DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

Size: px
Start display at page:

Download "DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES"

Transcription

1 SECTION SPECIALTIES TOILET PARTITIONS: Owner Preferences: Solid core phenolic, polymer based solid surfacing, and solid plastic toilet compartment and screen systems. No Stainless Steel panels are allowed with written authorization from the Project Manager. All panels must be the manufacturer's standard panels pre-machined for field installation. The solid phenolic core panels must have a matte finish melamine surface. The solid plastic panels must be filled with methyl methacrylate. Ceiling hung mounting is preferred Minimum standard spacing of toilet partitions shall be 3 ft. o.c., Minimum standard depth to be 5-0. Partitions to be standard floor mounted, metal toilet partitions. Where added support is needed in stalls for persons with disabilities, specify that pilasters, for these stalls only, extend to the floor. All toilet stalls designated usable by individuals with disabilities shall be 60 x 60. The water closet must be located 18 (inches) from the wall or partition. A fraction of ¼ (inches) either way is an approved installation tolerance. In some renovation work where tight toilet room dimensions indicate a problem, these can be addressed at the Office of Engineering Design and Construction for solutions. A memorandum describing any departures for ADAAG and/or University standards for accessibility will be included with construction documents and a copy provided to the ADA Coordinator for the University. Install splash guards between all urinals. Submit manufacturer's specifications and product data, shop drawings, sample panels, color samples, hardware and accessories, and operation and maintenance manuals TOILET ACCESSORIES Submit manufacturer's specifications and product data, shop drawings, sample panels, color samples, hardware and accessories, and operation and maintenance manuals. Accessories -- Hardware, accessories and mounting brackets: Chromium plated nonferrous cast alloy in manufacturer's standard styles. Soap Dispensers, paper towel dispensers, toilet paper dispensers, trash receptacles and feminine product dispensers will be surface mounted. All of these items will be provided by the University through the Facilities department and installed by the contractor. For restroom layout and design considerations the design team will receive a list of products from the USA Project Manager. Toilet accessories to conform to requirements of ANSI A117.1 and UFAS for making facilities and accessories accessible to and usable by the physically handicapped. Toilet accessories to conform to requirements of ASTM F446 for grab bars and accessories for test methods, anchorage and functional performance. Provide products of the same manufacturer for each type of accessory unit and for units exposed in the same areas, unless otherwise acceptable to the Architect. Stamped names and labels on exposed faces of units will not be permitted, except where otherwise indicated. Toilet accessories material to be Stainless Steel: AISI Type 302/304 with polished No. 4 finish, 22 gage minimum. Sheet Steel to be Cold-rolled complying with ASTM A366, 20 gage minimum. Provide surface preparation and metal pretreatment as required for applied finish. Mirror Glass to be ASTM C1036, Type I, Class 1, Quality q2, 0.25 thick, with silvering, electro-plated copper coating, and protective organic coating. UPDATED - JULY 21, 2017 Page 1 of 5

2 CONTRACTOR TO PROVIDE AND INSTALL Mirrors over lavatories: Specify framed mirrors without shelves. If possible, locate mirrors on walls opposite lavatories. Specify long mirrors, for use by persons with disabilities, with bottom 2 ft. above floor and with top located at same height as smaller mirrors. Check and coordinate mirror locations to prevent image reflection through room entrances. Provide 18" x 36" mirror at all single lavatories. Provide single 30" x 36" mirror at double lavatories. At three or more lavatories provide gang type mirror, 36 high and approximate length of lavatory run Provide article shelf just below mirrors. Gage: 18 gage stainless steel 6" wide with raised front and back edges. Provide tilt mirrors at handicap lavatories. Grab Bars: The Design Associate should follow the ADA Accessibility Guidelines for Buildings and Facilities (ADAAG) that defines requirements for installing grab bars in public bathing and toileting facilities The diameter of grab bars should be 1¼ to 1½ inch (30-40 mm) (or the shape shall provide an equivalent gripping surface). There shall be a 1½ inch (40 mm) clearance from the wall. Grab bars should not rotate in their fittings. The required mounting height is universally 33 to 36 inches ( mm) from the centerline of the grab bar to the finish floor. ADA-style grab bars and their mounting devices should withstand more than 250 pounds (1112 N) of force. Side grab bars must be a minimum of 42 inches long and mounted 12 inches from the rear wall, and rear grab bars must be a minimum of 36 inches long and mounted a maximum of 6 inches from the side wall. Grab bars should be constructed of 18-gauge (1.2mm), type 304 satin-finish stainless steel tubing with concealed mounting flange 1 8" (3mm) thick, type 304 stainless steel plate, 2" W x 3 1 8" H (50 x 80mm), with screw holes for concealed anchors. Covers to be 22-gauge (0.8mm), type 304 stainless steel with satin finish, 3 1 4" (85mm) diameter. Cover snaps over mounting flange to conceal screws. Sanitary napkin disposals: Install in the partition wall where applicable to be shared between stalls. Garment Hooks: Each toilet stall shall have a garment hook. The hooks shall be mounted on the partition; hooks in stalls for use by individuals with disabilities shall be on the partition, reachable from the water closet and approximately 54 in. above the floor. Hook can incorporate door bumper hook. Mop Sinks: Provide floor mounted mop sinks. Mop and Broom holders: Install mop and broom holders in each Custodial Work Station with six holders and five hooks (Bobrick B-224 or approved substitute). Mount such that two mop holders will occur over mop sink. Install locker in custodial workstations. UPDATED - JULY 21, 2017 Page 2 of 5

3 Splash Guards: Install splash guards on all walls adjacent to mop sinks in Custodial Work Stations, to faucet height. Diaper Changing Station: At all Assembly area and areas open to the public, provide one diaper changing station for each toilet room. OWNER TO PROVIDE / CONTRACTOR TO INSTALL Jumbo Toilet Tissue Holders Paper Towel dispensers Soap Dispensers Hand Sanitizer Dispenser: WHITE BOARDS Furnish a written guarantee to the University signed by an officer of the manufacturer of the chalkboard stating that all chalkboards which do not retain the original writing quality, the original erasing quality, and the original visual acuity for 20 years after date of acceptance will be replaced and installed without charge to the University. Whiteboards shall be porcelain enameled steel of construction equal to, or better than, the following: Writing surface shall have a minimum of 2 coats of porcelain enamel on 24 gauge cold rolled stretcher-leveled enameling steel. Core shall be 3/8 inch tempered hardboard or 80 pcf density particle board. Backing shall be aluminum.015 inch thick. Trim shall be aluminum in manufacturer s standard sections; include chalk trough and map rail complete with map hooks, 4 hooks per section. Mount on primed wood grounds. Except for approved special conditions, all chalkboards shall be mounted with the chalk trough 36 inches above the floor and with a vertical dimension of 48 inches from chalk trough to top of board. For electrically operated boards provide access panels for servicing motors, drives and controls. Switches shall be key operated. Coordination with Division 16 is required. Anchors shall be screw anchors, toggle bolts, hollow wall anchors, or other approved type to suit construction on which compartments are hung. Wood, lead, and plastic plugs are prohibited. Fasteners shall be vandal-proof type screws. Provide marker tray to all boards. METAL WALL LOUVERS: Louvers and vents for air distribution systems should be specified in Division 15H. The HVAC Contractor shall be required to furnish and install all interior louvers and vents. If such items are an integral part of the exterior design of a building and are not connected directly to an air distribution system, specify that the General Contractor purchase and install them. DOOR LOUVERS: Include these in the specifications for doors. IDENTIFYING DEVICES UPDATED - JULY 21, 2017 Page 3 of 5

4 The University has a standardized modular grid system for all campus signage. All signage must meet ADA requirements. The Associate shall follow the guideline issued by the Engineering Design and Construction department. Review and approvals of the identifying devices must be made by the Engineering Design and Construction department before preparing final drawings and specifications for signage. FIRE EXTINGUISHERS AND CABINETS Cabinets to be non lockable type. All portable fire extinguishers and non-valved cabinets shall be furnished and installed by the General Contractor. All portable fire extinguishers and components shall conform with National Fire Protection Association (NFPA) Pamphlet 10, latest edition. Each extinguisher shall be approved by Underwriter s Laboratory (UL) and bear their label with current dated inspection attached. The selection and locations of fire extinguishers are subject to the review and approval of the University Architect and designated University personnel. Extinguishers meeting the described requirements, including those manufactured by Fire Chief, Kidde, and General, will be considered for acceptance. Refer to NFPA pamphlet 10, chapters 2, 3, and 4. Chapter 2 is used to determine the classification of potential fires and the rating or relative fire extinguishing effectiveness of various types of extinguishers. Chapter 3 assists in selection of extinguishers which is dependent upon the character of anticipated fires, property construction and occupancy, the vehicle or hazard to be protected, ambient temperature conditions, and other factors. The maintenance of extinguishers is determined by Chapter 4. Fire Extinguisher cabinets shall be painted steel, flanged recessed (similar to fire hose cabinets), lockable and comparable to the preferred Duo Panel Break Glass style of cabinet. The full fire rating and acoustical rating of the structure walls must be maintained. Penetration of walls by cabinets or other penetrations, unless openings and voids are sealed with fireproof materials, is prohibited. Fire-rated walls must not have the rating reduced by penetration s or reduction of thickness. An acceptable means of identifying fire extinguisher location must be done by an arrow type sign. See Appendix A, a of NFPA pamphlet 10. All fire extinguishers are to be new, complete, tested, certified, ready for use, and conform to the following: CARBON DIOXIDE EXTINGUISHERS: Red enameled-steel or aluminum equipped with valve, discharge hose and horn, squeeze-grip lever, and mounting bracket, if not cabinet installed./ Minimum rating 5 BC. MULTI-PURPOSE EXTINGUISHERS: Red enameled-steel pressurized type equipped with pressure gauge, discharge nozzle, squeeze-grip lever, and mounting bracket, if not cabinet installed. These extinguishers are dry chemical for Class A, B, and C fires. Minimum rating 4A 60 BC. For computer rooms, expensive laboratory installations and similar locations, which must be protected from damage, provide FM 200 with at least 9 lbs. 2A 10BC rating. Submit for approval product data, and O&M submittals. The contractor is responsible for coordinating the partition types with the dimensions of the recessed fire extinguisher cabinets. The contractor must provide the appropriate size recessed cabinet for each fire extinguisher location shown on the contract documents. The contractor is also responsible for field measuring the partitions to ensure that each recessed cabinet will fit. Extinguishers in the hallways and common areas shall be mounted in semi recessed cabinets in accordance with ADA specifications. The top of the extinguisher shall be no higher than 44 from the floor. Extinguishers mounted in mechanical and equipment rooms need not have a cabinet. In accordance with NFPA 10, each 10 lb extinguisher covers 3000 square feet with additional extinguishers in labs and elevator rooms. Parking Decks should have extinguishers permanently mounted. As a minimum, parking decks shall have at least one at the top and bottom of every ramp and at each door to or at the top and bottom of each stairway. UPDATED - JULY 21, 2017 Page 4 of 5

5 If not already provided, a fire extinguisher is to be mounted on a wall mounted bracket with a sign in each mechanical room. DEMOUNTABLE PARTITIONS: If outlets, switches, etc. are furnished by the partition manufacturer, specify devices of same quality as those specified in Division 16. (Note limitations and prohibitions regarding conduit types and sizes.) TOILET AND SHOWER ACCESSORIES EMERGENCY SHOWERS AND EYE WASHES Provide emergency showers with floor drains and eyewashes within 100 feet or within 10 seconds of a chemical substance deemed hazardous. UPDATED - JULY 21, 2017 Page 5 of 5

DIVISION 10 SPECIALTIES

DIVISION 10 SPECIALTIES DIVISION 10 SPECIALTIES 11/11 SECTION 10 21 13.16 PLASTIC LAMINATE TOILET COMPARTMENTS PART 1 - GENERAL 1.01 SECTION INCLUDES Plastic laminate toilet compartments, urinal screens, head rail braced. 1.02

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

ASI Guide Specification

ASI Guide Specification SECTION 10 2800 TOILET ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Provide toilet accessories with attachment hardware and rough-in frames as required for complete, operational installation. B. Section

More information

BRADLEY COMMERCIAL TOILET ACCESSORIES

BRADLEY COMMERCIAL TOILET ACCESSORIES BRADLEY COMMERCIAL TOILET ACCESSORIES This Bradley guide specification is useful in specifying toilet and bath accessories for institutional projects, including K-12 and university facilities, municipal

More information

Element C Interiors Interior Construction

Element C Interiors Interior Construction Fittings and Interior PART 1 - GENERAL 1.01 OVERVIEW A. Includes marker and tack boards, lockers, storage shelving, handrails and wall protection, access doors, aquariums, fire extinguishers, and signage.

More information

University of Delaware

University of Delaware KEY STATION Campus must have a key station minimum 20 x 16 1 Computer hook up for time and attendance Furniture Seating for 20 Employee mailbox 3 Key Boxes (2 boxes should hold 30 keys; 1 box should hold

More information

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers.

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers. SECTION 10 44 13 - FIRE-PROTECTION SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Ship Program Washroom Accessories. Keys. Combination Towel / Waste

Ship Program Washroom Accessories. Keys. Combination Towel / Waste Keys 24-17 BobKey 330-43 Cat 74 Door Key 822-25 BobKey Combination Towel / Waste 369-130 TowelMate Accessory, Optional 3944-130 TowelMate Accessory, Optional 3944-134 LinerMate Accessory, Optional B-369

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES SECTION 105200 - FIRE-PROTECTION SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

Plumbing Guidelines 2012 IBC/ANSI A

Plumbing Guidelines 2012 IBC/ANSI A Plumbing Guidelines 2012 IBC/ANSI A117.1-2009 This document provides basic and fundamental information for accessible plumbing fixtures, toilet rooms and bathing facilities. It is not intended to replace

More information

Plumbing Guidelines 2015 Minnesota Accessibility Code Based on the 2012 IBC and 2009 ANSI A117.1

Plumbing Guidelines 2015 Minnesota Accessibility Code Based on the 2012 IBC and 2009 ANSI A117.1 Plumbing Guidelines 2015 Minnesota Accessibility Code Based on the 2012 IBC and 2009 ANSI A117.1 This document provides basic and fundamental information for accessible plumbing fixtures, toilet rooms

More information

DIVISION 10 SPECIALITIES

DIVISION 10 SPECIALITIES DIVISION 10 10200-01 SANITARY ACCESSORIES 01.1 Manufacturer: As noted on Drawings. Provide wall blocking as required. Provide accessories if required on Drawings. 01.2 Grab bars: one 42 behind and on side

More information

SECTION IDENTIFYING DEVICES

SECTION IDENTIFYING DEVICES PRT 1 -GENERL 1.01 RELTED DOCUMENTS SECTION 10 1425 IDENTIFYING DEVICES. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type. PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

More information

CLINICAL SERVICES ADMINISTRATION (214)

CLINICAL SERVICES ADMINISTRATION (214) CLINICAL SERVICES ADMINISTRATION (214) 1 - M EDICAL SERVICE AREA 1 - OFDC2 - Interview Room A5075 Dispenser, Soap, Disposable 1 VV Disposable soap dispenser. One-handed dispensing operation. Designed to

More information

Gen 4.5 New Build Palettes

Gen 4.5 New Build Palettes SpringHill Suites New Build This Master Specification Document, as an Instrument of Service, is provided in confidence, for use in preparing final construction specifications for a Marriott CFRST Project.

More information

DOMESTIC WATER PACKAGED BOOSTER PUMPS

DOMESTIC WATER PACKAGED BOOSTER PUMPS DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot

More information

JAMES P. KISSANE, ARCHITECT

JAMES P. KISSANE, ARCHITECT UNISEX RESTROOM 6" X 9" UNISEX H.C. RESTROOM SIGN; BLUE NOTE: THE FASTENING HARDWARE FOR THE WALL BRACKETS FOR THE AND THE URINAL AND GRAB BARS MUST BE ABLE TO SUPPORT A 300 LB. WEIGHT. CONTRACTOR IS REQUIRED

More information

Division 10. Specialties

Division 10. Specialties Division 10. Specialties 10 10 00. Information Specialties 10 11 00. Visual Display Surfaces 1. The type of visual display boards used throughout a specific project shall be determined during the design

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

ROVAL COLLECTION PAPER TOWEL DISPENSERS TOILET TISSUE DISPENSERS MIRRORS AUTOMATIC HAND DRYERS

ROVAL COLLECTION PAPER TOWEL DISPENSERS TOILET TISSUE DISPENSERS MIRRORS AUTOMATIC HAND DRYERS ROVAL COLLECTION TOILET TISSUE DISPENSERS PAPER TOWEL DISPENSERS AUTOMATIC HAND DRYERS MIRRORS ROVAL COLLECTION INTRODUCING ROVAL by ASI From ASI comes a collection of washroom accessories that is not

More information

SPACE TYPE: JUDICIAL CHAMBER

SPACE TYPE: JUDICIAL CHAMBER SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

A. Section Joint Sealants: Seal fixtures to walls and floors.

A. Section Joint Sealants: Seal fixtures to walls and floors. SECTION 224000 - PLUMBING FIXTURES PART 1 GENERAL 1.1 SECTION INCLUDES A. Water closets. B. Urinals. C. Lavatories. D. Sinks. E. Service sinks. F. Showers. G. Wash fountains. H. Eye wash fountains. 1.2

More information

SECTION CUSTOM FABRICATED FOODSERVICE EQUIPMENT

SECTION CUSTOM FABRICATED FOODSERVICE EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 40 11 CUSTOM FABRICATED FOODSERVICE EQUIPMENT SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in

More information

Gen 4 New Build TurningPointS 2.0

Gen 4 New Build TurningPointS 2.0 TownePlace Suites New Build This Master Specification Document, as an Instrument of Service, is provided in confidence, for use in preparing final construction specifications for a Marriott CFRST Project.

More information

Cleaning Service Levels

Cleaning Service Levels Restrooms Empty waste receptacles and change liner, as needed. Restock dispensers: soap, paper towel and toilet tissue. Clean mirrors; clean and disinfect urinals, toilets, and sinks. Polish stainless

More information

room data sheet GASTOWN HOTEL 110 WATER STREET, VANCOUVER, BC 1/11 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet GASTOWN HOTEL 110 WATER STREET, VANCOUVER, BC 1/11 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

room data sheet CORDOVA RESIDENCE 1/11 54 EAST CORDOVA STREET, VANCOUVER, BC RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet CORDOVA RESIDENCE 1/11 54 EAST CORDOVA STREET, VANCOUVER, BC RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point. PART 1 - GENERAL 1.01 Toilet rooms and utility rooms to have floor drains at lowest point. 1.02 Utilize Exposed Flushometers. 1.03 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 104413 FIRE EXTINGUISHER CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

room data sheet TAMURA HOUSE 396 POWELL STREET, VANCOUVER, BC 1/8 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet TAMURA HOUSE 396 POWELL STREET, VANCOUVER, BC 1/8 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

Elements Headwall System (P2008A)

Elements Headwall System (P2008A) Figure 1. Elements Headwall System American Society of Mechanical Engineers 3 (ASME ) ASME B16.22: Wrought Copper and Copper Alloy Solder Joint Pressure Fittings American Standard Test Method 4 International

More information

A. Provide products and workmanship in accordance to: (Where applicable)

A. Provide products and workmanship in accordance to: (Where applicable) SECTION 10 00 00 SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Fire Extinguishers, Cabinets, and brackets. 2. Wire Shelving. 3. Coat Racks. B. Related Sections: Documents relating to the

More information

ROVAL COLLECTION PAPER TOWEL DISPENSERS TOILET TISSUE DISPENSERS MIRRORS AUTOMATIC HAND DRYERS

ROVAL COLLECTION PAPER TOWEL DISPENSERS TOILET TISSUE DISPENSERS MIRRORS AUTOMATIC HAND DRYERS ROVAL COLLECTION TOILET TISSUE DISPENSERS PAPER TOWEL DISPENSERS AUTOMATIC HAND DRYERS MIRRORS ROVAL COLLECTION INTRODUCING ROVAL by ASI From ASI comes a collection of washroom accessories that is not

More information

Bobrick - Washroom Accessories. Conversion Chart

Bobrick - Washroom Accessories. Conversion Chart ABS-AMERICAN BUILDING SUPPLY, INC. PRESTIGE BUILDINGS Corporate Headquarters Class A Office Projects Civic Center Icons Universities Restroom Usage and Accessory Requirements: Low to moderate traffic Minimal

More information

Electrical Information

Electrical Information Electrical Information Breaker Panel 1: Service Type: Unreadable Panel Type: Unreadable Panel Number: Unreadable Manufacturer: Unreadable Amps: Unreadable Location: Storage Room Notes: Exterior Disconnect

More information

EQUIPMENT GUIDE LIST - CHAPTER

EQUIPMENT GUIDE LIST - CHAPTER SYMBOL QNTY ACQ/INS DESCRIPTION SPEC REFERENCE DETAIL DEPARTMENT OF MEMORIAL AFFAIRS - MAINTENANCE AND SERVICE BUILDING EGL_703.TXT PERSONNEL FACILITIES: DESK, 1524 mm (60"), WITH PENCIL DRAWER, FILE,

More information

REQUIREMENTS & GUIDELINES

REQUIREMENTS & GUIDELINES SMALL CENTERS IN A RESIDENCE (6-12 Children) REQUIREMENTS & GUIDELINES Mecklenburg County Code Enforcement and the North Carolina Department of Health and Human Services Division of Child Development are

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

room data sheet MARR HOTEL 401 POWELL STREET, VANCOUVER, BC 1/9 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet MARR HOTEL 401 POWELL STREET, VANCOUVER, BC 1/9 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

ALABAMA. Downloaded

ALABAMA. Downloaded Housekeeping/Laundry/Maintenance ALABAMA Downloaded 01.15.11 (e) Maintain an effective pest control program so that the facility is free of pests and rodents. In the laundry, provision shall be made to

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

Capital Projects Group Fire Extinguishers Specification

Capital Projects Group Fire Extinguishers Specification Capital Projects Group Fire Extinguishers Specification Specification 21 20 05 Revision 0 Date: August 2018 Fire Extinguishers Specification Specification 21 20 05 Publication Date: August 2018 COPYRIGHT

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-10 44 16 (May 2015) ------------------------ Preparing Activity: NASA Superseding UFGS-10 44 16 (May 2012) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement

More information

room data sheet MARBLE ARCH HOTEL 518 RICHARDS STREET, VANCOUVER, BC 1/14 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet MARBLE ARCH HOTEL 518 RICHARDS STREET, VANCOUVER, BC 1/14 RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 22 40 00 Plumbing Fixtures 1. General A. Definitions 1. Section includes a. Water closets and urinals b. Lavatories, sinks, and service sinks c. Electric water coolers, drinking fountains, d. Showers

More information

MOLSON S BANK BUILDING 166 EAST HASTINGS STREET, VANCOUVER, BC

MOLSON S BANK BUILDING 166 EAST HASTINGS STREET, VANCOUVER, BC RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

Vanilla Box Design Criteria

Vanilla Box Design Criteria Description: 1. Floor: 2. Walls: 3. Ceiling: A. Finished and sealed 4 thick concrete slab on 10 mil poly vapor barrier on 4 of crushed stone throughout, including toilets. A. Interior gypsum board walls

More information

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 14 42 13 XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform

More information

A. Section Includes: Fire extinguishers and cabinets including necessary accessories.

A. Section Includes: Fire extinguishers and cabinets including necessary accessories. SECTION 10522 FIRE EXTINGUISHERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire extinguishers and cabinets including necessary accessories. B. Related Sections: 1. 09900 - Painting 2. 10400 - Identifying

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

CUSTODIAL SERVICES CUSTOMER SERVICE GUIDE

CUSTODIAL SERVICES CUSTOMER SERVICE GUIDE CUSTODIAL SERVICES CUSTOMER SERVICE GUIDE WHAT WE CLEAN AND HOW OFTEN WE CLEAN IT As part of an ongoing effort to improve custodial customer service, we developed the Custodial Services Customer Service

More information

Use a minimum loading pad 6' curb length of a hard surface to connecting curb and sidewalk.

Use a minimum loading pad 6' curb length of a hard surface to connecting curb and sidewalk. Appendix H ACCESSIBILTY The AODA Built Environment Standard is currently in development by a committee of people from the business and public communities, as well as persons with disabilities. The public

More information

SOCI AL WORK SERVI CE (282)

SOCI AL WORK SERVI CE (282) SOCI AL WORK SERVI CE (282) 1 - RECEPTION AREA 1 - WRC01 - Waiting A free standing hand sanitizer dispenser. For use throughout a healthcare facility. Unit does not A5076 Dispenser, Hand Sanitizer, Free

More information

ARCHITECTURAL WASHROOM & JANITORIAL ACCESSORIES 420 Eddystone Avenue, TORONTO, ON, M3N 1H7, Ph : (41) 744-3039 Email : bandp@bellnet.ca, saferail@bellnet.ca Email:bandp@bellnet.ca, saferail@bellnet.ca

More information

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60'

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60' ±60' Lease Line Lease Outline Drawing Needles Towne Center 1004 E. Broadway St.,, Needles, CA 92363 ± 900 SF Width ± 15' Depth ± 60' Plans produced by: ID Plans 6/16/2017 (813) 657-2545 C 2017 Site map

More information

Unit # E ± 1,200 SF Width ± 20' Depth ± 60'

Unit # E ± 1,200 SF Width ± 20' Depth ± 60' Lease Outline Drawing ±60' Lease Line Sunnymead Plaza 24907 Sunnymead Blvd., Unit # E, Moreno Valley, CA 92553 Unit # E ± 1,200 SF Width ± 20' Depth ± 60' Plans produced by: ID Plans 6/13/2017 (813) 657-2545

More information

Partitions. Accessories. Lockers. No-Touch Washroom Accessories

Partitions. Accessories. Lockers. No-Touch Washroom Accessories Partitions. Accessories. Lockers No-Touch Washroom Accessories Automatic Paper Towel Dispensers Standard Features Proximity sensing no-touch operation Dispenses a pre-set length per cycle from 8" or 9"

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

Unit HH Gregg. ± 30,000 SF Width ±26' Lakeland Retail Center. Lease Outline Drawing. Unit HH Gregg. Depth ± 145' HVAC Units & Information

Unit HH Gregg. ± 30,000 SF Width ±26' Lakeland Retail Center. Lease Outline Drawing. Unit HH Gregg. Depth ± 145' HVAC Units & Information Lease Outline Drawing Lakeland Retail Center 4000 US Hwy. 98, Unit HH Gregg, Lakeland, FL 33809 ±26' ±200' Lease Line Unit HH Gregg ±46' Lease Line ±21' Unit HH Gregg ±145' Lease Line ± 30,000 SF Width

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

WILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST. PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly

WILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST. PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly WILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly Collect & properly dispose of recycling as needed Dust, or wipe all

More information

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

EXHIBIT A-1 CITY OF BELLFLOWER JANITORIAL MAINTENANCE SPECIFICATIONS

EXHIBIT A-1 CITY OF BELLFLOWER JANITORIAL MAINTENANCE SPECIFICATIONS EXHIBIT A-1 CITY OF BELLFLOWER JANITORIAL MAINTENANCE SPECIFICATIONS Janitorial Service Specifications Services shall include furnishing all labor, equipment, tools, fuel, materials, insurance, supervision,

More information

REAR. Exit 5'-9" 6'-1" 8'-3" 6'-1" Freezer Entrance Stall

REAR. Exit 5'-9 6'-1 8'-3 6'-1 Freezer Entrance Stall North Bridges REAR 67' 8' 29' Unit # 120 10955 Jones Bridge Rd. Alpharetta, GA 30022 8' 6'-10" Freezer 7'-1" CONTINENTAL REALTY CORP. 1427 Clarkview Road Suite 500 Baltimore, MD 21209 12' 13'-3" 6' 11'-11"

More information

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY 08 70 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the design and coordination for all necessary hardware and coordination for all doors. Hardware shall include but not necessarily be limited to

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

GSL Artira Inclined Lift Specifications L DS Section

GSL Artira Inclined Lift Specifications L DS Section SECTION 14 42 13 INCLINE WHEELCHAIR LIFTS Display hidden notes to specifier. (Don't know how? Click Here ) PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts. B. Outdoor inclined

More information

Unit # H ± 2,000 SF Width ± 25' Depth ± 80'

Unit # H ± 2,000 SF Width ± 25' Depth ± 80' ±80' Lease Line Lease Outline Drawing Sunnymead Plaza 24907 Sunnymead Blvd., Unit # H, Moreno Valley, CA 92553 Unit # H ± 2,000 SF Width ± 25' Depth ± 80' Unit # H Plans produced by: ID Plans 6/13/2017

More information

Paradise Marketplace. Unit # AOP +/- 1,600 SF +/- 12' +/- 11' +/- 8' 11'-7" +/- 85' +/- 74' +/- 20' MAIN FLOOR +/- 20' +/- 85' Width.

Paradise Marketplace. Unit # AOP +/- 1,600 SF +/- 12' +/- 11' +/- 8' 11'-7 +/- 85' +/- 74' +/- 20' MAIN FLOOR +/- 20' +/- 85' Width. Electrical Information Breaker Panel 1: Service Type: Not Listed Panel Type: Not Listed Panel Number: Not Listed Manufacturer: Not Listed Amps: Not Listed Location: Rear of Storage Room Notes: Unlabeled

More information

PLUMBING FIXTURES CHAPTER 27

PLUMBING FIXTURES CHAPTER 27 CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,

More information

SECTION FIRE EXTINGUISHER CABINETS

SECTION FIRE EXTINGUISHER CABINETS SECTION 104413 FIRE EXTINGUISHER CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

B. Shop Drawings: For fire protection cabinets. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For fire protection cabinets. Include plans, elevations, sections, details, and attachments to other work. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Stanfield School District Cleaning Standards

Stanfield School District Cleaning Standards Stanfield School District Cleaning Standards Universal Precautions Always wear protective gloves. Do not use gloves that have holes or tears. Treat all body fluid spills as if they were contaminated. Items

More information

A. All fixtures shall meet the requirements of ANSI A117.1, ANSI Z124.2 and the State of Texas Accessibility Standards (TAS).

A. All fixtures shall meet the requirements of ANSI A117.1, ANSI Z124.2 and the State of Texas Accessibility Standards (TAS). PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION PLUMBING

SECTION PLUMBING SECTION 22 10 00 PLUMBING PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the sanitary sewer system (including soil and vent piping),

More information

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION SECTION 224100 - RESIDENTIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

University of Wisconsin - Whitewater Universal Design Guidelines

University of Wisconsin - Whitewater Universal Design Guidelines University of Wisconsin - Whitewater Universal Design Guidelines The purpose of these guidelines is to foster good design and discussion that fully encompasses the principals of Universal Design (UD) into

More information

SECTION PLUMBING FIXTURES AND TRIM. A. Types of plumbing fixtures required for the project include the following:

SECTION PLUMBING FIXTURES AND TRIM. A. Types of plumbing fixtures required for the project include the following: SECTION 15440 PART I - GENERAL 1.01 WORK INCLUDED A. Types of plumbing fixtures required for the project include the following: 1. Water Closets 2. Urinals 3. Lavatories 4. Mop Sink 5. Sinks 6. Electric

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

SCOPE OF WORK. 506 N. Chadbourne Ave, San Angelo, TX. 1. Build and outfit kitchen are in accordance with established drawing

SCOPE OF WORK. 506 N. Chadbourne Ave, San Angelo, TX. 1. Build and outfit kitchen are in accordance with established drawing SCOPE OF WORK 506 N. Chadbourne Ave, San Angelo, TX Contractor shall be required to provide labor, supervision, and equipment to build a small multipurpose kitchen and Americans with Disabilities Act (ADA)

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

Paradise Marketplace REAR FRONT. Unit # AOH +/- 1,700 SF +/- 20' +/- 85' +/- 85' +/- 20' MAIN FLOOR +/- 20' +/- 85' Width. Depth

Paradise Marketplace REAR FRONT. Unit # AOH +/- 1,700 SF +/- 20' +/- 85' +/- 85' +/- 20' MAIN FLOOR +/- 20' +/- 85' Width. Depth Electrical Information Breaker Panel 1: Service Type: 120/208 Panel Type: Type 1 Panel Number: 383-21 Manufacturer: Challenger Amps: 200 Location: Near Exit Door of Main Space Notes: Breaker Panel 2: Service

More information

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 14 42 13 INCLINE WHEELCHAIR LIFTS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts.

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 104413 - FIRE PROTECTION CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Type A Units Accessibility Requirements rev.

Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Type A Units Accessibility Requirements rev. Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Units Accessibility s rev. 11/12/12 Unit 2005 CT State Building Code () A117.1 (2003) **indicates CT Amendment to

More information

ADA Checklist Transient Lodging, Hotels, Motels, Inns, Boarding Houses, Dormitories and similar facilities

ADA Checklist Transient Lodging, Hotels, Motels, Inns, Boarding Houses, Dormitories and similar facilities ADA Checklist Transient Lodging,, Motels, Inns, Boarding Houses, Dormitories and similar facilities 205 North 400 West Salt Lake City, Utah 84103 (800) 662 9080 (800) 550 4182 TTY www.disabilitylawcenter.org

More information

MD-CU 29 4 ANTIMICROBIAL COPPER ALLOYS AND ASSOCIATED FABRICATED PRODUCTS MASTER LABEL AND ASSOCIATED FABRICATED PRODUCTS

MD-CU 29 4 ANTIMICROBIAL COPPER ALLOYS AND ASSOCIATED FABRICATED PRODUCTS MASTER LABEL AND ASSOCIATED FABRICATED PRODUCTS MD-CU 29 4 ANTIMICROBIAL COPPER ALLOYS AND ASSOCIATED FABRICATED PRODUCTS MASTER LABEL The Master Label consists of the label that will accompany the Antimicrobial Alloys and a label that will accompany

More information