Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Size: px
Start display at page:

Download "Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing."

Transcription

1 9/20/2016 2:27 PM Second Revision No NFPA [ Section No ] Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. (SAF-MEA) Submitter Full Name: SAF-MEA Submittal Date: Tue Jun 21 11:39:31 EDT 2016 NOTE: This Public Comment appreared as CC Note No. 1 in the First Draft Report. The Correlating directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballots of Pappas and Tierney to revise the definition by combining the two sentences to read as follows: Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. (SAF-MEA) This action will be considered as a public comment. Public Comment No. 5-NFPA [Section No ]

2 9/20/2016 2:27 PM Second Revision No NFPA [ Section No ] Two releasing operations shall be permitted for educational occupancy classroom doors secured against unwanted entry in accordance with the provisions of Chapter 15. Submitter Full Name: SAF-MEA Submittal Date: Mon Jun 20 10:04:56 EDT 2016 It is the position of the TC on Means of Egress that increasing the number of latch/lock releasing operations is dangerous and could create a hazard to occupants. Technology exists that will meet the current code requirement for not more than one latch/lock releasing operation. The need for multiple operations is contrary to decades of experience resulting in fatalities in schools and other buildings. Single-action egress is an important aspect of life safety for all emergencies. Public Comment No. 42-NFPA [New Section after ]

3 9/20/2016 2:27 PM Second Revision No NFPA [ Section No ] Delayed-Egress Electrically Electrical Locking Systems Approved, delayed-egress electrically electrical locking systems shall be permitted to be installed on door assemblies serving lowand ordinary-hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system in accordance with Section 9.6 or an approved, supervised automatic sprinkler system in accordance with Section 9.7, and where permitted in Chapters 11 through 43, provided that all of the following criteria are met: (1) The delay of the delayed-egress electrically electrical locking system shall deactivate allowing unobstructed egress upon actuation of one of the following: (a) Approved, supervised automatic sprinkler system in accordance with Section 9.7 (b) Not more than one heat detector of an approved, supervised automatic fire detection system in accordance with Section 9.6 (c) Not more than two smoke detectors of an approved, supervised automatic fire detection system in accordance with Section 9.6 (2) The delay of the delayed-egress electrically electrical locking system shall deactivate allowing unobstructed egress upon loss of power controlling the lock or locking mechanism. (3)* An irreversible process shall release the electrical lock in the direction of egress within 15 seconds, or 30 seconds where approved by the authority having jurisdiction, upon application of a force to the release device required in under all of the following conditions: (a) The force shall not be required to exceed 15 lbf (67 N). (b) The force shall not be required to be continuously applied for more than 3 seconds. (c) The initiation of the release process shall activate an audible signal in the vicinity of the door opening. (d) Once the electrical lock has been released by the application of force to the releasing device, rearming the delay electronics shall be by manual means only. (4)* A readily visible, durable sign that conforms to the visual characters requirements of ICC/ANSI A117.1, Accessible and Usable Buildings and Facilities, shall be located on the door leaf adjacent to the release device in the direction of egress, and shall read as follows: (a) (b) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS, for doors that swing in the direction of egress travel PULL UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS, for doors that swing against the direction of egress travel (5) The egress side of doors equipped with delayed-egress electrically electrical locking system shall be provided with emergency lighting in accordance with Section 7.9. (6) Hardware for new installations shall be listed in accordance with ANSI/UL 294, Standard for Access Control System Units The provisions of for sensor-release of electrical locking systems shall not apply to door assemblies with delayed-egress electrically electrical locking systems. Submitter Full Name: SAF-MEA Submittal Date: Mon Jun 20 11:11:25 EDT 2016 NOTE: This Public Comment appeared as CC Note No. 7 in the First Draft Report. The Correlating directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballot of Tierney to revise the term delayed egress electrically locking systems to delayed egress electrical locking systems and make consistent use of the term. This action will be considered as a public comment.

4 9/20/2016 2:27 PM Public Comment No. 8-NFPA [Section No ]

5 9/20/2016 2:27 PM Second Revision No NFPA [ Section No ] Elevator Lobby Exit Access Door Assemblies Locking. Where permitted in Chapters 11 through 43, door assemblies separating the elevator lobby from the exit access required by shall be permitted to be electrically locked, provided that all the following criteria are met: (1) The electrical locking hardware is listed in accordance with ANSI/UL 294, Standard for Access Control System Units. (2) The building is protected throughout by a fire alarm system in accordance with Section 9.6. (3) The building is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (4) Waterflow in the sprinkler system required by (3) is arranged to initiate the building fire alarm system. (5) The elevator lobby is protected by an approved, supervised smoke detection system in accordance with Section 9.6. (6) Detection of smoke by the detection system required by (5) is arranged to initiate the building fire alarm system and notify building occupants. (7) Initiation of the building fire alarm system by other than manual fire alarm boxes unlocks the electrical locks on the elevator lobby door assembly. (8) Loss of power to the elevator lobby electrical lock system unlocks the electrical locks on the elevator lobby door assemblies. (9) Once unlocked, the elevator lobby door assemblies remain electrically unlocked until the building fire alarm system has been manually reset. (10) Where the elevator lobby door assemblies remain mechanically latched after being electrically unlocked, latch-releasing hardware in accordance with is affixed to the door leaves. (11) A two-way communication system is provided for communication between the elevator lobby and a central control point that is constantly staffed. (12) The central control point staff required by is capable, trained, and authorized to provide emergency assistance. (13) The provisions of for delayed-egress electrically electrical locking systems are not applied to the elevator lobby door assemblies. (14) * The provisions of for sensor-release of electrical locking systems are not applied to the elevator lobby door assemblies. Submitter Full Name: SAF-MEA Submittal Date: Tue Jun 21 15:36:35 EDT 2016 : The revision responds to CC Note 7.

6 0 9/20/2016 2:27 PM Second Revision No NFPA [ Section No ] As a minimum, the following items shall be verified: (1) Floor space on both sides of the openings is clear of obstructions, and door leaves open fully and close freely. (2) Forces required to set door leaves in motion and move to the fully open position do not exceed the requirements in (3) Latching and locking devices comply with (4) Releasing hardware devices are installed in accordance with (5) Door leaves of paired openings are installed in accordance with (6) Door closers are adjusted properly to control the closing speed of door leaves in accordance with accessibility requirements. (7) Projection of door leaves into the path of egress does not exceed the encroachment permitted by (8) Powered door openings operate in accordance with (9) Signage required by (3), , , and is intact and legible. (10) Door openings with special locking arrangements function in accordance with (11) Security devices that impede egress are not installed on openings, as required by (12) Where required by , door hardware marking is present and intact. (13) Emergency lighting on sensor-release of electrical locking systems and doors equipped with delayed-egress electrically electrical locking systems is present and functioning in accordance with Section 7.9. Submitter Full Name: SAF-MEA Submittal Date: Mon Jun 20 11:23:14 EDT 2016 The committee believes that verifying the presence of emergency lighting is appropriate, but functional testing of emergency lighting is covered in Section 7.9 and therefore does not need to be part of the door inspection procedures. The requirement for verifying the presence of emergency lighting is consistent with the other provisions in The revision also responds to CC Note 7, which replaces 'electrically' with 'electrical'. Public Comment No. 61-NFPA [Section No ]

7 3 9/20/2016 2:27 PM Second Revision No NFPA [ Section No. A ] A None of the special locking arrangements addressed in are intended to allow credentialed egress, request to exit, or similar provisions, where an occupant cannot leave the building without swiping a card through a reader. Where such an arrangement is desired to keep track of occupants, the swiping of cards needs to be procedural but not necessary for releasing the door lock or latch. Free egress needs to be available at all times. Another option to free egress is the use of a delayed-egress electrically electrical locking system. Submitter Full Name: SAF-MEA Submittal Date: Tue Jun 21 15:40:13 EDT 2016 : The revision responds to CC Note 7.

8 9/20/2016 2:53 PM Second Revision No NFPA [ Section No ] * Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all of the following conditions are met: The locking means is approved. (1) The locking means can shall be capable of being engaged without opening the door. (2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key or tool, tool, or special knowledge or effort. (3) The unlocking and unlatching requires releasing mechanism shall open the door leaf with not more than one releasing operation. (4) The releasing mechanism for unlocking and unlatching means are mounted shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, can shall be unlocked unlockable from the classroom side of the door without the use of a key, tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room by staff with the necessary key or other credential. (7) The locking means does shall not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by , addresses shall address the use of the locking and unlocking means from within and outside the room. (10) Staff is drilled in the engagement and release of the locking means, from within and outside the room, as part of the emergency egress drills required by Supplemental Information File Name A docx Description Submitter Full Name: SAF-END Submittal Date: Tue Jul 26 13:56:33 EDT 2016 The supports the First Draft text with minor modifications as directed by the Correlating. During the First Draft, the section was inadvertantly added with no charging statement. A statement has been added to the front of the Section to clarify that classroom doors are permitted to be locked to prevent unwanted entry only if the locking means is approved and all of the criteria in the list are met. The committee used some of the changes as proposed in Public Comment No.183 as the basis for edits to the section. Numbered items were updated with the word "shall" for editorial correction. Text was added to clarify that the unlocking and unlatching operation in the classroom cannot require the use of key, tool, special knowledge or effort which is consistent with other locking and latching provisions in Chapter 7. A minimum height for the location of the releasing mechanism, consistent with Chapter 7, was added to ensure that the mechanism was not located on the floor or low on the door and the text was updated to clarify that it is the releasing mechanism that must be located within the 34-48" range. Item 7 has been updated to delete 'by staff' from the First Revision as it was too specific. It may not just be staff opening the door, it could be first responders for example. The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry and accepted the need that a second locking means may be needed for existing buildings. The multiple provisions proposed as part of / address the concerns for accomplishing door locking in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. Annex: While the Section is written to apply only to classroom doors, newly proposed Annex language explains to AHJs and

9 9/20/2016 2:53 PM facilities how the section may be useful in other areas of educational occupancies that may also need to be secured. Public Comment No. 183-NFPA [Section No ] Public Comment No. 20-NFPA [New Section after ]

10 A While Section establishes locking criteria for classroom doors only, there may be situations where a school s emergency action plan identifies other areas that may need to be secured. The provisions of this Section may be considered when evaluating those areas as well. Examples of those areas are administrative offices, gymnasiums, teacher lounges, libraries, auditoriums, and cafeterias.

11 9/20/2016 2:53 PM Second Revision No NFPA [ Section No ] * Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all of the following conditions are met: The locking means is approved. (1) The locking means can shall be capable of being engaged without opening the door. (2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key or tool, tool, or special knowledge or effort. (3) The unlocking and unlatching requires releasing mechanism shall open the door leaf with not more than two releasing operations. (4) The releasing mechanism for unlocking and unlatching means are mounted shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, can shall be unlocked unlockable from the classroom side of the door without the use of a key, tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room by staff with the necessary key or other credential. (7) The locking means does not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by , addresses shall address the use of the locking and unlocking means from within and outside the room. (10) Staff is drilled in the engagement and release of the locking means, from within and outside the room, as part of the emergency egress drills required by Supplemental Information File Name A docx _Terra_attachment.docx Description For staff use Submitter Full Name: SAF-END Submittal Date: Fri Jul 29 10:16:44 EDT 2016 The supports the First Draft text with minor modifications as directed by the Correlating. During the First Draft, the section was entertainingly added with no charging statement. A statement has been added to the front of the Section to clarify that classroom doors are permitted to be locked to prevent unwanted entry only if the locking means is approved and all of the criteria in the list are met. The committee used some of the changes as proposed in Public Comment No.185 as the basis for edits to the section. Numbered items were updated with the word "shall" for editorial correction. Text was added to clarify that the unlocking and unlatching operation in the classroom cannot require the use of key, tool, special knowledge or effort which is consistent with other locking and latching provisions in Chapter 7. A minimum height for the location of the releasing mechanism, consistent with Chapter 7, was added to ensure that the mechanism was not located on the floor or low on the door and the text was updated to clarify that it is the releasing mechanism that must be located within the 34-48" range. Item 7 has been updated to delete 'by staff' from the First Revision as it was too specific. It may not just be staff opening the door, it could be first responders for example. The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry and accepted the need that a second locking means may be needed for existing buildings. The multiple provisions proposed as part of / address the concerns for accomplishing door locking in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs.

12 9/20/2016 2:53 PM The proposed language supports a safe installation and necessary guidance for situations that are already occurring in existing buildings. The language is written so that it is done to protect occupants but also to ensure the door is operable for safe and quick egress during emergencies. There are currently close to 100,000 existing public school buildings across the country. Without this guidance, non-compliant, and dangerous, installations will continue to occur. Other protection measures are required and relied upon by the Code as part of a total life safety approach. The intent of Chapter 15 is to provide those other measures necessary to ensure that total protection approach. For example, it is critical to ensure the door can be unlocked and opened from outside the room so as to not impede the ability for authorized responders to enter the classroom. The language permits not more than two releasing operations, two releasing operations are not mandatory. It is ultimately up to the local AHJ to approve the locking arrangement. Approval of locking devices may depend on individual scenarios such as classroom use, occupant load, and staffing. The committee supports this as a package of requirements that, together, provide the necessary guidance needed for classroom door locking in existing educational occupancies. The recognizes that hardware does exists, and could be used, that allows two locking mechanisms/devices with one releasing action, such as residential hotel locks. The proposed language addresses the inevitable existing conditions that cannot utilize the "hotel locks." Annex: While the Section is written to apply only to classroom doors, newly proposed Annex language explains to AHJs and facilities how the section may be useful in other areas of educational occupancies that may also need to be secured. Public Comment No. 185-NFPA [Section No ] Public Comment No. 21-NFPA [New Section after ] Public Comment No. 121-NFPA [Section No ]

13 A While Section establishes locking criteria for classroom doors only, there may be situations where a school s emergency action plan identifies other areas that may need to be secured. The provisions of this Section may be considered when evaluating those areas as well. Examples of those areas are administrative offices, gymnasiums, teacher lounges, libraries, auditoriums, and cafeterias.

14 9/20/2016 2:53 PM Second Revision No NFPA [ New Section after ] Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key, tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than one releasing operation. (4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the classroom side of the door without the use of a key, tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by , shall address the use of the locking and unlocking means from within and outside the room. (10) Staff is drilled in the engagement and release of the locking means, from within and outside the room, as part of the emergency egress drills required by Submitter Full Name: SAF-END Submittal Date: Fri Jul 29 12:01:57 EDT 2016 The Workship on School Safety, Codes and Security - Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions provisions proposed are based on the provisions for locking classroom doors in educational occupancies. In addition to the reasons documented for allowing door locking in educational occupancies, the protection features are predicated on equal if not greater staffing found in day care occupancies.

15 1 9/20/2016 2:53 PM Second Revision No NFPA [ New Section after ] Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key, tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than two releasing operations. (4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the classroom side of the door without the use of a key, tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by , shall address the use of the locking and unlocking means from within and outside the room. (10) Staff is drilled in the engagement and release of the locking means, from within and outside the room, as part of the emergency egress drills required by Submitter Full Name: SAF-END Submittal Date: Fri Jul 29 12:30:40 EDT 2016 The Workshop on School Safety, Codes and Security - Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions provisions proposed are based on the provisions for locking classroom doors in educational occupancies. In addition to the reasons documented for allowing door locking in educational occupancies, the protection features are predicated on equal if not greater staffing found in day-care occupancies. The multiple provisions proposed as part of / address the concerns for accomplishing door locking in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. The proposed language supports a safe installation and necessary guidance for situations that are already occurring in existing buildings. The language is written so that it is done to protect occupants but also to ensure the door is operable for safe and quick egress during emergencies. Without this guidance, non-compliant, and dangerous, installations will continue to occur. Other protection measures are required and relied upon by the Code as part of a total life safety approach. The intent of Chapter 17 is to provide those other measures necessary to ensure that total protection approach. For example, it is critical to ensure the door can be unlocked and opened from outside the room so as to not impede the ability for authorized responders to enter the day-care classroom. The language permits not more than two releasing operations, two releasing operations are not mandatory. It is ultimately up to the local AHJ to approve the locking arrangement. Approval of locking devices may depend on individual scenarios such as classroom use, occupant load, and staffing. The committee supports this as a package of requirements that, together, provide the necessary guidance needed for classroom door locking in existing day-care occupancies. The recognizes that hardware does exists, and could be used, that allows two locking mechanisms/devices with one releasing action, such as residential hotel locks. The proposed language addresses the inevitable existing conditions that cannot utilize the "hotel locks."

16 2 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] * Door Locking to Prevent Unwanted Entry. Where approved, doors, other than those complying with , shall be permitted to be locked to prevent unwanted entry provided that all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, a tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than one releasing operation. (4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, a tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means does not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80. Supplemental Information File Name A docx Description Submitter Full Name: SAF-MER Submittal Date: Mon Aug 01 11:34:45 EDT 2016 The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions proposed as part of 38/ cover the concerns for accomplishing door locking in business occupancies, such as those buildings on college and university campuses, in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. While the provisions are written to apply to doors in business occupancies, the annex text clarifies the intent of this section is to apply only to doors where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces. There have been recent events where security has been an issue in both office buildings and well as educational settings where both uses could benefit from the security offered from this proposed text. Public Comment No. 190-NFPA [New Section after ]

17 A The intent of this section is to apply only where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces.

18 5 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] * Door Locking to Prevent Unwanted Entry. Where approved, doors, other than those complying with , shall be permitted to be locked to prevent unwanted entry provided that all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, a tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than one releasing operation. (4) For existing doors, the releasing mechanism shall open the door leaf with not more than two releasing operations. (5) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (6) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, a tool, or special knowledge or effort. (7) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (8) The locking means does not modify the door closer, panic hardware, or fire exit hardware. (9) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80. Supplemental Information File Name A docx Description Submitter Full Name: SAF-MER Submittal Date: Mon Aug 01 11:37:55 EDT 2016 The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions proposed as part of 38/ cover the concerns for accomplishing door locking in business occupancies, such as those buildings on college and university campuses, in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. While the provisions are written to apply to doors in business occupancies, the annex text clarifies the intent of this section is to apply only to doors where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces. There have been recent events where security has been an issue in both office buildings and well as educational settings where both uses could benefit from the security offered from this proposed text. For existing doors, it is permitted that the releasing mechanism can open the door with not more than two releasing operations. The proposed language supports a safe installation and necessary guidance for situations that are already occurring in existing buildings. The language is written so that it is done to protect occupants but also to ensure door is operable for safe and quick egress during emergencies. The recognizes that hardware does exists, and could be used, that allows two locking mechanisms/devices with one releasing action, such as residential hotel locks. The proposed language addresses the inevitable existing conditions that cannot utilize the "hotel locks." Public Comment No. 192-NFPA [New Section after ]

19 A The intent of this section is to apply only where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces.

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 47 10/21/2015 9:37 AM First Revision No. 5041-NFPA 101-2015 [ Global Input ] Throughout the document, change electrically controlled egress door assemblies to door hardware-release of electrically locked

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA This report is provided for information only. BMHA is not asking for Adhoc Health Care to sponser as

More information

Effective Messaging on School Door Locking

Effective Messaging on School Door Locking 2017 NFPA Conference & Expo Effective Messaging on School Door Locking Ron Coté, P.E. NFPA At the conclusion of this program participants will be able to: 1. Understand the conflicting needs of security

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/28/2015 10:41 AM First Revision No. 6036-NFPA 5000-2015 [ Global Input ] Throughout the document, change door electrically controlled egress door assemblies to hardware-release of electrically

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Page 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M,

More information

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Position Statement Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Maintaining school safety in light of recent terrorist events is challenging for everyone,

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

BCAC Egress Work Group

BCAC Egress Work Group 2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. BCAC item E-17.1 E?? 15 1006.2.1, 1006.3 1006.2.1 Egress based on occupant load and common path of egress travel distance.

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

NFPA 80 Overview January 21, 2016

NFPA 80 Overview January 21, 2016 NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

Page 1 of 10 Second Revision No. 8-NFPA 600-2014 [ Section No. 3.3.17 ] 3.3.17* Incident Management System (IMS). A system that defines the roles and responsibilities to be assumed by responders and the

More information

Enhancing K-12 Security

Enhancing K-12 Security The official publication of ALOA SPAI, an international association of security professionals October 2016 SECURING YOUR SUCCESS Enhancing K-12 Security Recent code proposals may shake up safety practices

More information

About the Instructor & Presenter:

About the Instructor & Presenter: About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

E25 (D) Automatic controls for general means of egress lighting

E25 (D) Automatic controls for general means of egress lighting Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

Fire and Smoke Door Inspections Qualified Training 02/03/17

Fire and Smoke Door Inspections Qualified Training 02/03/17 Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance

More information

ICC code change proposals are being reviewed, evaluated, prioritized, and desired results determined by the BHMA Task Group working on the proposals.

ICC code change proposals are being reviewed, evaluated, prioritized, and desired results determined by the BHMA Task Group working on the proposals. BHMA ICC Code Proposals John Woestman, March 23, 2015 ICC code change proposals are being reviewed, evaluated, prioritized, and desired results determined by the BHMA Task Group working on the proposals.

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment of 25 5/14/2015 2:32 PM Public Comment No. 22-NFPA 14-2014 [ New Section after 1.4 ] A.1.4 A.1.4 It is the intent of the Commi ee to recognize that future edi ons of this standard are a further refinement

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS The York County Department of Fire Safety reviews all commercial building plan submittals for compliance with the 2015 International

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work. 3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;

More information

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification First Correlating Revision No. 3-NFPA 101-2016 [ Section No. 6.1.8.1.1 ] 6.1.8.1.1* Definition One- and Two-Family Dwelling Unit. A building that contains not more than two dwelling units, with independent

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Second Revision No. 2-NFPA [ Section No ]

Second Revision No. 2-NFPA [ Section No ] Page 1 of 8 Second Revision No. 2-NFPA 410-2014 [ Section No. 10.2 ] 10.2* Fire Extinguishers. In addition to extinguishers required by NFPA 409, extinguishers shall be provided for aircraft maintenance

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM 3 of 326 11/21/2013 1:03 PM First Revision No. 88-NFPA 72-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2011 2014 edition. NFPA 96, Standard

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

Safety Tips for the Office

Safety Tips for the Office Safety Tips for the Office An office fire can be devastating - resulting in business interruption or permanent closure, loss of lives, jobs, property and information. Offices are loaded with combustible

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Second Revision No. 102-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement

Second Revision No. 102-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement of 1 9/22/2014 12:54 PM Second Revision No. 102-NFPA 72-2014 [ Global Comment ] 10.12.2 Visible notification appliances, textual visible notification appliances, and speaker notification appliances located

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

1 of 4 10/26/2015 1:58 PM. Committee Input No NFPA [ Section No ]

1 of 4 10/26/2015 1:58 PM. Committee Input No NFPA [ Section No ] National Protection Association Report http://submittals.nfpa.org/terraviewweb/formlaunch?id=/terraview/c... 1 of 4 10/26/2015 1:58 PM Committee Input No. 3514-NFPA 5000-2015 [ Section No. 8.7.2 ] National

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance 2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information