1 Installation manual detector and controller Code no Page 1/30 CONTENTS Controller... 2 Function of the Relays... 2 Gas Detectors... 2 Cabling... 4 Mechanical Installation of the gas detectors... 6 SCAN20 Series Gas Detection Controllers... 8 SCAN200E Controller DGTec2 Gas Detector DGTm3 Gas Detector DGTi2 Gas Detector DGTt2 Gas Detector DGTk2 Gas Detector MAINTENANCE AND CALIBRATION RECYCLING PUBLISHER Detector Oy, Telekatu 8, Turku, Finland Telephone , detector@detector.fi Detector Oy 2017 Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy. All efforts have been made to ensure the content of this booklet to be correct, however Detector Oy does not take responsibility for damage caused by errors or missing information in this booklet. Technical specifications may change without prior notice.
2 Code no Installation manual detector and controller Page 2/30 INSTALLATION IN GENERAL Controller The controller shall preferable be installed at a central place, where personnel is present at all times, i.e. in the control room. The controller shall be protected from dirt and water coming along the wall or the mounting plate. The controller shall not be installed in the area under monitoring, e.g. in a refrigeration compressor room. In constraining situations, as minimum requirement gas alarming sound and/or flashing equipment shall be installed at the entrance of the room. Do not install any third-party components or devices on the gas detection controller. Use of uninterrupted power source is recommended to maintain monitoring during power outage. A map containing all gas detector and alarm device locations shall be available near the gas detection controller. It is also advisable to provide any site-specific instructions for alarm events. Gas detection controller and gas detectors require regular maintenance. The controller and detectors shall be maintained at the same time to ensure reliable operation of the system. It is recommended to test any external alarm functionality during the maintenance. Function of the Relays Ensure the compatibility of the load and relays beforehand. The relays in the AVACO SYSTEMS products are designed for resistive load. When connecting capacitive / inductive loads, e.g. flashes or contactors, the load must be adapted appropriate to the relays. In most cases this can be done by connecting a metal oxide varistor or an RC filter parallel to the relay tips. Apply relay controls only after successful system test. Gas Detectors The gas detectors need regular maintenance. The accessibility has to be taken into account when choosing the installation place, if necessary, maintenance platforms has to be arranged. Do not expose gas detectors to strong infrared radiation or steam clouds. Gas detectors are to be installed as late as possible during construction work to avoid any damage due to welding and painting. However, installation and stabilization must be carried out before using any gases or liquids the detectors are to measure. Stabilization time is 2 to 4 days or more depending on sensor type and temperature unless otherwise noted. Bypass all relay controls during the stabilization.
3 Installation manual detector and controller Code no Page 3/30 To protect the gas detector from dirt and moisture the casing has to be installed with the sensor protection cover directed downwards. Also, the cabling shall be done from below for the same reasons. When the cabling in constraining situations is done from above, the gland has to be sealed properly. During gas detector installation or when making electrical changes into the gas detection system, the power must be disconnected to prevent damage. The gas detector shall be assembled near to a presumptive leakage place to achieve a fast response, however, the density of the gas shall be taken into account when defining the assembly height. when monitoring gases, which are heavier than air the gas detectors shall be assembled at a height of cm from the floor level. Thus, there is enough space between the gas detector and the floor for the maintenance of the gas detector and for the cleaning of the floor. If there are possibilities of mechanical damage, a protection shield shall be assembled around the sensor. when monitoring gases, which are lighter than air the gas detectors shall be assembled at or near to the ceiling. when the density for the measured gas is approximately the same as for air the gas detectors shall be installed at the breathing height. Install splash protection in areas where detectors are exposed to water. (see page 7, consult manufacturer for more information) A heated enclosure may be required when using the detector outside of normal operating temperature and/or humidity. The detectors are meant for alarm limit based detection of gases and solvents. These devices require regular maintenance and testing to ensure correct operation. Full calibration must be done at least once a year and testing more often. On-site safety statement will define the correct test interval. Test gas pressure at detector gas inlet shall be within ±10% of nominal air pressure. Calibration and test gas concentration must not exceed the range of the detector. In case of flammable gas the concentration must be 0 50 %LEL. Excess gas concentration may damage the sensor element. Make sure the gas flow at the calibration adapter is unobstructed. Contact your dealer for most of calibration gases. In unclear situations regarding the installation of the gas detectors, kindly contact DETECTOR Oy, or the local authorities for occupational health and safety or the fire brigade.
4 Code no Installation manual detector and controller Page 4/30 Cabling The gas detectors are cabled to the controllers as own circuits, by e.g. JAMAK 2x(2+1)x0.5 mm 2 or by an equivalent cable. At ATEX sites standard EN will specify the cable type. The type of the gas detector defines the number of wires in the cable. If the cable is exposed for vandalism or mechanical stress, an armoured cable shall be used. Signal cable shields are grounded only from the controller to prevent ground current loops. If the gas detector casing is not earth connected, the signal cable shield shall be connected to the casing. When using other than recommended cable, correct operation of the system is not guaranteed. The type of the gas detector, the supply voltage and the cable cross-section area defines the maximum cable length. It is recommended to use the following formula for calculating the maximum cable length, when the distance is over 300 m. The formula is valid for AVACO SYSTEMS gas detectors, when the cable cross section area, the maximum allowed loss of voltage, the specific resistance of the used cable material and the power consumption of the gas detector are known. Wire area [mm 2 ] * Voltage Loss [V] Cable [m]= 2 * Detector Current [A] * Wire Resistance Factor [ Ω m * mm2 ] Formula 1, calculation of the maximum cable length. Voltage Loss: The minimum required voltage for the gas detector is subtracted from the supply voltage; the result is the biggest allowed loss of voltage in the cable, which is used in the formula as voltage loss. Detector Current: The current consumption in Ampere written on the equipment plate or in the inspection sheet for the equipment. Wire Area: The wire cross section area in square millimetres. Wire Resistance Factor: The specific resistance for the wire material, for copper Ω/m*mm 2. The result for cable length is expressed in meters. For example, a wire with a maximum voltage loss of 10V, cross section area of 0.8 mm 2 and with gas detector current consumption of 205 ma, the maximum cable length is calculated to be approximately m.
5 Installation manual detector and controller Code no Page 5/30 Figure 1, Recommended cabling for 2-wire connection when gas detector casing is isolated from surface using non conducting plate. Figure 2, Alternative cabling for 2-wire connection. Figure 3, Recommended cabling for 4-wire connection when gas detector casing is isolated from surface using non conducting plate.
6 Code no Installation manual detector and controller Page 6/30 Figure 4, Alternative cabling for 4-wire connection. Mechanical Installation of the gas detectors All gas detectors are enclosed in IP54 metallic casing and delivered with insulating mounting base. The sensor, sensor cover and electronics inside the case varies according the model and features. Earth bonding connector is found at the bottom part of the casing. Install cable entry at downwards position to prevent water from entering the casing. Do not remove the instrument label. Stainless steel double skin weather enclosures are available (see page 7). The protector prevents, e.g. snow, rain, water from cleaning devices. The splash protector parts include the bottom plate, top plate, rain guard and pipe mount kit. The parts are separately available to suite the needs on-site. Figure 5, Gas detector casing dimensions and attachment holes.
7 Installation manual detector and controller Code no Page 7/30 Figure 6, Installation position for ceiling and wall mounted versions. Sensor cover is pointing downwards. Figure 7, Duct mounted version includes 132 mm long probe and mounting ring. 168 mm 149 mm 255 mm 142 mm Figure 8, Stainless steel double skin weather enclosure with rain cover (H225 x W168 x D149 mm), image without pipe mounting kit.
8 Code no Installation manual detector and controller Page 8/30 SCAN20 Series Gas Detection Controllers Inputs: 2 or 4 inputs, current signal (0)4 20 ma Outputs: 7 relay contacts, 230 VAC 1.0 A / 24 VDC 1.0 A to for resistive load. 2 freely scalable 4 20 ma standard current outputs (option). RS485, typical industrial protocols (option). Alarm information as SMS message via external GSM modem (option). Display: White back lighted 20x4 character LCD display. Channel specific indicators for alarm levels I, II, and III. Common indicators for alarms off, emergency shutdown of solenoid valve and fault alarm. Enclosure: ABS-plastic. Equipped with external mounting brackets for easy wall installation. Dimensions: 259 x 237 x 97 mm (w x h x d) excluding cable glands Weight: 1550 g Degree of protection: IP66 Operating voltage: 230 VAC / 24 VDC Operating temperature: ºC Operating humidity: % RH, non-condensing Note: The controller is delivered with complete and project specific installation documents.
9 Installation manual detector and controller Code no Page 9/30 Figure 9, SCAN20 gas detection controller general view and mounting dimensions. The photo is missing the bottom cable entry.
10 Code no Installation manual detector and controller Page 10/30 Figure 10, SCAN20 gas detection controller terminal blocks found on the circuit board (version E or later). NOTE: Connections described here are not connected in all SCAN20 models.
11 Installation manual detector and controller Code no Page 11/30 SCAN200E Controller Construction: Installation: Inputs: Outputs: Display: Operating Voltage: Operating Temperature: Operating Humidity: Note: Controller consisting of CPU unit and input and relay modules. Possibility to connect subcontrollers equipped with input and relay modules to the controller. Maximum distance between the controller unit and sub-controllers using RS485 is one kilometre. In a 19 rack or in a metal or PC enclosure, fixed to the wall by screws pcs, in 8 input units, standard current signal 0(4) 20mA, voltage signals 0(2) 10V and direct measuring. From 8 to 128 relays in modules of 8 relays. Relay contacts for 230 VAC 1 A resistive load. RS-232 for modem/maintenance. The optional GSM modem enables alarm SMS for up to 3 different cell phone numbers. RS-485 for Modbus/Profibus (optional). 240 x 128 pixel back lighted LCD display, indicators for the alarm levels I, II, III and for malfunction 230 VAC / 24 VDC 0 50 C % RH, non-condensing The controller is delivered with complete and project specific installation documents. Figure 11, SCAN200E Controller general view (R-model, 9U).
12 Code no Installation manual detector and controller Page 12/30 Figure 12, SCAN200E Controller relay and A/D modules.
13 Installation manual detector and controller Code no Page 13/30 DGTec2 Gas Detector Sensor Type: Output Signal: Operating Voltage: Max. Power Consumption: Cabling: Typical Sensor Life in clean air: Typical T90 Response: Operating Temperature: Operating Humidity: Degree of Protection: Weight: Note: Electrochemical 4 20 ma, linear response see figures, regulated 0.9 W 2-wire connection, e.g. JAMAK 2x(2+1)x0.5 mm years depending on the type of sensor seconds depending on the type of sensor according to the cell in use, ask manufacturer O2 sensor 0 99% RH, for other sensors 15 90% RH, non-condensing IP g The calibration is done by using the handheld calibration device (IRC) via infrared link. Therefore the infrared lens of the device must be clearly visible. If ambient air pressure differs more than 5% from normal atmospheric, the detector shall be recalibrated at the installation site. Figure 13, DGTec2 gas detector general view. The model and the size of the sensor protection depend on the type of the gas specific sensor. Duct mounted DGTec2d is also available.
14 Code no Installation manual detector and controller Page 14/30 Figure 14, DGTec2 connections and layout on the circuit board. The circuit board version depends on the target gas. Figure 15, DGTec2 oxygen/o2 connections and layout on the circuit board.
15 Voltage [V] Installation manual detector and controller Code no Page 15/30 DGTec2 maximum load resistance vs. operating voltage on LO and HI selections Resistance [Ω] Figure 16, DGTec2 operating voltage and maximum load resistance.
16 Code no Installation manual detector and controller Page 16/30 DGTm3 Gas Detector Sensor Type: Output Signals: Operating Voltage: Max. Power Consumption: Cabling: Typical Sensor Life in clean air: Typical T90 Response: Operating Temperature: Operating Humidity: Degree of Protection: Weight: Note: Electrochemical 4 20 ma, linear response see figures, regulated 0.9 W 2-wire connection, e.g. JAMAK 2x(2+1)x0.5 mm 2 5 years < 30 seconds C, continuous C, intermittent 10 95% RH, non-condensing IP g The calibration is done by using the handheld calibration device (IRC) via infrared link. Therefore the infrared lens of the device must be clearly visible. If ambient air pressure differs more than 5% from normal atmospheric, the detector shall be recalibrated at the installation site. Figure 17, DGTm3 gas detector general view.
17 Voltage [V] Installation manual detector and controller Code no Page 17/30 Figure 18, DGTm3 connections and layout on the circuit board. DGTm3 maximum load resistance vs. operating voltage on LO and HI selections Resistance [Ω] Figure 19, DGTm3 operating voltage and maximum load resistance.
18 Code no Installation manual detector and controller Page 18/30 DGTi2 Gas Detector Sensor Type: NDIR Infrared Sensor Output Signals: 4 20 ma, linear response Operating Voltage: 24 VDC ±20 %, regulated Max. Power Consumption: 3.0 W Cabling: 4-wire connection, e.g. JAMAK 2x(2+1)x0.5 mm 2 Typical Sensor Life in clean air: 5 years Typical T90 Response: < 60 seconds Operating Temperature: C Operating Humidity: 0 95% RH, non-condensing Degree of Protection: IP54 Weight: 450 g Note: The calibration is done by using the handheld calibration device (IRC) via infrared link. Therefore the infrared lens of the device must be clearly visible. If ambient air pressure differs more than 5% from normal atmospheric, the detector shall be recalibrated at the installation site. Indication lights: Constant green: Normal operation mode. Constant yellow: Sensor failure. Blinking red: Gas alarm. Blinking will stop when the gas concentration is lower than the alarm limit.
19 Installation manual detector and controller Code no Page 19/30 Figure 20, DGTi2 gas detector general view. Figure 21, DGTi2 connections and layout on the circuit board. Buzzer and relay on DGTi2r.
20 Code no Installation manual detector and controller Page 20/30 DGTt2 Gas Detector Sensor Type: Solid-State Output Signals: (0)4 20 ma or (0)2 10 V linear or logarithmic response. NOTIFY ON ORDER! DGTt2r includes a relay 24 V / 1 A for resistive load, additionally a buzzer and acknowledge button for buzzer. Operating Voltage: VDC (when only relay output used), VDC (when current output used) or VAC Max. Power Consumption: 4.0 W Cabling: 4-wire connection, e.g. JAMAK 2x(2+1)x0.5 mm 2 Typical Sensor Life: 3 5 years Operating Temperature: C reduced sensitivity C Operating Humidity: % RH, non-condensing Degree of Protection: IP54 Weight: 390 g Note: The calibration is done by using the handheld calibration device (IRC) via infrared link. Therefore the infrared lens of the device must be clearly visible. Indication lights: Constant green: Normal operation mode. Constant red: Sensor failure. Blinking red: Gas alarm. Blinking will stop when the gas concentration is lower than the alarm limit.
21 Installation manual detector and controller Code no Page 21/30 Figure 22, DGTt2 gas detector general view (-w, wall mounted). The DGTt2 gas detector can also be mounted to the ceiling (model -c) or to a duct (model -d). Figure 23, DGTt2 connections and layout on the circuit board. NOTE: Availability of connections depends on the DGTt2 model.
22 Code no Installation manual detector and controller Page 22/30 Figure 24, DGTt2r alarm and delay settings. Figure 25, DGTt2r alarm and delay settings.
23 Installation manual detector and controller Code no Page 23/30 Figure 26, DGTt2 jumpers on the circuit board.
24 Code no Installation manual detector and controller Page 24/30 DGTk2 Gas Detector Sensor Type: Catalytic Output Signals: 4 20 ma, linear response DGTk2r includes a relay 24 V / 1 A for resistive load, additionally a buzzer and acknowledge button for buzzer. Activation delay is set at factory, see production documents. Operating Voltage: 24 VDC ±20%, regulated Max. Power Consumption: 4.0 W Cabling: 4-wire connection, e.g. JAMAK 2x(2+1)x0.5 mm 2 Typical T90 Response: According to IEC Operating Temperature: C Operating Humidity: 0 95% RH, non-condensing Degree of Protection: IP54 Weight: 620 g Note: The calibration is done by using the handheld calibration device (IRC) via infrared link. Therefore the infrared lens of the device must be clearly visible. Calibration and test gas concentration must not exceed the range of the detector nor 50 % LEL. When exposed to a shock e.g. a drop, DGTk2 must be recalibrated. The sensor element shall be oriented downwards. Indication lights: Constant green: Normal operation mode. Constant red: Sensor failure. Blinking red: Gas alarm. Blinking will stop when the gas concentration is lower than the alarm limit.
25 Installation manual detector and controller Code no Page 25/30 Figure 27, DGTk2 gas detector general view. Figure 28, DGTk2 connections and layout on the circuit board. NOTE: Availability of connections depends on the DGTk2 model.
26 Code no Installation manual detector and controller Page 26/30 MAINTENANCE AND CALIBRATION The gas detectors and controllers are tested and calibrated by the manufacturer. Installation instructions and calibration reports are included. Gas detection equipment requires regular maintenance to ensure appropriate operation. Consider the future maintenance at the time of installation. We will help you to plan and conduct maintenance planning and calibration. Maintenance contracts are custom made to suite individual needs. We also conduct installation inspections. Controller and detector attachment, wiring and settings will be checked. Detectors will be tested with calibration gas to ensure that everything from sensor element to external alarms are functioning properly. End users receive introduction to using the system. Inspection report contains any possible correction needs. Installation inspection and any other trainings are planned according to customer needs. Contact manufacturer or distributor regarding any maintenance needs. DETECTOR OY Telekatu 8 FI TURKU FINLAND Tel detector@detector.fi
27 Installation manual detector and controller Code no Page 27/30 RECYCLING Please follow the instructions for recycling the gas detectors: - Enclosures to metal recycling - Printed Circuit Boards to electronic recycling - Catalytic, semiconductor and infrared sensors to metal recycling - Electrochemical sensors to hazardous waste - Polymer parts to burnable waste Do not dispose the detectors with residential waste. Ask Detector Oy for further information. DETECTOR OY Telekatu 8 FI TURKU FINLAND Tel detector@detector.fi
28 Code no Installation manual detector and controller Page 28/30 Figure 29, Declaration of conformity for DGT series gas detectors.
29 Installation manual detector and controller Code no Page 29/30 Figure 30, Declaration of conformity for SCAN series gas detection controllers.
30 Code no Installation manual detector and controller Page 30/30 Figure 31, ISO 9001 quality system certificate.
SCAN20 Series Gas Detection Controller
SCAN20 Series Gas Detection Controller USER S MANUAL Code Number 2071 1022 SCAN20 USER S MANUAL Code no. 2071 1022 Page 1/14 Foreword This manual is made for SCAN20 Controllers equipped with the software
More informationSCAN200E USER S MANUAL
SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We
More informationWarranty Registration
WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period
More informationSnifter ATEX22 VERSION. User Manual. Distributor
Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec
More informationDräger Polytron 5200 CAT Detection of flammable gases and vapours
Dräger Polytron 5200 CAT Detection of flammable gases and vapours The Dräger Polytron 5200 CAT is a cost-effective explosion-proof transmitter for the detection of flammable gases in the lower explosion
More informationDräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors
Dräger Polytron 5700 Fixed Gas Detector Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Including e-box for increased safety wiring The Dräger
More informationModel D12-IR. Digital Gas Transmitter...
Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact
More informationSAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR
SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations
More informationDräger Polytron 8310 IR Detection of flammable gases and vapour
Dräger Polytron 8310 IR Detection of flammable gases and vapour The Dräger Polytron 8310 IR is an advanced explosion proof transmitter for the detection of combustible gases in the lower explosion limit
More informationDetectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.
Détecteur de gaz OLCT80 Detectors-Transmitters for Flammable, Toxic Gases and Oxygen Non-intrusive operation via intrinsically safe infrared remote control Disponible en version déportée, ADF ou de SI
More informationDräger Polytron 5700 IR Detection of flammable gases and vapours
Dräger Polytron 5700 IR Detection of flammable gases and vapours The Dräger Polytron 5700 IR is a cost effective explosion-proof transmitter for the detection of flammable gases in the lower explosive
More informationProcess Control PIP PCEA001 Fixed Gas Detection Guidelines
November 2015 Process Control PIP PCEA001 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical
More informationSieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required
Sieger Sensepoint The Sensepoint range of flammable, toxic and oxygen gas detectors offer users a high quality, low cost solution to their industrial gas monitoring needs. Sieger Sensepoint Fit For Purpose
More informationOilSET-1000 (12 VDC)
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009
More informationSET-2000 Hi Level/Oil
Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve
More informationReplaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge
Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays
More informationWARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro
A d e v i h c r D c o n e m u WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship
More informationINSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATI AND OPERATING INSTRUCTIS PRODUCTS CMD Series CO Detectors FGD Series Refrigerant Detectors AGD Series Toxic Gas Detectors CGD Series Combustible Gas Detectors (All transmitters are factory set
More informationSET Installation and Operating Instructions. Level switch for one sensor
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel.: +358 29 006 260 Fax: +358 29 006 1260 7.11.2013 Internet: www.labkotec.fi 1/14 SET-1000 Level switch for one sensor Copyright 2013 Labkotec Oy
More informationSAFEYE XENON 700. Hydrocarbons and ethylene detection. Heated optics. 10-year Warranty for the Xenon flash bulb. SIL 2 according to IEC 61508
Open-Path Gas Detection System SAFEYE XENON 700 Hydrocarbons and ethylene detection Heated optics 10-year Warranty for the Xenon flash bulb SIL 2 according to IEC 61508 Certifications The Fixed Gas Detection
More informationGL-CO-RFG Channel Gas Leak Alarm System
Four Elms Road Edenbridge Kent TN8 6AB UK Features & Benefits Remote sensors for natural gas, LPG and CO 1 x SPST relay outputs DIN-rail as standard, panel mounting kit available Adjustable alarm thresholds
More informationWarranty Registration
WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period
More informationAmmonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications January 15, 2018 Revision 6 Ammonia detection system codes and design specifications Following is a discussion of ammonia detection system design
More informationDanfoss gas detection units
Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning
More informationTouchpoint 1. The Touchpoint 1 controller provides 24 hour protection from flammable, toxic or Oxygen gas hazards.
Touchpoint 1 The Touchpoint 1 controller provides 24 hour protection from flammable, toxic or Oxygen gas hazards. Touchpoint 1 controller User Friendly Self-contained, wall mounted enclosure Ultra-clear
More informationDanfoss gas detection unit Type GD Heavy Duty
Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx
More informationQPM21 Series Duct CO 2 and Air Quality Sensors
Document No. CE1N1962 QPM21 Series Duct CO 2 and Air Quality Sensors Description Features Application The Carbon Dioxide (CO 2 ) Duct Sensors are directly wired to the controller via twisted pair and/or
More informationQD6310. Fixed Gas Detector Operation Manual
QD6310 Fixed Gas Detector Operation Manual Safety Information Before using the device, please first carefully read and follow the following information to operate the device: Please don't use the defective
More informationDanfoss gas detection units
Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning
More informationTOXIC GAS AND OXYGEN DETECTOR DTX 420 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2
TOXIC GAS AND OXYGEN DETECTOR INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2 1 Introduction These instructions must be read carefully by any person who has or will have the responsibility
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor
Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000
More informationOperation and Maintenance Manual
Operation and Maintenance Manual GDS-48 Remote Bridge Sensor for Combustible Gases AUTHORIZED DISTRIBUTOR: GasDetectorsUSA.com - Houston, Texas USA sales@gasdetectorsusa.com - 832-615-3588 CAUTION: FOR
More informationSIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL
SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL P3359E 8th edition - November 2005 Simrad Optronics ASA Kabelgaten 4B P.O. Box 174, Økern NO-0509 OSLO, NORWAY Phone +47 22 66 60 00 Fax +47 22 66 60 01
More information3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.
Fixed Gas Monitoring Solutions Detection of explosive gases, toxic gases and oxygen Infrared XP IR version SIL 2 high reliability IP 66 E n o r t c e l i c 3years W a r r a t n y Certifications: The Fixed
More informationDuct and Rough Service Carbon Monoxide Sensor
Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.
More informationTC100N. Fixed Gas Detector Operation Manual
TC100N Fixed Gas Detector Operation Manual Safety Information Before using this device, please carefully read the following safety information: After opening the packing box, please check if there is any
More informationSieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required
Sieger Sensepoint The Sensepoint range of flammable, toxic and oxygen gas detectors offer users a high quality, low cost solution to their industrial gas monitoring needs. Sieger Sensepoint Fit For Purpose
More informationAT-G-SENSE Gas Sensing System
AT-G-SENSE Gas Sensing System INSTALLATION & OPERATING MANUAL INSTALLATION INSTRUCTIONS Open the AT-G-SENSE by undoing the two screws. Remove metal faceplate, turn over and check connection terminals (maximum
More informationRecalibrate the way you look at gas detection
Catalogue Gas detection solution Recalibrate the way you look at gas detection Next generation gas detection for industrial refrigeration The next generation of Danfoss gas detectors are based on a digital
More informationUnipoint Controller. The Unipoint, a simple DIN rail mounted controller
Unipoint ontroller The Unipoint, a simple DIN rail mounted controller Unipoint DIN ontroller Typical Applications Small and medium integrated systems ustom control cabinets and panels Unmanned equipment
More informationSensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications
Sensepoint The Sensepoint range of flammable, toxic and Oxygen gas detectors offer users a high quality, low cost solution to their industrial gas monitoring needs. Sensepoint Fit For Purpose Flammable,
More informationBuzzer Unit. TAN-5000 Series. Operating Manual
PT1E-1040 Buzzer Unit TAN-5000 Series Operating Manual Request for the Customers Read and understand this operating manual before using the buzzer unit. Use the buzzer unit in accordance with the operating
More informationDuct Air Quality Sensors
1 962 QPM2102D QPM2160D, QPM2162D QPM2100, QPM2102 QPM2160, QPM2162 Duct Air Quality Sensors QPM21 With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1 )
More informationMulti-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.
Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,
More informationOLC(T) 100 FIXED GAS DETECTOR
Fixed Gas Detector OLC(T) FIXED GAS DETECTOR Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Aluminium or Stainless Steel version CERTIFICATIONS The
More informationVentostat Wall Mount. Amphenol Advanced Sensors. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. Features:
Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package. Patented
More informationSIMRAD GD10 IR GAS DETECTOR
1 SIMRAD GD10 IR GAS DETECTOR Operating Manual 5th Edition P3359E October 1999 1 CONTENTS Section Page 1. PRODUCT DESCRIPTION 3 1.1 General description 3 1.2 Construction 3 1.3 Application areas 4 1.4
More informationDräger Polytron 5200 CAT Detection of flammable gases and vapours
Dräger Polytron 5200 CAT Detection of flammable gases and vapours The Dräger Polytron 5200 CAT is a cost-effective explosion-proof transmitter for the detection of flammable gases in the lower explosion
More informationHygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring
Data Sheet 907021 Page 1/8 Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring For measuring relative air humidity, temperature, and carbon dioxide concentration
More informationDräger Polytron 8200 CAT Detection of flammable gases and vapors
Dräger Polytron 8200 CAT Detection of flammable gases and vapors The Dräger Polytron 8200 CAT is an advanced explosion proof transmitter for the detection of flammable gases in the lower explosion limit
More informationSieger Apex. Flexibility that meets your requirements
Sieger Apex Flexibility that meets your requirements Sieger Apex Easy to Install Sensor can be remotely mounted up to 100m from the transmitter On board relays allow for local audible/ visual alarms Strong
More informationSET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions
SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...
More informationP R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification
P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.
More informationSIMRAD GD10PE IR GAS DETECTOR
SIMRAD GD10PE IR GAS DETECTOR Operating Manual P3404E 1st edition Jan. 2004 www.simrad-optronics.com CONTENTS 1. PRODUCT DESCRIPTION... 5 1.1 General description... 5 1.2 Construction... 5 1.3 Application
More informationSignalpoint. The Signalpoint range of flammable, toxic and Oxygen gas detectors offer users a low cost solution to their indoor gas monitoring needs
Signalpoint The Signalpoint range of flammable, toxic and Oxygen gas detectors offer users a low cost solution to their indoor gas monitoring needs Signalpoint One-Stop Shop Flammable, toxic and Oxygen
More informationDigital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6
Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas
More informationDual Input ph/orp Analyzer
Instruction Sheet PN 51A-1055pH/rev.I February 2006 Model 1055 SOLU COMP II Dual Input ph/orp Analyzer Model Option 1055-22-32 For additional information, please refer to the Instruction Manuals CD shipped
More informationTouchpoint 4. The Touchpoint 4 controller provides protection of personnel and plant from flammable, toxic and Oxygen gas hazards
Touchpoint 4 The Touchpoint 4 controller provides protection of personnel and plant from flammable, toxic and Oxygen gas hazards Touchpoint 4 Controller User Friendly Self-contained, wall mounted enclosure
More informationLINEAR HEAT DETECTION CABLE DURÁN-SAFE
LINEAR HEAT DETECTION CABLE DURÁN-SAFE Installation & User Manual 2018 DURAN ELECTRONICA S.L. - All rights reserved www.duranelectronica.com I-manSAFECABLE-v05 TABLE OF CONTENTS Pages 1. INTRODUCTION...
More informationSensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications
Sensepoint The Sensepoint range of flammable, toxic and oxygen gas detectors offer users a high quality, low cost solution to their industrial gas monitoring needs. Sensepoint Fit For Purpose Flammable,
More informationSAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)
SAFETY MANUAL Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) Sensor Module (GTS) Transmitter (GTX) Detector (GT3000) SAFETY CERTIFIED GT3000
More informationDräger Polytron 5100 EC Detection of toxic gases and vapors
Dräger Polytron 5100 EC Detection of toxic gases and vapors The Dräger Polytron 5100 EC is a cost-effective explosion proof transmitter for the detection of toxic gases or oxygen. It uses a high performance
More informationWIO200 Water In Oil measuring instrument
WIO200 Water In Oil measuring instrument You have made the right decision by choosing a measuring instrument from PAJ Systemteknik. Many customers buy our high standard products every year. There are at
More informationOperating Manual MS220DA
ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN
More informationDual Input ph/conductivity Analyzer
Instruction Sheet PN 51A-1055pHC/rev.I January 2006 Model 1055 SOLU COMP II Dual Input ph/conductivity Analyzer Model Option 1055-22-30 For additional information, please refer to the Instruction Manuals
More informationIMR 5000 Operating Manual S/N: SAMPLE For information only! IMR Environmental Equipment Inc.
IMR 5000 Operating Manual S/N: For information only! IMR Environmental Equipment Inc. INTRODUCTION 3 SAFETY INSTRUCTIONS 3 SYSTEM DESCRIPTION - IMR 5000 GAS ANALYSIS SYSTEM 4 Function chart IMR 5000 -
More informationQAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR
QAS-10000 SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749, RICHMOND, ONTARIO, CANADA. K0A
More informationNitrogen Dioxide (NO2) Single-Point Gas Detection System
Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary
More informationModel 3300 Technical Support and Installation Manual
Model 3300 Technical Support and Installation Manual Manual # T15011 Document Revision: A1 1. OVERVIEW 1 2. BASIC OPERATION 1 2.1 General 1 2.2 Field-of-View 2 2.3 Range 2 2.4 Environment 2 2.5 Configuration
More informationDräger Polytron 5720 IR Toxic Gas Detection
Dräger Polytron 5720 IR Toxic Gas Detection The Dräger Polytron 5720 IR is a cost-effective explosion proof transmitter for the detection of carbon dioxide in volume percentage or ppm It uses a high-performance
More informationEx SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...
14 Ex SOLENOID / ALARM DRIVER PRepower 5203B Table of contents Warnings... 16 Safety instructions... 17 Declaration of Conformity... 19 How to dismantle SYSTEM 5000... 20 Application... 21 Technical characteristics...
More informationThe EN54 Part 2 & 4 Fire System
Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54
More informationDräger Polytron 8700 IR Detection of flammable gases and vapors
Dräger Polytron 8700 IR Detection of flammable gases and vapors The Dräger Polytron 8700 IR is an advanced explosion proof transmitter for the detection of combustible gases in the lower explosion limit
More informationSET-2000 Oil/Sludge 12 VDC
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with
More informationRS Pro Infrared Temperature Sensor
Instruction Manual RS Pro Infrared Temperature Sensor Stock Number: 161-8103 Introduction The RS Pro Infrared Temperature Sensor is a device for measuring the temperature of the surface of a solid or liquid
More informationGas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH
Data sheet Gas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH Danfoss gas detecting sensor program, type GD is a range of products designed to meet all industrial refrigeration and air conditioning applications.
More informationDESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR
DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR 70086 The information in this doucment is applicable to sensors built in September, 2008 or later (Firmware 3.0) The information and technical
More informationIGD.CO.UK
APPLICATION DATA SHEET S p e c i f i c a t i o n 2 SO22 WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700+ D e t e c t o r Website: C o n t r o l P a n e l - Wall mounting or 19 Rack
More informationDetection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version
Fixed Gas Detector Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Aluminium or Stainless Steel version Certifications Pending The Fixed Gas Detection
More informationMODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR
MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR INSTALLATION OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749 RICHMOND, ONTARIO CANADA
More informationTwo-Channel Gas Controller
Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously
More informationGLD-30 Gas Leak Detector
GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators
More informationSPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System
SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following
More informationCarbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output
Features Electrochemical sensor element (0)2-10 Vdc or (0)4-20 ma output, jumper selectable Standard IP65 plastic enclosure Measuring ranges 0-50 ppm 0-100 ppm 0-150 ppm 0-200 ppm 0-250 ppm 0-300 ppm 0-500
More informationOIL FILM DETECTOR (Flame-proof Version) SODL-1600
OIL FILM DETECTOR (Flame-proof Version) SODL-600 The model SODL-600 is a flame-proof type oil film detector. This model monitors a water surface for the presence of an oil film floating on the surface.
More informationHygro/hygrothermal transducers (hygrometric)
Data Sheet 907031 Page 1/7 Hygro/hygrothermal transducers (hygrometric) for measuring relative humidity and temperature for mounting indoors, outdoors, and in air ducts with resistance, current or voltage
More informationDräger Polytron 7000 Fixed gas detector
DETECTION PERSONAL PROTECTION DIVING TECHNOLOGY SYSTEM TECHNOLOGY SERVICES Dräger Polytron 7000 Fixed gas detector ST-3751-2003 The Dräger Polytron 7000 is a gas detector that can satisfy all toxic and
More informationDetection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People
Fixed Gas Detector Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Certifications The Fixed Gas Detection People The OLC/OLCT CT range of fixed ddetectors
More informationSIL725 Safety Annunciator
SIL725 Safety Annunciar Configurable SIL2 Annunciar certified IEC61508 SIRA certified at safety integrity level SIL2 IEC61508 Modular construction from 1 128 alarm channels Multi-redundant design Choice
More informationHigh Pressure Conductivity Monitor
Product Data Sheet PDS 71-EDS880/1/rev.A August 2006 Model EDS880/1 High Pressure Conductivity Monitor COMPLETE SYSTEM FOR THE DETERMINATION OF CONDUCTIVITY IN HIGH PRESSURE SYSTEMS SENSOR INSTALLS DIRECTLY
More informationQAF63.2-J QAF63.6-J. Frost detectors. for use on the air side
s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10
More informationQ-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air
Document No. 155-755 Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air Description Features Application The Q-Series Relative Humidity and
More informationIndustrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw
Industrial Solid State Contactor TE10S Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw Partial load failure (PLF) detection option User Manual Copyright Eurotherm Automation
More informationZareba Metro Gas Detector
Zareba Metro Gas Detector The Metro addressable gas detector enables remote monitoring of flammable and toxic gas hazards Metro Gas Detector One-Stop Shop Flammable and toxic gas monitors available Methane,
More informationHygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring
Data Sheet 907021 Page 1/9 Hygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring For measuring relative air humidity, temperature, and fresh
More informationSMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS
SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH
More informationSAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL
SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements
More informationDual Input Toroidal Analyzer
Instruction Sheet PN 51A-1055T/rev.H February 2006 Model 1055 SOLU COMP II Dual Input Toroidal Analyzer Model Option 1055-21-31 For additional information, please refer to the Instruction Manuals CD shipped
More informationP R O D U C T D ATA S H E E T
P R O D U C T D ATA S H E E T www.internationalgasdetectors.com Transmitters Control Systems OLIVER Sensors IGD Accessories TOCSIN 640 Pre-Configured Gas Detection System, CO2, O2 or N2O With all the features
More information