning, organisation, control, monitoring and review of preventative and protective measures with regard to the nature of the activities and size of the undertaking Moderate 25.6 A formal fire evacuation procedure for the premises must be developed to ensure the safe evacuation of everyone in the building. Substantial 25.8 A procedure and suitable arrangements should be put in place to ensure that the fire & rescue service are called in the event of a confirmed fire. Substantial 25.9 At the time of the survey there were no arrangements in place to meet the fire service on their arrival and to pass on all relevant information to them. Arrangements should be put in place to provide all relevant information regarding the building, including any hazards to fire-fighters Substantial Page 32

33 Title: ABC Car Workshop Fire Risk Assessment Appendix Partially obstructed exit route Fire door not closing into its rebate selector Vent in a fire door Double fire doors requiring a door P a g e 33

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

Fire Risk Assessment Keys Meadow Primary School

Fire Risk Assessment Keys Meadow Primary School Fire Risk Assessment Keys Meadow Primary School Issue Date: Issued To: Version Number: Approved By: 19 th May 2016 Jane Jenner 1 CS Fire Risk Assessment - Company Name XXX REGULATORY REFORM (FIRE SAFETY)

More information

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Rodwell House

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW.

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW. Waterstones 69-71 High Street, Solihull, West Midlands, B91 3SW. BAFE Certificate Number: 0040921 CONTENTS: BAFE SP205 Certificate of Compliance 3 Introduction 5 Risk Assessment Methodology 6 PAS 79 Fire

More information

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Hazeldene House

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Harpwood Care

More information

FIRE RISK ASSESSMENT Self Assessment

FIRE RISK ASSESSMENT Self Assessment FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of

More information

S12 Fire Safety Risk Assessment H&SFS01-1 / 9

S12 Fire Safety Risk Assessment H&SFS01-1 / 9 S12 Fire Safety Risk Assessment H&SFS01 Risk ratings The following risk ratings are based on two factors: The overall fire risk rating for the site The risk rating for the individual recommendations /control

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Fire Risk Assessment Case Study

Fire Risk Assessment Case Study Appendix B Fire Risk Assessment Case Study The purpose of this case study is to illustrate one practical approach to conducting a fire risk assessment. The checklist and proformas used in this case study

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Kent Business School in conjunction with Council & the Vice Chancellor Kent Business

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person:

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person: Site No. a division of Allsaved Ltd. Fire Safety Log Book Premises Address: Responsible Person: Introduction An Introduction to Your Fire Safety Log Book The Regulatory Reform (Fire Safety) Order 2005

More information

A basic guide to... Fire Safety for Scout Premises

A basic guide to... Fire Safety for Scout Premises A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Estates in conjunction with Council & the Vice Chancellor Brotherhood Boiler House,

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

PREMISES FIRE SAFETY LOGBOOK

PREMISES FIRE SAFETY LOGBOOK 0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Following a near miss (after a fire or where evidence suggests that a fire could have occurred).

Following a near miss (after a fire or where evidence suggests that a fire could have occurred). Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons

More information

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report 42 Haslucks Croft, Shirley, Solihull, B90 2EQ (t) 0121 249 1281 (m) 07814 203 977 www.veritas-consulting.co.uk The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Report Client The Company

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates East Oast, University of

More information

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Responsible Person:

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

FIRE RISK ASSESSMENT review

FIRE RISK ASSESSMENT review COVER SHEET review in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Employer or other

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

UNIVERSITY COLLEGE LONDON REGULATORY REFORM (FIRE SAFETY) ORDER 2005

UNIVERSITY COLLEGE LONDON REGULATORY REFORM (FIRE SAFETY) ORDER 2005 UNIVERSITY COLLEGE LONDON REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Responsible Person (e.g. employer) or person having control of the premises: University College London Address

More information

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Page 1 of 23 Section 1: Details of Premises all questions on this page are compulsory LBHF Ward UPRN Name

More information

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007)

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007) FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. This Fire Safety Log book has been prepared to assist the responsible person in coordinating

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

ISLE OF WIGHT FIRE & RESCUE SERVICE

ISLE OF WIGHT FIRE & RESCUE SERVICE ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

Fire Risk Management Policy. UK September 2017

Fire Risk Management Policy. UK September 2017 UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No

More information

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

Fire Risk Assessment Standish House Saint Peters Grove W6 9AY 22/06/17

Fire Risk Assessment Standish House Saint Peters Grove W6 9AY 22/06/17 Assessment Standish House Saint Peters Grove W6 9AY 22/06/17 Page 1 of 23 Section One: Details of Premises All questions on this page are compulsory LBHF Ward Ravenscourt Park UPRN Name of Premises (known

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Procedures. April 2016

Fire Procedures. April 2016 Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents

More information

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;

More information

Arbour House. Fire Policy and Procedures

Arbour House. Fire Policy and Procedures Arbour House Fire Policy and Procedures Policy Review Date: May 2017 Introduction Arbour House School endeavours to ensure that risks from fire are identified and that arrangements are in place to control

More information

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1 Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

Fire Safety Risk Assessment Large Premises

Fire Safety Risk Assessment Large Premises Fire Safety Risk Assessment Large Premises Premises Name: Person Completing this Assessment: Date of Assessment: Date of Next Review: (Recommended Annually) Fire Safety Risk Assessment (Large Premises)

More information

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school

More information

University of Kent; Vice Chancellor; Director of Kent Hospitality

University of Kent; Vice Chancellor; Director of Kent Hospitality COVER SHEET Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Vice Chancellor; Director of Kent Hospitality Rutherford College (excludes Extension)

More information

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN FINAL VERSION Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN August 2017 Responsible Person (e.g. employer) or person having control of

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN REVISED Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN July 2017 Responsible Person (e.g. employer) or person having control of the

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Science Block Hillcrest Rd, London W5 2JL 020 8997 2022 Bursar J Powell

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Name & Address of the Society IDENTIFY PEOPLE AT RISK 01 Have you identified who is at risk? 02 Have you identified

More information

FIRE SAFETY POLICY. This policy refers to both Wellington Senior School and Wellington Prep School

FIRE SAFETY POLICY. This policy refers to both Wellington Senior School and Wellington Prep School FIRE SAFETY POLICY This policy refers to both Wellington Senior School and Wellington Prep School Headmaster Henry Price Author Bursar Date Reviewed 27.06.2017 for implementation on 25.07.2017 Date of

More information

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma Reference Number: This risk assessment and ALL associated documents must be retained. Date : Sept 17 The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma This Fire Risk Assessment

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Fire Precautions (Workplace) Regulations Before beginning the risk assessment, check to see if your workplace has a Fire Certificate. If the workplace does have a Fire Certificate,

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Clockhouse Nursery and Early ears Hillcrest Rd, London W5 2JL 020 8997

More information

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY PART 1: FIRE SAFETY INTRODUCTION Our priority is to minimise the risk to life and to reduce injury by maintaining the physical fire safety of the

More information

KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES

KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES Member of staff responsible : Headmaster Date of policy review : June 2018 Date of next review : June 2019 Approved by Governors : June 2018 KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES

More information

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21 FIRE RISK ASSESSMENT Hatton House Page 1 of 21 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises 9 6 Fire

More information

Fire Risk Assessment DURSTON HOUSE SCHOOL Castlebar Road, Ealing, London, W5 2DR. Prepared by: Steven Cox BA(Hons), ACII, AIOSH

Fire Risk Assessment DURSTON HOUSE SCHOOL Castlebar Road, Ealing, London, W5 2DR. Prepared by: Steven Cox BA(Hons), ACII, AIOSH Fire Risk Assessment DURSTON HOUSE SCHOOL 12-14 Castlebar Road, Ealing, London, W5 2DR Prepared by: Steven Cox BA(Hons), ACII, AIOSH Hettle Andrews & Associates Limited Eleven Brindleyplace 2 Brunswick

More information

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY 1. Policy

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY   1. Policy Fire Safety Policy 1. Policy It is the policy of Malden Oaks to minimise the risks to students, staff and others which may arise from fire. This is achieved by ensuring precautions are taken to avoid fires

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY INTRODUCTION Cwmni CYNNAL recognises its duty of care to employees and all reasonable steps will be taken to secure the health and safety of employees.

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

NOT PROTECTIVELY MARKED. Fire Legislation

NOT PROTECTIVELY MARKED. Fire Legislation Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information