1 Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for the protection of student, staff and visitors lives as well as property. It is therefore the policy of this department to inspect and repair AISD Life Safety Systems in accordance with National, State, local ordinances, and within this document. To provide these services LSS personnel will comply with department policy and procedure, in addition LSS personnel will be On Call as required. II. ADMINISTRATION The Life Safety Systems (LSS) Section is a component of the AISD Police Department and is under the direct supervision of the LSS Section Supervisor. The authority and responsibility of personnel assigned to the LSS Section are those outlined in the approved AISD job descriptions for Alarm Tech I, II, & III, Suppression Tech I & II, Video System Administrator, Access Control Clerk, LSS Foreman, and LSS Supervisor. III. PROCEDURE 1. Communications a. In addition to logging in and out on the AISD Time and Attendance, LSS personnel will advise dispatch of start of duty upon arrival at work and end of duty when ending shift. b. Upon arrival at a service location LSS personnel will notify dispatch. The technician will provide the dispatcher with the work order number associated with the location of work. If a work order is not assigned, the technician will provide dispatch with a description of service to be provided at the location. When the technician leaves the location, the technician will notify the dispatcher of the completed assignment. If the work order is not completed the dispatcher shall be informed. c. LSS Supervisor and/or Foreman are to review and assign work orders daily to ensure all work orders are processed in a timely manner. d. Close all completed work orders by the end of the work shift. Any work orders which require multiple days of service will be noted in the work order system (i.e. parts ordered, additional equipment/personnel needed, prohibited by inclement weather, etc). e. When a service call or work order for a repair of Fire Alarm or Fire Suppression System does not result in the system being 100% operable, the employee shall transmit a System Impairment Notification stating the system status to the LSS foreman and the Supervisor prior to ending that work shift. 2. Inspection, Maintenance, and Repair a. Technicians will coordinate Life Safety Systems inspections and repairs with AISD dispatch and the campus or facilities manager (ex. would be activation/testing of audible alarms). b. LSS personnel will conduct and/or verify that contractor inspections are performed in accordance with the most current National, State and local Codes.

2 c. After inspections are completed the appropriate service label or tag shall be applied in accordance with state law and/or local code. d. Inspection reports shall be completed, scanned, and entered on the AISD Police Department W drive consistent with existing file protocol. e. All systems shall be repaired as needed to maintain a minimum of a 97% operations rate. 3. On Call procedures: To provide a level of service consistent with our goal of maintaining LSS at or above 97% operability, it is necessary that LSS personnel serve on-call duty as required and outlined below. a. On-call technicians begin their seven day on-call cycle at 6:00 a.m. Tuesday and remain on call until 6:00 a.m. the following Tuesday. b. On call technicians are to acknowledge every page by calling the dispatcher within 10 minutes or as soon as possible after receipt of the page. Additionally, the on-call technician will inform the dispatcher of his/her estimated arrival time at the location to be serviced. If the service call does not require immediate response and/or does not pose an immediate threat of harm and/or loss of property then the item may to be placed on the blotter for action during regular working hours. c. In the event of an audible alarm that is disrupting a school in session, the on call technician will first phone the location in an attempt to walk the staff through the procedure to silence an alarm. d. On-call technicians are on call 24 hours a day. In the event a technician is on-duty, the on duty technician will be notified of any problem before the on-call technician is notified. The on-duty technician will determine if the on-call technician is required to respond. The alarm supervisor and/or foreman may designate an alternate on-call technician as incidents and call-outs dictate. e. An on-duty technician may be called to trouble shoot an issue; however the on-call technician is still responsible for responding to all pages received from dispatch. f. The on-call technician will contact the dispatcher to close the CAD number assigned to a service call upon completion of the call. g. On-call technicians will respond to all fire alarm trouble conditions. A comprehensive listing of fire events and Life Safety personnel responsibilities is available on the W- drive. h. On-call technicians will respond to security alarm trouble conditions where the security system causes the campus/property to be at risk of property loss or is substantially unprotected, and if the alarm sends trouble or alarm signals continuously (run away alarms). i. The following issues are considered to be maintenance rather than emergency calls and can be deferred by having the item placed on the blotter: Low battery signal (provided power is present), Telco 1 OR Telco 2 (not both), sounder relay troubles, smoke detector calibration troubles and RF supervision troubles. In addition, in the event of a fire or fire sprinkler system activation at an AISD facility, AISD dispatch shall notify the LSS Supervisor, Foreman, and the on call technician. 2

3 The LSS supervisor shall provide the AISD Police Dispatch supervisor with a matrix that identifies and defines Micro Key automation software event codes. The dispatcher shall notify the on-call technician in accordance with response matrix. 4. Life Safety Systems inspected and repaired include, but are not limited to the following: a. Fire Alarm System Coordinate alarm inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire alarm system inspections in accordance with the latest edition of NFPA 72, State and local Codes. Inspection reports shall be completed, scanned, and entered on the AISD Police Department Repair system as needed to maintain operation b. Fire Sprinkler System Coordinate sprinkler system inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire sprinkler system inspections in accordance with the latest edition of NFPA 25, State and local Codes. W drive in accordance with existing file protocol Repair system as needed to maintain operation. c. Portable Fire Extinguisher Coordinate extinguisher inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire extinguisher inspections in accordance with the latest edition of NFPA 10, State and local Codes. Repair or recharge as needed to maintain operation. d. Kitchen Exhaust Hood Fire Suppression System Coordinate system inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire suppression system inspection in accordance with the latest edition of NFPA 17a & 96, State and local Codes. Repair system as needed to maintain operation. e. Paint Spray Booth Fire Suppression System Coordinate system inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire suppression system inspection in accordance with the latest edition of NFPA 17, State and local Codes. Repair system as needed to maintain operation. f. FM 200 Fire Suppression System Coordinate system inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire suppression system inspection in accordance with the latest edition of NFPA 2000, State and local Codes. Repair system as needed to maintain operation 3

4 Surveillance Camera Maintenance and Repair: g. Fire Hydrants Coordinate hydrant inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire hydrant inspection in accordance with the City of Austin Private Fire Hydrant Inspection and Test Procedures. Inspection shall be entered in WERS then reports shall be scanned and entered on the AISD Police Department Repair Hydrants as needed to maintain proper operation. h. Back Flow Device Coordinate back flow inspections with Facilities Manager and AISD dispatch. Maintenance personnel will perform fire hydrant inspection in accordance with the City of Austin Private Fire Hydrant Inspection and Test Procedures. Inspection shall be entered in WERS the n reports shall be scanned and entered on the AISD Police Department W drive in accordance with existing file protocol. Repair Hydrants as needed to maintain proper operation. i. Intrusion System Repairs as needed to maintain operation at or above 97%. j. AES Radio Repairs as needed to maintain operation at or above 97%. Access Control Systems Repairs as needed to maintain operation at or above 97%. k. Gas Detection System (New system procedures to be defined) The Camera system is supported by LSS technicians between the hours of 8:00 a.m. and 4:30 p.m. during regular school work days and at other times determined by the LSS Supervisor or Foreman In order to maintain the surveillance cameras at or above 97% operability, the LSS technicians shall: 1. Repair camera as needed to maintain proper operation 2. Cameras identified for repair will receive an initial response within 24 hours. The initial response will determine the general nature of the camera problem and determine whether a site visit to the camera for further testing and/or repair will be required. 3. Initial site visits for further testing will be accomplished within 3 working days from the time the camera was reported to LSS for repair. 4. When a camera is identified as an urgent repair by the LSS technician, the camera will be repaired within 10 days. The work order system will be noted of the repair necessary and the requirement of parts ordered. Dependant on vendor stock, bidding process, and shipping the possibility of additional repair days may be required. 5. Cameras which require specialized equipment i.e. lifts for testing shall have testing accomplished within 18 working days from the time the camera was reported to LSS for repair. 4

5 Work Repair Prioritization Standards In order to ensure life safety systems are maintained at 97 percent operating status the following work repair prioritization standard will be followed: WORK ORDER PRIORITIZATION STANDARDS PRIORITY 1- Emergency Definition: Immediate danger to public health and safety, disruption to normal operations and/or potential catastrophic financial loss. Examples: Ruptured water line, Fire Alarm causing A/C to shut-down, Fire Sprinkler activation, Fire pump running, Fire alarm activation as a result of a fire in a building, Fire Suppression System Activation, server down causing camera failure on entire campus. RESPONSE TIME: Less than 2 hours to make temporary repairs to allow use of facility. Permanent repairs made within 5 days PRIORITY 2- Urgent Definition: High Priority requiring a 24 hour response. Examples: Fire alarm panel trouble, Fire alarm or Fire Sprinkler Supervisory Signals, Intrusion system EZM or Power Supply Failure, Multiple cameras down at a facility issue. RESPONSE TIME: Within 24 hours to make temporary repairs to allow use of facility. Permanent repairs completed within 10 days. Priority 3-Routine Definition: Routine troubles and maintenance items which must be addressed but do not rise to the level of Urgent or Emergency. Examples: Fire and Security System Low Battery, card access door not working, routine camera repairs. RESPONSE TIME: Within 2 working days, Work completed within 30 working days Priority 4-Scheduled Work Definition: Work which may require coordination with multiple departments, contractors or may require extra staff or specialized equipment such as lifts, pumps etc. Examples: Installation of additional card access doors and hardware. REPONSE TIME: Within 30 working days, Work completed within 90 working days. Priority 5- Project Work Definition: Work that has been identified and is performed district wide on an ongoing basis, or work deferred pending availability of labor, scheduling issues or funding. REPONSE TIME: As soon as resources and scheduling issues are resolved. 5

6 AISD Police Department Policy 8.07 Life Safety Systems Original Issue Date: April 30, 2013 Last Revision Date: September 4, 2014 Next Review Date: December 5, 2018 Office of Primary Responsibility: LSS Editor: CE Reviewed By: CE APPROVED: Eric Mendez Chief of Police 6

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Austin Independent School District Police Department Policy and Procedure Manual Policy 4.08A Emergency/Non-Emergency Response - Vehicle I. POLICY (7.15.1; 7.26.1 TPCAF) The AISD Police Department s primary

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

REED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES

REED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES Source: Departmental Directive issued by the CS Director. Original publication: January 27, 2011 Latest review & revision: August 2018 Departmental Policy

More information

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire

More information

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

ELEVATOR RESCUE PROCEDURE

ELEVATOR RESCUE PROCEDURE ELEVATOR RESCUE PROCEDURE Office of Environmental Health & Safety December 2013 Table of Contents I. Purpose:... 3 II. Scope:... 3 III. Responsibility:... 3 IV. Types of Emergencies:... 3 V. Definitions:...

More information

Fire System Impairment Policy

Fire System Impairment Policy Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,

More information

UNIVERSITY. Facilities Management

UNIVERSITY. Facilities Management EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability

More information

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY Origination Date: July 1 st 2009 1. PURPOSE The purpose of this policy is to create a safe environment for faculty, staff, students and visitors by applying

More information

FIRE PROTECTION INTRODUCTION

FIRE PROTECTION INTRODUCTION SECTION IV. Fire/Life Safety Chapter 1. Fire Protection Revision Date 11/19/02 Review Date 01/2007 FIRE PROTECTION INTRODUCTION PURPOSE It is the policy of Duke University to take all possible steps to

More information

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham

More information

Evacuation of Primary PSAP

Evacuation of Primary PSAP Evacuation of Primary PSAP Supersedes: 10-14-04 Effective: 10-31-14 Alternate PSAP / Backup Center Boston Fire Alarm, located at 59 the Fenway, serves as the alternate PSAP for the City of Boston. Five

More information

The WAVE Plus Instant Notification System for Schools and Colleges

The WAVE Plus Instant Notification System for Schools and Colleges Instant Notification System for Schools and Colleges Duress alarm has been activated in the School of Engineering! Schools strive to provide a safe environment for students and teachers. In an emergency,

More information

Grossmont Cuyamaca Community College District Fire Report 2014

Grossmont Cuyamaca Community College District Fire Report 2014 Grossmont Cuyamaca Community College District Fire Report 2014 Overview The Higher Education Opportunity Act (Public Law 110-315) became law in August, 2008. It requires all academic institutions to produce

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator.

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator. Community Health Center ================================================================= Subject: EMERGENCY EVACUATION PROCEDURE ================================================================= Policy

More information

Emergency Action Fire Prevention Plan

Emergency Action Fire Prevention Plan Emergency Action Fire Prevention Plan Table of Contents Section Title Page 1.0 Purpose 2 2.0 Scope and Application 2 3.0 Responsibilities 2-3 University Safety Coordinator 2-3 Department Heads, Supervisors

More information

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit) DUQUESNE UNIVERSITY Fire Protection System Impairment Program (Red etag Permit) Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Exceptions 2 Definitions

More information

FIRE PREVENTION PLAN EMERGENCY ACTION

FIRE PREVENTION PLAN EMERGENCY ACTION FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

SCALES NW EMERGENCY ACTION PLAN

SCALES NW EMERGENCY ACTION PLAN Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

Risk Management Services

Risk Management Services Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are

More information

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat,

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat, University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

HOT WORK SAFETY PROGRAM:

HOT WORK SAFETY PROGRAM: HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.

More information

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY University of Maryland FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building

More information

Grossmont Cuyamaca Community College District Fire Report 2012

Grossmont Cuyamaca Community College District Fire Report 2012 Grossmont Cuyamaca Community College District Fire Report 2012 Overview The Higher Education Opportunity Act (Public Law 110-315) became law in August, 2008. It requires all academic institutions to produce

More information

Campus Emergency Response Plan Standard Operating Procedure

Campus Emergency Response Plan Standard Operating Procedure Campus Emergency Response Plan Standard Operating Procedure August 2015 Austin Campus Brownsville Campus Corpus Christi Campus Harlingen Campus Pharr Campus San Antonio South Campus San Antonio North Campus

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Fire and Evacuation Guide

Fire and Evacuation Guide Emergency Response Plan Student Health and Counseling Services Updated 6/10/13 Fire and Evacuation Guide In compliance with California Code of Regulations Title 8, Section 3220 1 General Fire Procedure

More information

University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911

University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911 University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE - 911 FIRE - 911 MEDICAL EMERGENCY - 911 Anyone discovering excessive heat, smoke, or fire will immediately sound an alarm and report

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

Mulch fires, trash can fires, or other fire outside a building should be reported by the following methods:

Mulch fires, trash can fires, or other fire outside a building should be reported by the following methods: University of Maryland FIRE EVACUATION PLAN HEALTH SCIENCE FACILITY I (HSF I) POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will

More information

Impairments to Fire Protection Equipment

Impairments to Fire Protection Equipment Impairments to Fire Protection Equipment INTRODUCTION Buildings and equipment are provided with fire protection and/or detection systems to reduce property damage and interruption to business in the event

More information

University of Maryland FIRE EVACUATION PLAN

University of Maryland FIRE EVACUATION PLAN University of Maryland FIRE EVACUATION PLAN PLAZA PARKING GARAGE POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

RAMBLER PARK FIRE SAFETY INFORMATION

RAMBLER PARK FIRE SAFETY INFORMATION RAMBLER PARK FIRE SAFETY INFORMATION Parmenter Realty Partners 7557 Rambler Rd. Dallas, Texas 75231 214-373-9561 214-373-9620 (fax) RAMBLER PARK RAMBLER PARK FIRE SAFETY INFORMATION II. Objective To provide

More information

Evacuation Fire Safety Program

Evacuation Fire Safety Program Evacuation Fire Safety Program Emergency Procedures Provisions must be made for prompt medical attention in case of serious injury. The location and phone number of emergency service providers will be

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

Fire Watch Program. Building Administrators Building Administrators will inform building occupants about fire watch events and building evacuations.

Fire Watch Program. Building Administrators Building Administrators will inform building occupants about fire watch events and building evacuations. SUNY Cortland - Environmental Health and Safety Office Fire Watch Program Date of Inception: May 12, 2011 Latest Revision/Review Date: August 1, 2018 Previous Revision/Review Date: June 28, 2017 Fire Watch

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT DATE: February 21, 2018 NO: FROM: CHIEF ERIC JONES TO: ALL PERSONNEL INDEX: Emergency Vehicle Response Emergency Vehicle

More information

Applying Performance-based Fire Alarm System Design Part 4

Applying Performance-based Fire Alarm System Design Part 4 Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss

More information

Upon activation of the building fire alarm system or verbal command to evacuate a building: All personnel shall evacuate the building immediately.

Upon activation of the building fire alarm system or verbal command to evacuate a building: All personnel shall evacuate the building immediately. Emergency Preparedness Evacuation Plan Upon activation of the building fire alarm system or verbal command to evacuate a building: All personnel shall evacuate the building immediately. 1. Staff in labs

More information

Emergency Support Function #2 Communication

Emergency Support Function #2 Communication Emergency Support Function # 2 Communication Primary Agency RU Office of Emergency Preparedness RU Information Technology RU University Relations 911 Centers Secondary/Support Agencies Regional Law Enforcement

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Building Emergency Response Scenario

Building Emergency Response Scenario Building Emergency Response Scenario Following is a use case scenario of a building fire incident and covers alert generation and propagation to dispatch followed by the first responder use of building

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued

More information

TULANE UNIVERSITY EMERGENCY ACTION PLAN

TULANE UNIVERSITY EMERGENCY ACTION PLAN TULANE UNIVERSITY EMERGENCY ACTION PLAN This is the Emergency Action Plan developed by Tulane University applicable for the prescribed building and department. It has been designed to assist personnel

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally

ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally Sec. 4-13-1 Definitions Alarm site. The single premises or location (one (1) street address) served by an alarm system or systems that are under the control

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

Hot Work Policy and Procedures

Hot Work Policy and Procedures Environmental Health & Safety Office of the Fire Marshal Hot Work Policy and Procedures In Accordance With New Jersey Fire Code And National Fire Protection Association 505 Ramapo Valley Road, Building

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2 FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting

More information

Nova Scotia Fire Dispatch Minimum Standards (2017)

Nova Scotia Fire Dispatch Minimum Standards (2017) Fire Service Association of Nova Scotia Nova Scotia Fire Dispatch Minimum Standards (2017) July 14, 2017 Scope This document sets out the minimum standards to which fire dispatch operations are expected

More information

SMALL TOOL REPLACEMENT PLAN

SMALL TOOL REPLACEMENT PLAN SMALL TOOL REPLACEMENT PLAN SCOPE This guideline shall apply to all members of the Stoney Point Fire Department (SPFD) and shall be adhered to by all members. PURPOSE The purpose of this SOG is to establish

More information

FIRE IMPAIRMENT NOTICE

FIRE IMPAIRMENT NOTICE Notification of Fire System Isolation FIN NORA No. Complete Fire Impairment Notice (FIN) before any impairment. Note 3 business days notice is required. Submit the FIN to the BAC Airport Facilities on

More information

HUDSON VALLEY COMMUNITY COLLEGE BUILDING EMERGENCY ACTION PLAN FOR OUTSIDE EMERGENCY ASSISTANCE: DIAL 911 TO REACH THE SARATOGA CTY POLICE & FIRE

HUDSON VALLEY COMMUNITY COLLEGE BUILDING EMERGENCY ACTION PLAN FOR OUTSIDE EMERGENCY ASSISTANCE: DIAL 911 TO REACH THE SARATOGA CTY POLICE & FIRE HUDSON VALLEY COMMUNITY COLLEGE BUILDING EMERGENCY ACTION PLAN BUILDING NAME: TEC-SMART FOR OUTSIDE EMERGENCY ASSISTANCE: DIAL 911 TO REACH THE SARATOGA CTY POLICE & FIRE PURPOSE: To establish an action

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800) The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater

More information

FROM: CITY MANAGER DEPARTMENT: POLICE FIRE SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE

FROM: CITY MANAGER DEPARTMENT: POLICE FIRE SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE TO: HONORABLE CITY COUNCIL FROM: CITY MANAGER DEPARTMENT: POLICE FIRE DATE: APRIL 23, 2007 CMR:219:07 SUBJECT: SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE This is an informational

More information

KELTRON LS 7000 ALARM MANAGEMENT SYSTEM Keltron Alarm Monitoring, Dispatch, and Reporting Software

KELTRON LS 7000 ALARM MANAGEMENT SYSTEM Keltron Alarm Monitoring, Dispatch, and Reporting Software KELTRON LS 7000 ALARM MANAGEMENT SYSTEM Keltron Alarm Monitoring, Dispatch, and Reporting Software OVERVIEW The Keltron LS 7000 Alarm Management System software and computers make up the dispatch portion

More information

Dutchess Community College. Emergency Action Plan. Conklin Hall College Residence

Dutchess Community College. Emergency Action Plan. Conklin Hall College Residence Dutchess Community College Emergency Action Plan Conklin Hall College Residence June 2014 1 TABLE OF CONTENTS Purpose Page 3 Introduction Page 3 Evacuation Page 4 Fire Emergencies Page 5 Evacuating Individuals

More information

The following departments are responsible for preservation oflife and fire safety at the University of Toledo.

The following departments are responsible for preservation oflife and fire safety at the University of Toledo. Name of Policy: Fire and life safety management.toledo Policy Number: 3364-60-03 Ut1.l Approving Officer: President Responsible Agent: Director of Environmental Health and Radiation Safety Revision date:

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

Site Security Plan - Operations Baron Winds Project

Site Security Plan - Operations Baron Winds Project Site Security Plan - Operations Baron Winds Project August 2017 Table of Contents 1. Introduction... 3 2. Access Roads... 3 3. Wind Turbines... 3 4. Substation... 4 5. Operations and Maintenance Building...

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

British Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY

British Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY BCIT Safety Manual Contents 1. Purpose... 2 2. Definitions... 2 3. Reference Materials... 5 4. Roles & Responsibilities... 5 4.1 BCIT Employees, Students, Contractors and Visitors... 5 4.2 Supervisors...

More information

Preliminary Site Security Plan Operations Cassadaga Wind Farm

Preliminary Site Security Plan Operations Cassadaga Wind Farm Preliminary Site Security Plan Operations Cassadaga Wind Farm January 2016 Table of Contents 1. Introduction... 3 2. Access roads... 3 3. Wind Turbines... 3 4. Substations... 3 5. Operations and Maintenance

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS TABLE OF CONTENTS 1.0 INTRODUCTION...1 1.1 BARS (Box Alarm Readout Systems) ALARM BOXES...1 1.2 ERS (Emergency Reporting System) ALARM BOXES...2 1.3

More information

Property Name & Address [ Property Name ] - [ Property Address ]

Property Name & Address [ Property Name ] - [ Property Address ] Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

X0.01 Emergency Management. Approved: September 27, 2002 Revised: July 15, Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT

X0.01 Emergency Management. Approved: September 27, 2002 Revised: July 15, Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT Texas A&M AgriLife Extension Service Procedures 34.07.99.X0.01 Emergency Management Approved: September 27, 2002 Revised: July 15, 2012 Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT Texas A&M

More information

Vacant Building Loss Prevention Best Practices

Vacant Building Loss Prevention Best Practices Vacant Building Loss Prevention Best Practices Vacant properties are susceptible to a unique set of hazards that should be considered and addressed to avoid losses. Occupants are often the eyes and ears

More information

Emergency Notification Plan. Developed By: Cleveland State University Police Department Office of Emergency Management

Emergency Notification Plan. Developed By: Cleveland State University Police Department Office of Emergency Management Emergency Notification Plan Developed By: Cleveland State University Police Department Office of Emergency Management 216.687.2184 Rev.2.0 June, 2015 EMERGENCY NOTIFICATION, RESPONSE AND EVACUATION The

More information

BUILDING SECURITY and EVACUATION RELATED POLICIES: REVIEWED: AS NEEDED

BUILDING SECURITY and EVACUATION RELATED POLICIES: REVIEWED: AS NEEDED POLICY 120 BUILDING SECURITY and EVACUATION REVISED: 1/93, 01/02, 09/08, 08/10, 04/11, 07/11, 12/13, 10/15, 07/16, 08/18 CFA STANDARDS: RELATED POLICIES: REVIEWED: AS NEEDED A. PURPOSE The purpose of this

More information

FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR

FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR March 20-23, 2018 (Tuesday Friday) Conducted at the FM Global Emergency Response Consultants Training Center In Rome, Georgia The challenging

More information

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community. CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All

More information

Hospice of Rutherford County Policies and Procedures

Hospice of Rutherford County Policies and Procedures Subject: Fire Prevention/Evacuation Page: 1 of 5 Policy Date: 1994 Revised: 10/06, 09/08, 09/09, 8/12 Approval: Date: I. P O L I C Y Hospice of Rutherford County identifies and corrects potential fire

More information

EMERGENCY RESPONSE/ FIRE PREVENTION

EMERGENCY RESPONSE/ FIRE PREVENTION 10.0 ARKANSAS TECH UNIVERSITY EMERGENCY RESPONSE/ FIRE PREVENTION This Emergency Response / Fire Prevention Plan has been developed for the Office of Facilities Management to comply with Local, State and

More information

Annual Fire Safety Report

Annual Fire Safety Report Annual Fire Safety Report 2015-2017 PREPARED BY: Mindy Rouillard Senior Area Coordinator University Housing Services Michael Speros Executive Director University Housing Services 1 P a g e Contents Fire

More information

Safety & Security update April 2014

Safety & Security update April 2014 Safety & Security update April 2014 Corridor Locks New locks installed on every classroom door that allow the doors to be locked from the inside with a push button. Completed in August 2013. In-House project

More information

Building Emergency Policies and Procedures

Building Emergency Policies and Procedures Building Emergency Policies and Procedures For Langsam Library 2911 Woodside Cincinnati, OH 45221 June 2017 University of Cincinnati Department of Public Safety Department Table of Contents A. Introduction

More information

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus Issued By: Office of Finance and Administration Name: Chief Financial Officer Effective Date: November

More information

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level

More information