Powell. Fabrication & Manufacturing Inc. Hypo Batch Controller with Temperature Indicator (Digital ORP/ORP/Temperature System) 2400 Series
|
|
- Barnard West
- 5 years ago
- Views:
Transcription
1 Powell Fabrication & Manufacturing Inc Hypo Batch Controller with Temperature Indicator (Digital ORP/ORP/Temperature System) 2400 Series Introduction A sodium hypochlorite batch controller has been designed for bleach producers. The batch controller measures and displays the chlorine content of the bleach on a solid state digital D.C. millivolt meter as the sodium hydroxide is chlorinated. The sodium hydroxide must be at a predetermined strength before chlorination of the batch is begun. The batch controller utilizes two ORP meters that perform a redundant safety feature. If the control meter should fail, the safety meter will still alarm. A temperature meter has been installed to alarm and shutdown on high batch temperature. The digital meters are installed inside of a 30"h x 24"w x 8"d NEMA 4 case with a window in the front of the cabinet for easy visibility of the meters. The oxidation-reduction method utilizing silver and platinum electrodes immersed in the bleach solution measure the chlorine content of the bleach. The standard electrode holders are constructed of PVC plastic and are designed for 2" or larger pipe. An optional holder designed to mount between any size pipe flange is available. Two complete chlorine control loops are provided with the batch controller, one is referenced as "Chlorine Control Indication", and the other as "Chlorine Safety Indication." As the sodium hydroxide is chlorinated, a voltage is produced proportional to the degree of chlorination and is displayed on the digital D.C. millivolt meter, with two adjustable set points. When the chlorine is added to the sodium hydroxide, the voltage increases until the low set point of the chlorine control meter is reached, thus turning on the chlorine control alarm light and alarm horn. Usually, the low set point is used only to notify the operator that the batch is nearing completion. After the alarm horn sounds, it is silenced by the alarm silence button. The first set point will sound a horn, which may be silenced by the operator. After the operator silences the alarm, he can reduce the rate of chlorine flow being added to the batch if he desires. He then waits for the chlorine control shutdown light to turn on and the alarm horn to sound. If the optional automatic chlorine valve is installed, it will shut off when the chlorine control shutdown activates, and indicate valve open on the controller pilot light. If an automatic valve is not installed, the operator is expected to manually shut off the chlorine at this point. When the temperature alarm is reached the operator needs to slow the rate that chlorine is added to the system. If the temperature continues to raise the shutdown will close the optional chlorine valve. The batch controller has been designed to lockout the chlorine valve so that it can not open automatically after the ORP shutdown alarm has been reached. If the millivoltage drops below the shutdown set point and the operator turns the chlorine valve control switch to the "release" position and then back to the on position, the shutdown alarm will reset to the normal mode and the chlorine valve will turn on. The operator has full control of the optional chlorine valve and can turn it on or off as desired. Since the alarms for both meters are adjustable, the operator has a choice on the alarm and shutdown points of each meter. The temperature alarm does not lock out the automatic valve and will automatically reopen the chlorine valve when the batch cools.
2 Typically, the batch controller is placed at a convenient operator location with the alarm horn remotely mounted in any location within hearing range. The electrodes are usually placed on the suction side of a recirculation pump for the batch, or through a tank wall with field fabricated and installed bulkhead fittings. Special electrode holders will be designed for any application. Installation NOTE: Recommended installation of the digital batch controller provides for dual ORP readings from the same bleach tank, causing the redundancy for an independent backup input and alarm of the batch chlorination. Wiring or plumbing, which defeats the backup or redundancy of the second meter reading of an individual batch, is not recommended by Powell Fabrication & Manufacturing, Inc. 1. The electrodes are installed into the pipe line using PVC electrode adapters that are designed to screw into a ¾" NPT thread. These adapters can be installed into PVC cross with threaded bushings or by drilling, taping, and gluing the PVC pipe. The set of electrodes should be installed in the suction side of the recirculating bleach pump line, and should be in the pipe line so that the line will always be completely full when the bleach is pumped. Optionally, the ORP ring will fit between flanges. The electrodes can also be installed into the chlorination tank and since there are many ways this can be accomplished, please call the plant for suggestions. Install the set of positive and negative electrodes opposite each other as described by the electrode instruction sheet. 2. Insert the threaded titanium well into the piping to the tank. The well has a ½" NPT thread. Make sure the well is in the main stream of bleach flow or tank wall for good heat transfer. Often this is accomplished by inserting a threaded bushing into an end outlet of a tee. Make sure there are no obstructions the well will contact when screwing the titanium well into the adapter. Thread the spring loaded RTD probe holder into the well a little more than hand tight. 3. Locate the batch controller in an area of choice. The temperature of the area must be between 14 0 F and F for the meters to operate correctly. 4. The positive and negative wire from the first set of electrodes attached to the low voltage terminal board of the batch controller low voltage terminals #1 and #2 using #16 THHN copper wire. 5. The positive and negative wire from the second set of electrodes attached to the low voltage terminal board of the batch controller low voltage terminal #3 and #4 using #16 THHN copper wire. Connect temperature probe wiring as shown on the electrical print from the RTD probe to low voltage to terminals #5, #6, and #7. 6. The horn is located in the area of choice. Conduit is connected from the batch controller to the horn. The horn is connected to the high voltage terminals #4 and #5. 7. The chlorine shutoff valve, power and limit switch, optional, is wired in conduit to the batch controller. To indicate valve open position, the limit switch is connected to the high voltage terminal #8 and #9. The power for the chlorine liquid valves is connected to the high voltage terminal #6 and #7.
3 8. The 120-volt control power for the unit is connected to terminal #1, #2 and #3 on the high voltage terminal board according to the terminal board connection diagram. 9. Without the chlorine car turned on, put 120-volt power to the batch controller and adjust the meters to the desired settings. The meters have been factory programmed, however, the alarm and shutdown points may need to be adjusted. The meters are adjusted to the desired set points by entering keystrokes into the lower front panel keypad. key consecutively until desired parameter appears. Pause until the set point appears, then press the ">" key to select the next unit to be changed, and the "^" key to obtain new value. When set point is correct, press the ">" key until the right most digit flashes and press the "E" key to store the new value into memory. Pressing "X" will cancel the current operation and return the display to the scaled input value. Example: Action pressed) Press and release > Press and release ^ Display "I" Input (MVDC Reading) "P" Peak (Peak value since last time "X" was "S1" Set point one (Setpoint one) Flashing Digit Scroll to desired digit *Repeat previous steps until desired set point is displayed. Press and release E To enter value and resume normal display Press "X" To return to normal display at any time 10. After the alarms are set, prepare your caustic dilution and begin chlorination. Titrate your bleach as you chlorinate and make sure that the alarm and shutdown points are set to achieve the results you desire. Normal Set Points Please note the batch controller will control the end point of the bleach reaction since the lower the residual caustic, the higher the voltage from the electrodes. Depending on the strength of bleach you manufacture, the end point voltage will vary. The only way to determine the correct end point voltage for your system is to produce a batch of bleach by the titration method and record the millivoltage at the end of the batch. Using this end point for a reference, the controller set points can be adjusted.
4 Below are two examples for reference only. The set points of the alarm contacts are your choice. Example #1 Chlorine Control Meter (left unit) Set Point MVDC Set Point MVDC Chlorine Safety Meter (right unit) Set Point MVDC Set Point MVDC Temperature Meter (Bottom Unit) Set Point 1-85 o F Set Point 2-87 o F The above example is set up to have the system operate from the control meter for ORP and use the contacts of the safety meter for redundant control. Example #2 Chlorine Control Meter Set Point MVDC Set Point MVDC Chlorine Safety Meter Set Point MVDC Temperature Meter (Bottom Unit) Set Point 1-90 o F Set Point 2-85 o F Results in shutdown of optional chlorine valve and sounds horn. Set Point MVDC The above example show an important feature of the controller and that is the low alarm, SP1, can be set higher than the high alarm, SP2. Therefore, as in example #2, the controlling meter can be set to alarm and shutdown the chlorine valve by SP2 contact first, or the safety meter would shutdown the system using its SP2 contact. Effectively the low alarms in both meters are not being used in this example. As mentioned above, setting of the contacts is the operator s job, but if you have any problems, please call us.
5 Specifications Power Requirements 120 volt, 1 phase, 15-amp circuit NOTE: Cabinet is internally fuse protected by 2-5 amp fast blow fuses. Electrical Relay Contacts: Voltage Meter Range: Temperature Meter Range: -336 o to o Inductive at 35% P.F. Continuous - 5 amps Make - 15 amp. Break amps. Resistive at 75% P.F. Continuous, Make, and Break -5 amps 0-2 VDC with two alarm contacts External wiring provided by customer: Control power, cabinet to electrodes and thermocouple, horn and optional chlorine shutoff system. Standard Equipment: -- Two digital ORP controllers, one digital temperature meter in NEMA 4 case. -- Alarm horn. -- Two silver electrodes with Kynar holder and PVC dust cap. -- Two platinum electrodes with Kynar holder and PVC dust cap ohm RTD probe with titanium well PVC electrode holder (Four required). -- Instructions and set up procedure; wiring diagrams. Maintenance As consecutive batches are chlorinated and titrated, results are compared with the set point values, the end point alarm will begin to drift indicating dirty electrodes. Refer to electrode maintenance to clean and replace electrodes. Powell Fabrication & Manufacturing Inc 740 East Monroe Road St. Louis, MI Phone Fax info@powellfab.com L:\Literature\Batch Controllers\1800 rev2.doc
Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11
Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.
More informationCimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2
Series 21 - Specifications INDEX Description Page Operational Specification 2 Analog Operational Specification - Communications Options 3 Digital Operational Specification - Communications Options 4 Hardware
More informationWater Technologies. Strantrol System 3i. Technical Guide
Water Technologies Strantrol System 3i Technical Guide Table of Contents Warning Notifications...i Mounting Chapter 1...1 1.1 Environmental Conditions...1 Plumbing Chapter 2...3 2.1 Sample Stream General
More informationJ-PRO-22 Pump Proportional Feed Chlorinator Installation & Start-Up Guide
J-PRO-22 Pump Proportional Feed Chlorinator Installation & Start-Up Guide Thank you for purchasing a Clean Water System! Please review this start-up guide entirely before beginning to install your system
More informationJ-PRO V 230V Dual Voltage Chlorinator Installation & Start-Up Guide
J-PRO-22 110V 230V Dual Voltage Chlorinator Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance, your system will be providing
More informationMASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model
More informationCarbon Monoxide Transmitter
Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or
More informationVERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER
1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning
More informationLIQUIDATOR Electronic Ionization System
LIQUIDATOR Electronic Ionization System Operation and Installation Manual LIQUITECH LIQUIDATOR Series Electronic Controller Unit LIQUITECH Model QLTF Flow Cell LiquiTech, Inc. 421 Eisenhower Lane South
More informationOPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"
OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)
More informationModel Q45P/R. ph/orp Monitor...
Model Q45P/R ph/orp Monitor... Sensor Mounting Configurations The Differential Difference ORP Monitor ATI's versatile Q45P/R ph/orp system is designed for use in all industrial and municipal applications.
More informationProfessional Series. Chemical Feed System Model # US Patent No. 6,752,930 B2
Professional Series Chemical Feed System Model # 22152-02 US Patent No. 6,752,930 B2 Product Manual SureWater Technologies, Inc. The Solution X-2 Model # 22152-02 Table of Contents 1. Installation Instruction
More informationModel Q45P/R. ph/orp Monitor...
Model Q45P/R ph/orp Monitor... Sensor Mounting Configurations The Differential Difference ORP Monitor ATI's versatile Q45P/R ph/orp system is designed for use in all industrial and municipal applications.
More informationPowerWizard. Level 1.0 & Level 2.0 Control Systems Training
PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts
More informationAccuBrine automated brine maker Technical Specifications
Cargill Deicing Technology AccuBrine automated brine maker Technical Specifications All 4 models included Automated Blending System Model (ABM) Automated Blending Remote Truck Fill Model (ABRTF) Automated
More informationUse this Specification Template to develop a specification to be used for requesting a quote or defining a job work description.
Use this Specification Template to develop a specification to be used for requesting a quote or defining a job work description. This document is a framework for creating a specification. It may contain
More informationChlorine gas leak detector
INSTRUCTION MANUAL FOR Chlorine gas leak detector with battery back up series M 4510 C 2007 Controlmatik ABW d.o.o. 1 CONTENT 1.0 General description:... 3 2.0 The Unit... 4 3.0 Controls and Displays...
More informationORP/MILLIVOLT CONTROLLER
LAKEWOOD INSTRUMENTS MODEL 330 ORP/MILLIVOLT CONTROLLER INSTALLATION & OPERATION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, Wisconsin 53224 USA Phone (800) 228-0839 Fax
More informationDual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual
We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationSTRANTROL SET POINT CONTROLLER INSTALLATION, OPERATION & MAINTENANCE MANUAL
STRANTROL SET POINT CONTROLLER INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents General Guidelines... i Warning Notifications...ii Mounting/Plumbing...1 Mounting the Controller...1 Wrapping
More informationMASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page
More informationBeacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08
Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3
More informationph COOLING TOWER CONTROLLER
LAKEWOOD INSTRUMENTS MODEL 350 ph COOLING TOWER CONTROLLER INSTRUCTION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI 53224 USA Phone (800) 228-0839 Fax (414) 355-3508 http://www.lakewoodinstruments.com
More informationLow Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers
Low Water Cutoff (LWCO) IQ Option Card p/n 102711-01, 102714-01 for Hot Water Boilers Instruction Sheet 102-360 APPLICATION The Low Water Cutoff (LWCO) IQ Option Cards are advanced, microprocessor based
More informationElectronic Flow Switches
Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
More informationJ-PRO-22 Pump Proportional Feed Hydrogen Peroxide Installation & Start-Up Guide
J-PRO-22 Pump Proportional Feed Hydrogen Peroxide Installation & Start-Up Guide Thank you for purchasing a Clean Water System! Please review this start-up guide entirely before beginning to install your
More informationFireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
More informationPremier Hazard STC Instructions
PREMIER HAZARD Ltd Bessingby Industrial Estate Bridlington YO16 4SJ Tel: +44 (0) 113 239 1111 Fax: +44 (0) 113 239 1131 www.premierhazard.co.uk info@premierhazard.co.uk Premier Hazard STC Instructions
More informationDual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual
We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationUser Manual System 11
User Manual System 11 www.pulseinstrument.com Copyright 2007 Pulse Instruments All Rights Reserved 943 Flynn Road, Camarillo, CA 93012 Phone: (800) 462-1926 Fax: (800) 878-9172 SYSTEM 11 Water Disinfection
More informationPF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)
PF1000 CONTROLLER for the AQUARIUS I/II DEIONIZED WATER HEATING SYSTEM Heateflex Corporation 405 E. Santa Clara St. TEL: (626)599-8566; FAX: (626)599-9567 Rev. 07 10/19/10, (PF1000) 1 2 TABLE OF CONTENTS
More informationMODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT
TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel
More informationMODEL ORP/pH Digital Controller
MODEL 554000 ORP/pH Digital Controller Operating Manual Rola-Chem Digital Controller PN 554102 6/01/2012 Page: 1 of 20 QUICK START REFERENCE Use this section for reference - please read all safety instructions
More information1020 Industrial Drive, Orlinda, TN fax
Operation Manual Ultraviolet Disinfection System 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2 Theory of Operation... 2 1.3
More informationExcellence through Versatility
Controllers Excellence through Versatility Located in Acton, Massachusetts, Liquid Metronics has been providing quality products and service to the water treatment industry worldwide for over 20 years.
More informationOzone Generator and Ozone PCB Tests and Fault Troubleshooting
September 2015, SOM PAGE 1 T003. Ozone Generator and Ozone PCB Tests and Fault Troubleshooting Ozone Generator and Ozone PCB Tests and Fault Troubleshooting For specific details of the BioTector analyzer
More informationF PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.
F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com
More informationINDUSTRIAL GRADE WATER SOFTENERS LWT INDUSTRIAL SERIES
INDUSTRIAL GRADE WATER SOFTENERS LWT INDUSTRIAL SERIES 1,200,000 TO 3,000,000 GRAINS CAPACITY WATER SOLUTIONS * CUSTOM ENGINEERING * INDUSTRIAL PERFORMANCE (Single, Twin, Triple or Quadruple Demand Systems)
More informationParagon. Induced Draft, Counter Flow Optional Accessories
ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.
More information95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.
95M-200 Gas-Fired Direct Vent Modulating Hot Water Boiler Control Manual And Troubleshooting Guide P/N 24000604, Rev. C [04/09] WARNING! Revise boiler control parameters only if you fully understand the
More informationQAF64.2-J QAF64.6-J. Frost detector. for use on the air side
s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage
More informationTM Series. Induced Draft, Counter Flow Optional Accessories
ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.
More informationINSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS
INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly
More informationD350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS
D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for
More informationHOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4
HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall
More informationSEA FROST BAITFREEZER 110-VOLT AIR-WATER Twin Valve
372 ROUTE 4 BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com SEA FROST BAITFREEZER 110-VOLT AIR-WATER Twin Valve Operation and Installation
More informationEclipse 90 UV Scanner Model A Version 1
85 Instruction Manual 10/14/010 Eclipse 90 UV Model 5600-90A Version 1 C US Introduction This sensor features a high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames that cycle on and
More informationDA100 Digital Pyrometer Installation and Operating Instructions
DA100 Digital Pyrometer Installation and Operating Instructions Installation Instructions Preparation 1. Read these instructions thoroughly and ensure all steps are understood before performing installation.
More informationSPRITE Warewash Dispensing System
SPRITE Warewash Dispensing System Reference Manual DM-400 NUMERIC Series Online and downloadable Product Manuals and Quick Start Guides are available at www.hydrosystemsco.com Please check online for the
More informationCapital Controls SERIES 70CV3000 CHLOROMATIC VALVE
Capital Controls SERIES 70CV3000 CHLOROMATIC VALVE Integrated Gas Control Valve with Integral Controller The Series 70CV3000 Chloromatic Intelligent Gas Flow Control Valve is designed to control chemical
More informationLEAKSTOPPER RANGE Multizone water leak detection systems
LEAKSTOPPER RANGE Multizone water leak detection systems WHAT DOES THE PRODUCT DO? The LeakStopper detects water leaks and instantly triggers an alarm to warn you. It is capable of monitoring between 2
More informationBeacon 800 Gas Monitor Operator s Manual
Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be
More informationLEAKSTOPPER 1 Single zone water leak detection system
LEAKSTOPPER 1 Single zone water leak detection system WHAT DOES THE PRODUCT DO? The LeakStopper 1 detects the presence of water in environments where it is not supposed to be. Should water be detected
More informationCentro-Matic Automated Lubrication Systems System Controls
Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the
More informationUnfired Steam Generators (Series RB) Installation, Operation and Maintenance
Unfired Steam Generators (Series RB) Installation, Operation and Maintenance Horizontal USG Vertical USG 534-EN Please read and save these instructions Disclaimers This Installation, Operation, and Maintenance
More informationInstallation & Maintenance Manual
Installation & Maintenance Manual 12. GaSteam Parts 12.1 EXPLODED VIEW OF ENCLOSURE UG045 1 base 11 gas/electronics cover 21 flue gasket 2 electric pump gasket 12 flue cap 22 pipe fitting section 3 drain
More informationInternal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR ELECTRICAL OR HIGH-DENSITY MAGNETIC ANTI-SCALE OR WATER CONDITIONING APPLIANCE IGC 91-2009 1. PURPOSE 1.1 The purpose
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationOwner s Manual RD432-0 Chemical Controller
Owner s Manual RD432-0 Chemical Controller Table of Contents I. Introduction page 2 A. Water Chemistry page 2 B. Safety page 3 C. System Components page 4 D. Specifications page 7 E. Controller Panel Descriptions
More informationLEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL
LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water
More informationWallace & Tiernan Liquid Feed System LVN-2000 Liquid V-Notch
Wallace & Tiernan Liquid Feed System LVN-2000 Liquid V-Notch Overview continues to be the leader in the chemical feed and disinfection of potable water, wastewater and industrial process applications.
More informationPZ2 Series Manual. PROZONE INTERNATIONAL, Inc. Ozone Water Purification Systems. INSTALLATION GUIDE and OPERATION MANUAL. Prozone PZ2 Series
PZ2 Series Manual PROZONE INTERNATIONAL, Inc. Ozone Water Purification Systems INSTALLATION GUIDE and OPERATION MANUAL Prozone PZ2 Series Ozone Generator Systems SAFETY READ AND FOLLOW ALL INSTRUCTIONS.
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 1F81-51 Programmable Electronic Digital Multi-stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationWARNING Important Safety Information
1 Specifications Premier Series Non-Programmable Thermostats MODEL 3000 MODEL 3200 1 2 3 4 Specifications Installation Testing Your New Thermostat Programming User Settings WARNING Important Safety Information
More informationOzone Generator Systems
PZ2-4V - Commercial and Residential Pools & Spas Ozone Generator Systems INSTALLATION GUIDE and OPERATION MANUAL T. O3 NATURAL TECHNOLOGY Reduces Chemical Usage, Improves Sanitation Produces Crystal Clear
More informationwww.severntrentservices.com CAPITAL CONTROLS Series 70CV3000 Chloromatic TM Intelligent Gas Flow Control Valve The Series 70CV3000 Chloromatic TM Intelligent Gas Flow Control Valve is designed to control
More informationSprite III Warewash Dispensing System
Sprite III Warewash Dispensing System Reference Manual DM-700 Series Online and downloadable Product Manuals and Quick Start Guides are available at www.hydrosystemsco.com Please check online for the latest
More informationTempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications
Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates
More informationINSTALLATION & OPERATION MANUAL
INSTALLATION & OPERATION MANUAL ALARM, DIVERT TO DRAIN MODEL: 00850244 Manufactured With Pride In The USA www.ameriwater.com 800-535-5585 AmeriWater 3345 Stop 8 Rd. Dayton, OH 45414 PN 98-0113 REV B proposed
More informationLXGeR and LXGePR GLASSWASHER
Item # Quantity C.S.I. Section 11400 and STANDARD FEATURES Racks per hour Light Normal 30 24 38 29.62 gallons of water per rack 1.14 gallons of water per rack Hot water or chemical sanitation units available
More informationWATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00
I&M NUMBER: 316-42-16-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More informationIMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS
Operating Manual MODELS RC554XP AND 554000 ORP/pH Digital Controller FEED ph ALERT FEED ORP ALERT F LOW ph MODE AUTO FEED ONCE SET LEVEL FEED TIME HI LOW ph CALIB ORP ph ORP IMPORTANT SAFETY INSTRUCTIONS
More informationDIGITAL METERS Large Display Temperature Meters Instruction Manual
DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large
More informationORP (mv) Controller Model: ORP-XP2. UP DOWN ENTER Time & Date Main Menu Alarm Reset
Instruction Manual ORP (mv) Controller Model: ORP-XP2 Power Control Alarm Comms UP DOWN ENTER Time & Date Main Menu Alarm Reset Supplied by: Convergent Water Controls Pty Ltd 2/4 Huntley Street, PO Box
More informationSTRANTROL SYSTEM3 INSTALLATION, OPERATION & MAINTENANCE MANUAL
STRANTROL SYSTEM3 INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents SECTION PAGE Introduction Shipping Package Contents... 1 General Guidelines... 1 Warning Notifications...2 Part I: Mounting/Plumbing...5
More informationMODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL
TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External
More informationLEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL
LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,
More informationAQUAS POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: APN 1000, 1250, 1500, and 2000 AQUAS Pool Package
100298232_2000552224_Rev A AQUAS POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: APN 1000, 1250, 1500, and 2000 AQUAS Pool Package The AQUAS pool package system is a high efficiency commercial condensing
More informationLGB Gas fired boiler
LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms
More informationArmstrong Flo-H2O Water to Water Instantaneous Heater Installation and Maintenance & Operation
Armstrong Flo-H2O Water to Water Instantaneous Heater Installation and Maintenance & Operation AY-414 This bulletin should be used by experienced personnel as a guide to the installation and maintenance
More informationLAKEWOOD INSTRUMENTS MODEL 353 ORP/MILLIVOLT CONTROLLER
LAKEWOOD INSTRUMENTS MODEL 353 ORP/MILLIVOLT CONTROLLER INSTRUCTION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI 53224 USA Phone (800) 228-0839 Fax (414) 355-3508 http://www.lakewoodinstruments.com
More informationJ-PRO V 230V Dual Voltage Hydrogen Peroxide Pump Installation & Start-Up Guide
J-PRO-22 110V 230V Dual Voltage Hydrogen Peroxide Pump Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance, your system
More information24 VAC SYSTEM CONTROL KIT
24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas draft induced appliances with a 24 VAC Gas Valve and a 30-millivolt
More informationINSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER
INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER LOVE LOVE CONTROLS a Division of Dwyer Instruments, Incorporated PO Box 338 Michigan City, IN 46361-0338 (800) 828-4588 (219) 879-8000 FAX (219)
More informationINSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST DC3002 and DC3003 SOLID STATE LEAD/LAG CONTROLLER with DC FAN CONTROL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just
More informationWATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00
I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be
More information873A Series Electrochemical Analyzers ph, Contacting Conductivity, Electrodeless Conductivity, and Resistivity
Product Specifications PSS 6-1C1 F 873A Series Electrochemical Analyzers ph, Contacting Conductivity, Electrodeless Conductivity, and Resistivity METAL ENCLOSURE VERSION MOUNTING HARDWARE NOT SHOWN EASY-TO-USE
More informationDMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 DMWD 1 to 4 Zone Water Detection with Distance to Leak Measurement Installation and Operation Manual
More informationTempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications
Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates
More informationMODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL
MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL TABLE OF CONTENTS Product Overview... 2 Operation... 3 Installation... 5 Troubleshooting... 9 Ordering Information, Warranty and Service...10
More informationRQE Series Temperature Controllers
RQE Series Temperature Controllers For more than 45 years, Thermal Care has manufactured industrial temperature control equipment with the best available component technologies. Our RQE Series mold temperature
More informationRamsey Motion Monitoring Systems
Ramsey Motion Monitoring Systems 60-200 Motion Monitoring Accurate Sensing of Underspeed, Overspeed and Zero Speed Conditions on Rotating Shafts and Machinery The Ramsey Series 60-200 Motion Monitoring
More informationUV Scanner. Model Specification. Introduction. 854 Instruction Manual
854 Instruction Manual 10/11/010 UV Model 5600-91 C US Introduction This sensor features a high temperature and high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames in applications that
More information24 VAC Intermittent Pilot Gas Ignition Control
C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame
More informationWATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2
I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More informationU-CLASS SPA SYSTEMS. Dealer TechBook by Gecko Alliance. Technical Specifications, Programming, Installation & User's Instructions!
U-CLASS SPA SYSTEMS Dealer TechBook by Gecko Alliance Technical Specifications, Programming, Installation & User's Instructions! UC-CF TABLE OF CONTENTS Specifications 2 Description System features Electrical
More informationBeacon 110 Gas Monitor Operator s Manual
Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 1F83-51 Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL
More informationStancor Duplex Oil-Minder System Submittal SE Volt Single Phase Duplex SE-100 Pumps with Floats and Oil-Minder Probe
Stancor Duplex Oil-Minder System Submittal SE-100 115 Volt Single Phase Duplex SE-100 Pumps with Floats and Oil-Minder Probe Solid State, NEMA 4x Duplex Oil-Minder Control The Stancor Duplex Oil-Minder
More information