Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

Size: px
Start display at page:

Download "Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw"

Transcription

1 Industrial Solid State Contactor TE10S Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw Partial load failure (PLF) detection option User Manual Copyright Eurotherm Automation 1996 All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Automation SA TE10S/PLF Part No. HA174784ENG User Manual Iss.1 Printed in France 07/96 I

2 EUROPEAN DIRECTIVES SAFETY The TE10S products installed and used in accordance with this User Manual are designed to comply with the essential protection requirements of the European Low Voltage Directive 73/23/EEC dated 19/02/73 (amended by Directive 93/68/EEC dated 22/07/93). MARK The CE Mark of TE10S products implies that the essential protection requirements of the European Low Voltage Directive are observed. The TE10S Technical Construction File is approved by a Notified Body, LCIE (Laboratoire Central des Industries Électriques). For further information on CE Mark, please contact your nearest Eurotherm office. DECLARATION OF CONFORMITY A CE Declaration of Conformity is available on request. ELECTROMAGNETIC COMPATIBILITY (EMC) For industrial environments, excluding residential environments The TE10S products are considered as components without any direct function as defined in the EMC Directive. The system or installation in which these products are incorporated must complies with the essential protection requirements of the EMC Directive. However, Eurotherm certifies that the TE10S products, when installed and used in accordance with their User Manual, meets the following EMC test standards and enables the system or installation in which there are installed to comply with the EMC Directive in regards to the TE10S products. II TE10S/PLF User Manual

3 EMC TEST STANDARDS Test EMC test standards Immunity Electrostatic discharge IEC (EN ) - 06/1995 Fast transients IEC (EN ) - 01/1995 Radioelectric frequency IEC (pren ) electromagnetic fields Emission Radiated and Conducted EN The choice of the Conducted Emission applicable standard depends on the application : EN IEC (pren ) Applies for the second environment FILTER EMC To reduce the conducted emissions that occur when using thyristor units, the EMC internal filter is added from April 1996 VALIDATION BY A COMPETENT BODY In order to guarantee the best service, Eurotherm has validated the compliance of the TE10S products with these test standards through design and laboratory tests that have been validated with a Technical Construction File by a competent body, LCIE (Laboratoire Central des Industries Électriques). EMC INSTALLATION GUIDE In order to help you reduce risks related to the effects of electromagnetic interference depending on the installation of the product, Eurotherm can supply you with the 'EMC Installation Guide' (Part No. HA ). TE10S/PLF User Manual III

4 MANUALS IN USE This TE10S/PLF User Manual (Part No. HA174784ENG) applies to TE10S series with PLF from January The TE10S/PLF User Manual Part No. HA are valid for products manufactured before this date. PRECAUTIONS Read completely this Manual before installation. EUROTHERM cannot be held responsible for any damage to persons or property, or for any resulting financial loss or cost caused by the inappropriate product use or the failure to observe this manual. PERSONNEL The installation, configuration, commissioning and maintenance of the power unit must only be performed by a person qualified and authorised to perform work in an industrial low voltage electrical environment. INDEPENDENT SAFETY It is the responsibility of the user and it is highly recommended, given the value of the equipment controlled using TE10S, to install independent safety devices. This alarm must be tested regularly. Eurotherm can supply suitable equipment. FURTHER INFORMATION For any further information and if in doubt, please contact your EUROTHERM office where technicians are at your disposal should you require advice or assistance with the commissioning of your installation. IV TE10S/PLF User Manual

5 TE10S Industrial Solid State Contactor for static switching of resistive loads and shortwave infrared heating tubes up to 20 kw Partial load failure (PLF) detection option CONTENTS page Installation and use safety... 2 Technical specifications... 3 Mounting and dimensions... 4 Control Signal... 5 Front view... 6 Terminals and connectors... 7 Wiring... 8 PLF Alarm specifications... 9 Setting up PLF detection Ordering code Thyristor protection fuse Derating curves TE10S/PLF User Manual 1

6 INSTALLATION AND USE SAFETY DANGER! Failure to take note of the information may have serious consequences for the safety of personnel and may even result in the risk of electrocution. Installation and use in a correctly cooled electrical cabinet, with guarantees of protection from condensation and pollution. The cabinet must be closed and connected to safety earth conforming to IEC 364 or applicable National Standards. It is the user's responsibility to ensure that the installation, wiring and protection of the installation is in accordance with relevant standards and wiring regulations (e.g. VDE 0160). Before making any connections or disconnections make sure that the cables and wires are insulated from the supply voltage. The earth connection must be connected first and disconnected last. Control signal wiring must be kept separate from power cables. Disconnect the TE10S completely before dismounting. The recommended high speed fuse is only designed to protect the thyristors. It is not a substitute for fuse designed to protect the installation and wiring. Thyristors are not isolating devices. It is necessary to provide an additional protection and isolation to comply with wiring regulations, to allow safe intervention. Access to internal parts not allowed to non qualified personnel. The temperature of the heatsink may exceed 100 C. Take care when touching the heatsink and protect it from accidental contact during ON state and during 15 min after unit disconnection. 2 TE10S/PLF User Manual

7 TECHNICAL SPECIFICATIONS Power Nominal current 16, 25, 32 or 40 amps (at 45 C) Nominal line-to-line voltage 120, 240, 480 or 500 Vac (+10%;-15%) Nominal mains frequency 50 or 60 Hz (±2 Hz) Firing mode Logic firing (ON/OFF). Zero crossing OFF state leakage current Typical less than 30 ma Input Command signal Environmental Operating temperature Universal DC input (voltage or current) DC signal 5 V and 5 ma (nominal) Polarity insensitive '+' and '-' can be crossed 0 to 60 C, altitude 2,000 m maximum Storage : -10 to 70 C Atmosphere Non conductive, non explosive, non corrosive Humidity RH : 5 to 95% non condensing Pollution Pollution degree 2 (comply with IEC 664) Isolation (1min factory test) Main isolation to earth : 2,000 Vac Power to control : 3,600 Vac Thyristors protection External fuse, Varistor and RC snubber Unit protection degree IP20 (IEC 529 : 11.4 table 5) Cooling Air natural convection Alarm (option) Partial load failure detection Mounting Vertrical on DIN rail Weight 480g (16A); 660g (25A); 930g (32A); 1060g (40 A) Guarantee Two years (see your local representative) As a result of the constant improvement of its products, Eurotherm may modify these specifications without warning. For any further information and if in doubt, please contact your Eurotherm office. TE10S/PLF User Manual 3

8 MOUNTING SPECIFICATIONS Dimensions in mm 92, EUROTHE R M LOAD FAIL. DEF.CHARGE ε 45 ADJUST / REGL GN D Clip fixing on DIN rail EN x7.5 and 35x15 52,5 (16A), 70 (25A) 105 (32A), 122,5 (40A) Distance between two TE10S : 10 mm up to 45 C, 17.5 mm over 45 C (adaptor BD173730) Ground continuity. Due to electromagnetic compatibility requirements make sure that TE10S mounting DIN rail is bolted to the metal ground (panel or cabinet) and going on good electrical contact. 4 TE10S/PLF User Manual

9 INPUT SIGNAL Command signal Sygnal type : DC logic signal. Universal input : accepts a voltage or current command signal. Polarity insensitive, '+' and '-' can be crossed. ON state : voltage higher than 5 Vdc and current higher than 5 ma. Maximum voltage less than 32 V. Maximum current (auto limit) : 10 ma at 32 Vdc OFF state : voltage less than 2 Vdc or current less than 0.5 ma. Signal indication Command signal indication by green indicator light (light emitting diode) on front fascia. TE10S/PLF User Manual 5

10 FRONT VIEW Power terminals : 1 to 4 PLF Alarm Red indicator light 1 2 Terminals 1 & 3 : Controlled Phase Terminals 2 & 4: Direct Phase EUROTHERM ε LOAD FAIL. DEF.CHARGE ADJUST / REGL. 1 2 PLF setting potentiometer Input signal Green indicator light 3 4 Input pluggable connector Safety earth 6 TE10S/PLF User Manual

11 TERMINALS AND CONNECTORS Power terminals : screw for cable 1.5 to 16 mm 2, cable stripping length 16 mm tightening torque 1.2 N.m Safety earth wiring : same cable section as power, tightening torque 2 N.m Input connection: between terminals 5 & 6 Pluggable connector for cable sizes 0.5 to 1.5 mm 2 wire stripping length 7 mm, tightening torque 0.4 N.m Bottom view PLF alarm 7 contact connector 8 16 mm Power cable stripping guide DC control input signal connector 5 6 Power terminals Fixing clip Safety earth screw DIN rail TE10S/PLF User Manual 7

12 WIRING L N Isolation and protection. User installation Thyristor protection higt-speed fuse TE10S 1 2 EUROTHERM ε 1 2 1A Fuse 2216 controller Logic EUROTHERM 2216 output 1A L 1B N E V+ V Thermocouple input PLF alarm contact Input Load Safety earth Example of TE10S wiring (PLF option, 240V nominal). Controlled by EUROTHERM 2216 controller 8 TE10S/PLF User Manual

13 PLF SPECIFICATIONS The 'Partial Load Failure' (PLF) alarm detects an increase in load impedance due to the breakage, the destruction or the disconnexion of the heating elements. The PLF detection is indicated by red indicator light (light emitting diode) on front fascia. Partial load failure detection changes the alarm relay state. The relay is de-energised in the alarm state, or when the TE10S is not powered. Option PLF : the contact is open in the alarm state; option IPF : the contact is closed in the alarm state. Relay contact rating : 0,25 A (250 Vac or 30 Vdc). Detection sensitivity of partial load failure : failure detection of 1 element for 6 identical parallel heater elements (for single-phase applications). The PLF detection operates under the following conditions: firing time 1 s input signal duty cycle must be over 20% the on-time load current must be greater than 5 amps (16 and 25 A nominal) or 8 amps (32 and 40 A nominal). TE10S/PLF User Manual 9

14 SETTING UP PLF DETECTIONThe 'Partial Load Failure' (PLF) alarm detects an increase in load impedance. In order to carry out PLF adjustment, the current when fully conducting must be greater than 20% of the nominal unit current. As a general rule, since the load current is less than the nominal thyristor current, the following setting must be carried out: Check that the thyristors are conducting (load current on and input green indicator light is illuminated) If the PLF detection red indicator light (identified on front as 'Load fail. / Déf. Charge') is illuminated, turn the 25 turn PLF potentiometer (identified on front as 'Adjust / Régl') anticlockwise until the PLF red indicator light switches off. Turn the potentiometer clockwise until the indicator lights comes on. Slowly turn back the potentiometer (anticlockwise) until the red indicator light is just extinguished. The PLF detection control is now set to give maximum sensitivity. If an erratic alarm appears, reduce the sensitivity by turning the potentiometer anticlockwise (e.g. 1/4 turn or more until the fault disappears). Resetting the alarm is achieved either by removing power from the unit or by a returning to the previous load current. 10 TE10S/PLF User Manual

15 ORDERING CODE Model / Current / Voltage / Input / Option / End code code code code TE10S 16A 120V LGC Partial load failure 00 25A 240V detection. 32A 480V 40A 500V Alarm relay contact in alarm state Open : PLF Closed : IPF THYRISTOR PROTECTION FUSE Current Fuse Fuse and fuse-holder range rating code 16 A 20 A FU1038 / 16A / A 32 A FU1038 / 25A / A 40 A FU1451 / 32A / A 50 A FU1451 / 40A / 00 TE10S/PLF User Manual 11

16 DERATING CURVES I RMS (amps) TE10S max RMS current allowed vs ambient temperature 50 I N = 40 A IN = 32 A 20 IN = 25 A 10 0 IN = 16 A IN -current rating (at 45 C) ( C) 12 TE10S/PLF User Manual

17 Solid State Contactors TE10S Power Controllers TE10A ε E U R O T H E R M ADDENDUM TE10S User Manual Part N : HA174780ENG, HA174782ENG, HA174784ENG, HA175436ENG TE10A User Manual Part N : HA175247ENG, HA175548ENG NOMINAL CURRENT UP TO 50 A and SHORT WAVE INFRARED APPLICATIONS Copyright Eurotherm Automation S.A All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Automation SA. Part N. HA ENG - Issue /98

18 TECHNICAL SPECIFICATION MAXIMUM CURRENT In order to take into account supply voltage variations and heating element resistance dispersion (all types of heating elements including short wave infrared), a 0.8 safety coefficient must be used on the thyristor unit current rating to determine the maximum value of the load nominal current which the unit can safely control. SHORT WAVE INFRARED (SWIR) APPLICATIONS Applications using short wave infrared heaters in Single Cycle, Fast Cycle or Advanced Single Cycle are reserved to 16 A, 25 A and 40 A current rating. With a safety coefficient of 0.8 the maximum current for SWIR which can be controlled is: TE10 rating SWIR maximum controlled current 16 A 13 A 25 A 20 A 40 A and 50 A 32 A 2 Addendum TE10 (50A/SWIR)

19 RANGE DIMENSIONS AND WEIGHT Height 115 mm / Depth 92.5 mm Models Nominal current Width (mm) Weight (g) TE10S/DC, TE10S/AC TE10S/PDSIO 16 A 25 A 40 A 50 A TE10S/PLF TE10A/Burst TE10A/PA 16 A 25 A 40 A 50 A THYRISTOR PROTECTION FUSE TE10 rating 16 A 25 A 40 A 50 A Fuse rating 20 A 32 A 50 A 63 A Fuse & fuse-holder Code Dimensions(mm) FU1038/16A/00 81 x 17.5 x 68 FU1038/25A/00 81 x 17.5 x 68 FU1451/40A/00 95 x 26 x 86 FU2258/50A/ x 35 x 90 Attention! Addendum TE10 (50A/SWIR) For SWIR applications, the high-speed fuse must not be used 3

20 60 I RMS (A) IN = 50 A 50 IN = 40 A IN = 25 A 20 IN = 16 A Operation tempereature ( C) Current derating as a fonction of ambient temperature (I N = nominal current at 45 C) Dotted line : limit due to recommended fuse Addendum TE10 (50A/SWIR)

Single phase solid state contactors ENG. User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION

Single phase solid state contactors ENG. User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION 7100S ε 7100 Single phase solid state contactors ENG User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION 7100S SMART CONTROLLERS SINGLE-PHASE INDUSTRIAL SOLID STATE CONTACTORS 7000 series User Manual

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

7000 RANGE 7300S SMART CONTROLLER THREE-PHASE SOLID STATE CONTACTOR. User Manual

7000 RANGE 7300S SMART CONTROLLER THREE-PHASE SOLID STATE CONTACTOR. User Manual 7000 RANGE 7300S SMART CONTROLLER THREE-PHASE SOLID STATE CONTACTOR User Manual Copyright Eurotherm Limited 2003 All rights reserved. All reproduction or transmission in any form whatsoever and using any

More information

SINGLE-PHASE POWER THYRISTOR UNITS 7000 RANGES. User Manual

SINGLE-PHASE POWER THYRISTOR UNITS 7000 RANGES. User Manual 7100A ADVANCED CONTROLLERS SINGLE-PHASE POWER THYRISTOR UNITS 7000 RANGES User Manual Copyright Eurotherm Limited 2002 All rights reserved. All reproduction or transmission in any form whatsoever and using

More information

7100A User Manual. Single Phase Power Thyristor Units Issue 4.4

7100A User Manual. Single Phase Power Thyristor Units Issue 4.4 7100A User Manual Single Phase Power Thyristor Units Issue 4.4 HA176499ENG March 2011 7100A ADVANCED CONTROLLERS SINGLE-PHASE POWER THYRISTOR UNITS 7000 RANGES User Manual Copyright Eurotherm Automation

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

7200S ENG. Two phase solid state contactor. Two phase Load Control. User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION

7200S ENG. Two phase solid state contactor. Two phase Load Control. User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION 7200S ε Two phase solid state contactor ENG Two phase Load Control User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION 7000 Range 7200S SMART CONTROLLER THREE-PHASE SOLID STATE CONTACTOR USER MANUAL

More information

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics... 14 Ex SOLENOID / ALARM DRIVER PRepower 5203B Table of contents Warnings... 16 Safety instructions... 17 Declaration of Conformity... 19 How to dismantle SYSTEM 5000... 20 Application... 21 Technical characteristics...

More information

Power supply Vs = Vdc ±10% Input 30mA at 30Vdc

Power supply Vs = Vdc ±10% Input 30mA at 30Vdc GD 40A SOLID STATE RELAYS WITH LOGIC CONTROL AND DIAGNOSTICS Main applications Plastics extrusion lines and injection moulding machines Packing and packaging machines Polymerization plant for synthetic

More information

Installation Instructions CS3 Three Phase Solid State Relay

Installation Instructions CS3 Three Phase Solid State Relay Installation Instructions CS3 Three Phase Solid State elay 1 PK522-3 0037-75550 March 2018 Important Safeguards HIGH VOLTAGE is used in the operation of this equipment; DEATH ON CONTACT may result if personnel

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product

More information

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24 Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24 Soft starting of 1-Phase Scroll Compressors Enclosed solution Integrated current limit Rated operational voltage: 230 VACrms, 50/60

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

Bulletin 1608N MiniDySC Dynamic Sag Corrector

Bulletin 1608N MiniDySC Dynamic Sag Corrector User Manual Bulletin 1608N MiniDySC Dynamic Sag Corrector Single Phase Voltage Sag Correction 2...6 Amps (250...750 VA) Important User Information Solid-state equipment has operational characteristics

More information

Operation and use. Functions and characteristics

Operation and use. Functions and characteristics Operation and use Function Vigirex relays measure the earth-leakage current in an electrical installation via their associated toroids. Vigirex relays may be used for: b residual-current protection (RH10,

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

Power Supply Display Module PSDM. Installation and Operation Manual

Power Supply Display Module PSDM. Installation and Operation Manual Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious

More information

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description Three phase AC pumps and ventilators soft starter Description Benefits Easy to use. The is equipped with a self-learning algorithm that automatically adjusts the start parameters to optimise the motor

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH

More information

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR Solid State Relays SOLITRON MIDI Current Sensing Type, R AC semiconductor contactor Integrated current monitoring Zero switching (1A) Direct copper bonding (DCB) technology LED-indication Cage clamp output

More information

ANNEALING FURNACE MODEL 414 User Maintenance Manual/Handbook

ANNEALING FURNACE MODEL 414 User Maintenance Manual/Handbook ANNEALING FURNACE MODEL 414 User Maintenance Manual/Handbook Isothermal Technology Limited, Pine Grove, Southport, PR9 9AG, England Tel: +44 (0)1704 543830 Fax: +44 (0)1704 544799 Internet: www.isotech.co.uk

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information

Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Soft starting of 1-Phase Scroll Compressors Enclosed solution Integrated current limit Rated operational voltage: 230 VACrms, 50/60

More information

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

YP7999A1000 ControLinks Fuel Air Ratio Control Panel YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

INSTRUCTION & SERVICE MANUAL

INSTRUCTION & SERVICE MANUAL INSTRUCTION & SERVICE MANUAL D2xC1 ALARM HORN AND STROBE For Use In Hazardous Locations 3) Ratings and Markings 3.1 ATEX / IECEx certification The D2xC1 Alarm Horn and Strobe complies with the following

More information

ISIS SAFETY SYSTEM Installation guide

ISIS SAFETY SYSTEM Installation guide ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly

More information

PCR-300 PCR-300 RC. Installation and Operating Instructions

PCR-300 PCR-300 RC. Installation and Operating Instructions PCR-300 PCR-300 RC Installation and Operating Instructions Electronic refrigeration control EB-PCR-04 EN1H-1924GE23 R1207 TABLE OF CONTENTS 11 Unpacking the unit and conditions of use 3 12 General instructions

More information

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Soft starting of 1-Phase Scroll Compressors Enclosed solution Integrated current limit Rated operational voltage: 230 VACrms,

More information

Soft Starter Centrifugal Pump Soft Starter Series

Soft Starter Centrifugal Pump Soft Starter Series Soft Starter Centrifugal Pump Soft Starter Series Type RSWT Optimised algorithm for centrifugal pumps Simple User Interface 3-phase controlled Internally bypassed Multi voltage operation Integrated overload

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor DSF xx15.xx xhv Ex-Atex Product ID Type # Product # Drawing # DSF 1215.01 SHV Ex-atex (5m) 304Z-05197 113216 DSF 1415.01 AHV Ex-atex S148 304Z-05256 113351 DSF 1615.01 SHV Ex-atex (5m) 304Z-05196 113214

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

L1L2L3. 99 Washington Street Melrose, MA Phone Toll Free Visit us at

L1L2L3. 99 Washington Street Melrose, MA Phone Toll Free Visit us at PHASE ROTATION METER 6608 L1/A L2/B 690V 600V CAT III 300V CAT IV L1L2L3 L3/C L R PHASE ROTATION MODEL 6608 User Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431

More information

DTA04. Motor thermistor relay. Benefits. Description

DTA04. Motor thermistor relay. Benefits. Description Motor thermistor relay Benefits High operating safety. The thresholds are determined by the Motor PTC. Beyond the specified temperature the output stops the motor/s. Save time and costs.there is no need

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

Ordering Key. Dielectric strength

Ordering Key. Dielectric strength Controllers AC Semiconductor Controller Type Soft starting and stopping of 3-phase squirrel cage motors Low inrush and reduced vibration during starting Integrated bypassing of semiconductors Rated operational

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SHANGHAI INSPECTION AND TESTING INSTITUTE OF INSTRUMENTS AND AUTOMATION SYSTEMS CO., LTD. 103 Cao Bao Road Shanghai, 200233 People s Republic of China Mr. Xu

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

PAC1500Xi PORTABLE APPLIANCE CHECKER

PAC1500Xi PORTABLE APPLIANCE CHECKER PAC1500Xi PORTABLE APPLIANCE CHECKER OPERATING INSTRUCTIONS 211A912 CONTENTS 1) Safety... 1 2) Introduction & Description... 2 3) Applications... 2 4) Test Sequence... 3 5) Visual Inspection... 3 6) Earth

More information

Gas cylinder scale Model GCS-1

Gas cylinder scale Model GCS-1 Electronic pressure measurement Gas cylinder scale Model GCS-1 WIKA data sheet PE 87.19 Applications Level measurement of liquid gases in gas cabinets and gas distribution systems Level measurement in

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

122.1mm. Relay Open in alarm N/O. snubber. line. Com N/C. Closed in alarm. snubber line 2A Com snubber Open in alarm ALARM 1 N/O. Relay.

122.1mm. Relay Open in alarm N/O. snubber. line. Com N/C. Closed in alarm. snubber line 2A Com snubber Open in alarm ALARM 1 N/O. Relay. ALARM 1 INPUT ALARM 2 RESET 92 and 92i Installation and Operating Instructions This controller meets the requirements of the European Directives on Safety and EMC. It is the responsibility of the installer

More information

Project planning (original) EN. Functional safety. Inverter i550-cabinet kw

Project planning (original) EN. Functional safety. Inverter i550-cabinet kw Project planning (original) EN Functional safety Inverter i550-cabinet 0.25... 45 kw This page intentionally left blank! Contents Contents Safety instructions 4 Basic safety measures 4 Residual hazards

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

for relative humidity and temperature with calibration certificates

for relative humidity and temperature with calibration certificates 1 859 1859P01 1859P02 QFA4160 AQF4150 Symaro Room Sensor for relative humidity and temperature with calibration certificates QFA4160 Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for

More information

Model Number Structure

Model Number Structure Element Burnout Detector Accurate Detection of Element Burnout Regardless of Capacities Accurately detects a burned heater element or elements incorporated by a molding machine or packing machine and outputs

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1. Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction

More information

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon INSTRUCTION MANUAL Minialite Intrinsically Safe Round LED This instruction sheet describes installations which conform to EN60079:Part14:2008 Electrical Installation in Hazardous Areas. When designing

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy. Installation manual detector and controller Code no. 20711062 Page 1/30 CONTENTS Controller... 2 Function of the Relays... 2 Gas Detectors... 2 Cabling... 4 Mechanical Installation of the gas detectors...

More information

Application. Specifications. Finish

Application. Specifications. Finish Spec-00051 I( McLean Electronics Cooling Thermal Accessories McLean Electronics Cooling: Thermal Accessories Touch-Safe Heaters Industry Standards curus Component Recognized; File No. E150057 IP 20 CE

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-nA Edition 08/207 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Dale Power Solutions Ltd

Dale Power Solutions Ltd DC THYRISTOR SYSTEMS DATASHEET Features Erskine Single Phase Input DCV Range 24V, 48/50V or 110V nominal Up to 63 Amps per charger Constant voltage/current limited output Standard alarm module LCD metering

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net

More information

INSTRUCTION MANUAL (ATEX)

INSTRUCTION MANUAL (ATEX) INSTRUCTION MANUAL (ATEX) ISmA1M Minialarm Intrinsically Safe Round ISmA1M Volume Control Tone Generator S3 Tone Selection Switches Fig 1 Simplified block diagram The ISmA1M sounder is CE marked for compliance

More information

XUX0AKSAM12 photo-electric sensor - XUX - multi - Sn 0..40m VDC - M12

XUX0AKSAM12 photo-electric sensor - XUX - multi - Sn 0..40m VDC - M12 Characteristics photo-electric sensor - XUX - multi - Sn 0..40m - 12..24VDC - M12 Complementary Enclosure material Lens material Maximum sensing distance Output type Add on output Status LED [Us] rated

More information

Archive. LC2200 Level Controller. 1. Safety information. 2. General product information. 3. Installation. 4. Setting up the controller

Archive. LC2200 Level Controller. 1. Safety information. 2. General product information. 3. Installation. 4. Setting up the controller 4025250/10 IM-P402-77 AB Issue 10 LC2200 Level Controller Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Setting up the controller 5.

More information

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature 1 858 1858P01 1858P02 1859P02 Symaro Room Sensors for relative humidity (high accuracy) and temperature AQF3150 QFA31 Use Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for r h and

More information

Electronic Temperature Controller 70304,

Electronic Temperature Controller 70304, Electronic Temperature Controller 70304, 70304.2 Instruction Manual Version 1.00.01 List of content 1 General information... 4 2 Declaration of conformity... 4 3 Safety instructions... 5 4 Warranty...

More information

Dry Bath Heating Systems

Dry Bath Heating Systems Dry Bath Heating Systems Instruction Manual N2400-4001 Dry Bath Heating System, Single Block, Digital N2400-4002 Dry Bath Heating System, Dual Block, Digital www.starlabgroup.com DECLARATION OF CONFORMITY

More information

TOUCH-SAFE HEATERS INDUSTRY STANDARDS

TOUCH-SAFE HEATERS INDUSTRY STANDARDS 763.576.3200 SPEC-00051 L763.422.2211 ACCESSORIES ENCLOSURE HEATERS ACCESSORIES ENCLOSURE HEATERS TOUCH-SAFE HEATERS INDUSTRY STANDARDS curus Component Recognized; File No. E150057 IP 20 CE APPLICATION

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

Series P215LR/BR Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter)

Series P215LR/BR Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter) PSC9713 European Refrigeration Controls Catalogue Catalog Section 4 Product Bulletin Series Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression

More information

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must

More information

Performance Data. Accessories Enclosure Heaters. curus Component Recognized; File No. E IP 20 CE

Performance Data. Accessories Enclosure Heaters. curus Component Recognized; File No. E IP 20 CE 763.576.3200 SPEC-00051 O763.422.2211 THERMAL MANAGEMENT ACCESSORIES ENCLOSURE HEATERS Accessories Enclosure Heaters TOUCH-SAFE HEATERS INDUSTRY STANDARDS curus Component Recognized; File No. E150057 IP

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor Product ID Type # Product # Drawing # DSF 1210.00 SHV Ex-atex (2m) 374Z-05066 110428F1 DSF 1210.00 SHV Ex-atex (5m) 374Z-05176 110428F1 DSF 1210.00 SHV Ex-atex (10m) 374Z-05590 110428F1 DSF 1410.00 SHV

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExS110D and BExS110D-R Sounder For use in Flammable Gas and Dust Atmospheres BExS110D BExS110D-R 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

INSTALLATION AND OPERATING MANUAL

INSTALLATION AND OPERATING MANUAL INSTALLATION AND OPERATING MANUAL Spectron Gas Control Systems GmbH Fritz-Klatte-Str. 8 65933 Frankfurt Germany Tel.: +49 69 38016-0 Fax: +49 69 38016-200 Email: info@spectron.de www.spectron.de 1 GES_K12_0915.docx

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

INDEX WARNINGS AND RECOMMENDATIONS 2 COMPLIANCE DECLARATIONS 3 RANGE AND SIZES 3 ELECTRICITY SUPPLY 3 INSTALLATION 4 INSTRUCTIONS FOR UNINSTALLING

INDEX WARNINGS AND RECOMMENDATIONS 2 COMPLIANCE DECLARATIONS 3 RANGE AND SIZES 3 ELECTRICITY SUPPLY 3 INSTALLATION 4 INSTRUCTIONS FOR UNINSTALLING Tuscany TUS1500 INDEX WARNINGS AND RECOMMENDATIONS 2 COMPLIANCE DECLARATIONS 3 RANGE AND SIZES 3 ELECTRICITY SUPPLY 3 INSTALLATION 4 INSTRUCTIONS FOR UNINSTALLING THE RADIATOR 5 INSTRUCTIONS FOR USE 6

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Insulation monitoring device for unearthed AC/DC control circuits (IT systems) TDB103005en/05.2013 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Product description The

More information

Series 65 Product Guide MAN 3036

Series 65 Product Guide MAN 3036 Series 65 Product Guide MAN 3036 TABLE OF CONTENTS Page No. 1 Ionisation Smoke Detector... 1 1.1 Operating Principles:... 1 1.2 Product Codes... 2 1.3 Integrating Version:... 2 1.4 Options:... 2 1.5 Safety

More information

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR Installation Manual DDS-S SENSOR 1 TRANSLATED DOCUMENT This manual has been compiled according to standard UNE-EN-ISO 12100. INSTALLATION MANUAL DDS-S SENSOR Read thoroughly all of these instructions before

More information

4) Intrinsic Safety Certification

4) Intrinsic Safety Certification INSTRUCTION MANUAL Minialert Intrinsically Safe Round Combined Unit Section Volume Control Tone Generator S2 S3 Tone Selection Switches Fig 1 Simplified block diagram The combined unit is CE marked for

More information

PROTECT SRB 200EXi-1A

PROTECT SRB 200EXi-1A 2 Installation up to zone 1/21 J S L1 0V X1 X3 S11 S12 S21 S22 Installation up to zone 2 A1 F1 F2 U B U EXi U i 0V S12 S22 X1 X3 K1 Logic K2 K1 K2 13 23 U EXi SRB 200EXi U B -1A U i K1 K2 PA PA A1 A2 13

More information

Product Data Sheet 4114 N/17HH-218. The engineer's choice

Product Data Sheet 4114 N/17HH-218. The engineer's choice The engineer's choice 4114 N/17HH-218 INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 4 3.1 Electrical Operating Data... 4 3.2 Electrical Interface - Output

More information

TH100 Three in One Instant Hot Water Tap

TH100 Three in One Instant Hot Water Tap TH100 Three in One Instant Hot Water Tap Installation, Use and Maintenance Customer Care Department The Group Ltd. Harby Road Langar Nottinghamshire NG13 9HY T : 01949 862 012 F : 01949 862 003 E : customer.care@cda.eu

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information