Metasys Integrator TITUS Application

Size: px
Start display at page:

Download "Metasys Integrator TITUS Application"

Transcription

1 Metasys Connectivity Technical Manual Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application Details 3 Component Requirements 6 Vendor Contact Information 7 Design Considerations 7 Cable Connections 8 Cable Pinouts 8 Connecting the Cable 8 Metasys Integrator Setup 10 Point Mapping Tables 12 TITUS 8015 (Rev. 150F with Schedules) VAV, Dual-duct, and Fan Powered Controllers 12 TITUS 4015, 8010, 8015, and 8710 VAV, Single-duct, and Fan Powered Controllers 18 TITUS 4015, 8010, and 8710 VAV, Dual-duct, and Fan Powered Controllers 20 Zcom Room Diffuser 22 Metasys Network Setup 26 Mapping to a CS Object 26 Custom Integration Johnson Controls, Inc. 1 Code No. LIT

2 2 Metasys Integrator Metasys Integrator TITUS Application

3 lntroduction This document explains Metasys Integrator TITUS applications. Use this document with the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5), which provides information on installing and commissioning the Metasys Integrator unit. For information on TITUS equipment, see TITUS documentation (obtainable from a TITUS representative). Note: If you use a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator Series 300 in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0), as shown in the figures in this application note. Application Details The Metasys Integrator unit allows TITUS 4015, 8010, 8015, and 8710 Variable Air Volume (VAV), Dual-duct, and Fan Powered Controllers to become an integral part of the Metasys and Metasys Companion Networks. Once the TITUS System Interface and Network Coordinator (SINC/ or SINC/1-1030) are connected to a Metasys or Companion Network via the Metasys Integrator unit, each of the 4015, 8010, 8015 and 8710 VAV, Dual-duct, Fan Powered Controllers, and Zcom Controllers can be accessed by the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. The SINC device connects to the Metasys Integrator unit through the RS-232 port. Once connected, it is the interface between TITUS equipment and non-titus devices (such as the Metasys Integrator unit). Each Metasys Integrator vendor port can connect to one SINC device. Each SINC device can connect up to 32 VAV, dual-duct, fan powered controllers, or Zcom controllers. Any Metasys Integrator unit supported SINC controllers (including TITUS, Nesbitt, and ASI) can be on the same vendor port. The controllers are connected in a daisy-chain configuration. Figure 1 shows TITUS and Metasys integration, and Figure 2 shows TITUS and Metasys Companion integration. Metasys Integrator Metasys Integrator TITUS Application 3

4 um p um p N1LAN Standard NCU Metasys Integrator RS-232 SINC/ RS-232 to RS-485 Converter RS-485 (two wire) UNT N2 Bus TDI-8015 Controller TDI-8015 Controller TDI-8015 Controller TDI-8015 Controller Note: If you use a UPM enclosure, you must install the Metasys Integrator Series 300 in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 1: TITUS and Metasys Integration asivav Panel Unit Workstation Metasys Integrator RS-232 SINC/ RS-232 to RS-485 Converter UNT RS-485 (two wire) N2 Bus TDI-8015 Controller TDI-8015 Controller TDI-8015 Controller TDI-8015 Controller Note: A PC version and converter may be substituted for the Panel unit. asivavcp Note: If you use a UPM enclosure, you must install the Metasys Integrator Series 300 in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 2: TITUS and Metasys Companion Integration 4 Metasys Integrator Metasys Integrator TITUS Application

5 Metasys Integrator Metasys Integrator TITUS Application 5

6 Component Requirements Metasys Release Requirements To integrate TITUS equipment, you need: TITUS SINC/ System Interface and Network Coordinator (TITUS SINC/ for Zcom) TITUS 4015, 8010, 8015, and 8710 VAV, Dual-duct, and Fan Powered Controllers or TITUS Zcom Controllers RS-232 cable for connecting the SINC device to the Metasys Integrator unit 2-wire, half-duplex, balanced RS-485 cable (for connecting the SINC device to 4015, 8010, 8015, and 8710 VAV, Dual-duct, and Fan Powered Controllers if the devices are not already networked) Metasys Integrator unit N2 Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Network) portable PC for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics cable for connecting portable PC to the Metasys Integrator unit the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on the CD-ROM) This document describes the RS-232 cable and the vendor communication tables. TITUS documentation describes their equipment. The remaining components are described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). To integrate TITUS equipment into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release 6.0 or higher Metasys Integrator software/firmware Release 9.0 or higher Metasys To integrate TITUS equipment into the Metasys Companion Network, Companion you need: Release Requirements Metasys Companion Release 5.0 or higher Metasys Integrator software/firmware Release 9.0 or higher Vendor Component Requirements Integration between the Metasys Integrator unit and TITUS has been tested with the equipment listed in Table 1. Changes to this equipment or integration of TITUS products not discussed in this document require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this document. 6 Metasys Integrator Metasys Integrator TITUS Application

7 Table 1: TITUS Part and Software Version Numbers TITUS Product Model Number TITUS 4015 VAV, Dual-duct, and Fan Powered Controller TITUS 8010 VAV, Dual-duct, and Fan Powered Controller TITUS 8015 VAV, Dual-duct, and Fan Powered Controller TITUS 8015/1 VAV and Adjustable Fan Powered Controller TITUS 8710 VAV, Dual-duct, and Fan Powered Controller TD (Firmware Rev. 154) TD (Firmware Rev. 137) TD (Firmware Rev. 150E, 150F, and 152A) TDI-8015 (Firmware Rev. 137) TD (Firmware Rev. 142) SINC/ TITUS Zcom Controller ZCOM (Firmware Rev.1.3) SINC/ SINC/ RS-485 Two Wire Cable (25 ft) Vendor Contact Information Design Considerations TITUS, Inc Executive Drive East, Suite 90 Richardson, Texas Phone: (972) FAX: (972) When integrating TITUS equipment, keep the following considerations in mind: Make sure all TITUS equipment is set up, started, and running properly before attempting to integrate with the Metasys or Companion Network. (The TITUS representative is responsible for operation of TITUS equipment.) Make sure 8015 Controllers using Firmware Rev. 150F and Zcom Controllers using Firmware Rev. 1.3 have the baud rate set to 9600 baud (if the only type of controller on the SINC network). All other supported controllers should have the baud rate set to If you mix versions, make sure that the baud rate is set to that of the controller with the lowest baud rate. All controllers on a SINC network must be set to the same baud rate. (The TITUS representative is responsible for setting the controller s baud rate.) RS-232 cable distance between the Metasys Integrator unit and the SINC device can be a maximum of 50 feet. Cable distance between the SINC device and the last controller can be a maximum of 10,000 feet (for 16 controllers or less). For more than 16 controllers (from 17 to 32), the maximum distance is 4,000 feet. Disconnect the Metasys Integrator unit while controllers are commissioned. Metasys Integrator Metasys Integrator TITUS Application 7

8 Cable Connections Cable Pinouts Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the TITUS SINC device: Vendor Port A or B on Integrator DB-9 Female RS-232 Port on SINC Device DB-9 Male Signal Pin Pin Signal RD TD GND RS-232 (50 ft maximum) TX RX GND asivav2 Figure 3: Cable Pinouts Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the male end of the cable to the RS-232 port on the SINC device. Metasys Integrator SINC Device Vendor Port A or B RS-232 Cable RS-232 Port asivav3 Figure 4: Port-to-Port Connection 8 Metasys Integrator Metasys Integrator TITUS Application

9 Metasys Integrator Metasys Integrator TITUS Application 9

10 Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to the Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers The following table provides setup information specific to TITUS applications. For detailed procedures, see the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). Table 2: Metasys Integrator Setup for TITUS Applications Vendor Communication Table (.VCT File) TITUS 8015 (Firmware Rev. 150F without schedules) TTS_VAVF.VCT TITUS 8015 (Firmware Rev. 150F with schedules) TTS_VAVS.VCT TITUS 4015 (Firmware Rev. 154) TTS_VAVA.VCT and TTS_VASD.VCT TITUS 8010 (Firmware Rev. 137) TITUS 8015 (Firmware Rev. 150E and 152A) TITUS 8710 (Firmware Rev. 142) TITUS Zcom (Firmware Version 601A, Rev. 1.3) TTS_ZCOM.VCT Port Setup Baud Rate 4015, 8010, or 8710 Controller 8015 Controller (Firmware Rev. 150E and 152A) 8015 Controller (Firmware Rev. 150F) Zcom Controller (Firmware Rev. 1.3) or Word Length 8 Start Bit 1 Stop Bits 2 Parity None Interface RS-232 Network Setup Vendor Address 1-16,000 Timeout Value 1000 ms Poll Delay (Zcom only) 55 ms 100 ms Performance Guide 1200 Baud 9600 Baud 4015, 8010, or 8710 Controllers 8015 Controller (Firmware Rev. 150E and 152A) 8015 Controller (Firmware Rev. 150F with schedules) 8015 Controller (Firmware Rev. 150F without schedules) Zcom Controller 8 seconds 8 seconds 5 seconds 4 seconds --- N/A N/A 2 seconds 2 seconds 1 second 10 Metasys Integrator Metasys Integrator TITUS Application

11 Metasys Integrator Metasys Integrator TITUS Application 11

12 Point Mapping Tables TITUS 8015 (Rev. 150F with Schedules) VAV, Dual-duct, and Fan Powered Controllers To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference point for Primary Airflow is 6. Table 3 shows the points available for mapping in the TITUS 8015 (Firmware Rev. 150F with Schedules) VAV, Dual-duct, and Fan Powered Controller. Note: All points except 1 write to the controller s EEPROM. Points 7, 8, 10-14, 17, 18, 21, and 22 also write to the controller s EEPROM. Care should be taken to limit the number of writes to these points. Table 3 is also available without points 26 to 105 to use the TITUS 8015 Firmware Rev. 150F without schedules. Table 3: TITUS 8015 VAV, Dual-duct, and Fan Powered Controllers NPT 1 NPA Unit Description DegF DegF DegF Min cfm cfm DegF DegF DegF BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 BI 9 BI 10 BI 11 BI 12 BI 13 BI 14 BI 15 BI 16 BI 17 1 Network Point Type 2 Network Point Address Active HTG Temperature Setpoint Active CLG Temperature Setpoint Present Zone Temperature Afterhours Total Time Controller Personality Primary Airflow Auxiliary Airflow Aux Temperature 1 Aux Temperature 2 Aux Temperature 3 Zone Temperature Too High Zone Temperature Too Low Primary Airflow Too High Primary Airflow Too Low Mode is Heating Mode is Deadband Mode is Cooling Emergency State 1 Emergency State 2 Electric Heat 1 0-off, 1-on Electric Heat 2 0-off, 1-on Electric Heat 3 0-off, 1-on Hot Water Valve Open Hot Water Valve Closed Holiday Status Time Synchronization Needed Lights Status 0-off, 1-on 12 Metasys Integrator Metasys Integrator TITUS Application

13 Continued on next page... Metasys Integrator Metasys Integrator TITUS Application 13

14 The unit stands for Military Time. This time value should be entered in 24-hour format with a period separating the hours and minutes. The controller rounds down to the nearest hour. For example, would be equivalent to 4:18 p.m. NPT 1 (Cont.) NPA Unit DegF DegF DegF DegF DegF DegF DegF Min DegF 11 cfm 12 cfm 13 cfm 14 cfm 15 cfm 16 cfm 17 cfm 18 cfm 19 cfm 20 cfm 21 cfm 22 cfm 23 cfm 24 cfm 25 cfm 26 * 27 1 Network Point Type 2 Network Point Address Description Controller State 1-unoccupied, 2-occupied, 3-night setback, 4-morning warmup, 5-restore state The following points have a range of 0-255: Cooling Occupied Temperature Setpoint Heating Occupied Temperature Setpoint Cooling Unoccupied Temperature Setpoint Heating Unoccupied Temperature Setpoint Cooling Night Setback Temperature Setpoint Heating Night Setback Temperature Setpoint Changeover Temperature Setpoint Afterhours Time Allowed Zone Temperature Alarm Range The following point ranges depend on the cooling or heating K-factor and duct area size: Cooling Airflow Occupied Minimum Setpoint Cooling Airflow Occupied Maximum Setpoint Heating Airflow Occupied Minimum Setpoint Heating Airflow Occupied Maximum Setpoint Fan Airflow Setpoint Cooling Airflow Alarm Range Heating Airflow Alarm Range Cooling Unoccupied Minimum Airflow Setpoint Cooling Unoccupied Maximum Airflow Setpoint Heating Unoccupied Minimum Airflow Setpoint Heating Unoccupied Maximum Airflow Setpoint Cooling Night Setback Minimum Airflow Setpoint Cooling Night Setback Maximum Airflow Setpoint Heating Night Setback Minimum Airflow Setpoint Heating Night Setback Maximum Airflow Setpoint Occupied 1 Holiday Occupied 2 Holiday * - Military Time. This time value should be entered in 24-hour format with a period separating the hours and minutes. The controller rounds down to the nearest quarter hour. For example, would be equivalent to 4:18 p.m. Continued on next page Metasys Integrator Metasys Integrator TITUS Application

15 NPT 1 (Cont.) NPA 2 Unit Description Network Point Type * 2 Network Point Address The following points have a range of 0-24: Unoccupied 1 Holiday Unoccupied 2 Holiday Night Setback Holiday Morning Ready Holiday Lights ON 1 Holiday Lights OFF 1 Holiday Lights ON 2 Holiday Lights OFF 2 Holiday Occupied 1 Monday Occupied 2 Monday Unoccupied 1 Monday Unoccupied 2 Monday Night Setback Monday Morning Ready Monday Lights ON 1 Monday Lights OFF 1 Monday Lights ON 2 Monday Lights OFF 2 Monday Occupied 1 Tuesday Occupied 2 Tuesday Unoccupied 1 Tuesday Unoccupied 2 Tuesday Night Setback Tuesday Morning Ready Tuesday Lights ON 1 Tuesday Lights OFF 1 Tuesday Lights ON 2 Tuesday Lights OFF 2 Tuesday Occupied 1 Wednesday Occupied 2 Wednesday Unoccupied 1 Wednesday Unoccupied 2 Wednesday Night Setback Wednesday Morning Ready Wednesday Lights ON 1 Wednesday Lights OFF 1 Wednesday Lights ON 2 Wednesday Lights OFF 2 Wednesday Occupied 1 Thursday * - Military Time. This time value should be entered in 24-hour format with a period separating the hours and minutes. The controller rounds down to the nearest quarter hour. For example, would be equivalent to 4:18 p.m. Continued on next page... Metasys Integrator Metasys Integrator TITUS Application 15

16 NPT 1 (Cont.) NPA Unit * 1 Network Point Type 2 Network Point Address Description Occupied 2 Thursday Unoccupied 1 Thursday Unoccupied 2 Thursday Night Setback Thursday Morning Ready Thursday Lights ON 1 Thursday Lights OFF 1 Thursday Lights ON 2 Thursday Lights OFF 2 Thursday Occupied 1 Friday Occupied 2 Friday Unoccupied 1 Friday Unoccupied 2 Friday Night Setback Friday Morning Ready Friday Lights ON 1 Friday Lights OFF 1 Friday Lights ON 2 Friday Lights OFF 2 Friday Occupied 1 Saturday Occupied 2 Saturday Unoccupied 1 Saturday Unoccupied 2 Saturday Night Setback Saturday Morning Ready Saturday Lights ON 1 Saturday Lights OFF 1 Saturday Lights ON 2 Saturday Lights OFF 2 Saturday Occupied 1 Sunday Occupied 2 Sunday Unoccupied 1 Sunday Unoccupied 2 Sunday Night Setback Sunday Morning Ready Sunday Lights ON 1 Sunday Lights OFF 1 Sunday Lights ON 2 Sunday Lights OFF 2 Sunday * - Military Time. This time value should be entered in 24-hour format with a period separating the hours and minutes. The controller rounds down to the nearest quarter hour. For example, would be equivalent to 4:18 p.m. Continued on next page Metasys Integrator Metasys Integrator TITUS Application

17 NPT 1 (Cont.) NPA Unit Description Controller State: State is Occupied*** 0-N/A, 1-true State is Unoccupied*** 0-N/A, 1-true State is Night Setback*** 0-N/A, 1-true State is Morning Ready*** 0-N/A, 1-true Restore State to Daily Event Schedule*** 0-N/A, 1-true Synchronize Time 0-N/A, 1-true Fan Status** 0-off, 1-on Heat Override Status** 0-off, 1-on Changeover Status** 0-off, 1-on Cancel Emergency Status*** 0-N/A, 1-true Assume Emergency State 1*** 0-N/A, 1-true Assume Emergency State 2*** 0-N/A, 1-true Cooling Damper Closed*** 0-N/A, 1-true Cooling Damper Open*** 0-N/A, 1-true Cooling Damper Minimum*** 0-N/A, 1-true Cooling Damper Maximum*** 0-N/A, 1-true Heating Damper Closed*** 0-N/A, 1-true Heating Damper Open*** 0-N/A, 1-true Heating Damper Minimum*** 0-N/A, 1-true Heating Damper Maximum*** 0-N/A, 1-true Restore Cooling Damper*** 0-N/A, 1-true Restore Heating Damper*** 0-N/A, 1-true 1 Network Point Type 2 Network Point Address ** Auto Release commands will be sent to the controller for these points. *** Do not map these points to Companion points. If you map these points to Metasys objects, make sure the Auto Restore option in the object s Definition and Focus Window is disabled. Metasys Integrator Metasys Integrator TITUS Application 17

18 TITUS 4015, 8010, 8015, and 8710 VAV, Single-duct, and Fan Powered Controllers To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Present Zone Temperature is 3. Table 4 and Table 5 show points available for mapping in TITUS 4015 (Firmware Rev. 154), 8010 (Firmware Rev. 137), 8015 (Firmware Rev. 150E, 150F, and 152A), and 8710 (Firmware Rev. 142) Controllers. Note: All points except 1 write to the controller s EEPROM. Points 7, 8, 10, 11, 12, 17, 18, 21, and 22 also write to the controller s EEPROM. Care should be taken to limit the number of writes to these points. Table 4: TITUS 4015, 8010, 8015 and 8710 VAV, Single-duct, and Fan Powered Controllers NPT 1 NPA Unit Description 2 1 DegF Active HTG Temperature Setpoint 2 DegF Active CLG Temperature Setpoint 3 DegF Present Zone Temperature 4 Min Afterhours Total Time 5 DegF Controller Personality 6 cfm Primary Airflow BI 1 Zone Temperature Too High BI 2 Zone Temperature Too Low BI 3 Primary Airflow Too High BI 4 Primary Airflow Too Low BI 5 Mode is Heating BI 6 Mode is Deadband BI 7 Mode is Cooling BI 8 Emergency State 1 BI 9 Emergency State 2 BI 10 Electric Heat 1 0-off, 1-on BI 11 Electric Heat 2 0-off, 1-on BI 12 Electric Heat 3 0-off, 1-on BI 13 Hot Water Valve Open BI 14 Hot Water Valve Closed BI 15 Holiday Status BI 16 Time Synchronization Needed 1 Network Point Type 2 Network Point Address Continued on next page Metasys Integrator Metasys Integrator TITUS Application

19 NPT 1 (Cont.) NPA 2 Unit Description 1 Controller State 1-unoccupied, 2-occupied, 3-night setback, 4-morning warmup, 5-restore state The following points have a range of 0-255: 2 DegF Cooling Occupied Temperature Setpoint 3 DegF Heating Occupied Temperature Setpoint 4 DegF Cooling Unoccupied Temperature Setpoint 5 DegF Heating Unoccupied Temperature Setpoint 6 DegF Cooling Night Setback Temperature Setpoint 7 DegF Heating Night Setback Temperature Setpoint 8 DegF Changeover Temperature Setpoint 9 Min Afterhours Time Allowed The following point ranges depend on the cooling or heating K-factor and duct area size: 10 cfm Fan Airflow Setpoint 11 cfm Cool Minimum Airflow Setpoint 12 cfm Cool Maximum Airflow Setpoint 13 cfm Heat Minimum Airflow Setpoint 14 cfm Heat Maximum Airflow Setpoint Controller State: 1 State is Occupied** 0-N/A, 1-true 2 State is Unoccupied** 0-N/A, 1-true 3 State is Night Setback** 0-N/A, 1-true 4 State is Morning Ready** 0-N/A, 1-true 5 Restore State to Daily Event Schedule** 0-N/A, 1-true 6 Synchronize Time** 0-N/A, 1-true 7 Fan Status* 0-off, 1-on 8 Heat Override* 0-off, 1-on 9 Changeover Status* 0-off, 1-on 10 Cancel Emergency Status** 0-N/A, 1-true 11 Assume Emergency State 1** 0-N/A, 1-true 12 Assume Emergency State 2** 0-N/A, 1-true 13 Cooling Damper Closed** 0-N/A, 1-true 14 Cooling Damper Open** 0-N/A, 1-true 15 Cooing Damper Minimum** 0-N/A, 1-true 16 Cooling Damper Maximum** 0-N/A, 1-true 17 Heating Damper Closed** 0-N/A, 1-true 18 Heating Damper Open** 0-N/A, 1-true 19 Heating Damper Minimum** 0-N/A, 1-true 20 Heating Damper Maximum** 0-N/A, 1-true 21 Restore Cooling Damper** 0-N/A, 1-true 22 Restore Heating Damper** 0-N/A, 1-true 1 Network Point Type 2 Network Point Address * Auto Release commands will be sent to the controller for these points. ** Do not map these points to Companion points. If you map these points to Metasys objects, make sure Auto Restore in the object s Definition and Focus Window is disabled. Metasys Integrator Metasys Integrator TITUS Application 19

20 TITUS 4015, 8010, and 8710 VAV, Dual-duct, and Fan Powered Controllers To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Present Zone Temperature is 3. Table 5: TITUS 4015, 8010, and 8710 VAV, Dual-duct, and Fan Powered Controllers NPT 1 NPA Unit Description 2 1 DegF Active HTG Temperature Setpoint 2 DegF Active CLG Temperature Setpoint 3 DegF Present Zone Temperature Min DegF cfm cfm cfm cfm Afterhours Total Time Controller Personality Primary Airflow Auxiliary Airflow Primary Airflow-Heating Dual-duct Auxiliary Airflow-Heating Dual-duct BI 1 Zone Temperature Too High BI 2 Zone Temperature Too Low BI 3 Primary Airflow Too High BI 4 Primary Airflow Too Low BI 5 Mode is Heating BI 6 Mode is Deadband BI 7 Mode is Cooling BI 8 Emergency State 1 BI 9 Emergency State 2 BI 10 Electric Heat 1 0-off, 1-on BI 11 Electric Heat 2 0-off, 1-on BI 12 Electric Heat 3 0-off, 1-on BI 13 Hot Water Valve Open BI 14 Hot Water Valve Closed BI 15 Holiday Status BI 16 Time Synchronization Needed BI 17 Lights Status 0-off, 1-on 1 Network Point Type 2 Network Point Address * - Military Time. This time value should be entered in 24-hour format with a period separating the hours and minutes. The controller rounds down to the nearest quarter hour. For example, would be equivalent to 4:18 p.m. ** Auto Release commands will be sent to the controller for these points. *** Do not map these points to Companion points. If you map these points to Metasys objects, make sure the Auto Restore option in the object s Definition and Focus Window is disabled. Continued on next page Metasys Integrator Metasys Integrator TITUS Application

21 NPT 1 (Cont.) NPA 2 Unit Description 1 Controller State 1-unoccupied, 2-occupied, 3-night setback, 4-morning warmup, 5-restore state The following points have a range of DegF Cooling Occupied Temperature Setpoint 3 DegF Heating Occupied Temperature Setpoint 4 DegF Cooling Unoccupied Temperature Setpoint 5 DegF Heating Unoccupied Temperature Setpoint 6 DegF Cooling Night Setback Temperature Setpoint 7 DegF Heating Night Setback Temperature Setpoint 8 DegF Changeover Temperature Setpoint 9 Min Afterhours Time Allowed The following point ranges depend on the cooling or heating K-factor and duct area size: 10 cfm Fan Airflow Setpoint 11 cfm Cool Minimum Airflow Setpoint 12 cfm Cool Maximum Airflow Setpoint 13 cfm Heat Minimum Airflow Setpoint 14 cfm Heat Maximum Airflow Setpoint 15 cfm Fan Airflow Setpoint Heating Dual-duct Controller State: 1 State is Occupied** 0-N/A, 1-true 2 State is Unoccupied** 0-N/A, 1-true 3 State is Night Setback** 0-N/A, 1-true 4 State is Morning Ready** 0-N/A, 1-true 5 Restore State to Daily Event Schedule** 0-N/A, 1-true 6 Synchronize Time** 0-N/A, 1-true 7 Fans Status* 0-off, 1-on 8 Heat Override* 0-off, 1-on 9 Changeover Status* 0-off, 1-on 10 Cancel Emergency Status** 0-N/A, 1-true 11 Assume Emergency State 1** 0-N/A, 1-true 12 Assume Emergency State 2** 0-N/A, 1-true 13 Cooling Damper Closed** 0-N/A, 1-true 14 Cooling Damper Open** 0-N/A, 1-true 15 Cooing Damper Minimum** 0-N/A, 1-true 16 Cooling Damper Maximum** 0-N/A, 1-true 17 Heating Damper Closed** 0-N/A, 1-true 18 Heating Damper Open** 0-N/A, 1-true 19 Heating Damper Minimum** 0-N/A, 1-true 20 Heating Damper Maximum** 0-N/A, 1-true 21 Restore Cooling Damper** 0-N/A, 1-true 22 Restore Heating Damper** 0-N/A, 1-true Metasys Integrator Metasys Integrator TITUS Application 21

22 Zcom Room Diffuser To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Seconds Timer is 7. 1 Network Point Type 2 Network Point Address ** Auto Release commands will be sent to the controller for these points. *** Do not map these points to Companion points. If you map these points to Metasys objects, make sure the Auto Restore option in the object s Definition and Focus Window is disabled. The following table shows the points available for mapping in the TITUS Zcom Room Diffuser: Table 6: Zcom Room Diffuser NPT 1 NPA 2 Unit Description 1 Deg Supply Air Temperature 2 Deg Reference Supply Air Temperature 3 Deg Induced Air Temperature 4 Deg Implied Zone Temperature 5 Active User Adjust 6 Out of Range Timer 7 Sec Seconds Timer 8 Min Minutes Timer 9 % Motor Position 10 Min Aux Heat Timer 11 DegF Heat Setpoint 12 % Cooling Requirement 13 % Heating Requirement 14 DegF Active Cooling SP (F or C) 15 DegF Active Heating SP (F or C) 16 % Active Damper Position (0 100%) BI 1 Zone Temp Alarm High BI 2 Zone Temp Alarm Low BI 3 Zone Temp Limit Alarm HI/HI BI 4 Zone Temp Limit Alarm LO/LO BI 5 Hi Out of Range Alarm BI 6 Zone Mode is DB BI 7 Zone Mode is Cool BI 8 Zone Mode is Heat BI 9 Master Mode is Off BI 10 Master Mode is Cool BI 11 Master Mode is Heat BI 12 Master Mode is Vent BI 13 After Hours Request BI 14 Out of Range Alarm BI 15 Damper Control BI 16 Aux Heat 0-off, 1-on BI 17 Damper Operation 0-off, 1-on 22 Metasys Integrator Metasys Integrator TITUS Application

23 1 Network Point Type 2 Network Point Address Continued on next page... Metasys Integrator Metasys Integrator TITUS Application 23

24 NPT 1 (Cont.) NPA 2 Unit Description 1 Code Heat Override 0-Default 1-Minimum Open 2-Full Open 3-Full Close 2 Code Cool Override 0-Default 1-Minimum Open 2-Full Open 3-Full Close 3 DegF Cooling Temperature Setpoint (F) 4 DegF Heating Temperature Setpoint (F) 5 DegC Cooling Temperature Setpoint (C) 6 DegC Heating Temperature Setpoint (C) 7 Deg User Adjust Setpoint 8 Deg Throttle Range 9 Min Integral Time 10 % Cooling Min Position 11 % Heating Min Position 12 Deg Aux Heat Temp Offset 13 Min Aux Heat Delay 14 Deg Zone Temp Offset 1 Celsius Units Enabled 0-no, 1-yes 2 Aux Heat Enabled 0-no, 1-yes 3 Cooling Override Min* 0-no, 1-yes 4 Cooling Override Full Open* 0-no, 1-yes 5 Cooling Override Full Close* 0-no, 1-yes 6 Heating Override Min* 0-no, 1-yes 7 Heating Override Full Open* 0-no, 1-yes 8 Heating Override Full Close* 0-no, 1-yes 1 Network Point Type 2 Network Point Address * A command to a 0 state releases the override to the default value. 24 Metasys Integrator Metasys Integrator TITUS Application

25 Metasys Integrator Metasys Integrator TITUS Application 25

26 Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). This section contains details specific to TITUS applications. Mapping to a CS Object Table 7: Software Model and CS Object Definition Application Software Model Display NT Command (on Models and Attribute Attribute TITUS 8015 Controllers (Firmware Rev. 150F) All Supported TITUS Controllers Dual-duct All Supported TITUS Controllers Single-duct Zcom Room Diffuser Tables CD-ROM) (recommended) (recommended) TTS_VAVF.DDL 3 2 TTS_VAVA.DDL TTS_VASD.DDL TTS_ZCOM.DDL Present Zone Temperature 3 Present Zone Temperature 3 Present Zone Temperature 4 Implied Zone Temperature Cooling Occupied Temperature Setpoint 2 Cooling Occupied Temperature Setpoint 2 Cooling Occupied Temperature Setpoint 7 User Adjust Setpoint 26 Metasys Integrator Metasys Integrator TITUS Application

27 Metasys Integrator Metasys Integrator TITUS Application 27

28 Custom Integration For information on integrating products which are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team. Both the Metasys Compatible Global Catalog and the System Integration Project Data Sheet can be accessed from The Advisor by performing the following steps: 1. Click on the Systems Products button located on the left side of The Advisor home page. 2. Click on the Product Literature link. 3. Click on the Manuals-FANS link. 4. Click on the Metasys Connectivity Sales Resource Manual link. 5. Find the System Integration Project Data Sheet link in the Table of Contents. Click on this link to view an online copy of the System Integration Project Data Sheet, or click on the Metasys Compatible Global Catalog link below it to view a list of released Connectivity products. The System Integration Project Data Sheet (LIT ) can also be found in the Metasys Connectivity Sales Resource Manual (FAN 629). If you need further assistance, contact the Johnson Controls Field Support Center. 28 Metasys Integrator Metasys Integrator TITUS Application

29 Notes Metasys Integrator Metasys Integrator TITUS Application 29

30 30 Metasys Integrator Metasys Integrator TITUS Application Notes

31 Notes Controls Group FAN E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Metasys Integrator Release 9.0 Milwaukee, WI Printed in U.S.A. Metasys Integrator Metasys Integrator TITUS Application 31

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Metasys Integrator Vilter Application

Metasys Integrator Vilter Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

Metasys Integrator Liebert Application

Metasys Integrator Liebert Application Application Note Issue Date May, 00 Metasys Integrator Liebert Application lntroduction Application Details Component Requirements 0 Vendor Contact Information Design Considerations Cable Connections Cable

More information

Metasys Integrator McQuay Application

Metasys Integrator McQuay Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component

More information

Metasys Integrator York Application

Metasys Integrator York Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator York Application lntroduction Page * Application Details * Component

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Modbus RTU RS485 Manual

Modbus RTU RS485 Manual Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

Owner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON

Owner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON Owner s Manual Part Number 33CSSP2-FC 33CS Fan Coil Programmable Thermostat SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation.

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

Owner s Manual. Part Number 33CS250-01

Owner s Manual. Part Number 33CS250-01 33CS Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-01 GENERAL Carrier s 7-day, commercial, programmable thermostats

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

T600MEP-2 Programmable Economizer Thermostat

T600MEP-2 Programmable Economizer Thermostat Installation Instructions Issue Date January 19, 2005 T600MEP-2 Programmable Economizer Thermostat Application The T600MEP-2 is a programmable thermostat for control of single- or two-stage unitary rooftop

More information

Owner s Manual. Part Number 33CS250-FS and 33CS220-FS

Owner s Manual. Part Number 33CS250-FS and 33CS220-FS Debonair 33CS Flush-Mounted Flatstat Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-FS and 33CS220-FS GENERAL

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Owner s Manual. Part Number 33CS250-RC

Owner s Manual. Part Number 33CS250-RC CONTENTS Page GENERAL... 1 CONFIGURATION... 1-4 Transmitter Display... 1 Transmitter Indicator... 1 Transmitter Front Panel Buttons... 1 Set Clock... 2 Programming Thermostat Schedules... 3 OPERATION...5

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

ComfortSense 7500 Commercial Thermostat. User Guide

ComfortSense 7500 Commercial Thermostat. User Guide ComfortSense 7500 Commercial Thermostat User Guide 507505-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...2 Home Screen Information...3 Operating Mode Selection...5

More information

AireLogic. Digital Control System. User Manual

AireLogic. Digital Control System. User Manual AireLogic Digital Control System User Manual Rev. 04-11-13 1 Table of Contents OVERVIEW... 6 NETWORKING... 8 AIRELOGIC DEFAULT SETTINGS... 8 UNIT OPERATING MODES... 9 MRT Controls:... 9 UNIT OFF MODE...

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical Service Literature Corp. 0808 L6 06/08 IMC BACnet Module General The IMC BACnet Module (BP1) allows communication between the Lennox IMC M1 8 controller and a BACnet MS/TP network. This module is mounted

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

OWNER S MANUAL. Part Number P

OWNER S MANUAL. Part Number P OWNER S MANUAL CPV230 Commercial Thermostat Part Number P374-2300 CONTENTS Page GENERAL...2 CONFIGURATION...3-12 Thermostat Display...3 Heat or Cool Indicator...4 Thermostat Front Panel Buttons...4 Thermostat

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS VENSTAR FAN COIL THERMOSTAT FAN COIL THERMOSTAT T1075 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS 3 Occupied, 1 Unoccupied Override capable 3 speed fan control Auto 2-pipe changeover when used with accessory

More information

AdaptAire. Digital Control System. User Manual

AdaptAire. Digital Control System. User Manual AdaptAire Digital Control System User Manual Rev. 10-22-07 1 Table of Contents OVERVIEW... 6 NETWORKING... 7 ADAPTAIRE DEFAULT SETTINGS... 7 UNIT OPERATING MODES... 8 MDT Controls:... 8 UNIT OFF MODE...8

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

User s Manual

User s Manual 997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE Emerson Blue Wireless Comfort Interface - Homeowner User Guide Message to Homeowners Congratulations on choosing the Emerson Blue

More information

ETN-24-SUPER-PROG (US Program - Celsius)

ETN-24-SUPER-PROG (US Program - Celsius) Meitavtec Ltd (Contel group) Tel: 972 (3) 962 6462 Fax: 972 (3) 962 6620 www.meitavtec.com support@meitavtec.com ETN24SUPERPROG (US Program Celsius) Owner s Manual Installation and Operating Instructions

More information

Elegance. SMT-700 User manual. Ver

Elegance. SMT-700 User manual. Ver Elegance SMT-700 User manual Ver 3.0. 0807 Congratulations on the purchase of your new Thermostat! Your new air conditioning system thermostat has been built using the best components and design philosophy

More information

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2. VCB-X Modular Service Tool Technical Guide VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.0 and up Table of Contents INTRODUCTION... 3 Modular Service Tool...3 SYSTEM

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1234-1 BACnet Thermostat Group: Applied Air Systems Part Number: IM 1234 Date: December 2014 Use with Daikin MicroTech Integrated Systems or as standalone Table of

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

OWNER S MANUAL. Part Number P RF

OWNER S MANUAL. Part Number P RF OWNER S MANUAL CPE230RF Commercial Programmable Thermostat Wireless Transmitter Part Number P474-2300RF CONTENTS Page GENERAL... 2 CONFIGURATION... 3-12 Transmitter Display... 3 Transmitter Indicator...

More information

AdaptAire. Digital Control System. User Manual. Expert Systems

AdaptAire. Digital Control System. User Manual. Expert Systems AdaptAire Digital Control System User Manual Expert Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 10 ADAPTAIRE DEFAULT SETTINGS... 10 UNIT OPERATING MODES... 11 MRT Controls:...

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

Multistate Alarm. Introduction

Multistate Alarm. Introduction Object Dictionary 1 Multistate Alarm Introduction The Multistate Alarm object adds the alarming capability for a Boolean or multistate attribute for any object, such as the Present Value of a Binary Input

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat:

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat: SM CAUTION Follow the Installation Instructions before proceeding. Set the thermostat mode to OFF prior to changing settings in setup or restoring Factory Defaults. This Explorer thermostat has the ability

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

4 Wiring Brochure Wiring and

4 Wiring Brochure Wiring and - Brochure tekmarnet 4 Thermostat 544 D 544 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring

More information

Installation, Start-Up, and Operating Instructions

Installation, Start-Up, and Operating Instructions Installation, Start-Up, and Operating Instructions CONTENTS Page SAFETY CONSIDERATIONS...1 GENERAL...1 INSTALLATION...1-5 Install Batteries...1 Select Transmitter Location (Optional)...1 Mount Transmitter

More information

Installation, Start-Up, and Operating Instructions

Installation, Start-Up, and Operating Instructions Installation, Start-Up, and Operating Instructions IMPORTANT: Read entire instructions before starting the installation. SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow

More information

1 For All Programmable Digital Thermostat

1 For All Programmable Digital Thermostat OWNER'S MANUAL P/N P374-2300FM 1 For All Programmable Digital Thermostat Am OFF OVERRIDE Meets California Title 24 unts flush to the wall 7 Day Programmable 3 Occupied, 1 Unoccupied Auto-Changeover Large,

More information

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Please read this manual carefully before installation and use.

Please read this manual carefully before installation and use. Doylestown, PA 18902 USA Phone: 215-766 1487 - Fax: 215-766 1493 Email: support@scillc.com - www.scillc.com FMT-24-SUPER-PROG With freeze protection Owner s Manual Installation and Operating Instructions

More information

ATC32U03 igate Communicating, Programmable Thermostat

ATC32U03 igate Communicating, Programmable Thermostat ATC32U03 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 11/3/17 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature

More information

For Raychem ACS-30 Controls Systems

For Raychem ACS-30 Controls Systems ACS-30 Protocol Interface Mapping For Raychem ACS-30 Controls Systems Firmware Version 5.05 THERMAL BUILDING SOLUTIONS EN-RaychemACS30-AR-H58324 03/16 Table of Content Section 1. Introduction... 3 1.1

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

ATC32U01 igate Communicating, Programmable Thermostat

ATC32U01 igate Communicating, Programmable Thermostat ATC32U01 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 7/2/12 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

- Data Brochure tekmarnet 4 Thermostat 542e

- Data Brochure tekmarnet 4 Thermostat 542e - Data Brochure tekmarnet 4 Thermostat 542e D 542e 03/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in

More information

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,

More information

ComfortSense 7500 Thermostat. User Guide

ComfortSense 7500 Thermostat. User Guide ComfortSense 7500 Thermostat User Guide 507503-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...3 Home Screen Information...3 Operating Mode Selection...6

More information

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS

More information

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include: Model Number: Product/System Title: 8635-ST Static Pressure Controller Contents of this manual supplement include: 1) Sequence of operation 2) Description of new software items 3) Deleted software menu

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS Contents T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS OWNER S GUIDE Features... 2 Settings... 3 Programming... 5 63-2638 FEATURES Typically used in buildings (including: restaurants,

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS 63-2652 FEATURES Typically used in buildings (including: restaurants, shopping malls, office buildings and banks) under 55,000 square feet.

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Using the Room View Window

Using the Room View Window CIT5 User s Guide 4-1 Chapter 4 Introduction The Room View window uses a tabbed display to present the information about one selected room. This chapter describes the tabs and features of the Room View

More information

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions DESCRIPTION The RC-90 is a precision digital thermostat designed for 24 VAC single stage heating and

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions - Brochure tekmarnet 4 Thermostat 542 D 542 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring

More information

User Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015

User Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015 User Guide Color Touchscreen Programmable Residential Thermostat ComfortSense 7500 Model: 13H14 507503-01 10/2015 Supersedes 7/2015 TABLE OF CONTENTS Features... 2 Temperature Dial Indicator... 3 Home

More information

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide SC 5211 2-Stage Heat Pump Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat Pump Systems Large Display With Backlight Selectable

More information

Minimum Core Module Version: 4.0, build 1608 See full list of supported models below. Document Revision Date: 1/9/2018

Minimum Core Module Version: 4.0, build 1608 See full list of supported models below. Document Revision Date: 1/9/2018 Integration Note Manufacturer: Tekmar Model Number(s): Tekmar Net 4 Minimum Core Module Version: 4.0, build 1608 Comments: See full list of supported models below. Document Revision Date: 1/9/2018 OVERVIEW

More information

Homeowner s Guide / 1

Homeowner s Guide / 1 Overview Options Programming Your Homeowner s / 1 Message to the Homeowners Your premium Comfort Control 2 HD Communicating is designed to give you and your family the indoor comfort you desire. It s easy

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Critical Environments Model 8682KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Manual Supplement Contents of this manual supplement

More information

Installation, Service, and Troubleshooting Instructions

Installation, Service, and Troubleshooting Instructions 33CS TEMP System Unitary Controller Thermostat Installation, Service, and Troubleshooting Instructions Page GENERAL........................................ 2 TEMP System Components......................

More information