Application Note on Reading the Vigilohm IM400 Insulation Monitoring Device Installed in Conext Core XC and XC-NA Series Inverters

Size: px
Start display at page:

Download "Application Note on Reading the Vigilohm IM400 Insulation Monitoring Device Installed in Conext Core XC and XC-NA Series Inverters"

Transcription

1 Application Note on Reading the Vigilohm IM400 Insulation Monitoring Device Installed in Conext Core XC and XC-NA Series Inverters AP-XC-001-EN Revision B DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and incorporates by reference, the relevant product manuals for the Schneider Electric Conext Core XC and XC-NA Series Grid- Tied Photovoltaic Inverters. Before reviewing this Application Note you must read the relevant product manuals. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding. Failure to follow these instructions will result in death or serious injury. Audience This Application Note is intended for anyone who will operate the Conext Core XC and XC-NA Series Grid Tie Photovoltaic Inverter. Operators must be familiar with all the safety regulations pertaining to operating high-voltage equipment as dictated by local code. Operators must also have a complete understanding of this equipment s features and functions. Overview Certain versions of the Schneider Electric Conext Core XC and XC-NA Series use a Vigilohm IM400 Insulation Monitoring Device to monitor insulation resistance of the inverter and its associated components (for example, the medium voltage transformer and PV array) to ground in a floating PV system. The IM400 device is located inside the DC cabinet, as shown in Figure 1 on page 2. The inverters have a feature that will allow the DC cabinet door to be opened without interrupting inverter operation (opening any other doors will interrupt inverter operation). This feature is intended only to allow the DC cabinet door to be opened to read the display of the Vigilohm insulation monitoring device, and must be closed again immediately after reading the display. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE Do not open any cabinet doors on the Conext Core XC and XC-NA Series inverter other than the DC cabinet door, and do not remove any barriers inside the DC cabinet. Failure to follow these instructions will result in death or serious injury.

2 DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE The settings on the Vigilohm IM400 Insulation Monitoring Device are configured in the factory and may be changed only by Schneider Electric authorized service personnel. Do not attempt to change the settings. Failure to follow these instructions will result in death or serious injury. HAZARD OF EQUIPMENT DAMAGE NOTICE Close the DC cabinet door as soon as you have read the display of the isolation monitor. Avoid longer than necessary operation with the DC cabinet door open. Failure to follow these instructions can result in damage to equipment, can compromise the environmental protection of the inverter. DC cabinet Vigilohm IM400 insulation monitoring device Conext Core XC Series DC cabinet Conext Core XC-NA Series Figure 1 Location of the Vigilohm IM400 device 2 AP-XC-001-EN Revision B

3 Indicator Lights The IM400 indicator lights are illustrated in Figure 2 and described in Table 1. IM400 Status (red) Not in use in Conext Core XC and XC-NA Series inverters Insulation Status (green) Not in use in Conext Core XC and XC-NA Series inverters Insulation Alarm (yellow) Figure 2 IM400 indicator lights appearing on the IM400 device in a particular Conext Core XC and XC-NA Series installation may be different. Table 1 Indicator lights IM400 Status Insulation OK Insulation Alarm Description Vigilohm IM400 de-energized. OFF OFF OFF OFF ON OFF Vigilohm IM400 energized. No insulation fault detected. OFF OFF ON Vigilohm IM400 energized. Insulation fault detected. OFF OFF Flashing Vigilohm IM400 energized. No insulation fault detect but transient insulation fault has been detected. OFF OFF Vigilohm IM400 energized but inoperative. Call for service. AP-XC-001-EN Revision B 3

4 Reading the IM400 Insulation Monitoring Device Normal Operation The IM400 device continually measures insulation resistance of the inverter, PV array, and its associated components to ground and displays the readings on the IM400 user interface. This section describes the status of the indicator lights on the IM400 user interface during normal operation, when an insulation fault occurs, and when the insulation fault is determined to be transient. When the measured insulation resistance is at acceptable levels, the IM400 displays the green Insulation OK indicator light (see Figure 3). The Insulation OK light is green. Insulation Fault Figure 3 Sample IM400 screen during normal operation appearing on the IM400 device in a particular Conext Core XC and XC-NA Series installation may be different. When the IM400 measures a decrease in insulation resistance below acceptable levels, the device records an error and sends a signal to the inverter s control logic that a ground fault has occurred. The device also displays the Ins. Alarm screen, turns off the green Insulation OK indicator light, and turns on the yellow Insulation Alarm indicator light (see Figure 4 on page 5). The Insulation Alarm indicator light remains on and the display screen flashes continually until the resistance levels rise to within the normal range. 4 AP-XC-001-EN Revision B

5 Note: The date and time information on the status bar of the Ins. Alarm display screen is not one of the supported features of Conext Core XC and XC-NA Series and should be ignored. The display screen flashes. The Insulation Alarm light is yellow. Transient Fault Figure 4 Sample IM400 display screen when an insulation fault occurs appearing on the IM400 device in a particular Conext Core XC and XC-NA Series installation may be different. If the insulation resistance returns to normal levels after an insulation alarm event occurs, the IM400 changes the Insulation Alarm indicator light from a steady yellow to flashing yellow and turns on the green Insulation OK light (see Figure 5). The display screen stops flashing and changes to the normal operation screen (see Normal Operation on page 4). The Insulation OK light is green. The Insulation Alarm light flashes yellow. Reset button Figure 5 Sample IM400 display screen when a transient fault occurs appearing on the IM400 device in a particular Conext Core XC and XC-NA Series installation may be different. The yellow Insulation Alarm light will continue to flash until it is reset manually. To reset it, press the lowest button in the three-button column on the IM400 device (see Figure 5). AP-XC-001-EN Revision B 5

6 Copyright 2013 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS DOCUMENTATION IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT Date: December 2013 Revision: Revision B Document Number: AP-XC-001-EN Contact Information For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: 6 AP-XC-001-EN Revision B

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM # Manual Number: 01-62-768 Revision : 1.2 Date: 03/20/17 Installation Instructions Remanufactured Veeder-Root Overfill Alarm and Acknowledgement Switch Overfill Alarm PMP # 62625 OEM # 790091-001 Acknowledgement

More information

Safety Function: Single-beam Area Access Control (AAC)

Safety Function: Single-beam Area Access Control (AAC) Application Technique Safety Function: Single-beam Area Access Control (AAC) Products: Guardmaster Dual-input Safety Relay, Single-beam Area Access Control Sensors with E-stop Safety Rating: CAT. 4, PLe

More information

RTO. User guide 05/

RTO. User guide 05/ RTO User guide Version: RT0 M&S (master & slave) Characteristics: Constant lighting, temperature regulation with a low inertia heating system. Building opening hour scheduler and presence detection. 05/2013

More information

Ultrasonic Wall Switch Occupancy Sensor Single Circuit

Ultrasonic Wall Switch Occupancy Sensor Single Circuit Instruction Bulletin 63249-420-414A1 02/2014 Ultrasonic Wall Switch Occupancy Sensor Single Circuit Commercial Grade with Ground, Single and Multi Location Switching SLSUWS1277C and SLSUWS3277C Retain

More information

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL. Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3

More information

AN FXPS7xxx series pressure sensor self-test features. Document information

AN FXPS7xxx series pressure sensor self-test features. Document information Rev. 1 15 November 2018 Application te Document information Information Keywords Abstract Content self test, digital barometric absolute pressure (DBAP), absolute pressure sensor, engine management, comfort

More information

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root # Manual Number: 01-61-141 Revision : 1.7 Date: 10/27/16 Installation Instructions Remanufactured Veeder-Root Position Sensitive Sump Sensor PMP # 62323 Replaces Veeder-Root #794380-323 Contents Disclaimer...

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit Instruction Bulletin 63249-420-418A1 02/2014 Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit Commercial Grade with Ground SLSPWD1277C Retain for Future Use INTRODUCTION The Passive Infrared

More information

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS LV-S-5 DIRECT CONTACT STRAY VOLTAGE DETECTOR Instruction Manual GENERAL DESCRIPTION The LV-S-5 is a hand held stray voltage detector for testing exposed metallic surfaces and conductors for the presence

More information

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10 Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10 Installation Manual FANKIT02-IA-US_en-10 IMUS-FANK-TL21 Version 1.0 CA US SMA America, LLC Legal Restrictions Legal Restrictions Copyright 2013

More information

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors Manual Number: 01-61-133 Revision : 1.8 Date: 10/27/16 Installation Instructions Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors PMP # 62322, 62352 Replaces Veeder-Root

More information

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209 Manual Number: 01-60-291 Revision : 5.6 Date: 12/11/15 Installation Instructions Remanufactured Veeder-Root Sump Sensor PMP # 62208, 62209 Replaces Veeder-Root #794380-208, -209 Contents Disclaimer...

More information

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10 Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10 Installation Manual FANKIT02-IA-US_en-12 Version 1.2 CA US SMA America, LLC Legal Restrictions Legal Restrictions Copyright 2014 SMA America,

More information

Installation and operation manual

Installation and operation manual Installation and operation manual - + BRC1HHDAW BRC1HHDAS BRC1HHDAK English Table of contents Table of contents 1 General safety precautions 2 1.1 For the user... 2 1.2 For the installer... 2 2 About this

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Ion Endeavor Controller Digital Level Control with Alternation Page 1 of 8 General Overview The Ion Endeavor is a pump controller that senses a water level of up to 72", has a configurable water level/pump

More information

Vigilohm IM10-H, Vigilohm IM20-H

Vigilohm IM10-H, Vigilohm IM20-H Vigilohm IM10-H, Vigilohm IM20-H VIGED310023EN 09/2011 Vigilohm IM10-H, Vigilohm IM20-H Insulation Monitoring Device for Hospitals User Manual 09/2011 VIGED310023EN www.schneider-electric.com The information

More information

FiRe mobile-2 Operation Manual

FiRe mobile-2 Operation Manual FiRe mobile-2 Operation Manual P/N 00-3230-505-0003-01 ISS 07JAN15 Copyright Trademarks and patents Manufacturer Version 2015 UTC Fire & Security. All rights reserved. The FiRe mobile-2 name and logo are

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS N99V /99 PRM Polarity Reversing Module What is the PRM? The PRM Polarity Reversing Module is used to reverse the polarity of the positive and negative voltages powering smoke

More information

Square D Clipsal Outdoor Light-Level Sensor

Square D Clipsal Outdoor Light-Level Sensor Square D Clipsal Outdoor Light-Level Sensor SLC5031PEWP for Use with C-Bus Wired Networks Instruction Bulletin Retain for future use. Square D Clipsal Outdoor Light-Level Sensor 63249-420-231A3 Instruction

More information

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

CoMo-Control. Operating Manual. English (translation of original instructions) Documentation no.: a

CoMo-Control. Operating Manual. English (translation of original instructions) Documentation no.: a Operating Manual English (translation of original instructions) Documentation no.: 3404207a Trademarks The trademarks of other companies are exclusively used for the products of those companies. Copyright

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460 Manual Number: 01-60-309 Revision : 5.5 Installation Instructions Remanufactured Veeder-Root Steel Tank Interstitial Sensor PMP # 62420, 62460 Replaces Veeder-Root #794380-420, -460 Contents Disclaimer...

More information

Manual No: Revision: D. Sump Sensor. Installation Guide

Manual No: Revision: D. Sump Sensor. Installation Guide Manual No: 576013-301 Revision: D Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Gardian W51. Approvals

Gardian W51. Approvals Gardian W51 120 V pre-assembled electric heating cables for pipe freeze protection and roof & gutter de-icing Installation Instructions Description Gardian W51 120 V pre-assembled self-regulating heating

More information

COOPER POWER SERIES. S.T.A.R. TM Fiber optic cable installation instructions. Fault Indicators MN320004EN. Fiber optic fitting (To led display)

COOPER POWER SERIES. S.T.A.R. TM Fiber optic cable installation instructions. Fault Indicators MN320004EN. Fiber optic fitting (To led display) Fault Indicators MN320004EN Effective March 2017 Supersedes August 2004 (S320-42-2) S.T.A.R. TM Fiber optic cable installation instructions COOPER POWER SERIES Fiber optic fitting (To led display) Mounting

More information

Industrial Strength Leak Detection

Industrial Strength Leak Detection Industrial Strength Leak Detection Don t let an undetected leak or spill ruin the environment or your reputation... TraceTek Technology: Find leaks before major damage is done... TraceTek Technology: Sensor

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC 2CKA001473B9007 19.05.2017 System Manual Busch-Infoline Handicapped toilet signal set 1510 UC-... -101 Table of contents Table of contents 1 Notes on the instruction manual... 3 2 Safety... 4 2.1 Information

More information

QuickStat-TC Installation & Operation Manual

QuickStat-TC Installation & Operation Manual QuickStat-TC Installation & Operation Manual General Information A F Use of this Manual This manual covers the installation and operation of the Raychem QuickStat-TC thermostat and must be used with the

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61975 Edition 1.0 2010-07 High-voltage direct current (HVDC) installations System tests INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XC ICS 29.130.10; 31.080.01 ISBN

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

Duct Mount. Installation Instructions

Duct Mount. Installation Instructions Duct Mount Installation Instructions 00809-0600-4975 Legal Notice The Flame Detector described in this document is the property of Rosemount. No part of the hardware, software, or documentation may be

More information

COOPER POWER SERIES. CT Protector Retrofit Kit. Voltage Regulators MN225057EN. Effective March 2017 Supersedes March 2010 (S )

COOPER POWER SERIES. CT Protector Retrofit Kit. Voltage Regulators MN225057EN. Effective March 2017 Supersedes March 2010 (S ) Voltage Regulators MN225057EN CT Protector Retrofit Kit Effective March 2017 Supersedes March 2010 (S225-50-55) COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below.

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below. Important notice Dear Customer, On 7 February 2017 the former NXP Standard Product business became a new company with the tradename Nexperia. Nexperia is an industry leading supplier of Discrete, Logic

More information

KFP-CF Series Operation Manual

KFP-CF Series Operation Manual KFP-CF Series Operation Manual P/N 501-415103-2-31 REV 03.10 ISS 13NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire

More information

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL OWNERS MANUAL CARBON MONOXIDE DETECTOR MODELS Panel mount and Remote Detectors (R) (353 and 353R) 353 FAMILY MODEL OWNERS/INSTALLATION MANUAL Page 1 of 22 LOG OF REVISIONS REV NO. PAGE NO. DATE DESCRIPTION

More information

For use with models: BP , BP , BP

For use with models: BP , BP , BP For use with models: BP2400-24, BP2400-110, BP2400-220 For safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit. Thank You for Choosing The

More information

EN Z Subject to change due to technical improvements! Operating instructions

EN Z Subject to change due to technical improvements! Operating instructions SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE Operating instructions Temperature differential controller 3 inputs, 1 output These operating instructions are part of the product. Read

More information

Power Management Module-c (PMM-c)

Power Management Module-c (PMM-c) Power Management Module-c (PMM-c) 60 160 kva Installation, Operation and Maintenance 11/2013 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider

More information

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits 01 VAMP 120 & 121 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during work

More information

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL. Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...

More information

Central Inverter SUNNY CENTRAL 500-US

Central Inverter SUNNY CENTRAL 500-US Central Inverter SUNNY CENTRAL 500-US Maintenance Manual SC500U-eng-WH-IUS115210 98-4107310 Version 1.0 CA US SMA America, LLC Legal Restrictions Copyright 2012 SMA America, LLC. All rights reserved.

More information

BLT-999W-2 Item # 60757

BLT-999W-2 Item # 60757 BLT-999W-2 Item # 60757 2 Read these instructions completely before beginning installation. Failure to follow them could cause a heater malfunction resulting in serious injury and/or property damage. WARNING:

More information

Infrared Thermometer

Infrared Thermometer 572-2 Infrared Thermometer PN 4307046 March 2013, Rev. 1, 08/13 2013 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their

More information

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL No moving parts to stick, wear or hang-up. 20 Series Pump Control Low Water Cut-Off Combination 120 VAC Operating Voltage Max. Pressure 20 psi LISTED No replacement or rebuilding of floats or mechanical

More information

Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW. Installation Instructions REGISTERED DESIGN

Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW. Installation Instructions REGISTERED DESIGN Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW Installation Instructions REGISTERED DESIGN Copyright Notice The concepts, products and designs described in this document are the subject of

More information

700G Series. Pressure Gauge. Safety Information

700G Series. Pressure Gauge. Safety Information Safety Information 700G Series Pressure Gauge PN 4098606 November 2011 2011 Fluke Corporation. All rights reserved. Printed in USA. All product names are trademarks of their respective companies. LIMITED

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual for Model 2100 Fire+Smoke systems from Smoke Guard, Inc. 287 N. Maple Grove - Boise, ID 83704 Phone: (800) 574-0330 Fax: (208) 639-7851 E-Mail: info@smokeguard.com Website:

More information

Important Safeguards. Save these instructions for future reference. (continued on next page)

Important Safeguards. Save these instructions for future reference. (continued on next page) User Guide 2. Important Safeguards WARNING To reduce the risk of fire, electric shock or other injury, read and follow the safety precautions and instructions in this User Guide. Save these instructions

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

Vigilohm IM10, Vigilohm IM20

Vigilohm IM10, Vigilohm IM20 Vigilohm IM10, Vigilohm IM20 VIGED310022EN 09/2011 Vigilohm IM10, Vigilohm IM20 Insulation Monitoring Device User Manual 09/2011 VIGED310022EN www.schneider-electric.com The information provided in this

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual H-IM-LLC February 2018 Part No. 25092501 Replaces H-IM-LLC (01/2014) Lead Lag Control System Table of Contents General Safety Information 2 Inspection 2 Warranty Statement

More information

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature Critical Environment Technologies Canada Inc. Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature OPERATION MANUAL REV: A JUNE-2-2008 #145, 7391 Vantage Way Delta, BC V4G 1M3 Canada Phone:

More information

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS KSAIF KSAIF0501AAA & KSAIF0601AAA Wi-Fi Interface Kit for Ductless Systems INSTALLATION INSTRUCTIONS NOTE: Read and become familiar with these instructions before beginning installation. TABLE OF CONTENTS

More information

CabLite ECO Installation Manual

CabLite ECO Installation Manual CabLite ECO Installation Manual REV : 4.1 DATE: 1/17/2018 MANUAL NUMBER : 32 ELECTRONIC CONTROLS, INC. 7073 NORTH ATLANTIC AVE CAPE CANAVERAL, FL 32920 WWW.ECIAMERICA.COM REV DATE DESCRIPTION 1.0 10/28/2013

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Manual No: 577013-838 Revision: B Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including,

More information

Infrared Thermometer. Getting Started

Infrared Thermometer. Getting Started 572-2 Infrared Thermometer Getting Started PN 4307046 March 2013 2013 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their

More information

NEMA Standards Publication SB Fire Service Annunciator and Interface

NEMA Standards Publication SB Fire Service Annunciator and Interface NEMA Standards Publication Fire Service Annunciator and Interface Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1847 Rosslyn, Virginia 22209 www.nema.org All

More information

INTRODUCTION / TABLE OF CONTENTS

INTRODUCTION / TABLE OF CONTENTS 1 2 INTRODUCTI / TABLE OF CTENTS Step One The LVCN 51 Series Continuous Relay Controller is a general purpose level controller which provides single tank level indication with dual relays and a repeater

More information

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788 PNEUMERCATOR Liquid Level Control Systems LEAK/POINT LEVEL ALARM CONSOLE OPERATION MANUAL DRAWING NO. 20068 REV. N/C MODEL COPYRIGHT 2017 PNEUMERCATOR CO., INC. 1785 EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

Satchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES

Satchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES Satchwell DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL DC1100 Specification No. 04-03-105 The DC1100 energy controller is a self configuring optimiser/

More information

GEM-C Wireless User & Installation Manual. Revision October Apollo Solar Electric Limited. Documentation

GEM-C Wireless User & Installation Manual. Revision October Apollo Solar Electric Limited. Documentation Documentation GEM-C Wireless User & Installation Manual Revision October 2014 Apollo Solar Electric Limited Contents GEM-C Wireless User Manual 3 Important Safety Information 3 Introduction 4 The GEM-C

More information

JOVY SYSTEMS RE User Manual Rev. 1.00

JOVY SYSTEMS RE User Manual Rev. 1.00 JOVY SYSTEMS RE-7550 User Manual Rev. 1.00 Index - Introduction... 3 - Copyrights and Liability disclaimer........ 3 - Specifications.. 4 - Safety/ Caution instructions....... 4 - RE-7550 hardware description......

More information

AN10943 Decoding DTMF tones using M3 DSP library FFT function

AN10943 Decoding DTMF tones using M3 DSP library FFT function Rev. 1 17 June 2010 Application note Document information Info Content Keywords M3, LPC1300, LPC1700, DSP, DFT, FFT, DTMF Abstract This application note and associated source code example demonstrates

More information

Arc Flash Analysis. Arc flash hazard analysis is required to determine the risk to personnel, warn them of the

Arc Flash Analysis. Arc flash hazard analysis is required to determine the risk to personnel, warn them of the GROUP Arc Flash Analysis Arc Flash Hazard Analysis : Arc flash hazard analysis is required to determine the risk to personnel, warn them of the hazards, and to instruct working personals as to what kind

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

Paralda Air Purifier USER MANUAL

Paralda Air Purifier USER MANUAL Paralda Air Purifier USER MANUAL www.alencorp.com 1 2 Helping People Live Better Table of Contents Air Purifier Safety Know Your Air Purifier Care & Maintenance Why You Should Replace Your Filter Alen

More information

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com Read and Save These Instructions Horizon Galaxy - Installation and Operations Manual Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC 27505 www.horizondehumidif iers.com 1 Safety Notes: The Horizon

More information

External Wireless Sounder

External Wireless Sounder External Wireless Sounder Model: WL RWS401 Installation and Programming Instructions Table of Contents Introduction... 3 Operational Functions... 3 Alarm / Tamper Indication... 3 Low Battery Indication...

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

Contents. English. French. Spanish

Contents. English. French. Spanish Contents Language Page English French Spanish 0 TABLE OF CONTENTS Topic INVENTORY OF CONTENTS QUICK SETUP DETAILED SETUP GUIDE BATTERY INSTALLATION 12 OR 24 HOUR TIME DISPLAY TIME SETTING FEATURES MIN

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories Operating & Instruction Manual 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980

More information

6502B RF Distribution

6502B RF Distribution 6502B RF Distribution User Guide Revision A - March 2004 Part Number 15247-201 Table of Contents Table of Contents About this User Guide Purpose...................................................... 1

More information

Model Number Structure

Model Number Structure Element Burnout Detector Accurate Detection of Element Burnout Regardless of Capacities Accurately detects a burned heater element or elements incorporated by a molding machine or packing machine and outputs

More information

English. Instruction and operation manual S 530. Leak detector for pneumatic systems

English. Instruction and operation manual S 530. Leak detector for pneumatic systems English Instruction and operation manual Leak detector for pneumatic systems Dear Customer, Thank you for choosing our product. The operating instructions must be read in full and carefully observed before

More information

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Page 1 of 8 General Overview Thank you for purchasing an Ion Genesis controller. Take the time to read the instructions carefully before using this appliance. We strongly recommend that you keep this instruction

More information

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where hydrogen gas may be present INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS Protects Life, Property, and Profits Compliant

More information

English. Instruction and operation manual S 530. Leak detector for pneumatic systems

English. Instruction and operation manual S 530. Leak detector for pneumatic systems English Instruction and operation manual S 530 Leak detector for pneumatic systems Dear Customer, thank you for choosing our product. The operating instructions must be read in full and carefully observed

More information

MLS. ALPHA-PAGE-LT v5.3. Contact monitoring-paging system. installation/owners manual #AP-LT53. Micro Logic Systems. phone 866-MLS-FREE

MLS. ALPHA-PAGE-LT v5.3. Contact monitoring-paging system. installation/owners manual #AP-LT53. Micro Logic Systems. phone 866-MLS-FREE MLS Micro Logic Systems ALPHA-PAGE-LT v5.3 Contact monitoring-paging system installation/owners manual #AP-LT53 Micro Logic Systems phone 866-MLS-FREE INTRODUCTION Alpha-Page-LT is a paging interface system

More information

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions Ceiling-Mounted Motion Detector 752/CD, 752/CP, 752/CU and 752/Cx180 Installation Instructions Contents 1.0 Description...3 1.1 Contents of the Box...3 2.0 Safety...4 3.0 Coverage Patterns...4 3.1 PIR

More information

VESDAnet Interface Card Product Guide. Document Number: 10672_05 Part Number: 30071

VESDAnet Interface Card Product Guide. Document Number: 10672_05 Part Number: 30071 VESDAnet Interface Card Product Guide Document Number: 10672_05 Part Number: 30071 Xtralis VESDA VESDAnet Interface Card Product Guide Intellectual Property and Copyright This document includes registered

More information

ALARM OUTPUT MODULE. Product #7736

ALARM OUTPUT MODULE. Product #7736 ALARM OUTPUT MODULE The Alarm Output Module (AOM) enables you to use weather station alarms or commands from your computer to automatically start or stop external devices such as indicator lights, audio

More information

T100 Air Purifier USER MANUAL

T100 Air Purifier USER MANUAL T100 Air Purifier USER MANUAL www.alencorp.com 1-800-630-2396 1 2 Helping People Live Better Table of Contents Air Purifier Safety Using Your Air Purifier Operating Your Unit Identification Of Parts Know

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. Multispectrum IR Flame Detector X3301 SAFETY MANUAL Multispectrum IR Flame Detector X3301 SAFETY-CERTIFIED MODEL X3301 MULTISPECTRUM INFRARED DETECTOR This manual addresses the specific requirements and recommendations applicable to the proper

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Manual No: Revision: D. Mag Sump Sensor. Installation Guide Manual No: 577013-812 Revision: D Mag Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector EN Motion detector themova S360-101 DE WH 1030565 themova S360-101 DE GR 1030566 themova S360-101 AP WH 1030555 themova S360-101 AP GR 1030556 1. Product characteristics 307067 Passive infra-red motion

More information

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL Copyrights 2007 Victron Energy B.V. All Rights Reserved This publication or parts thereof, may not be reproduced in any form, by any method, for any purpose.

More information

Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters

Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters Page 2 A NEMA Low Voltage Distribution Equipment Section Document ABP 11-2016 Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters Published by National Electrical Manufacturers Association

More information