CARBON DIOXIDE FIRE EXTINGUISHING SYSTEM
|
|
- Rolf Nelson
- 5 years ago
- Views:
Transcription
1 CARBON DIOXIDE FIRE EXTINGUISHING SYSTEM Carbon dioxide (CO) is a well-known extinguishing system for electrical equipment. The system consists of liquefied CO stored in pressurised cylinder, discharge valves, piping and electrical devices that automatically detect smoke or heat and quickly discharge the CO in the cylinders to extinguish the fire.
2 A carbon dioxide (CO) fire extinguishing system works by displaces the oxygen that supports combustion. It is applied by the total flooding principle with CO and hold until the combustion stops. A total flooding application can be defined as injecting CO into an enclosure or volume having the structural integrity to retain the agent during and after discharge. This system operated automatically by or manually by the operation of a system actuator. CO Features Leaves no residue after discharge Eco-friendly agent Non-damaging to property Effective on a wide range of flammable and combustible materials. CO Applications Electrical Room Generator Room Switch Room 9 S H 7 H S 3 CO Typical Arrangement 1. Electric Solenoid Pilot Cylinder (550 psi). 68L Carbon Dioxide Cyclinder 3. Manifold 4. Smoke Detector 5. Fire Curtain 6. 4V DC Tripping Device 7. Heat Detector 8. CO Discharge Nozzle 9. Twin Flasing Light 10. Fire Alarm Bell 11. CO Control Panel 1. Manual Pull Station SIDE ELEVATION TYPICAL CO PILOT CYLINDER ARRANGMENT Flexible FRONT ELEVATION TYPICAL CO PILOT CYLINDER ARRANGMENT 17 Discharge Connecting 1 38
3 Nett Volume CO Capacity Working Pressure Test Pressure Empty Weight Manufactured CYL-N 68L 45kg 150 bar 5 bar 75kg Mn Steel DOT-3AA BS 5045 Part 1 Gas Stored Pressure Power PC-S, PC-T Nitrogen 38 bar (550 psi) 4 V DC Type Mode Working Pressure Type Weight of Valve Standard 45KG-NV Forged Brass CuZn 3963 UP bar Manual/Pneumatic/Electric 700g DIN
4 Lenght Type Test Pressure HH-CH-13 6mm (1/4 ) 330mm (13 ) High Pressure Hose Steel Braided Rubber Hose 150 bar Discharge Hose 3 Lenght Type Test Pressure HH-DH-17 13mm(1/ ) 43mm(17 ) High Pressure Hose Steel Braided Rubber Hose 150 bar Discharge Pattern Discharge Type DN-UH15 DN-UH0 DN-UH5 15mm 0mm 5mm Brass Chrome Uni-bilateral With Orifice Pendent 45KG-PC Steel Galvanised 40
5 HHF-VP-3/8 10mm(3/8 ) Steel Galvanised HHF-TEE-1/ 13mm (1/ ) x 13mm(1/ ) x 6mm(1/4 ) Steel Galvanised HHF-PG-3/8 10mm(3/8 ) Steel Galvanised TD 180mm(W) x 90mm(D) x 40mm(H) Working Current 0.4A Aluminum Alloy Red Polyester 41
6 Smoke Curtain Colour Coating Finish Operating Temperature Standard FC Woven Fibreglass Fabric White Loomstate Basic Fabric 600 C BS 476: Part 7 MPB Ø00mm x 65mm(H) Aluminum Alloy Red Polyester SIZE No. of Zones Model no. Code no. (mm) (W x D x H) Normal Weatherproof PE-HP000 FAP-0ZCP-N 430 x 195 x x 195 x PE-HP4000 Power Supply Input Operating Charger Charging Rate STANDBY MODE Master Per zone (with detectors) Flashing Lights (Red LED) ALARM MODE Master Per Trigger Zone Output Devices Flashing Lights (Red LED) Per Bell FAP-04ZCP-N 55 x 178 x x 178 x 40 40V AC 50Hz 4V DC Automatic/Trickle Type 300mA (Trickle).5A (Boost) 75mA 5mA 75mA 10mA 70mA 100mA 75mA 30mA 4
7 UNIQUE Smoke Detector Model No. Description Alarm 4V DC 470 Ω AH0711 FAE-P0711 Wire 40mA Operating Temperature Range Operating Humidity Range Voltage Range Standby Current Sensitivity Setting Weight Colour -10 C to 55 C 10% to 93% Relative Humidity 1V-30V DC 5-75 µa Complies with UL 68 Fire- proof plastic Ø10mm x 47mm (H) 130g White EFFECTIVE ALERT AREA Building Height Under 4m 4m to 0m Area Covered 150m 75m UNIQUE Heat Detector 45 Model No. Description Alarm 4V DC 470 Ω Operating Temperature Range Operating Humidity Range Voltage Range Standby Current Sensitivity Setting Weight Colour EFFECTIVE ALERT AREA Building Height Under 4m 4m to 8m AH0333 FAE-H0333 Wire 40mA 0 C to 55 C 10% to 93% Relative Humidity 1V-30V DC 5-75 µa Complies with UL 68 Fire- proof plastic Ø111mm x 45mm (H) 137g White Fire Proof Building Ordinary Building 90m 50m 45m 30m 43
8 Model No. Lens Luminary (Casing & Hood) Weight KP305B (BULB), KP305L (LED) FAE-FLO-BU, FAE-FLO-LED High efficient prismatic polycarbonate lens optimized for omnidirectional viewing. Filament Bulb/Ultra Bright LED 10mm(W) x 77mm(D) x 108mm(H) Mild Steel Epoxy Powder Red Black casing with green and red lens UNIQUE Fire Alarm Bell Model No. Supply Voltage Sound Output Current Consumption D10 FAE-6AB 110/ 40V (AC) 1/4V (DC) db 0.05 A 150mm(6 ) Red 44
PORTABLE FIRE EXTINGUISHERS. Fire Safety.
WHAT THE RATINGS MEAN: The New Zealand Standard for classifiying, rating, and performance testing of Fire Extinguishers (AS/NZ1850:1997), was introduced at the request of manufacturers, who wanted a method
More informationHRS035-MS-022-RD 22 (559mm) 19mm x 30m 310mm Fixed Manual. HRS037-GI-019-RD 19 (483mm) 19mm x 36m 350mm Swing Manual
FIRE HOSE REEL CertIFIeD to Bs en 671-1: 1995 Certification No: Ps005704 BRITISH STANDARDS INSTITUTION APPROVAL FIRE HOSE REELS CERTIFIED TO BS EN 671 LICENCE NO. KM 51857 Certified Product AUSTRALIAN
More informationElement C3.4 Fire Fighting Equipment
.4 Fire Fighting Equipment Classification of Fires Class A Solids. Wood, paper, plastics Class B Liquids Petrol oil, paint Class C Gases LPG, natural gas Classification of Fires Class D Metals Zinc, sodium,
More informationData/ Specification Sheet
Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel
More informationFIRE SUPPRESSION SYSTEM
FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction
More informationExtinguishers. Commercial Industrial High rise buildings
Commercial Industrial High rise buildings Extinguishers Design, Supply, Installation, Testing, Commissioning, Maintenance, and Service of Firefighting and Fire Protection Systems Think fire protection......thank
More informationFireFlex DUAL Double Interlock, Self-contained system
FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated Double interlock preaction automatic sprinkler system combined with a clean agent fire extinguishing system, factory-assembled
More informationCORE Protection Fire System Specification
CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated
More informationTRIMAX ASIA ENGINEERING & CONSTRUCTION (PG U )
TRIMAX ASIA ENGINEERING & CONSTRUCTION (PG0176866-U ) FIRE PROTECTION EQUIPMENTS PARTS CATALOGUE TRIMAX ASIA ENGINEERING & CONSTRUCTION No. 24, Jalan Pantai, 12000 Butterworth, Penang, Malaysia. Fax: +6
More informationSPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.
More informationSPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND
1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation
More informationPRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)
LISTING NUMBER afp - 2086 Commonwealth Scientific and Industrial Research Organisation, Australia Ph.: 61 (0)3 9252 6000 Fax: 61 (0)3 9252 6011 Web site: http://www.activfire.gov.au E-mail: info@activfire.gov.au
More information1 of 7 UNIVERSAL FIRE ENGINEERING (ALOR SETAR) SDN BHD. EN3 Water & Foam Type Fire Extinguisher. Portable Carbon Dioxide Fire Extinguisher
UNIVERSAL FIRE ENGINEERING (ALOR SETAR) SDN BHD EN3 Water & Foam Type Fire Extinguisher Extinguisher Type 2L Foam, 6L Foam, 9L Foam, 9L Water Water and Foam fire extinguishers extinguish the fire by taking
More informationSAFETY THE BEST FOR YOUR EQUIPMENT
THE BEST SAFETY FOR YOUR EQUIPMENT The fire protection requirements involve adapting the fixed extinguishing systems to the various needs of the hazard to be protected. In many cases it is necessary to
More informationEmergency Response Procedures Contractors Instruction. Building nformation
Building nformation Emergency Response Procedures Contractors Instruction www.conceptsafety.com.au Building 2, Freeway Office Park 2728 Logan Road, Eight Mile Plains QLD 4113 Email: info@conceptsafety.com.au
More informationSECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary
More informationKITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.
More informationCarbon Dioxide Extinguishing Systems Fighting fire with CO2
Carbon Dioxide Extinguishing Systems Fighting fire with CO2 TECHNOLOGIES GAS-BASED SUPPRESSION SYSTEMS Highly effective for many applications Quick and effective fire fighting is the strong point of carbon
More informationInert Gas Fire Extinguishing System
s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, INERGEN 300 bar, engineered total
More informationConventional Fire Detection
SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct
More information+91-8048763768 Cease Fire & Electrical Services http://www.ceasefireengineers.com/ We are the supplier, trader and service provider of fire alarm equipment, fire suppression system, fire detection system,
More informationFire fighting Questions
Fire fighting Questions Question 1 (1 Mark) The sides and base of the fire tetrahedron are: a. fuel, nitrogen, oxygen, chemical reaction b. fuel, oxygen, heat, chain reaction c. heat, oxygen, nitrogen,
More informationELECTRONIC SOUNDER STROBE Model : AVD-C407
ELECTRONIC SOUNDER STROBE Model : AVD-C407 MULTRON range of combination Electronic Sounders with Strobe Lights are designed to complement our Fire Alarm products both technically and aesthetically as an
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More informationCO2 COCO GAS FLOODING SYSTEM
PRE INTRODUCTION: CO2 COCO GAS FLOODING SYSTEM The importance of erection, testing and commissioning are overlooked, in many projects while installing fixed Co2 extinguishing system. It is very common
More informationTwin-Agent Fire Fighting/Securing Systems Specifications
Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,
More informationPROFESSIONAL SUPPLIER
PROFESSIONAL SUPPLIER FOR FIRE-FIGHTING EQUIPMENT IRON MAN INDUSTRY LIMITED Sprinkler Small orifice, standard and quick response, spray sprinkler Designed for use in light hazard occupancies Requires less
More informationSECTION FM-200 FIRE SUPPRESSION SYSTEM
SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to
More informationCarbon Dioxide Fire Suppression Systems
Carbon Dioxide Fire Suppression Systems The original "clean agent," carbon dioxide suppresses fire without leaving behind water, foam or dry chemical to damage sensitive equipment. And because there is
More informationAgent Tanks PCL PCL PCL PCL - 600
Components Pg 2-1 Agent Tanks PCL - 160 PCL - 300 PCL - 460 PCL - 600 Model No. Diameter Height to top of valve Height with control head Height to valve outlet Weight PCL - 160 8.00 in. 17.65 in. 23.50
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, Sapphire, engineered, total flooding
More informationPower Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses
BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF
More informationGAS FLOODING SYSTEM FOR CIFF AT BASEMENT
CONSTRUCTION OF BUILDINGS FOR LABORATORIES AND ASSOCIATED FACILITIES INSTEM BANGALORE SCHEDULE OF QUANTITIES FOR (EQUIPMENT ROOM 3 & 4) Sl.No. Description Unit Quantity Rate (in INR) in figure HFC-227ea
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationFIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION
FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM LEADING THE WAY IN FIRE PROTECTION MEANS OF ESCAPE PROTECTION CASE STUDY: SSE HYDRO GLASGOW UK
More informationGAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen
GAS EXTINGUISHING SYSTEMS INERT GAS Argotec with argon or nitrogen NATUR AL without any damage to the atmosphere The extinguishing gases Argon and nitrogen extinguish a fire by oxygen displacement. When
More informationCARBON DIOXIDE CO 2 Industrial fire suppression systems
CARBON DIOXIDE CO Industrial fire suppression systems Kidde engineers developed carbon dioxide fire extinguishing over 0 years ago and Kidde have been responsible for every major improvement that has been
More informationInstitute for Plasma Research Welcomes you all on
Institute for Plasma Research Welcomes you all on Presented By: D.V.MODI, Safety Officer, IPR Compiled by: SAFETY COMMITTEE, IPR WHAT IS FIRE? The self-sustaining process of rapid oxidation of a fuel,
More informationThe Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE
Worldwide Safety Services Fire Extinguisher Training D 1 Objectives Understand the combustion process and different fire classes. Understand d fire extinguisher i types, operating procedures, capabilities,
More informationL+T GASETECHNIK. Klöpper-Waldmann GmbH & Co. K G. Alarm unit LSG4
Areas of application The LSG4 alarm unit is used for monitoring industrial systems, e.g. in the following areas: Alarm and hazard stati in production e.g. for monitoring temperature and pressure in reactors
More informationw w a. m o c. x e r fi. w u
1300 246 247 www.firex.com.au sales@firex.com.au Contents 1. About Firex 03 2. Fire Extinguishers 04 3. Fire Hose Reels 10 4. Fire Blankets 11 5. Accessories 12 6. Extinguisher Spare Parts 16 7. Fire Cabinets
More informationANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS
ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,
More informationmanufacturer since 1984
FIR RE AARM SYS Y TEMS The Relia able, Cap a apable and Professional manufacturer since 1984 m www.horinglih.com Cert No.506 Company Profile Horingih has designed high quality safety and protection products
More informationCO2 High Pressure Extinguishing System
CO2 High Pressure Extinguishing System Galley Duct System USERS MANUAL NO. 70749-G4 Yard: XXXXX Hull No.: XXXXX AFS Project No.: XXXXX Protecting life, environment and property... 70749G4_CO2_Galley_system.doc
More informationMODULE 2. Water-Based Suppression System Basics
MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE
More informationSTORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop
STORED PRESSURE 50, 125/150 lb. Stored Pressure These commercial stored pressure extinguishers are available in a choice of two sizes and three chemical options. The carriage design on both sizes provides
More informationAccessories. Safety Shut-off Valves. Certifications. Accessories. ASV375NT Safety Shut-off Valve. Combination Gas Control/Valve
In many typical oil & gas applications that are classified as Class I hazardous locations, the Cata-Dyne TM heater must be installed in accordance with CSA, FM and ATEX codes and regulations. As a result,
More informationGAS EXTINGUISHING SYSTEM INERT GAS. Argotec with carbon dioxide. Safe for certain.
GAS EXTINGUISHING SYSTEM INERT GAS Argotec with carbon dioxide Safe for certain. PPLICATIO VERSATILE Reliable extinguishing Fighting fires quickly and effectively is the strong point of Argotec extinguishing
More informationKidde Nitrogen Inert Gas Clean Agent Fire Suppression System
1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering
More informationINFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY
INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY >OLYL >H]LSLUN[O 4H[[LYZ SMOKELESS FLARE MONITOR Smokeless Flare Monitor (FM) Smokeless flares incinerate flammable hazardous
More informationTotalPac X Single interlock SUREFIRE system
DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of
More informationXenex Conventional Fire Detection & Alarm System
SECTI 4: page 1 Section 4: Xenex Conventional Fire Detection & Alarm System SECTI 4: page 3 Xenex system architecture Beam Transmitter Beam Receiver End of Line Call Point Smoke Detector Smoke Detector
More informationCO 2 EXTINGUISHING SYSTEMS
CO 2 EXTINGUISHING SYSTEMS CO 2 THE FIRE EXTINGUISHING CLASSIC: CLEAN, FAST AND RELIABLE TOTAL WALTHER, the acknowledged specialist in fire protection systems, has been manufacturing CO 2 extinguishing
More informationSIRENS PROGRAMMABLE MULTI-SOUND SIGNAL by Tomar Electronics
by Tomar Electronics SIRENS POWER ALARM PROGRAMMABLE MULTI-SOUND INDUSTRIAL SIGNALS The POWER ALARM siren is a heavy duty industrial audible alarm designed to operate under adverse industrial conditions
More informationSUPPORT EQUIPMENT MODULAR RAPIDLY DEPLOYABLE MOBILE RUGGED RELIABLE VERSATILE
SUPPORT EQUIPMENT MODULAR RAPIDLY DEPLOYABLE MOBILE RUGGED RELIABLE VERSATILE SUPPORT EQUIPMENT Deployable Rapid Assembly Shelter (DRASH) Support Equipment are shelter components that can be used to enhance
More informationOPERATING INSTRUCTIONS FOR THE TP18SX-HP
OPERATING INSTRUCTIONS FOR THE TP18SX-HP PLEASE READ THIS INSTRUCTION MANUAL PRIOR TO USING THE MACHINE Version 07/11 OVERVIEW The TP18SX-HP is a professional carpet extractor, with excellent performance.
More informationRisk Management Department. Fire Extinguishers
Risk Management Department Fire 1 Introduction to Fire Every school facility is equipped with fire extinguishers for staff to use to suppress fires. Used properly, a fire extinguisher can be an effective
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless
More informationSafe, Effective, Environment-friendly
IG-55 (Argon/Nitrogen) Safe, Effective, Environment-friendly Introduction With the phase out of the most commonly used but environmentally damaging Halon 1301 and CO 2 fire suppressant, inert gases are
More informationDeluge & Preac tion Systems
Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached
More informationPRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM
ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup
More informationThe complete conventional fire warning system
The complete conventional fire warning system www.espuk.com MAG2P 2 Zone Fire Panel 2 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call
More informationFIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION
FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM.AU LEADING THE WAY IN FIRE PROTECTION DESIGN SOLUTIONS THAT WORK FOR YOU Active Fire Curtain Barrier Assemblies comprise technologically
More informationHospitals and Major Medical Centers
Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety
More informationIRIS IP65 IRIS UNISCAN APPLICATION MANUAL
IRIS IP65 IRIS UNISCAN APPLICATION MANUAL 01/08/05 DESCRIPTION TABLE OF CONTENTS PAGE IRIS - UNISCAN... 1 SPECIFICATION... 1 SUPPLY VOLTAGE: -... 1 OUTPUTS: -... 1 TRANSMISSION: -... 1 CABLE: -... 1 FLAME
More informationGUILFORD COUNTY SCHOOLS
GUILFORD COUNTY SCHOOLS Fire Extinguisher Plan Policy In accordance with the regulations established by the United States Department of Labor pursuant to the Occupational Safety and Health Act and the
More informationSPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationFIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION
FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM LEADING THE WAY IN FIRE PROTECTION DESIGN SOLUTIONS THAT WORK FOR YOU CASE STUDY: FORTNUM & MASON LONDON UK Active Fire Curtain Barrier
More informationORENA BRAND CONVENTIONAL (ORENA Brand) CE
ORENA BRAND CONVENTIONAL (ORENA Brand) CE ODH02E 2 Zone Conventional Control Panel Zone Capacity: can be connected with 20 fire detectors and infinite manual call points Using environment: Temperature:
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections
More informationPriceList Category PartNbr Part Description Weight (l MSRP
Date Printed :4/22/2014 12:04:43 PM Effective 4-MAR-2014 CATALOG PRICING Note:Price amounts shown are in US$ PriceList Category PartNbr Part Description Weight (l MSRP ANSUL Restaurant Systems PIRANHA
More informationWelcome to Argonite fire protection from Ginge-Kerr
Welcome to Argonite fire protection from Ginge-Kerr Looking for fire protection of high value areas? Then you've come to the right place. As Halon systems go out, the Argonite system is coming in. All
More informationEC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA
Page 1 of 6 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal
More informationSPECIFICATION: ARGONITE Engineered Fire Suppression System
1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationTotalPac X Firecycle III Preaction Double interlock system
DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a multicycling Firecycle III system trim totally pre-assembled, pre-wired and factory tested. All electrical
More informationmirage standard response concealed pendent sprinkler vk492 (K5.6)
Page 1 of 6 1. DESCRIPTION Viking Mirage Standard Response Concealed Pendent Sprinkler VK492 is a thermosensitive glass-bulb spray sprinkler designed for installation on concealed pipe systems where the
More informationExcel-EN Conventional Fire Control Panel
Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs
More informationPORTABLE PERFORMANCE ANSUL Stored Pressure Fire Extinguishers
PORTABLE PERFORMANCE ANSUL Stored Pressure Fire Extinguishers READY FOR ACTION WHEN YOU ARE. Every year, cooking accidents, unattended candles, electrical failures, careless smoking and other incidents
More informationLF-4000 Series Conventional Fire Alarm Control Unit
LF-4000 Series Conventional Fire Alarm Control Unit Features: 1 to 36 Zone Control Panels Control Key Switch Easy Push Button Control Switches Zone Circuit Monitoring for Open and Short Sounder Circuit
More informationRDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:
RDM LOCK G-1 1400 Series Electromagnetic Lock The patented 1400 Series Electromagnetic Lock is universal for all types of applications, including outdoor use. The innovative design will reduce installation
More informationSPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection
1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in
More informationA. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.
1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationSita200plus. 200detectors. Single loop analogue addressable System
Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D
More informationec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)
Sprinkler 83h 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 and Pendent Sprinkler VK572 are thermosensitive glass bulb spray sprinklers
More informationPART 1 - GENERAL 1.1 WORK INCLUDED
PART 1 - GENERAL 1.1 WORK INCLUDED A. Nortec ML Series high pressure adiabatic in-space system[s] as indicated on drawing[s] and as indicated on schedule[s]. B. Complete and operable humidification system
More informationGlobal Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationCO 2 Fire Extinguishing Systems
Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword... 10 0.1 Application of the VdS guidelines... 10 1 General... 10 1.1 Scope... 10 1.2 Aims... 11 1.3 Description...
More informationEFBW series - BiWire Ultra control panel
4.2 Control panels and repeater panels EFBW series - BiWire Ultra control panel Eaton s new BiWire Ultra fire detection system is unlike any other standard conventional system as the panel, conventional
More informationPacked With Features. Smart Pulsar controls are conveniently
Packed With Features Filter cartridge is automatically cleaned each time the pedal is operated. Pull-through exhaust fan reduces wear on impeller blades. Unique Air Logic System maximizes air flow to the
More informationHigh Quality LED Lighting!
High Quality LED Lighting! IP65 GB Code: Ex ib II CT4 GB Certificate CNEx09.0865 Standard: GB3836.1-2000 GB3836.4-2000 Cree LED Light Source PC Shell Portable Mountable on a safety helmet Energy Saving
More informationPolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen
PolyGard Single Point Controller SPC-X3-XX for Toxic Gases and Oxygen DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor and
More informationCadet Entry Level Award(ELA) Part Four. Fire Safety
Cadet Entry Level Award(ELA) Part Four Fire Safety By the end of this ELA module you will Have an understanding of Fire Be able to reduce Fire risk at Work Know what to do when the Fire Alarm sounds Know
More informationFire Extinguisher Training
Fire Extinguisher Training The Fire Triangle Fire Safety, at its most basic, is based upon the principle of keeping fuel sources and ignition sources separate. The Fire Triangle Three things must be present
More informationAir. Pressure. Motion. nnnnnnnn
Air. Pressure. Motion. nnnnnnnn AIRTEC classic ejectors Page 10.001 AIRTEC column ejectors Vacuum generators with 1, 4, 6 and 8 independent vacuum circuits. Series HV and HF Page 10.010 MI and MIF Page
More informationPERFORMANCE AT HAND RED LINE Hand Portable Fire Extinguishers
PERFORMANCE AT HAND RED LINE Hand Portable Fire Extinguishers MODEL 5 The Model 5 has a slim design for use on vehicles and machinery where space is limited. Typical applications include small trucks,
More informationInstallation and user manual for the BiWire / Conventional Repeater Panel
Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....
More informationWorldwide Contacts.
Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed
More informationUFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCESA / NASA UFGS-21 21 00.00 40 (August 2010) --------------------------------- Preparing Activity: NASA Superseding UFGS-21 21 00.00 40 (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationDETECT-A-FIRE Heat Detectors
DETECT-A-FIRE Heat Detectors DETECT-A-FIRE thermal detectors are detection and release devices used for fire detection systems to activate alarms and actuate extinguishing systems. This rate compensated
More information