1 SC-103 JUNE 7, PT1 (Obsolete) FIREYE S 48PT2 INFRARED: 48PT1, 48PT2 and 48PT2-CEX ROD: 69ND1 For UV Self-Check Scanners use SC-101 For Hazardous Locations or NEMA 4X Scanners use SC-106 For Non Self-Check UV Scanners use SC ND1 APPROVED DESCRIPTION The 48PT2 scanner comes with cables rated for Tray Cable - Exposed Run (TC-ER) and complies with the crush and impact requirements of the standard for metal clad cable, UL PT1 (Obsolete) The 48PT1 lead sulfide infrared scanner contains a high impedance detector and is designed to be used only on P-Series controls. 48PT2 The 48PT2 lead sulfide infrared scanner contains a low impedance detector and is designed to detect low flicker frequency IR signals from gas and oil flames. It is designed for use on D-Series, Flame- Monitor, FlameWorx, MicroM and Burnerlogix controls. 48PT2-CEX The 48PT2-CEX is a 48PT2 mounted in a ATEX compliant housing for environments requiring the rating of Exd IIC T6 ATEX hazardous location. 69ND1 The 69ND1 flame rod is made of high temperature resistant metal and can be used only to detect gas flames. The rods come in 12, 18 and 24 inch lengths. CAUTION: Fireye scanners are for use only with Fireye controls. Do not connect Fireye scanners with controls not manufactured by FIREYE. CAUTION: If component checking is required during burner operation for constantly fired burners, utilize the infrared flame scanner (48PT2) with associated AutoCheck amplifier. For Flame-Monitor systems use the E1R1, E1R3 or E1R2 and for MicroM systems use the MEIR1 or MEIR4. Warning- all installation, service and troubleshooting of Fireye products must be performed by a qualified technician. 1

2 5.0 (127) (63.6) 1 DIA. (25.4) 2 1/2 (63.5) 1 1/4 DIA. (31.8) 13/16 HEX (20.6) 15/16 HEX (23.8) 2 3/8 (60.3) 2 3/8 (60.3) 1/2 (12.7) L.385 DIA. (8.7) TC-ER CABLE 1/2-14 STRAIGHT PIPE THD HEAT INSULATOR 1/2-14 TAPERED PIPE THD 1/2-14 NPT L LENGTH AS SPECIFIED: 12, 18, 24 (304.8, 457.2, 609.6) 48PT SERIES INFRARED 69ND1 ROD 3.96 (100.5) DIA. (37.1) 2 1/2 (63.5) 13/32 (10) 2.13 (54) 1/2-1 STRAIGHT PIPE THD HEAT INSULATOR 1 1/4 DIA. (31.8) 1/2-14 TAPERED PIPE THD.385 DIA. (8.7) TC-ER CABLE 48PT SERIES INFRARED Scanner Model Type Approx. Volts Across Cell Approx. Resistance* of Cell For information on the 45UV scanners, see Bulletin SC-101. For information on the 55UV scanners, see Bulletin SC-106. For information on the UV1A, UV2, and UV8A scanners, see Bulletin SC-102. Ambient Temp. Limits 48PT1 Infrared 125VDC 1.5 Meg. ohms 140 F/ 60 C, PT2 Infrared 7-15VDC 20K - 80K ohms 140 F / 60 C, PT2-CEX 69ND1 Flame Rod VAC Infinite Tip 2460 F 1500 F/816 C, -40 * Resistance measured with 20K Ohms/ Volt Meter For proper Flame Signal Voltage see technical bulletin for the appropriate control. 48PT2 scanners comply with NEMA 4X PART NUMBER DESCRIPTION USE WITH 48PT PT PT PT PT1-9007W 48PT PT PT PT PT2-CEX IR Straight Head 8 feet (2440mm) leads IR Straight Head 4 feet (1220mm) Leads IR 90 deg. Head 8 ft. (2440mm) Leads IR 90 deg. Head 4 ft. (1220mm) Leads Water Repellent IR Straight Head 8 feet (2440mm) leads IR Straight Head 4 feet (1220mm) Leads IR 90 deg. Head 8 ft. (2440mm) Leads IR 90 deg. Head 4 ft. (1220mm) Leads IR Straight Head, 1/2 NPT inlet Heat Insulator for 48PT Scanners 69ND1-1000K4 69ND1-1000K6 69ND1-1000K8 Flame Rod 12 inches (305mm) 1/2 in. mount Flame Rod 18 inch (460mm) 1/2 in. mount) Flame Rod 24 inches (710mm) 1/2 in. mount P-Series C & D Series, MicroM, -MONITOR, BurnerLogix P, C, D, M-Series, MicroM, MB Systems, BurnerLogix, -MONITOR 2

3 TENANCE 48PT1 and 48PT2, 48PT2-CEX Infrared Scanners and 69ND1 Flame Rods The viewing area of the scanner must be kept clean. Even a small amount of contamination will reduce the flame signal reaching the detector by a measurable amount. Wipe the viewing area routinely using a soft cloth dampened with concentrated detergent. Type 48PT1 scanner includes a replaceable # cell Type 48PT2, 48PT2-CEX scanner includes a replaceable # Firetron cell. Type 69ND1 Flame Rod. Rods should be routinely replaced as they oxidize. Flame Signal Strength. Routine observation of the flame signal strength or as read on the display of the -MONITOR will forewarn of any deterioration in the capability of the flame detector or its application. Periodic Safety Check. It is recommended that a procedure be established to test, at least once a month, the complete flame safeguard system. This test should verify the proper operation of all limit switches and safety interlocks as well as flame failure protection and fuel safety shutoff valve tightness. Rotation. It is recommended that control and scanner units purchased as spares be installed periodically. Contacts. There are no accessible contacts in the Fireye burner programming controls. Where contacts are used, their design assures long trouble-free life when the load circuits are maintained within the published load ratings. Humidity. In areas of high humidity, the control chassis should be removed and placed in a dry atmosphere when the system is expected to be out of service for an extended period. For scanner installation and wiring instructions, see the appropriate FIREYE technical bulletin for each control. CONTROL BULLETIN -MONITOR E-1101 D-Series D-1020, D-30, D-4041 M-Series C-4000 MB-Systems CC-82 MicroM MC-5000 BurnerLogix BL-1001 WARNING: FIREYE S CAN BE USED ONLY WITH THE APPROPRIATE FIREYE CONTROL. DO NOT CONNECT FIREYE S TO CONTROLS NOT MANUFACTURED BY FIREYE. INSTALLATION INFRARED TYPE 48PT2 The following UL standards have been revised and now allow the use of TC-ER rated cable on Commercial boilers and burners: UL 295: Commercial - Industrial Gas Burners Sections , , and UL 296: Oil Burners Sections , , and UL 726: Oil fired Boiler Assemblies Sections , , and UL 795: Commercial - Industrial Gas Heating Equipment Section Where possible, obtain the burner manufacturer s instructions for mounting the scanner, otherwise proceed as follows: 3

4 A single scanner is used to detect both pilot and main flames. The sight pipe on which the scanner mounts must be aimed so that the scanner sights a point at the intersection of main and pilot flames. Two IR Scanners may be installed on one burner if it is necessary to view two areas to obtain reliable detection of the flame. They should be wired in parallel. Proper scanner positioning must assure the following: 1. Reliable pilot flame signal. 2. Reliable main flame signal. 3. A pilot flame too short or in the wrong position to ignite the main flame reliably, must not be detected. 4. Scanner must have an unobstructed view of flame being monitored. 5. Flame being monitored must completely cover the scanner field of view. 6. To avoid nuisance shutdowns, it is important to avoid sighting hot refractory and to keep scanner temperature low (below 125 F) (52 C). 7. When the proper position has been established, drill a hole through the furnace wall and install a 4" to 8 length of threaded l / 2 black iron pipe on which to mount the 48PT2 scanner. 8. When satisfactory sighting position has been confirmed by operating tests, the sight tube should be firmly welded in place. MUST NOT SIGHT REFRACTORY COMBUSTION CHAMBER TARGET ABOVE REFRACTORY LINE-OF-SIGHT CENTER LINE OF SIGHTING TUBE Wiring Wiring Instructions: Wire the black and red wires (18 AWG) on the 48PT2 flame scanner to terminals S1 and S2 on the Fireye flame safeguard control. There is no polarity associated with the wire colors. Either wire (red or black) can be wired to either terminal (S1 or S2). Shield and Drain Wire: The scanner provides a shield and drain wire that are internally bonded to the metal threaded ½ NPT coupling nut. This allows a conduit clamp to provide an electrical ground around the exposed shield when entering a metal junction box or control cabinet, or connect the drain wire to a suitable ground connection when using a non-metallic (or metallic) junction box or control cabinet. Conduit required: On those applications where conduit is required, Fireye recommends the Thomas and Betts 449-TB (or suitable) fitting which is used to couple 3/8" flexible metal conduit to 1/2" EMT conduit.the set screw on the fitting bites into the flat section of the plastic on the 48PT2 scanner and seats onto the metal casing below, providing a secure connection. Extended Wiring: If necessary to extend scanner wiring, attach the cable supplied with the scanner to a junction box. Splice the cable wires to a pair of wires not smaller than #l8. Install the complete run in a separate 4

5 conduit to the control. Continuous conduit bonding between scanner and the control is mandatory! Scanner may be located up to 100 feet from control. Do not pass scanner wiring through any junction box containing other wires. Do not run other wires through scanner conduit. Asbestos insulated wire should be avoided. Keeping the Scanner Cool The Infrared Scanner (Temperature Limit 125 F) should never get too hot to grasp comfortably in the hand. Keep the scanner cool by one or more of the following methods. 1. Use 6 to 8 length of pipe between scanner and hot furnace front plate. 2. Use insulating tube (Part No ) on the end of the iron pipe. 3. Force air into sighting tube. Use Fireye Sealing Union (Part No ). 4. Make sure sighting tube does not extend more than halfway into refractory wall. Minimum Pilot Test This test assures that the flame detector will not detect a pilot flame too small to reliably light off the main flame. The test should be made on every new installation, and following any repositioning of the flame detector. THE MINIMUM TEST MUST BE ACCOMPLISHED BY A TRAINED AND QUALIFIED TECHNICIAN. REFRACTORY REFRACTORY REFRACTORY INSUFFICIENT MINIMUM NORMAL SPARK REJECTION TEST. CAUTION: The scanner must not sight the ignition spark directly or any part of the burner that can reflect the spark back to the scanner. The scanner must not see a pilot flame that is too small to reliably ignite the main flame. Test procedures vary according to the control used. See procedures as described in the technical bulletin for the control being installed. 5

6 6

7 7

8 NOTICE WARRANTIES When Fireye products are combined with equipment manufactured by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance. FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps, electronic tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part. FIREYE SC Manchester Road JUNE 7, 2018 Derry, New Hampshire (Supersedes June 17, 2015) 8

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC APPROVED The UV1A3/6, UV2/UV2A6/UV2C, 45UV2, 45UV3, UV90-3/6/9 Scanners are used with the M-Series, M-Series II, MicroM, FlameWorx, MB-2 and D-Series controls as well as the Fireye FLAME-MONITOR TM, BurnerLogix

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV1A UV8A UV90 UV1A UV8A SC-102 MARCH 28, 2013 FIREYE FLAME SCANNERS UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV1A UV8A UV5 UV90L SC-108 June 14, 2017 FIREYE FLAME SCANNERS UV non self-checking Scanner Models: UV1AL-3, UV1AL-6, UV90L-1, UV90L-2, UV5-1. UV1AL 45UV3 DESCRIPTION The UV1AL, UV90L, and UV5 scanners

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV90 SC-102 MAY 2002 FIREYE SCANNERS UV1A UV8A UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, UV2C,45UV2, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer to SC-101

More information

Fireye FLAME SCANNERS

Fireye FLAME SCANNERS UV7A4 SC-107 APRIL 3, 2013 Fireye SCANNERS UV7SC UV7R4 UV Non Self-Checking Scanner Models: UV7A4, UV7R4 UV Self-Check Scanner Model: UV7SC DESCRIPTION The non self-check UV7A4, UV7R4 and self-check UV7SC

More information

FIREYE C9707A ALL FUEL SCANNER

FIREYE C9707A ALL FUEL SCANNER 65-8065 APRIL 11, 2013 FIREYE C9707A ALL FUEL SCANNER The C9707A All Fuel Scanner is used with the FIREYE R9107A Flame Controller to provide continuous monitoring of burner flames in industrial and utility

More information

SOLID STATE Burner Management Controls SERIES D40-41

SOLID STATE Burner Management Controls SERIES D40-41 D-4041 JULY 8, 2013 SOLID STATE Burner Management Controls SERIES D40-41 70D41 ONLY 70D40 ONLY DESCRIPTION FIREYE Series D40-41 Burner Management Controls provide ignition and flame failure protection

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 FEBRAURY 6, 2017 MBCE-110/230FR Flame Sensor Module exida FMEDA SIL2 SEE NOTE 1 ON PAGE 4 DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the

More information

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION M-4000 JANUARY 29, 200 FIREYE M4RT1 FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government

More information

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC Sales@mmcontrol.com APPROVED The information provided in this bulletin is directed to competent boiler and combustion service technicians who are experienced in the installation and operation of Fireye

More information

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES MBD-00 FEBRUARY 00 MBUV-00D, MBUVS-00D MBIR-00D, MBFR-00D DIN RAIL MOUNT FLAMEWORX MODULES APPROVED Year 000 Compliant in accordance with BSI document DISC PD000-I:998 DESCRIPTION Fireye offers a complete

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-101 April 2001 DESCRIPTION AND INSTALLATION For 45UV5 UV self-checking Scanner Models: 45UV5-1005, 45UV5-1006, 45UV5-1007, 45UV5-1008, 45UV5-1009 and 45UV5-1105 For use only with designated Fireye controls

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-106 SEPTEMBER 3, 2013 DESCRIPTION AND INSTALLATION UV self-checking Scanner Models: 55UV5-1007, 55UV5-1009 For use only with designated Fireye controls For Infrared Photocell Scanners use SC103 For

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-101 JUNE 26, 2013 DESCRIPTION AND INSTALLATION For 45UV5 UV self-checking Scanner Models: 45UV5-1005, -1005CEX, 45UV5-1006, 45UV5-1007, -1007CEX, 45UV5-1009, -1009CEX and 45UV5-1105 For use only with

More information

FLAME SAFEGUARD FOR BURNER MANAGEMENT SYSTEMS

FLAME SAFEGUARD FOR BURNER MANAGEMENT SYSTEMS CX-784 February 1999 FLAME SAFEGUARD FOR BURNER MANAGEMENT SYSTEMS Year 2000 Compliant in accordance with BSI document DISC PD2000-I:1998 APPLICATION The 25SU3Model 4169T control and associated flame scanner(s)

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

Solid State Burner Management Controls Series D10-20 for Automatic Burners

Solid State Burner Management Controls Series D10-20 for Automatic Burners D-1020 AUGUST 22, 2005 Solid State Burner Management Controls Series D10-20 for Automatic Burners APPROVED DESCRIPTION Fireye Series D10-20 Burner Management controls provide ignition and main flame failure

More information

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED ED-5101 APRIL 3, 2013 ED510 DISPLAY MODULE FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS APPROVED DESCRIPTION The ED510 Display Module is designed to operate with the FLAME-MONITOR

More information

E340 BOILER CONTROL INSTALLATION MANUAL

E340 BOILER CONTROL INSTALLATION MANUAL E-3451 JUNE 1999 E340 BOILER CONTROL INSTALLATION MANUAL DESCRIPTION The E340 Boiler Room Control is a microprocessor-based Boiler Management System designed to interface with existing Fireye D Series

More information

55UV5 SCANNER MODEL 1010

55UV5 SCANNER MODEL 1010 133-721 MAY 6, 2013 55UV5 SCANNER MODEL 1010 NEMA 4X, IP66 CLASS I, DIV 2, GROUPS A, B, C, D CLASS II, CLASS III, DIV 2, GROUPS F and G APPROVED This bulletin is directed to the licensed boiler service

More information

Eclipse 90 UV Scanner Model A Version 1

Eclipse 90 UV Scanner Model A Version 1 85 Instruction Manual 10/14/010 Eclipse 90 UV Model 5600-90A Version 1 C US Introduction This sensor features a high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames that cycle on and

More information

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

UV Scanner. Model Specification. Introduction. 854 Instruction Manual 854 Instruction Manual 10/11/010 UV Model 5600-91 C US Introduction This sensor features a high temperature and high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames in applications that

More information

FIREYE E210/211 FLAME-MONITOR

FIREYE E210/211 FLAME-MONITOR E-2101 MAY 12, 2011 FIREYE E210/211 FLAME-MONITOR Microprocessor-Based Burner Management Control with Message Center and Self-Diagnostics DESCRIPTION The FIREYE FLAME-MONITOR control is a microprocessor

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

C7915A Infrared Flame Detector

C7915A Infrared Flame Detector C795A Infrared Flame Detector PRODUCT DATA When installed properly, can supervise the pilot flame and/ or the main burner flame. Mounts easily on a standard 3/ inch sight pipe. The infrared sensor plugs

More information

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD BURNER MANANGEMENT SYSTEM NXF4000-SPEC AUGUST 5 2017 PRODUCT GUIDE SPECIFICATION FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD GENERAL OVERVIEW 1.1.1. Each burner shall

More information

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies Flame Rod Holder & Flame Rod Assemblies The small size of these devices enable their application to flame detection in installations where space is limited. The holder and flame rod assemblies facilitate

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

Eclipse Self-Check UV Scanner

Eclipse Self-Check UV Scanner 856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly

More information

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS MC-5000 MAY 10, 2017 FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS APPROVED WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2

More information

RK / RK Methane Detector Operator s Manual

RK / RK Methane Detector Operator s Manual 61-1006RK / 61-0192RK Methane Detector Operator s Manual Part Number: 71-0228RK Revision: 0 Released: 10/29/18 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

FIREYE FLAME SAFEGUARD CONTROLS DESCRIPTION

FIREYE FLAME SAFEGUARD CONTROLS DESCRIPTION SB-2301 SEPTEMBER 17, 2013 FIREYE FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government.

More information

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES E-11 MARCH 28, 2013 E1 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES E1 with ED5 Display Module APPROVED DESCRIPTION The Fireye

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Keep these instructions with the boiler at all times. BOYERTOWN FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450 www.boyertownfurnace.com 5-25-12 2 Danger Warning Caution

More information

FIREYE YZ300 and YZ320 INTERLOCK ANNUNCIATOR For use with the Fireye BurnerLogix Control

FIREYE YZ300 and YZ320 INTERLOCK ANNUNCIATOR For use with the Fireye BurnerLogix Control YZEM-3001 June 2, 2017 FIREYE YZ300 and YZ320 INTERLOCK ANNUNCIATOR For use with the Fireye BurnerLogix Control APPROVED DESCRIPTION The FIREYE YZ300 (YZ320) Interlock Annunciator Module provides increased

More information

RK / RK CO 2 Detector Operator s Manual

RK / RK CO 2 Detector Operator s Manual 61-1004RK / 61-0191RK CO 2 Detector Operator s Manual Part Number: 71-0145RK Revision: C Released: 10/29/18 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents C7061C/F ULTRA VIOLET FLAME DETECTOR PRODUCT HANDBOOK APPLICATION The C7061C/F are flame detectors for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels. Explosion-proof

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

C7004B Flame Rod Holder

C7004B Flame Rod Holder Honeywell These Flame Rod Holders facilitate the use of flame rods for flame proving on gas burners or gas-pilot ignited oil burners controlled by electronic flame safeguard control systems. C7004B Flame

More information

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B)

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B) Dual sensor flame scanner (rev B) Application: - Wall fired and corner fired boilers - Gas, oil and coal multi-fuel burners Combined PbS IR sensor and high sensitivity UV tube Continuous self-checking

More information

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031 SLATE Rectification Ampli-Check Flame Amplifier R8001V1031 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single

More information

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071 SLATE UV Ampli-Check Flame Amplifier R8001S1071 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform.

More information

Flame Safeguard Fault Code Diagnostics

Flame Safeguard Fault Code Diagnostics Vino s Vine Tech Tips Series 02/2013 Flame Safeguard Fault Code Diagnostics As manager of Tech Services, it probably comes as no surprise I spend some time discussing fault codes and corresponding corrective

More information

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer CU-108 January 29, 2018 TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer DESCRIPTION APPLICATION The Fireye Paragon, type 105F1-1 flame scanner is a microprocessor based flame analysis device

More information

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY AUTOMATIC BURNER CONTROL SYSTEM The burner control unit Quad400 is suitable for the control of direct ignition burners up to 350 kw, pursuant to EN 746-2. Flame control by means of UV scanner or ionization

More information

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules PRODUCT DATA indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules.

More information

MaxLite LED Vapor Tight Linear Fixture

MaxLite LED Vapor Tight Linear Fixture General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

RK/ RK Combustible Gas Detector Operator s Manual

RK/ RK Combustible Gas Detector Operator s Manual 61-1003RK/61-0190RK Combustible Gas Detector Operator s Manual Part Number: 71-0120RK Revision: 0 Released: 2/11/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

EZ-FLAME Detector USER MANUAL

EZ-FLAME Detector USER MANUAL EZ-FLAME Detector USER MANUAL TABLE OF CONTENTS 1 Introduction... 1 1.1 Unpacking and Inspection... 1 1.2 About this Manual... 1 2 Description... 2 3 System Configuration... 3 3.1 Flexible Fiber Optic

More information

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules PRODUCT DATA indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules.

More information

RK-05 Combustible Gas Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual 65-2405RK-05 Combustible Gas Transmitter Operator s Manual Part Number: 71-0180RK Revision: 0 Released: 2/16/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Bert Uneken, Field Engineering Manager Ruben Kranenburg, Technical Support

Bert Uneken, Field Engineering Manager Ruben Kranenburg, Technical Support Bert Uneken, Field Engineering Manager Ruben Kranenburg, Technical Support Main Burner Main Reaction Furnace Design Weather shield View ports Weather shield LMV Burner Burner / Furnace connection Residence

More information

FIREYE EPD260, EPD261, EPD270 PROGRAMMER MODULES

FIREYE EPD260, EPD261, EPD270 PROGRAMMER MODULES EPD-201 AUGUS, 200 FIREYE EPD20, EPD21, EPD20 PROGRAER ODULES AN ALERNAIVE PROGRAER FOR USE WIH HE FLAE-ONIOR SYSE DESCRIPION he Fireye EPD20, EPD21, and EPD20 Programmer odules are used with the FLAE-ON-

More information

RK Transmitter Technical Notice

RK Transmitter Technical Notice 65-2450RK Transmitter Technical Notice Although this Operator s Manual was written for the 65-2400RK combustible gas LEL transmitter, the operational instructions are the same for the 65-2450RK hydrogen

More information

RK Combustible Gas Transmitter Operator s Manual

RK Combustible Gas Transmitter Operator s Manual 65-2400RK Combustible Gas Transmitter Operator s Manual Part Number: 71-0060RK Revision: C Released: 1/31/13 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

INSTALLATION USE & CARE MANUAL ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER

INSTALLATION USE & CARE MANUAL ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS IMPORTANT INFORMATION Warnings 2 Installation Instructions 3 Wiring Instructions 3 Outdoor

More information

COMPACT FLAME CONTROLLER CFC 2000

COMPACT FLAME CONTROLLER CFC 2000 COMPACT FLAME CONTROLLER CFC 2000 TECHNICAL DESCRIPTION EDITION: TB_CFC2000_EN_REV09_20150408 Important: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring

More information

ZB110/ZB230 FIREYE BurnerLogiX

ZB110/ZB230 FIREYE BurnerLogiX BLZ-1001 August 7, 2018 ZB110/ZB230 FIREYE BurnerLogiX MICROPROCESSOR-BASED BURNER MANAGEMENT CONTROL WITH INTEGRATED BOILER CONTROL OPERATION APPROVED DESCRIPTION The Fireye BurnerLogix Z System expands

More information

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents C796E,F Dynamic Self-Check Ultraviolet Flame Detector PRODUCT DATA C796F C796E Detectors can be mounted horizontally, vertically or at any other angle providing the orientation arrow is pointing down.

More information

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters 1200 North Main Street Fostoria, OH 44830 Phone: 800-495-4525 Fax: 419-435-0842 A DIVISION OF www.fostoriaindustries.com OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters *EXCLUDING

More information

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev. Flame scanner for fuel oil and coal flame (rev. A) Application: - Wall fired, corner fired and down-shot boilers - Oil, Orimulsion and pulverized coal burners PbS sensor to detect flame by infrared (IR)

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

IN TEXAS CALL (800) FIREYE. CONTRACT No. TXMAS (800)

IN TEXAS CALL (800) FIREYE. CONTRACT No. TXMAS (800) FIREYE CONTRACT No. TXMAS-7-840180 (800) 356-8000 FIREYE PART No. DESCRIPTION TxMAS CONTRACT PRICE 002608-001 Fireye Flange gasket for 65UV5. 3.51 104-15 Fireye Vibratory weatherproof horn for FE-5. 354.39

More information

Fireye Flame Safeguard Controls

Fireye Flame Safeguard Controls Fireye Flame Safeguard Controls SYSTEM COMPONENTS CATALOG CU-25 JUNE 5, 2013 FLAME SAFEGUARD CONTROLS Systems Components Products For over 70 years, Fireye has manufactured quality flame safeguard and

More information

RK-03 Hydrogen Detector Operator s Manual

RK-03 Hydrogen Detector Operator s Manual 61-1001RK-03 Hydrogen Detector Operator s Manual Part Number: 71-0371 Revision: P1 Released: 5/26/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

RK CO 2 Transmitter Operator s Manual

RK CO 2 Transmitter Operator s Manual 65-2397RK CO 2 Transmitter Operator s Manual Part Number: 71-0185RK Revision: B Released: 7/18/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

TJERNLUND PRODUCTS, INC.

TJERNLUND PRODUCTS, INC. TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com PRESSURE SWITCH AND INSTALLATION WITH

More information

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com Model 9001EXP Alarm No. 2080203(24)

More information

COMPACT FLAME CONTROLLER CFC 1000

COMPACT FLAME CONTROLLER CFC 1000 COMPACT FLAME CONTROLLER CFC 1000 TECHNICAL DESCRIPTION EDITION: TB CFC1000- REV.6 2012-03-07 Important: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring

More information

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual Part Number: 71-0132TA Revision: A Released: 4/23/10 www.toxalert.com Product Warranty Toxalert International, Inc. warrants gas alarm equipment

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

RK/ RK Oxygen Detector Operator s Manual

RK/ RK Oxygen Detector Operator s Manual 65-2502RK/65-2510RK Oxygen Detector Operator s Manual Part Number: 71-0074RK Revision: A Released: 3/1/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place 06 Elster GmbH Edition 0.6 Translation from the German 0556 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 5 Cert. version 0.6 Contents UV sensor UVS 5... Contents...

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector PRODUCT DATA FEATURES APPLICATION C706F C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832 FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832 February 2013 8835-R with C7061A U. V. Scanner s simplify installation of fl ame detectors on Fives North American burners. They also

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

FIREYE BurnerPRO MICROPROCESSOR-BASED INTEGRATED BURNER MANAGEMENT CONTROL DESCRIPTION. with UV & FR Flame Amplifiers

FIREYE BurnerPRO MICROPROCESSOR-BASED INTEGRATED BURNER MANAGEMENT CONTROL DESCRIPTION. with UV & FR Flame Amplifiers BP-1002 NOVEMBER 10, 2017 FIREYE BurnerPRO MICROPROCESSOR-BASED INTEGRATED BURNER MANAGEMENT CONTROL with UV & FR Flame Amplifiers DESCRIPTION The Fireye BurnerPRO is a compact, microprocessor based, primary

More information

CINCINNATI, OH USA

CINCINNATI, OH USA INSTRUCTION MANUAL Part No. 89731 Revised October 1997 CINCINNATI, OH 45241-4807 USA GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier.

More information

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B)

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B) Flame scanner for gas and oil burners (Rev. B) Application: - Wall fired boilers - Gas and oil burners High sensitive UV tube Continuous self-checking Rugged detector head for harsh environments: - Protection

More information

RK-02 Multi Point Detector Operator s Manual

RK-02 Multi Point Detector Operator s Manual 65-2485RK-02 Multi Point Detector Operator s Manual Part Number: 71-0237RK Revision: A Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL GASGUARD LEL 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL GasGuard LEL 3 Operating and Installation Manual 2 Table of Contents 3GasGuard LEL Operating and Instruction Manual General description. 4

More information

RK Multi Point Detector Operator s Manual

RK Multi Point Detector Operator s Manual 65-2480RK Multi Point Detector Operator s Manual Part Number: 71-0198RK Revision: C Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00 I&M NUMBER: 316-42-16-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

! The Caution Symbol (exclamation point) alerts you to a CAUTION, a safety or I&M NUMBER: 316-42-10-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4. Replacement Element Installation 5. Replacement Parts 5

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4. Replacement Element Installation 5. Replacement Parts 5 TABLE OF CONTENTS Warnings 2 Installation Instructions 3 Wiring Instructions 3 Mounting Instructions 4 Replacement Element Installation 5 Replacement Parts 5 Heater Coverage Areas 6 General Notes 6 Maintenance

More information

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4-5. Replacement Element Installation 5. Replacement Parts 5-6

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4-5. Replacement Element Installation 5. Replacement Parts 5-6 TABLE OF CONTENTS Warnings 2 Installation Instructions 3 Wiring Instructions 3 Mounting Instructions 4-5 Replacement Element Installation 5 Replacement Parts 5-6 Heater Coverage Areas 6 General Notes 6

More information

FLAME SAFEGUARD & COMBUSTION CONTROLS. Preface

FLAME SAFEGUARD & COMBUSTION CONTROLS. Preface Preface This manual provides the basic principles of operation and application of Fireye flame safeguard controls. It is not intended to improve on, or replace, any of the technical bulletins that are

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2335RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0177RK Revision: 0 Released: 4/12/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

North American Flame Detector Adapters 8832 through 8839 and Series R

North American Flame Detector Adapters 8832 through 8839 and Series R Combustion North American Flame Detector s 8832 through 8839 and Series R s simplify installation of flame detectors on North American burners. They also facilitate access to detectors for servicing. Most

More information

INSTALLATION USE & CARE MANUAL ALL WEATHER W-SERIES AND WD-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER

INSTALLATION USE & CARE MANUAL ALL WEATHER W-SERIES AND WD-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL ALL WEATHER W-SERIES AND WD-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS Warnings 2 Installation Instructions 3 Wiring Instructions 3 Mounting Instructions

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual GG-VL-R REFRIGERANT VENT LINE SENSOR Installation and Operation Manual 2 GG-VL-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

Model 9001, Alarm

Model 9001, Alarm INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com Model 9001, 9001.5 Alarm No.

More information

ECLIPSE INFORMATION GUIDE

ECLIPSE INFORMATION GUIDE ECLIPSE INFORMATION GUIDE JUNIOR INDUSTRIAL BURNERS Models 0 & 6 JIB Info 80 0/9 Easy to install and operate. Rugged construction for long life in industrial environments. Protection against overheating

More information

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place 8.. Edition 08.0 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 0 Translation from the German 008 009 Elster GmbH Contents UV sensor UVS 0......................

More information