MODULE 2. Water-Based Suppression System Basics

Size: px
Start display at page:

Download "MODULE 2. Water-Based Suppression System Basics"

Transcription

1 MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1

2 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE This module covers: Water supply sources Components of fire suppression such as piping, valves, sprinkler heads, tests, foam system Different types of automatic sprinkler systems Standpipe systems Foam and water mist suppression system 2

3 Water Supplies The typical water supply for a water-based suppression system is a connection to a public waterworks system. However, other sources of water supply are acceptable. Sources: NFPA 13: 23.2 Water supply types NFPA 13D: 6.2 Water supply sources NFPA 13R: 9.3 Water supply sources NFPA 20: 7.2 Water supplies 3

4 Water Supplies: Sources A public waterworks system An elevated tank A pressure tank designed to American Society of Mechanical Engineers (ASME) standards for a pressure vessel with a reliable pressure source A stored water source with an automatically operated pump A well with a pump of sufficient capacity and pressure to meet the sprinkler system demand Example of a water supply source: An elevated tank 4

5 Fire Department Connections NFPA states: The purpose of the Fire Department Connection is to supplement the water supply, but not necessarily provide the entire sprinkler system demand. Fire Department Connections are not intended to deliver a specific volume of water. FDCs are required for most NFPA 13 and 13R automatic sprinkler systems and standpipe systems NFPA 13 requires the fire department connection to be located on the street side of buildings OBC Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply with Section through

6 6

7 Piping In a wet pipe-sprinkler system water is constantly maintained within the piping Dry pipe-sprinkler systems prevent the water from entering the sprinkler system piping Materials Above ground piping material examples found in NFPA 13: steel, copper, and chlorinated polyvinyl chloride (CPVC). Below ground material examples found in NFPA 13: ductile iron, steel, concrete, plastic, copper Location NFPA 13: Pipe shall not be run under buildings NFPA 13: Where pipe must be run under buildings, special precautions shall be taken. 7

8 Valves A control valve controls the water to the sprinkler system and should be open at all times A check valve has two-port valves, one for fluid to enter and the other for fluid to leave. Pressure Requirements: NFPA 13: When water exceed 175 psi, valves shall be used in accordance with their pressure rating Automatic Sprinkler Systems Handbook, Eighth Edition 8

9 Backflow Preventers A device with check valves, air inlets, and/or relief valves installed on water piping designed to prevent the flow of water or other liquids, mixtures, or substances into the distributing pipes of a potable supply of water from any source or sources other than its intended source Means of backflow prevention air gap atmospheric vacuum breaker (AVB) reduced pressure valve assembly (RP) double check valve assembly (DC) NFPA 13: A check valve or other positive backflow prevention device shall be installed in the air supply to each system to prevent airflow or water flow from one system to another. NFPA 13: The back flow prevention assembly shall be forward flow tested to ensure proper operation. NFPA 13: The minimum flow rate shall be the system demand, including hose stream demand where applicable 9

10 NFPA 13: Automatic Sprinkler Systems Handbook, 2013 Edition 10

11 SPRINKLER Definition The component of a fire sprinkler system that discharges water after a fire has been detected NFPA 13: The following are characteristics of a sprinkler that define its ability to control or extinguish a fire: Thermal sensitivity Temperature rating Specific orifice size Installation orientation Example: sidewall or pendent sprinklers Water distribution characteristics Special service conditions Example: Corrosion-Resistant or Decorative Sprinklers Nozzle Definition NFPA 13: a device for use in applications requiring special water discharge patterns, directional spray, or other unusual discharge characteristics. 11

12 University of Toronto 12

13 Initiating Devices A system component that originates transmission of a changeof-state condition Includes smoke detectors, water flow alarm, fixed temperature detectors, rate of rise detectors, and heat detector 13

14 Test connections Verify proper operation of equipment Example: NFPA 13: Main drain test connections shall be provided at locations that will permit flow tests of water supplies and connections For inspection of sprinkler systems: Alarm test connections can be located anywhere downstream of the main control valve on a wet pipe system per NFPA 13: Trip test connections must be located on the highest, most remote branch line of a dry pipe system per NFPA 13: NFPA 13: 26.1 A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA

15 Alarm attachments NFPA 13: 8.17 System Attachments NFPA 13: A Central station, auxiliary, remote station, or propriety protective signaling systems are a highly desirable supplement to local alarms, especially from a safety to life standpoint. NFPA 13: Local Waterflow Alarms. A local waterflow alarm shall be provided on every sprinkler system having more than 20 sprinklers. 15

16 Automatic Sprinkler Systems: Wet Pipe Definition NFPA 13: Employs automatic sprinklers attached to a piping system containing water and connected to a water supply NFPA 13: Must be maintained at or above 40 F (4 C). The water discharges immediately from sprinklers opened by heat from a fire Fire Systems, Inc 16

17 Automatic Sprinkler System: Dry-Pipe Definition per NFPA 13: Employs automatic sprinklers that are attached to a piping stream containing air or nitrogen under pressure Are used when there is danger of some or all of the piping freezing. The release of pressure permits the water pressure to open a dry pipe valve, and the water then flows into the piping system and out the opened sprinklers Fire Systems, Inc 17

18 Automatic Sprinkler System: Deluge Definition per NFPA 13: Employs open sprinklers that are attached to a piping system that is connected to a water supply through a valve Valve is opened by the operation of a detection system installed in the same area When valve opens, water flows into the piping system and discharges from all sprinklers Fire Systems, Inc 18

19 Automatic Sprinkler System: Pre-Action Definition per NFPA 13: A system that employs automatic sprinklers that are attached to a piping system that contains air (under or not under pressure) Has a supplemental detection system installed in the same area as the sprinklers Per NFPA 13: Three basic types: single interlock, noninterlock, and double inter-lock typically used in areas containing high value equipment or contents and spaces which are highly sensitive to the effects of accidental sprinkler water discharge. 19

20 Automatic Sprinkler System: Other Anti-freeze Circulating Closed Loop Combined Dry Pipe-Preaction Gridded Looped Multi-Cycle 20

21 Standpipe Systems and Classes: Automatic A standpipe system that is attached to a water supply capable of supplying the system demand and that requires no action other than opening a hose valve to provide water at hose connections. Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II Wet: contains water at all times that is attached to a water supply capable of supplying the system demand at all times and that requires no action other than opening a hose valve to provide water at hose connections. Dry: permanently attached to a water supply capable of supplying the system demand at all times, containing air or nitrogen under pressure, the release of which (as from opening a hose valve) opens a dry pipe valve to allow water to flow into the piping system and out of the opened hose valve. Semi-automatic Dry: permanently attached to a water supply that is capable of supplying the system demand at all times arranged through the use of a device such as a deluge valve and that requires activation of a remote control device to provide water at hose connections. 21

22 Standpipe Systems and Classes: Manual Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II Wet: contains water at all times that relies exclusively on the fire department connection to supply the system demand. Dry: has no permanently attached water supply that relies exclusively on the fire department connection to supply the system demand. 22

23 Foam Proportioning Systems NFPA 11: Proportioning. The continuous introduction of foam concentrate at the recommended ratio into the water stream to form foam solution. Foam concentrate shall be introduced into the water flow by a concentrate controller utilizing balanced-pressure injection. Types of Foam Proportioning System (NFPA 11: ) Balance Pressure Pump-Type Proportioning In-Line Balanced Pressure Proportioning Direct Injection Variable Pump Output Proportioning 23

24 Foam Concentrate NPFA Foam Concentrate. A concentrated liquid foaming agent as received from the manufacturer. Types of Foam Concentrate (NFPA 11: ) Alcohol-Resistant Foam Concentrate Aqueous Film-Forming Foam Concentrate (AFFF) Fluoroprotein Foam Concentrate Film-Forming Fluoroprotein Foam Concentrate (FFFP) 24

25 Foam Generators Foam Generator Types (NFPA 11: ) Aspirator Type Jet streams of foam solutions aspirate sufficient amounts of air that is then entrained on the screens to produce foam Blower Type Foam solution is discharged as a spray onto screens through which an airstream developed by a fan or blower is passing 25

26 NFPA 11 Standard for Low-, Medium-, and High-Expansion Foam 2005 Edition 26

27 Foam-Water Suppression Systems Foam-water sprinkler system or foam-water spray systems are outlined in NFPA 16. Foam-water sprinkler: A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with appropriate discharge devices for extinguishing agent discharge and for distribution over the area to be protected. Foam-water spray: A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with foam-water spray nozzles for extinguishing agent discharge (foam followed by water or in reverse order) and for distribution over the area to be protected. 27

28 Foam-Water Suppression Systems (NFPA 11: 5.1) Low-expansion foam to protect outdoor storage tanks, interior flammable liquid hazards, loading racks, diked areas, and non diked spill areas (NFPA 11: 6.3) Medium and high-expansion foam shall be permuted to protect: (1) ordinary combustibles, (2) flammable and combustible liquids, combinations of (1) and (2), and liquefied natural gas (high-expansion only) 28

29 29

30 Foam-Water Suppression Systems: Dry Employs automatic sprinklers or nozzles that are attached to a piping system that contains air or nitrogen under pressure The release of the pipe permits the water pressure to open a valve known as a dry pipe valve. The water then flows into the piping system and out the opened sprinklers. 30

31 In Control Fire Protection 31

32 Foam-Water Suppression Systems: Preaction Employs automatic sprinklers or nozzles attached to a piping system containing air that might or might not be under pressure, with a supplemental detection system installed in the same area as the sprinklers. Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that have activated. 32

33 In Control Fire Protection 33

34 Foam-Water Suppression Systems: Deluge Employs open discharge devices, which are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system, which is installed in the same areas as the discharge devices. When the valve opens, water flows into the piping system and discharges from all discharge devices attached thereto 34

35 In Control Fire Protection 35

36 Water Mist Suppression Systems A distribution system connected to a water supply or water and atomizing media supplies Is equipped with one or more nozzles capable of delivering water mist intended to control, suppress, or extinguish fires NFPA 750 is the appropriate standard for the installation of water mist systems 36

37 Lessons Learned from Module 2 There are many types of water supplies for water-based suppression systems, such as elevated tanks and water transported from a lake or spring. A wet pipe automatic sprinkler system should not be installed in an area that goes below freezing and must be maintained at or about 40 degrees Fahrenheit. Foam concentrate is a foam fire-fighting agent that must be diluted with water There are two types of foam generators, blower and aspirator. It is important to be familiar with the OBC, NFPA, OFC, and OPC. 37

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement Second Revision No. 11-NFPA 16-2014 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 2015 edition. NFPA 13, Standard

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University Foam Systems WILLIAM HICKS MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI Associate Professor Eastern Kentucky University William.Hicks@eku.edu Objectives Classify high, medium, and lowexpansion

More information

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids. SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems

More information

Foam Products ENGLISH

Foam Products ENGLISH Foam Products ENGLISH Tyco Fire & Building Products Foam Products Today s technological innovations bring chemical and material fire hazards. Our lines of sprinklers and alarm valves have an excellent

More information

SECURITY BLANKET Foam Fire Protection Products

SECURITY BLANKET Foam Fire Protection Products SECURITY BLANKET Foam Fire Protection Products REAL DANGERS DEMAND REAL SOLUTIONS If your business manufactures, stores, or transports flammable liquids, the thought of a devastating fire always burns

More information

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems STEVEN WOLIN, VICE PRESIDENT, PRODUCT TECHNOLOGY & COMPLIANCE ANTONIO LUIS, TECHNICAL SERVICES MANAGER RELIABLE AUTOMATIC SPRINKLER

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

Foam Systems U.S. Quick Reference Guide

Foam Systems U.S. Quick Reference Guide Foam Systems U.S. Quick Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection

More information

Deluge & Preac tion Systems

Deluge & Preac tion Systems Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached

More information

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev 1.0 03-07-2017 Description Self Expanding Foam Systems (SEFS) are the alternative solution to existing flammable and combustible liquid

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO Foam Overview Applications Flammable Liquid Storage Tanks Diked Storage Tanks Loading Racks/Transfer Stations Closed Head Sprinkler Systems Deluge

More information

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS 210500 FIRE PROTECTION BASIC MATERIALS AND METHODS PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 087100 Door Hardware B. Section 220500 Plumbing Basic Materials and Methods

More information

TOTALPAC2 Integrated Fire Protection System

TOTALPAC2 Integrated Fire Protection System TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017 Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire

More information

Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters

Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters (Published jointly by American Fire Sprinkler Association and the National Center for Construction Education and Research.)

More information

Aircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

Aircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409 Aircraft Hangers DESCRIPTION Considering the value of commercial and military aircraft, it has become extremely important to have a reliable fixed fire protection system in aircraft storage, servicing,

More information

& Fire Extinguisher Training

& Fire Extinguisher Training & Fire Extinguisher Training D The fire is an exothermic reaction. Ignition Flammable material + air (O2) ----------> CO 2 +H 2 O+Heat Temperature The evolved heat will further promote the reaction to

More information

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: PORTABLE FIRE EXTINGUISHERS Guidelines: This checklist covers the "Uniform Fire Code" regulations

More information

Aircraft Hangars DESCRIPTION. A single fire area not larger than 40,000 sq. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

Aircraft Hangars DESCRIPTION. A single fire area not larger than 40,000 sq. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409 Aircraft Hangars DESCRIPTION Considering the value of commercial and military aircraft, it has become extremely important to have a reliable fixed fire protection system in aircraft storage, servicing,

More information

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop STORED PRESSURE 50, 125/150 lb. Stored Pressure These commercial stored pressure extinguishers are available in a choice of two sizes and three chemical options. The carriage design on both sizes provides

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,

More information

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-07 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection

More information

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-13 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

Water Spray Systems: NFPA 15

Water Spray Systems: NFPA 15 Water Spray Systems: NFPA 15 WILLIAM HICKS MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI Associate Professor Eastern Kentucky University William.Hicks@eku.edu System Maintenance Objectives Identify

More information

Technical Article. Foam Systems - Low Expansion, Medium Expansion, High Expansion. Martin Workman, Product Manager Special Hazards Division

Technical Article. Foam Systems - Low Expansion, Medium Expansion, High Expansion. Martin Workman, Product Manager Special Hazards Division Technical Article Foam Systems - Low Expansion, Medium Martin Workman, Product Manager Special Hazards Division March, 2006 Worldwide Fire Protection www.vikingcorp.com TABLE OF CONTENTS DEFINITION - FOAM

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

Fire protection for buildings

Fire protection for buildings Fire protection for buildings HI-FOG high-pressure water mist Ghelamco Group Protecting people, property and business continuity A fire in a building can lead to serious consequences. Even a harmless fire

More information

NFPA Edition Update

NFPA Edition Update NFPA 13 2013 Edition Update Session Agenda A2012 Code Cycle NFPA 13 Code Development Changes to NFPA 13 (NFPA 24) What Didn t Happen Next Steps 2 A2012 Code Cycle 800+ Proposal 500+ Comments TCC Meeting

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat

More information

2018 International Fire Code. Add new text as follows:

2018 International Fire Code. Add new text as follows: CCC-F-1-18 IFC: 311.2.2, 403.11.1.2, 1010.3.2; IBC: 424.3, 428.3.9, 506.2.2.1, 506.2.4.1, 1705.12.6, 2603.3, 3104.5.3, 2606.7.4; IRC: R101.2, R302.2.2, R313, R313.1, R313.1.1, R313.2, R313.2.1, R325.3,

More information

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring)

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring) Legend: 1 Deluge Valve (DV-5) 2 Isolation Valve 3 Diaphragm Supply Valve 4 Manual Control Station 5 Automatic Shut-off Valve 6 Automatic Drain Valve 7 Pressure Switch 8 Water Motor Gong 9 Releasing Panel

More information

2016 BACKFLOW PREVENTION EDUCATION COUNCIL OF COLORADO REGULATION SEMINAR FIRE SUPPRESSION SYSTEMS PANEL QUESTIONS

2016 BACKFLOW PREVENTION EDUCATION COUNCIL OF COLORADO REGULATION SEMINAR FIRE SUPPRESSION SYSTEMS PANEL QUESTIONS 2016 BACKFLOW PREVENTION EDUCATION COUNCIL OF COLORADO REGULATION SEMINAR FIRE SUPPRESSION SYSTEMS PANEL QUESTIONS NOVEMBER 22, 2016 JEFFERSON COUNTY FAIRGROUNDS COLORADO RURAL WATER, PUEBLO, CO UTE WATER

More information

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings Fire sprinklers have long been used in commercial buildings and large residential occupancies to provide economical life safety

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

PLAN REVIEW CHECKLIST

PLAN REVIEW CHECKLIST PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Box-in-Box Cold Storage Fire Protection Options

Box-in-Box Cold Storage Fire Protection Options Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

MSC Guidelines for Automatic Sprinkler Systems

MSC Guidelines for Automatic Sprinkler Systems S. J. Kelly, CDR, Chief of Engineering Division References a. Title 46 CFR 56.20, 56.50 & 56.60 (Subchapter F) b. National Fire Protection Association (NFPA) 13, 1996 Edition, Installation of Sprinkler

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5 Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18 NAVFAC PTS-D40 (February 2018) -------------------------------- Preparing Activity: NAVFAC SUPERSEDING PTS-D40 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D40 FIRE PROTECTION 02/18 NOTE:

More information

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) Generals Innovating fire extinguishing system for tunnel fires, for fully automatic intervention

More information

Module 7: Air Supply System

Module 7: Air Supply System Terms and Definitions Components of the Air Supply System Basic Functions of the Air Supply System Parts of a Compressor Characteristics of Compressors Loading and Unloading Process Characteristics of

More information

Tel Web: dyayan.com

Tel Web: dyayan.com 1 Our Products DYAYAN specializes in three main areas: - Manufacturing of Dry Chemical Powders - Manufacturing of Foam Concentrates - Project designing, assembly and maintenance of Fire Safety Systems.

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised Engine Module Page 1 of 5 SPRINKLER HEADS Types of Sprinkler Heads There are many different types of sprinkler heads utilized in fire protection systems. Most are equipped with a thermal detector that

More information

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E Advanced Integrated Fire Protection Systems TOTALPAC 2 Owner's Operation and Maintenance Manual FIRECYCLE III September 2009 FM-086G-0-5E TOTALPAC2 OWNER'S OPERATION & MAINTENANCE MANUAL Manufactured by

More information

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

TECHNICAL DATA 3% AR-AFFF

TECHNICAL DATA 3% AR-AFFF June 25, 21 Foam 14a The Viking Corporation, 21 N Industrial Park Drive, Hastings MI 4958 Telephone: 269-945-951 Technical Services: 877-384-5464 Fax: 269-818-168 Email: techsvcs@vikingcorp.com 1. DESCRIPTION

More information

Portable Fire Extinguishers

Portable Fire Extinguishers Portable Fire Extinguishers Workbook Activities The following activities have been designed to help you. Your instructor may require you to complete some or all of these activities as a regular part of

More information

Emergency shutdown systems. Procedures for bypassing ESD s

Emergency shutdown systems. Procedures for bypassing ESD s HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled

More information

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge OSHA Requirements Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge The requirements of this section apply

More information

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE TERM highly protected risk (HPR) is commonly used in

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX: Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean

More information

Ch. 11 Plumbing Systems

Ch. 11 Plumbing Systems Water Supply Potable Water: water suitable for human drinking Nonpotable: use for irrigation, flushing toilets, and the like Surface water comes from rain and snow that runs off into rivers and lakes.

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release Deluge System Pneumatic Release Deluge System Pneumatic Release When the fixed temperature release () is activated by fire, pressure in the release system escapes from the open device, allowing the pneumatic

More information

A.8.6 Part 6 : Special Fire Extinguishing Systems

A.8.6 Part 6 : Special Fire Extinguishing Systems A.8.6 Part 6 : Special Fire Extinguishing Systems CHAPTER 1 OBJECTIVE AND SCOPE 6.1 OBJECTIVE AND SCOPE 6.1.1 Objective This standard for special fire extinguishing system in part 6 is fire extinguisher

More information

Fire protection on chemical manufacturing sites

Fire protection on chemical manufacturing sites CFPA-E No 18:2008 Fire protection on chemical manufacturing sites FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation

More information

OPEN SPRINKLER SYSTEM

OPEN SPRINKLER SYSTEM OPEN SPRINKLER SYSTEM Introduction Competence and innovation driven by consistent market development and customer requirements have shaped the successful development of the SHIELD Brand. The extensive

More information

Fire fighting Questions

Fire fighting Questions Fire fighting Questions Question 1 (1 Mark) The sides and base of the fire tetrahedron are: a. fuel, nitrogen, oxygen, chemical reaction b. fuel, oxygen, heat, chain reaction c. heat, oxygen, nitrogen,

More information

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System pg. 1 INTRODUCTION : HPCL is in the process of procurement of Water mist

More information

Model F3 Dry Sprinklers

Model F3 Dry Sprinklers Features 1. The Model F3 utilizes Belleville Spring Closure Technology 2. Styles available for Model F3 Dry s: Pendent Recessed Pendent Concealed Horizontal Sidewall Recessed Horizontal Sidewall 3. 1½"

More information

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

FIRE SUPPRESSION SYSTEM

FIRE SUPPRESSION SYSTEM FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

TotalPac X Single interlock SUREFIRE system

TotalPac X Single interlock SUREFIRE system DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS AG AVB PVB DCVA PA 1 Abattoir (slaughter house) 2 Air compressor oil cooler 3 Agricultural chemicals (sprayers 4 Animal watering 5 Apartment building (within the scope of Part 3 of the Ontario Building

More information

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009 (II) 23, 25 June and 7, 9 July 2009 Organization by Co-organized by the Association of Registered Fire Service Installation contractors of Hong Kong Ltd (FSICA) Gas and Foam Suppression Systems Peter Bressington

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

INSPECTOR I SKILLS ADMINISTRATION

INSPECTOR I SKILLS ADMINISTRATION INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..

More information