1 Agenda Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems (SIG-NAS) First Draft Meeting Salt Lake City, UT July 25-26, 2016 Item Call to Order Item Roll Call and Introductions Item Approval of Meeting Agenda Item Approval of Meeting Minutes Item Staff/Chair Remarks Item Task Group Reports Item Public Inputs, Committee Inputs and First Revisions Item Old Business Item New Business Item Review Dates and Times for Future Meetings/Conference Calls Item Adjournment and Closing Remarks

2 NFPA 72 Second Draft Meeting Minutes Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems June 27, 2014 La Jolla, CA (& Telephone/WEB Conference) Call to Order The meeting of the SIG-NAS committee was called to order by chair, David Lowrey promptly at 8:04 AM PST Roll Call For a list of committee member s present or in attendance via telephone/web conference see the attachment Approval of Agenda Agenda was approved Approval Meeting Minutes June 2013 A task group was missed in the minutes titled Indirect Detection of Notification Appliances Members include Chair Robert Accosta, Members Leon Newsome, David Lowery, Doug Kline, Robert Schifiliti, Morris Toporek, David Newhouse, Daniel Grosch -- minutes approved with noted correction Staff Remarks & Using the New Process NFPA procedures and Roberts Rule of Law were reviewed. Opening comments by Barry Chase who also review the process timeline and terminology used in the process. Review of allowable committee actions on proposals and procedures were also reviewed Task Group Reports Chair Robert Accosta of the Indirect Detection of Notification Appliances task group updated the committee on its activity. No consensus has been reached at this time concerning flash durations and indirect viewing Public Comments and Second Revisions Committee deliberation and action on public comments. The committee heard from Leon Newsome, Director Product Compliance of Eaton (Cooper Notification Solutions) concerning research data on strobe output.

3 Other Business Adjournment A motion was made and seconded to adjourned at 6/27/ :48 PM PST. David Lowrey, Committee Chair SIG-NAS, thanked the committee members for their participation. Submitted by: David E. Becker, Principal

4

5

6

7 1 of /30/ :10 AM Public Input No. 210-NFPA [ Global Input ] Rewrite the "Exception" text throughout NFPA 72 and replace with standard subsection text. NFPA 72 contains numerous sections that are written with "Exception" text. This is inconsistent the direction provided in the Manual of Style and should be corrected. Differing types of style that are inconsistent with the MOS create confusion as the proper application of the code by the end user. As an example, is currently written with an "exception" as follows: "10.4.4* In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervising station transmitting equipment to provide notification of fire at that location. Exception: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted." This section could easily be rewritten to be consistent with the MOS in the following manner with the exception becoming core text in a subsection modifying : * In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervising station transmitting equipment to provide notification of fire at that location Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. The above is just one example but applies throughout to all "exception" text in NFPA 72. Submitter Full Name: Anthony Apfelbeck Organization: Altamonte Springs Building/Fire Safety Division Submittal Date: Thu May 19 08:52:10 EDT 2016

8 2 of /30/ :10 AM Public Input No. 335-NFPA [ Global Input ] Replace the terms Fire Alarm Control Panel and FACP through the document (including all diagrams) with the terms Fire Alarm Control Unit and FACU respectively. The terms Fire Alarm Control Panel and FACP are not defined in the code. The terms Fire Alarm Control Unit and FACU are defined in section * Submitter Full Name: Daniel Gauvin Organization: Tyco Fire Suppression and Building Products Submittal Date: Mon Jun 13 09:10:07 EDT 2016

9 4 of /30/ :10 AM Public Input No. 428-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value lumens/ft2 Is used the metric equivalent shall be lumens/m2 This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Thu Jun 23 11:23:21 EDT 2016

10 7 of /30/ :10 AM Public Input No. 560-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 1 Foot Is used the metric equivalent shall be 0.3 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 14:31:18 EDT 2016

11 11 of /30/ :10 AM Public Input No. 566-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 15 feet Is used the metric equivalent shall be 4.6 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 15:00:46 EDT 2016

12 12 of /30/ :10 AM Public Input No. 567-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 16 feet Is used the metric equivalent shall be 4.9 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 15:06:27 EDT 2016

13 13 of /30/ :10 AM Public Input No. 568-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 16.5 feet Is used the metric equivalent shall be 5.0 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 15:09:11 EDT 2016

14 16 of /30/ :10 AM Public Input No. 574-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 20 feet Is used the metric equivalent shall be 6.1 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 15:23:29 EDT 2016

15 17 of /30/ :10 AM Public Input No. 575-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 21 feet Is used the metric equivalent shall be 6.4 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 15:32:00 EDT 2016

16 24 of /30/ :10 AM Public Input No. 585-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 30 feet Is used the metric equivalent shall be 9.1 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Tue Jun 28 16:07:33 EDT 2016

17 32 of /30/ :10 AM Public Input No. 692-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapters 18, 26, 29 or its annexes that the value 50 feet Is used the metric equivalent shall be 15.2 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Wed Jun 29 14:29:30 EDT 2016

18 34 of /30/ :10 AM Public Input No. 697-NFPA [ Global Input ] The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the following Global Input, Any place in the body of Chapter 18 or its annex that the value 6 feet Is used the metric equivalent shall be 1.8 m This Task Group was established to provide conversion values from inch-pound units to Metric units in a consistent manner throughout the document. This will establish a baseline value for the use of each unit of measurement to provide consistency. Submitter Full Thomas Parrish Name: Organization: Telgian Corporation NFPA SIG-AAC Metric Task Group, Tom Parrish, A. M. Fred Leber, Affilliation: and Jeffery G. Van Keuren Submittal Date: Wed Jun 29 14:37:07 EDT 2016

19 47 of /30/ :10 AM Public Input No. 2-NFPA [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this Code and shall be considered part of the requirements of this document. 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA NFPA 10, Standard for Portable Fire Extinguishers, 2013 edition. NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2014 edition. NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 2015 edition. NFPA 70, National Electrical Code, 2014 edition. NFPA 75, Standard for the Fire Protection of Information Technology Equipment, 2016 edition. NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2015 edition. NFPA 101, Life Safety Code, 2015 edition. NFPA 110, Standard for Emergency and Standby Power Systems, 2016 edition. NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems, 2016 edition. NFPA 170, Standard for Fire Safety and Emergency Symbols, 2015 edition. NFPA 601, Standard for Security Services in Fire Loss Prevention, 2015 edition. NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, 2015 edition. NFPA 1031, Standard for Professional Qualifications for Fire Inspector and Plan Examiner, 2014 edition. NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems, 2016 edition. NFPA 1600, Standard on Disaster/Emergency Management and Business Continuity Programs, 2013 edition. NFPA 1620, Standard for Pre-Incident Planning, 2015 edition. 2.3 Other Publications.

20 48 of /30/ :10 AM ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY ANSI A-58.1, Building Code Requirements for Minimum Design Loads in Buildings and Other Structures. (Superseded by ASCE 7) ANSI S1.4a, Specifications for Sound Level Meters, 1985, reaffirmed (Superseded by ANSI/ASA S1.4 Part 3) ANSI /ASA S1.4 Part 3/IEC , Electroacoustics-Sound Level Meters - Periodic Tests, ANSI /ASA S3.41, American National Standard Audible Emergency Evacuation Signal, 1990, reaffirmed 2008.ANSI/ ASCE Publications. American Society Of Civil Engineers, 1801 Alexander Bell Drive, Reston, VA ASCE 7-10, Minimum Design Loads for Buildings and Other Structures, 2010, Supplement 1 and revised commentary, ASME Publications. ASME A17.1/CSA B44 13, Safety Code for Elevators and Escalators, ANSI/IEEE EIA Publications. Electronic Industries Alliance, 2500 Wilson Boulevard, Arlington, VA EIA Tr 41.3, Telephones IEEE Publications. IEEE, 449 and 501 Hoes Lane, Piscataway, NJ IEEE C2, National Electrical Safety Code, 2007.ANSI/TIA IMSA Publication. International Municipal Signal Association, 597 Haverty Court, Suite 100, Rockledge, FL IMSA Official Wire and Cable Specifications, ISO Publications. International Organization for Standardization, ISO Central Secretariat, Chemen de Blandonnet 8, CP 401, 1214 Vernier, Geneva Switzerland. ISO 7731, Danger signals for public and work places Auditory danger signals, Telcordia Publications. Telcordia Technologies, One Telcordia Drive, Piscataway, NJ GR-506-CORE, LATA Switching Systems Generic Requirements: Signaling for Analog Interface, GR-909-CORE, Fiber in the Loop Systems Generic Requirements, 2004.

21 49 of /30/ :10 AM TIA Publications. Telecommunications Industry Association, 1320 North Courthouse Road, Suite 200, Arlington, VA TIA -568-C.3, Optical Fiber Cabling Components Standard, June 2008, Addendum 1, ANSI/ UL Publications. Underwriters Laboratory, 333 Pfingsten Road, Northbrook, IL UL 217, Standard for Single and Multiple Station Smoke Alarms, 6th 8 th edition, 2006, revised ANSI/ UL 268, Standard for Smoke Detectors for Fire Alarm Systems, 6th edition, ANSI/ UL 827, Standard for Central-Station Alarm Services, 7th 8 th edition, , revised ANSI/ UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th 10 th edition, 2003, revised ANSI/ UL 985, Standard for Household Fire Warning System Units, 5th 6 th edition, 2000, revised ANSI/ UL 1638, Visual Signaling Appliances Private Mode Emergency and General Utility Signaling, 4th edition, 2001, revised ANSI/ UL 1730, Standard for Smoke Detector Monitors and Accessories for Individual Living Units of Multifamily Residences and Hotel/Motel Rooms, 4th edition, 2006, revised ANSI/ UL 1971, Standard for Signaling Devices for the Hearing Impaired, 3rd edition, 2002, revised 2013.

22 50 of /30/ :10 AM ANSI/ UL 1981, Central Station Automation Systems, 2nd 3rd edition, , revised ANSI/ UL 2017, Standard for General-Purpose Signaling Devices and Systems, 2nd edition, 2008, revised ANSI/ UL 2572, Mass Notification Systems, 1st edition, 2011, revised ANSI/ UL 60950, Information Technology Equipment Safety Part 1: General Requirements, 2nd edition, 2007, revised EIA Publications. Electronic Industries Alliance, 2500 Wilson Boulevard, Arlington, VA EIA Tr 41.3, Telephones IMSA Publication. International Municipal Signal Association, 165 East Union Street, Newark, NY IMSA Official Wire and Cable Specifications, ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211 Geneva 20, Switzerland. ISO 7731, Danger signals for public and work places Auditory danger signals, 2003 (reconfirmed 2009) Telcordia Publications. Telcordia Technologies, One Telcordia Drive, Piscataway, NJ GR-506-CORE, LATA Switching Systems Generic Requirements: Signaling for Analog Interface, GR-909-CORE, Fiber in the Loop Systems Generic Requirements, Other Publications. Merriam-Webster s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

23 51 of /30/ :10 AM 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2014 edition. NFPA 101, Life Safety Code, 2015 edition. NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, 2013 edition. NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, 2015 edition. NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems, 2016 edition. NFPA 5000, Building Construction and Safety Code, 2015 edition. Referenced current SDO names, addresses, standard names, numbers, and editions. Related Public Inputs for This Document Related Input Public Input No. 3-NFPA [Chapter H] Relationship Submitter Full Name: Aaron Adamczyk Organization: [ Not Specified ] Submittal Date: Mon Dec 21 17:16:12 EST 2015

24 54 of /30/ :10 AM Public Input No. 664-NFPA [ New Section after 2.3 ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 217, Standard for Single and Multiple Station Smoke Alarms, 6th edition, 2006, revised ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems, 6th edition, ANSI/UL 827, Standard for Central-Station Alarm Services, 7th edition, 2008, revised ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th edition, 2003, revised ANSI/UL 985, Standard for Household Fire Warning System Units, 5th edition, 2000, revised ANSI/UL 1638, Visual Signaling Appliances Private Mode Emergency and General Utility Signaling, 4th edition, 2001, revised ANSI/UL 1730, Standard for Smoke Detector Monitors and Accessories for Individual Living Units of Multifamily Residences and Hotel/Motel Rooms, 4th edition, 2006, revised ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, 3rd edition, 2002, revised ANSI/UL 1981, Central Station Automation Systems, 2nd edition, 2003, revised ANSI/UL 2017, Standard for General-Purpose Signaling Devices and Systems, 2nd edition, 2008, revised ANSI/UL 2572, Mass Notification Systems, 1st edition, 2011, revised ANSI/UL 60950, Information Technology Equipment Safety Part 1: General Requirements, 2nd edition, 2007, revised This proposal merely moves UL standards from Section ANSI Publications to a new Section titled UL Publications. Other NFPA codes such as NFPA 101, 13, etc. treat UL referenced standards in this same manner. The move will make it easier for code users to locate UL referenced standards. Assume existing Section will be renumbered In separate public inputs we proposed updates to UL referenced standards, and introduced new referenced standards. If those changes are accepted they should be relocated to this section. Also assume staff can delete these ANSI/UL standards are deleted from Section Submitter Full Name: Howard Hopper Organization: UL LLC Submittal Date: Wed Jun 29 12:20:57 EDT 2016

25 60 of /30/ :10 AM Public Input No. 552-NFPA [ Section No ] ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY ANSI A-58.1, Building Code Requirements for Minimum Design Loads in Buildings and Other Structures. ANSI S1.4a, Specifications for Sound Level Meters, 1985, reaffirmed ANSI S3.41, American National Standard Audible Emergency Evacuation Signal, 1990, reaffirmed ANSI/ASME A17.1/CSA B44 13, Safety Code for Elevators and Escalators, ANSI/IEEE C2, National Electrical Safety Code, ANSI/TIA-568-C.3, Optical Fiber Cabling Components Standard, June ANSI/UL 217, Standard for Single and Multiple Station Smoke Alarms, 6th edition, 2006, revised ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems, 6th edition, ANSI/UL 827, Standard for Central-Station Alarm Services, 7th edition, 2008, revised ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th edition, 2003, revised ANSI/UL 985, Standard for Household Fire Warning System Units, 5th edition, 2000, revised ANSI/UL 1638, Visual Signaling Appliances Private Mode Emergency and General Utility Signaling, 4th edition, 2001, revised ANSI/UL 1730, Standard for Smoke Detector Monitors and Accessories for Individual Living Units of Multifamily Residences and Hotel/Motel Rooms, 4th edition, 2006, revised ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, 3rd edition, 2002, revised ANSI/UL 1981, Central Station Automation Systems, 2nd edition, 2003, revised ANSI/UL 2017, Standard for General-Purpose Signaling Devices and Systems, 2nd edition, 2008, revised ANSI/UL 2572, Mass Notification Systems, 1st edition, 2011, revised ANSI/UL 60950, Information Technology Equipment Safety Part 1: General Requirements, 2nd edition, 2007, revised The deleted UL Standards should be removed from this section and placed under a separate section in Referenced Publications for UL Standards. Submitter Full Name: Ronald Farr Organization: UL LLC Submittal Date: Tue Jun 28 12:47:13 EDT 2016

26 65 of /30/ :10 AM Public Input No. 555-NFPA [ New Section after 2.4 ] TITLE OF NEW CONTENT Add New Section 2.?.? UL Publications Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 217, Standard for Single and Multiple Station Smoke Alarms, 8th edition, 2006, revised ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems, 7th edition, ANSI/UL 827, Standard for Central-Station Alarm Services, 8th edition, 2008, revised ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 10th edition, 2003, revised ANSI/UL 985, Standard for Household Fire Warning System Units, 6th edition, 2000, revised ANSI/UL 1638, Visual Signaling Appliances Private Mode Emergency and General Utility Signaling, 5th edition, 2001, revised ANSI/UL 1730, Standard for Smoke Detector Monitors and Accessories for Individual Living Units of Multifamily Residences and Hotel/Motel Rooms, 4th edition, 2006, revised ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, 3rd edition, 2002, revised ANSI/UL 1981, Central Station Automation Systems, 3rd edition, 2003, revised ANSI/UL 2017, Standard for General-Purpose Signaling Devices and Systems, 2nd edition, 2008, revised ANSI/UL 2572, Mass Notification Systems, 2nd edition, 2011, revised ANSI/UL 60950, Information Technology Equipment Safety Part 1: General Requirements, 3rd edition, 2007, revised This proposal requests to add a new section in Referenced Publications and places those UL Standards that were removed from (PI 552) under a separate section identified as UL Publications and also updates the referenced standards to the current editions. Submitter Full Name: Ronald Farr Organization: UL LLC Submittal Date: Tue Jun 28 12:52:13 EDT 2016

27 66 of /30/ :10 AM Public Input No. 513-NFPA [ New Section after 3.2 ] Enforcing Authority Definition 3.2.x Enforcing Authority: An agency or an organization that promulgates and/or enforces standards who has been given these responsibilities and powers by federal, state or local governmental laws. A.3.2.x Enforcing Authority. An enforcing authority may also be an authority having jurisdiction (AHJ). The enforcing authority may be an individual within the agency or organization assigned to carry out the duties and responsibilities of the enforcing authorities including developing regulations supported by the enforcing authority. This work is the results of a task group consisting of Lynn Nielson (chair), Art Black, Andrew Berezowski, Warren Olsen and Rodger Reiswig. Several cycles ago, the TCC at the time use of the term Enforcing Authority, where appropriate, to differentiate between an AHJ - who can be any entity responsible for approving something, including an owner - and the AHJ (Enforcing Authority) who has a legal or governmental responsibility for enforcing NFPA 72. This work is In accordance with the NFPA MOS. "Multiple Meanings. All words and terms used in NFPA documents that could be used, understood, or interpreted in more than one way shall be defined in the definitions chapter". This term is used in the following sections: ; ; ; ; ; ; Submitter Full Name: Lynn Nielson Organization: City Of Henderson Affilliation: Self (However, this PI is the result of a task group) Submittal Date: Mon Jun 27 12:56:48 EDT 2016

28 100 of /30/ :10 AM Public Input No. 186-NFPA [ Section No [Excluding any Sub-Sections] ] A fire alarm system component such as a bell, horn, speaker Textual Audible Notification Appliance, light, or text display that provides audible, tactile, or visible outputs, or any combination thereof. (SIG-NAS) As part of the CC TG on terms, the term "Speaker" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to a person. In this section the term is for an appliance and the proper term "Textual Audible Notification Appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed May 18 07:50:06 EDT 2016

29 101 of /30/ :10 AM Public Input No. 624-NFPA [ Section No ] Visible Visual Notification Appliance. A notification appliance that alerts by the sense of sight. (SIG-NAS) * Textual Visible Notification Appliance. A notification appliance that conveys a stream of visible information that displays an alphanumeric or pictorial message. (SIG-NAS) The term Visible Notification Appliance is used a total of 85 times in the 2016 edition of NFPA 72, the first of which is in It is used 3 times in the Origin and Development of NFPA 72, 47 times in the body of the Code, and 35 times in the Annex of the Code. Additionally, the term Visible Notification (without the term appliance ) is used 19 times in the body and Annex of the Code. The term Visual Notification Appliance is used a total of 4 times in the 2016 edition of NFPA 72, once in the body of the code at (3) and 3 times in the Annex of the Code. Additionally, the term Visual Notification is used once in the Annex of the Code (A ). This proposal seeks to change and standardize on the term Visual Notification Appliance or Visual Notification throughout the body and Annex of the Code (all 104 uses). The term visible is defined by Merriam-Webster as able to be seen or know to or noticed by the public. The term visual is defined by Merriam-Webster as relating to seeing or to the eyes. As such the term visual is much more accurate in the defining the purpose and action of an appliance that alerts by the sense of sight. By definition, a visible device must be seen. The opposite of visible is invisible, whereas the opposite of visual is audible; since there is no such thing as an invisible device, the term visual is much more appropriate as compared to audible devices in the Code. Currently, these terms are used somewhat interchangeably and this proposal seeks to standardize on just one term. This standardization on the term Visual Notification Appliance becomes more significant considering other Public Inputs being proposed by the UL STP Task Group on Indirect Viewing of Visual Signals. This task group is defining the terms direct visual alerting and indirect visual alerting, which is by nature defining whether a visual device is directly visible or not; therefore, the term Visible Notification Appliance would no longer be accurate if such proposals are approved. In other words, it is possible to provide alerting through the use of a Visual Notification Appliance that is not visible via the use of reflected light (i.e., indirect viewing). It should be noted that the term Textual Visible Notification Appliance is used a total of 7 times in the 2016 edition of NFPA 72, the first of which is in It is used 5 times in the body of the Code and 2 times in the Annex of the Code. This public input does not seek to change the use of this term as a Textual Visible Notification Appliance, such as an annunciator, monitor, CRT, display or printer, must be visible to be understood. Alerting with these devices requires the appliance to be visible, although in the strictest sense of the term they are by nature a visual device. As such, the technical committee may want to consider the adjustment of this term to be consistent with all other visual notification appliances. Submitter Full Name: Larry Rietz Organization: JENSEN HUGHES Affilliation: Self Submittal Date: Tue Jun 28 23:33:17 EDT 2016

30 113 of /30/ :10 AM Public Input No. 724-NFPA [ Section No ] The requirements of Chapters 10, 12, 14, 17, 18, 21, 23, 24, 26, and 27 shall apply unless otherwise noted in this chapter. if PI 722 is accepted this is redundant information and would not be required, this can lead to confusion and is additional non-required test that is not enforceable as code language. Related Public Inputs for This Document Related Input Public Input No. 722-NFPA [New Section after 1.3.4] Relationship would replace this code section Submitter Full Name: Thomas Parrish Organization: Telgian Corporation Submittal Date: Wed Jun 29 15:48:44 EDT 2016

31 130 of /30/ :10 AM Public Input No. 263-NFPA [ Section No ] Performance-based design alternatives for strobe visible notification appliance design shall be in accordance with As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:38:06 EDT 2016

32 131 of /30/ :10 AM Public Input No. 264-NFPA [ Section No ] Performance-based design documentation for strobes visible notification appliances shall be in accordance with (SIG-NAS) As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:42:17 EDT 2016

33 743 of /30/ :10 AM Public Input No. 729-NFPA [ Section No ] The requirements of Chapters 10, 14, 23, and 24 shall apply to the interconnection of notification appliances, the control configurations, the power supplies, and the use of the information provided by notification appliances. if PI 722 is accepted this is redundant information and would not be required, this can lead to confusion and is additional non-required test that is not enforceable as code language. Related Public Inputs for This Document Related Input Relationship Public Input No. 722-NFPA [New Section after 1.3.4] would relocate these requirement to ch 1 Submitter Full Name: Thomas Parrish Organization: Telgian Corporation Submittal Date: Wed Jun 29 15:54:51 EDT 2016

34 744 of /30/ :10 AM Public Input No. 712-NFPA [ New Section after ] Voltage Drop Calculations Voltage drop calculations shall be performed using one of the following methods: (1) The lump sum calculation method, which shall be calculated as follows: (a) Calculate the voltage drop using one of these formulas: i. VD = I * ((R * 2 * L)/1,000) OR ii. VD = (2 * K * I * L)/CM. (b) Subtract this calculated voltage drop from 20.4 volts (VS) in order to get the voltage value at the end of the circuit (VS VD = VEOL). The value for VEOL shall be a minimum of 16 volts (the minimum operating voltage required for a listed 24 vdc notification device). (2) The point-to point method, which requires a math-intensive approach where the voltage drop between each notification appliance is reiterated. This method is best done by utilizing a spreadsheet program. The calculated voltage at the last device on the circuit shall be a minimum of 16 volts (the minimum operating voltage required for a listed 24 vdc notification device). Where: VD = Voltage Drop VS = Starting voltage (20.4vdc, or the end of useful battery life) VEOL = Voltage at the end-of-line resistor I =Total load of the circuit in amperes utilizing current draws for each notification 16vdc (the UL maximum draws at the minimum listed voltage). R = Resistance in ohms per 1,000 feet, with respect to conductor K = ohms (the constant representing the mil-foot resistance of copper wire) L = length of circuit in feet (distance from panel to end-of-line resistor for class B circuits) CM = circular mill of wire, with respect to conductor. VSOURCE = voltage calculated at the previous device (3) Other methods acceptable to the authority having jurisdiction such as the center-load calculation method. This is intended to standardize the way in which designers calculate voltage drops for notification circuits. The methods shown on this proposal in calculating voltage drops are consistent with the methods described in the narrative of the NFPA 72 Fire Alarm Code Handbook. The base code for NFPA 72 does not provide guidance with regards to the methods to use when calculating voltage drops. Submitter Full Name: Lynn Nielson Organization: City Of Henderson Affilliation: Self

35 745 of /30/ :10 AM Submittal Date: Wed Jun 29 14:58:13 EDT 2016

36 746 of /30/ :10 AM Public Input No. 440-NFPA [ New Section after ] Notification appliances used for fire signaling only shall have the word "FIRE", stamped, imprinted, etc. on the appliance and be visible to the public. Notification appliances with multiple visible elements shall be required to have fire markings only on those visible elements used for fire signaling. In the current section, it is not clear if the intent of NFPA 72 is to allow strobes used for fire signaling only to not have the word "FIRE" stamped or imprinted on them. The intent of this proposal is to ensure that visible appliances used for fire signaling only should be identified as such. It will provide the building occupants better understanding of the specific emergency (rather than having non-marked visual appliances) Submitter Full Name: Sagiv Weiss-Ishai Organization: San Francisco Fire Department Affilliation: SFFD Submittal Date: Thu Jun 23 16:17:07 EDT 2016

37 747 of /30/ :10 AM Public Input No. 477-NFPA [ New Section after 18.4 ] Add new Section and renumber subsequent paragraphs Distinctive Carbon Monoxide Alarm Signal When a Carbon Monoxide sensor or alarm is required by other codes or standards or by the Authority Having Jurisdiction, a distinctive alarm signal pattern is required that is different from a fire evacuation signal The audible carbon monoxide alarm signal shall be a four-pulse temporal pattern and comply with the following: (1) Signals shall be a pattern consisting of four cycles of 100 milliseconds ± 10 percent on and 100 milliseconds ± 10 percent off, followed by 5 seconds ± 10 percent off. (2) After the initial 4 minutes of alarm, the 5-second off time shall be permitted to be changed to 60 seconds ± 10 percent. (3) The alarm signal shall be repeated in compliance with (1) and (2) until the alarm resets or the alarm signal is manually silenced The audible alarm signal shall be synchronized within a notification zone. With the dissolution of NFPA 720 as a separate standard, the submitter recommends that the distinctive alarm tone for a Carbon Monoxide alarm be included in Chapter 18 in a similar fashion to the distinctive fire alarm evacuation tone. Note to staff: When I submitted this PI, Terra View said "add a new section after This should be the new and all subsequent paragraphs renumbered. Submitter Full Name: Thomas Hammerberg Organization: Automatic Fire Alarm Association Affilliation: Automatic Fire Alarm Association Submittal Date: Mon Jun 27 09:02:34 EDT 2016

38 748 of /30/ :10 AM Public Input No. 123-NFPA [ Section No ] * Sound from normal or permanent sources, having a duration greater than of at least 60 seconds, shall be included when measuring maximum ambient sound level. Sound from temporary or abnormal sources shall not be required to be included when measuring maximum ambient sound level. The wording, "greater than 60" used in this section does not correlate the wording "of at least 60" used in sections , , , , and Submitter Full Name: Lynn Nielson Organization: City Of Henderson Submittal Date: Tue Apr 12 16:07:28 EDT 2016

39 749 of /30/ :10 AM Public Input No. 121-NFPA [ Section No ] Distinctive Evacuation Signal * To meet the requirements of Section 10.10, the alarm audible signal pattern used to notify building occupants of the need to evacuate (leave the building) or relocate (from one area to another) shall be the standard alarm evacuation signal consisting of a three-pulse temporal pattern. The pattern shall be in accordance with Figure and shall consist of the following in this order: (1) On phase lasting 0.5 second ±10 percent (2) Off phase lasting 0.5 second ±10 percent for three successive on periods (3) Off phase lasting 1.5 seconds ±10 percent Figure 18. ANSI/ASA S This Figure Temporal 1 - Temporal Pattern Parameters. should also be deleted Exception: Where approved by the authority having jurisdiction, continued use of the existing consistent evacuation signaling scheme shall be permitted A single-stroke bell or chime sounded at on intervals lasting 1 second ±10 percent, with a 2-second ±10 percent off interval after each third on stroke, shall be permitted The signal shall be repeated for a period appropriate for the purposes of evacuation of the building, but for not less than 180 seconds The minimum repetition time shall be permitted to be manually interrupted The minimum repetition time shall be permitted to be automatically interrupted for the transmission of mass notification messages in accordance with Chapter * The standard evacuation signal shall be synchronized within a notification zone.

40 750 of /30/ :10 AM ANSI/ASA was revised in 2015 to reflect the evacuation and relocation audible signaling requirements required by NFPA 72. This is the referenced standard and it should be used directly since it more completely addresses the temporal pattern specifications. Please note that FIGURE was not able to be deleted as part of the revision to this section. Submitter Full Name: Vince Baclawski Organization: Nema Submittal Date: Thu Apr 07 14:04:06 EDT 2016

41 751 of /30/ :10 AM Public Input No. 562-NFPA [ Section No ] Distinctive Evacuation Signal * To meet the requirements of Section 10.10, the alarm audible signal pattern used to notify building occupants of the need to evacuate (leave the building) or relocate (from one area to another) shall be the standard alarm evacuation signal consisting of a three-pulse temporal pattern. The pattern shall be in accordance with Figure and shall consist of the following in this order: (1) On phase lasting 0.5 second ±10 percent (2) Off phase lasting 0.5 second ±10 percent for three successive on periods (3) Off phase lasting 1.5 seconds ±10 percent Figure Temporal Pattern Parameters. Exception: Where approved by the authority having jurisdiction, continued use of the existing consistent evacuation signaling scheme shall be permitted A single-stroke bell or chime sounded at on intervals lasting 1 second ±10 percent, with a 2-second ±10 percent off interval after each third on stroke, shall be permitted ANSI/ASA S The signal shall be repeated for a period appropriate for the purposes of evacuation of the building, but for not less than 180 seconds The minimum repetition time shall be permitted to be manually interrupted The minimum repetition time shall be permitted to be automatically interrupted for the transmission of mass notification messages in accordance with Chapter * The standard evacuation signal shall be synchronized within a notification zone. Additional Proposed Changes File Name Description Approved ANSI-ASA_S pdf ANSI/ASA Standards 2015

42 752 of /30/ :10 AM ANSI/ASA was revised in 2015 to reflect the evacuation and relocation audible signaling requirements required by NFPA 72. This is the reference standard and it should be used directly since it more completely addresses the temporal pattern specifications. Submitter Full Name: Vince Baclawski Organization: Nema Submittal Date: Tue Jun 28 14:44:15 EDT 2016

43 753 of /30/ :10 AM Public Input No. 609-NFPA [ Section No ] Distinctive Signals. Carbon Monoxide audible signals shall comply with and evacuation signals shall comply with Distinctive Carbon Monoxide Signal. The audible carbon monoxide alarm signal shall be a four-pulse temporal pattern and comply with the following: (1) Signals shall be a pattern consisting of four cycles of 100 milliseconds ± 10 percent on and 100 milliseconds ± 10 percent off, followed by 5 seconds ± 10 percent off. (2) After the initial 4 minutes of alarm, the 5-second off time shall be permitted to be changed to 60 seconds ± 10 percent. (3) The alarm signal shall be repeated in compliance with (1) and (2) until the alarm resets or the alarm signal is manually silenced The audible carbon monoxide alarm signal shall be synchronized within a notification zone. ****INSERT FIGURE HERE**** FIGURE Temporal Pattern Parameters Carbon Monoxide Signal Distinctive Evacuation Signal * To meet the requirements of Section 10.10, the alarm audible signal pattern used to notify building occupants of the need to evacuate (leave the building) or relocate (from one area to another) shall be the standard alarm evacuation signal consisting of a three-pulse temporal pattern. The pattern shall be in accordance with Figure and shall consist of the following in this order: (1) On phase lasting 0.5 second ±10 percent (2) Off phase lasting 0.5 second ±10 percent for three successive on periods (3) Off phase lasting 1.5 seconds ±10 percent Figure Temporal Pattern Parameters. - Evacuation Signal Exception: Where approved by the authority having jurisdiction, continued use of the existing consistent evacuation signaling scheme shall be permitted A single-stroke bell or chime sounded at on intervals lasting 1 second ±10 percent, with a 2-second ±10 percent off interval after each third on stroke, shall be permitted The signal shall be repeated for a period appropriate for the purposes of evacuation of the building, but for not less than 180 seconds The minimum repetition time shall be permitted to be manually interrupted.

44 754 of /30/ :10 AM The minimum repetition time shall be permitted to be automatically interrupted for the transmission of mass notification messages in accordance with Chapter * The standard evacuation signal shall be synchronized within a notification zone. Additional Proposed Changes File Name Description Approved Figure_-_CO_temporal_pattern.docx CO alarm temporal pattern This revision is one of a numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change is recommended to provide recognition of use, application and/or installation requirement consistent with other device requirements in Chapter 17 and where such requirement is applicable to carbon monoxide detection devices. For this specific revision the section includes new text to address the temporal pattern for CO alarm signal and then accordingly separates and renumbers that text related to the fire evacuation signal temporal pattern. Related Public Inputs for This Document Related Input Public Input No. 610-NFPA [Section No ] Public Input No. 611-NFPA [New Section after ] Public Input No. 612-NFPA [Section No ] Relationship Submitter Full Name: Daniel O`Connor Organization: Jensen Hughes Affilliation: Task Group for the NFPA 720/72 consolidation Submittal Date: Tue Jun 28 21:37:54 EDT 2016

45

46 755 of /30/ :10 AM Public Input No. 742-NFPA [ New Section after ] Public Mode Audible Requirements for CO Where carbon monoxide alarm signals are transmitted to a constantly attended on-site location or off-premises location, selective public mode occupant notification shall be permitted to be limited to the notification zone encompassing the area where the carbon monoxide alarm signal was initiated Notification zones for carbon monoxide alarms shall be consistent with the emergency response plan for the protected premises * The boundaries of notification zones shall be coincident with the area where the alarm initiation originated and other signaling zones in accordance with the building s emergency response plan. For buildings other than those with dwelling units, due to the varying building size and use, the danger of carbon monoxide exposure is only in the area of coverage. Audible notification should be limited to that area to limit the evacuation and disruption to the entire building s operation or business, and is to be documented as such in the emergency response plan for the protected premises. The area of coverage as defined by NFPA ; Requirements for Carbon Monoxide Detectors Carbon monoxide detectors shall be installed as specified in the manufacturer s published instructions in accordance with (1) and (2), or (3): (1)*On the ceiling in the same room as permanently installed fuel-burning appliances (2)*Centrally located on every habitable level and in every HVAC zone of the building (3) A performance-based design in accordance with Related Public Inputs for This Document Related Input Public Input No. 743-NFPA [New Section after A ] Relationship Submitter Full Name: Anthony Mucci Organization: Tyco Integrated Security Submittal Date: Wed Jun 29 16:24:22 EDT 2016

47 756 of /30/ :10 AM Public Input No. 610-NFPA [ Section No ] Appliances that are an integral part of a smoke detector, carbon monoxide detector, smoke alarm, carbon monoxide alarm or other initiating device shall be located in accordance with the requirements for that device. This revision is one of a numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change is recommended to provide recognition of use, application and/or installation requirement consistent with other device requirements in Chapter 18 and where such requirement is applicable to carbon monoxide detection devices. Related Public Inputs for This Document Related Input Public Input No. 609-NFPA [Section No ] Relationship CO requirements integration Submitter Full Name: Daniel O`Connor Organization: Jensen Hughes Affilliation: Task Group for the NFPA 720/72 consolidation Submittal Date: Tue Jun 28 22:09:05 EDT 2016

48 757 of /30/ :10 AM Public Input No. 479-NFPA [ Section No ] Each ADS that does not require voice intelligibility shall be identified as requiring or not requiring voice intelligibility * Unless specifically required by other governing laws, codes, or standards, or by other parts of this Code, intelligibility shall not be required in all ADSs. Submitter recommends that designers only identify Acoustically Distinguishable Spaces (ADS) where intelligibility is not required. As a result, intelligibility will be required in all other ADSs. This way the designer will be required to identify the exceptions where intelligibility is not required and not have to add unnecessary labels to the drawings and designs. Submitter Full Name: Thomas Hammerberg Organization: Automatic Fire Alarm Association Affilliation: Automatic Fire Alarm Association Submittal Date: Mon Jun 27 09:14:31 EDT 2016

49 758 of /30/ :10 AM Public Input No. 62-NFPA [ Section No ] Intelligibility shall not be be permitted to be determined through quantitative measurements as described in D.2.4, but is not required to be determined through quantitative measurements. Paragraphs and 5 were new for 2013, and conflict with each other. Delete and modify to indicate that it is acceptable to require intelligibility testing per Annex D, however quantitative intelligibility testing is not a requirement of NFPA 72. Related Public Inputs for This Document Related Input Public Input No. 63-NFPA [Section No ] Relationship Submitter Full Name: Liane Ozmun Organization: Frankfurt Short Bruza Submittal Date: Wed Jan 27 16:20:43 EST 2016

50 759 of /30/ :10 AM Public Input No. 744-NFPA [ Sections , ] Sections , Intelligibility If acceptable to the authority having jurisdiction, intelligibility shall not be required to be determined through quantitative measurements Quantitative measurements as described in D.2.4 shall be permitted but are not required as one method to determine intelligibility. Intelligibility as it is exists in the code is not enforceable, especially for those jurisdictions that require intelligibility testing. This change will 1) enable AHJ's to require testing of those ADS's that need it and 2) provide a methodology for doing so. Submitter Full Name: Lynn Nielson Organization: City Of Henderson Affilliation: Self Submittal Date: Wed Jun 29 16:37:40 EDT 2016

51 760 of /30/ :10 AM Public Input No. 63-NFPA [ Section No ] Quantitative measurements as described in D.2.4 shall be permitted but are not required. If is revised to allow quantitative intelligibility testing per Annex D, even though it is not required by NFPA 72, this paragraph is not required. Related Public Inputs for This Document Related Input Public Input No. 62-NFPA [Section No ] Relationship Combine two paragraphs into single paragraph. Submitter Full Name: Liane Ozmun Organization: Frankfurt Short Bruza Submittal Date: Wed Jan 27 16:27:54 EST 2016

52 761 of /30/ :10 AM Public Input No. 596-NFPA [ Section No ] 18.5* Visible Characteristics Public Mode * Visible Signaling Public mode visible signaling shall meet the requirements of Section 18.5 using visible notification appliances * The coverage area for visible occupant notification shall be as required by other governing laws, codes, or standards. Where the other governing laws, codes, or standards require visible occupant notification for all or part of an area or space, coverage shall only be required in occupiable areas as defined in Several new and revised sections from through are being submitted together as they are all related to each other and need to be reviewed together. See attachment for proposed text Area of Coverage The designer of the visible notification system shall document the rooms and spaces that will have visible notification and those where visible notification will not be provided * Unless otherwise specified or required by other sections of this Code, the required coverage area for visible occupant notification shall be as required by other governing laws, codes, or standards Where required by the authority having jurisdiction, documentation of the effective intensity (cd) of the visible appliances for the area of coverage shall be submitted for review and approval Light, Color, and Pulse Characteristics The flash rate shall not exceed two flashes per second (2 Hz) nor be less than one flash every second (1 Hz) throughout the listed voltage range of the appliance * The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent. Exception: Lights used to meet the requirements of shall be permitted to be listed and labeled to have pulse durations up to 100 milliseconds The pulse duration shall be defined as the time interval between initial and final points of 10 percent of maximum signal * Lights used for fire alarm signaling only or to signal the intent for complete evacuation shall be clear or nominal white and shall not exceed 1000 cd (effective intensity) Lights used to signal occupants to seek information or instructions shall be clear, nominal white, or other color as required by the emergency plan and the authority having jurisdiction for the area or building.

53 762 of /30/ :10 AM * The strobe synchronization requirements of this chapter shall not apply where the visible notification appliances located inside the building are viewed from outside of the building * Appliance Photometrics. The light output shall comply with the polar dispersion requirements of ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent Appliance Location * Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in. (2.03 m) and not greater than 96 in. (2.44 m) above the finished floor or at the mounting height specified using the performance-based alternative of Where low ceiling heights do not permit wall mounting at a minimum of 80 in. (2.03 m), wall mounted visible appliances shall be mounted within 6 in. (150 mm) of the ceiling. The room size covered by a strobe of a given value shall be reduced by twice the difference between the minimum mounting height of 80 in. (2.03 m) and the actual lower mounting height * Visible appliances listed for mounting parallel to the floor shall be permitted to be located on the ceiling or suspended below the ceiling * Spacing in Rooms.

54 763 of /30/ :10 AM

55 764 of /30/ :10 AM Spacing shall be in accordance with either Table (a) and Figure or Table (b). Table (a) Room Spacing for Wall-Mounted Visible Appliances Maximum Room Size Minimum Required Light Output [Effective Intensity (cd)] ft m One Light per Room Four Lights per Room (One Light per Wall) NA NA NA NA: Not allowable. Table (b) Room Spacing for Ceiling-Mounted Visible Appliances Maximum Room Size Maximum Lens Height* ft m ft m Minimum Required Light Output (Effective Intensity); One Light (cd)

56 765 of /30/ :10 AM Maximum Room Size Maximum Lens Height* ft m ft m Minimum Required Light Output (Effective Intensity); One Light (cd) *This does not preclude mounting lens at lower heights. Figure Room Spacing for Wall-Mounted Visible Appliances Visible notification appliances shall be installed in accordance with Table (a) or Table (b) using one of the following: (1) A single visible notification appliance. (2) * Two groups of visible notification appliances, where visual appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of strobes operated by separate systems. (3) More than two visible notification appliances or groups of synchronized appliances in the same room or adjacent space within the field of view that flash in synchronization Room spacing in accordance with Table (a) and Figure for wall-mounted appliances shall be based on locating the visible notification appliance at the halfway distance of the wall In square rooms with appliances not centered or in nonsquare rooms, the effective intensity (cd) from one visible wall-mounted notification appliance shall be determined by maximum room size dimensions obtained either by measuring the distance to the farthest wall or by doubling the distance to the farthest adjacent wall, whichever is greater, as required by Table (a) and Figure If a room configuration is not square, the square room size that allows the entire room to be encompassed or allows the room to be subdivided into multiple squares shall be used * If ceiling heights exceed 30 ft (9.14 m), ceiling-mounted visible notification appliances shall be suspended at or below 30 ft (9.14 m) or at the mounting height determined using the performance-based alternative of , or wall-mounted visible notification appliances shall be installed in accordance with Table (a).

57 766 of /30/ :10 AM Table (b) shall be used if the ceiling-mounted visible notification appliance is at the center of the room. If the ceiling-mounted visible notification appliance is not located at the center of the room, the effective intensity (cd) shall be determined by doubling the distance from the appliance to the farthest wall to obtain the maximum room size * Spacing in Corridors The installation of visible notification appliances in corridors 20 ft (6.1 m) or less in width shall be in accordance with the requirements of either or Paragraph shall apply to corridors not exceeding 20 ft (6.1 m) in width In a corridor application, visible appliances shall be rated not less than 15 cd Corridors greater than 20 ft (6.1 m) wide shall comply with the spacing requirements for rooms in accordance with * Visible notification appliances shall be located not more than 15 ft (4.57 m) from the end of the corridor with a separation not greater than 100 ft (30.5 m) between appliances If there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area shall be treated as a separate corridor In corridors where more than two visible notification appliances are in any field of view, they shall flash in synchronization Wall-mounted visible notification appliances in corridors shall be permitted to be mounted on either the end wall or the side wall of the corridor in accordance with spacing requirements of * Performance-Based Alternative Any design that provides a minimum of lumens/ft 2 ( lumens/m 2 ) of illumination at any point within the covered area at all angles specified by the polar dispersion planes for wall- or ceiling-mounted visual appliances in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent, as calculated for the maximum distance from the nearest visual notification appliance, shall be permitted in lieu of the requirements of , excluding Documentation provided to the authority having jurisdiction shall include the following: (1) Inverse Square Law calculations using each of the vertical and horizontal polar distribution angles in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent. (2) The calculations shall account for the effects of polar distribution using one of the following: (3) The percentages from the applicable table(s) in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent (4) The actual results of laboratory tests of the specific appliance to be used as recorded by the listing organization Sleeping Areas.

58 767 of /30/ :10 AM Combination smoke detectors and visible notification appliances or combination smoke alarms and visible notification appliances shall be installed in accordance with the applicable requirements of Chapters 17, 18, and * Table shall apply to sleeping areas. Table Effective Intensity Requirements for Sleeping Area Visible Notification Appliances Distance from Ceiling Minimum Intensity to Top of Lens (cd) in. mm <24 < For rooms with a linear dimension greater than 16 ft (4.87 m), the visible notification appliance shall be located within 16 ft (4.87 m) of the pillow Location of Visible Notification Appliances for Wide Area Signaling. Visible notification appliances for wide area signaling shall be installed in accordance with the requirements of the authority having jurisdiction, approved design documents, and the manufacturer s instructions to achieve the required performance. Additional Proposed Changes File Name Description Approved DGPublic_Input_Draft_for_Chapter_18-28JUN2016.docx Support material for new and revised section 18.5 Based on nearly two years of research and human factors testing at a UL subscriber facility under the direction of UL Staff, this public input proposes revisions to section 18.5 and related sections to resolve the temporary fix in the 2016 edition for pulse duration and intensity. Submitter Full Name: Daniel Grosch Organization: UL LLC Submittal Date: Tue Jun 28 20:26:12 EDT 2016

59 768 of /30/ :10 AM Public Input No. 746-NFPA [ New Section after ] Area of Coverage for CO T Where carbon monoxide alarm signals are transmitted to a constantly attended on-site location or off-premises location in accordance with Chapter 7, selective public mode occupant notification shall be permitted to be limited to the notification zone encompassing the area where the carbon monoxide alarm signal was initiated Notification zones for carbon monoxide alarms shall be consistent with the emergency response plan for the protected premises * The boundaries of notification zones shall be coincident with the area where the alarm initiation originated and other signaling zones in accordance with the building s emergency response plan. For buildings other than those with dwelling units, due to the varying building size and use, the danger of carbon monoxide exposure is only in the area of coverage. Visible notification should be limited to that area to limit the evacuation and disruption to the entire building s operation or business, and is to be documented as such in the emergency response plan for the protected premises. The area of coverage as defined by NFPA ; Requirements for Carbon Monoxide Detectors Carbon monoxide detectors shall be installed as specified in the manufacturer s published instructions in accordance with (1) and (2), or (3): (1)*On the ceiling in the same room as permanently installed fuel-burning appliances (2)*Centrally located on every habitable level and in every HVAC zone of the building (3) A performance-based design in accordance with Related Public Inputs for This Document Related Input Public Input No. 748-NFPA [New Section after A ] Relationship Submitter Full Name: Anthony Mucci Organization: Tyco Integrated Security Submittal Date: Wed Jun 29 16:39:58 EDT 2016

60 769 of /30/ :10 AM Public Input No. 100-NFPA [ Section No ] * The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent. Exception: Lights used to meet the requirements of shall be permitted to be listed and labeled to have pulse durations up to 100 milliseconds. Duty cycle is calculated using the pulse duration and the flash rate (previous paragraph). Therefore, having this text is redundant. The 40% MAX duty cycle came from 2013 and prior editions that allowed 200 ms pulse duration. Using 200 ms with the max. of 2 flashes per sec.: 0.2 s pulse / 0.5 s period = 0.4 duty cycle = 40%. Since the 2016 edition allows 100 ms (down from 200 ms) for direct viewing, we should have reduced the max. duty cycle to 20%. But, there is no need to TIA the 2016 edition since 20% is still less than a max. of 40%. Submitter Full Name: Robert Schifiliti Organization: R. P. Schifiliti Associates, Inc. Submittal Date: Thu Mar 24 13:21:48 EDT 2016

61 770 of /30/ :10 AM Public Input No. 247-NFPA [ Section No ] * The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent. Exception: Lights Visible notification appliances used to meet the requirements of shall be permitted to be listed and labeled to have pulse durations up to 100 milliseconds. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term " visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 09:17:45 EDT 2016

62 771 of /30/ :10 AM Public Input No. 480-NFPA [ Section No ] * The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent. Exception: Lights used to meet the requirements of shall be permitted to be listed and labeled to have pulse durations up to 100 milliseconds. The duty cycle currently in the code is not correct for the prescribed pulse duration. The maximum duty cycle is 4 percent for a 20 millisecond pulse duration for a flash rate of two times per second and not 40 percent (calculated as 20 milliseconds divided by 500 milliseconds). The 4 percent requirement, in the submitter s opinion is unnecessary as the requirement of a 20 millisecond maximum pulse width and the requirement of a maximum of two flashes per second ensures a maximum duty cycle of 4% and this added requirement is redundant. Related Public Inputs for This Document Related Input Public Input No. 481-NFPA [Section No ] Relationship Submitter Full Name: Thomas Hammerberg Organization: Automatic Fire Alarm Association Affilliation: Automatic Fire Alarm Association Submittal Date: Mon Jun 27 09:16:48 EDT 2016

63 772 of /30/ :10 AM Public Input No. 481-NFPA [ Section No ] * The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent. Exception: Lights used to meet the requirements of shall be permitted to be listed and labeled to have pulse durations up to 100 milliseconds. This exception can introduce possible confusion in installations as there would be a need for testing and labeling of visible notification devices that are designed to meet this exception. This could place an undue burden on designers, installers, and the approving authority as they would have to properly specify and confirm that proper visible appliances are installed in the proper application. Related Public Inputs for This Document Related Input Public Input No. 480-NFPA [Section No ] Relationship Submitter Full Name: Thomas Hammerberg Organization: Automatic Fire Alarm Association Affilliation: Automatic Fire Alarm Association Submittal Date: Mon Jun 27 09:18:50 EDT 2016

64 773 of /30/ :10 AM Public Input No. 248-NFPA [ Section No ] * Lights Visible notification appliances used for fire alarm signaling only or to signal the intent for complete evacuation shall be clear or nominal white and shall not exceed 1000 cd (effective intensity). As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term " visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 09:21:38 EDT 2016

65 774 of /30/ :10 AM Public Input No. 611-NFPA [ New Section after ] Lights used for carbon monoxide alarm signaling Lights used for carbon monoxide alarm signaling shall be as required by the emergency plan and the authority having jurisdiction for the area or building, and shall not exceed 1000 cd (effective intensity). This revision is one of a numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change is recommended to provide recognition of use, application and/or installation requirement consistent with other device requirements in Chapter 18 and where such requirement is applicable to carbon monoxide detection devices. Related Public Inputs for This Document Related Input Public Input No. 609-NFPA [Section No ] Relationship CO requirements integration Submitter Full Name: Daniel O`Connor Organization: Jensen Hughes Affilliation: Task Group for the NFPA 720/72 consolidation Submittal Date: Tue Jun 28 22:16:27 EDT 2016

66 775 of /30/ :10 AM Public Input No. 249-NFPA [ Section No ] Lights Visible notification appliances used to signal occupants to seek information or instructions shall be clear, nominal white, or other color as required by the emergency plan and the authority having jurisdiction for the area or building. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term " visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 09:22:48 EDT 2016

67 776 of /30/ :10 AM Public Input No. 265-NFPA [ Section No ] * The strobe visible notification appliance synchronization requirements of this chapter shall not apply where the visible notification appliances located inside the building are viewed from outside of the building. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:45:09 EDT 2016

68 777 of /30/ :10 AM Public Input No. 450-NFPA [ Section No ] * Appliance Photometrics. The light output shall comply with the polar dispersion requirements of ANSI requirements for public mode signaling as described in of ANSI /UL 1971, Standard for Signaling Devices for the Hearing Impaired, Impaired ; ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories, or equivalent. Additional Proposed Changes File Name NFPA_72_2019_ docx Description Approved UL, at the request of NEMA, harmonized the visual signaling requirements in UL 1971, UL 1638 and ULC S526 into a bi-national Standard ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories. Reference in NFPA 72 needs to be revised to include both UL 1971 and UL Submitter Full Name: Daniel Grosch Organization: UL LLC Submittal Date: Fri Jun 24 11:28:54 EDT 2016

69 NFPA Public Input Form NOTE: All Public Input must be received by 5:00 pm EST/EDST on the published Public Input Closing Date. For further information on the standards-making process, please contact the Codes and Standards Administration at or visit For technical assistance, please call NFPA at FOR OFFICE USE ONLY Log #: Date Rec d: Date 6/24/2016 Name Daniel Grosch Tel. No Company Underwriters Labs LLC Street Address 333 Pfingsten Road City Northbrook State IL Zip Please indicate organization represented (if any) 1. (a) Title of NFPA Standard (b) Section/Paragraph UL LLC National Fire Alarm and Signaling Code NFPA No. & Year Public Input Recommends (check one): new text revised text deleted text 3. Proposed Text of Public Input (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strikethrough to denote wording to be deleted (deleted wording).] * Appliance Photometrics. The light output shall comply with the polar dispersion requirements for public mode signaling as described in of ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired; ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories, or equivalent. 4. : (Note: State the problem that would be resolved by your recommendation; give the specific reason for your Public Input, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.) UL, at the request of NEMA, harmonized the visual signaling requirements in UL 1971, UL 1638 and ULC S526 into a bi-national Standard ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories. Reference in NFPA 72 needs to be revised to include both UL 1971 and UL Copyright Assignment (a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Public Input. (b) Some or all of the text or other material proposed in this Public Input was not authored by me. Its source is as follows: (please identify which material and provide complete information on its source) I hereby grant and assign to the NFPA all and full rights in copyright in this Public Input (including both the Proposed Text and the Statement of Problem and Substantiation). I understand that I acquire no rights in any publication of NFPA in which this Public Input in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Public Input and that I have full power and authority to enter into this assignment. Signature (Required) PLEASE USE SEPARATE FORM FOR EACH PUBLIC INPUT To: Secretary, Standards Council National Fire Protection Association 1 Batterymarch Park Quincy, MA OR Fax to: (617) OR to: proposals_comments@nfpa.org 6/30/2016

70 778 of /30/ :10 AM Public Input No. 266-NFPA [ Section No ] Where low ceiling heights do not permit wall mounting at a minimum of 80 in. (2.03 m), wall mounted visible notification appliances shall be mounted within 6 in. (150 mm) of the ceiling. The room size covered by a strobe visible notification appliance of a given value shall be reduced by twice the difference between the minimum mounting height of 80 in. (2.03 m) and the actual lower mounting height. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:47:35 EDT 2016

71 779 of /30/ :10 AM Public Input No. 715-NFPA [ New Section after ] Indirect Viewing in Rooms Ceiling-mounted visual appliances shall be provided in rooms and areas used for exhibition purposes, or in rooms and areas where racks or shelving that exceed 5 feet in height are expected to be installed, or in rooms and areas where wall-mounted devices may become obstructed. This change attempts to solve the problem created by high shelving and partitions. Submitter Full Name: Lynn Nielson Organization: City Of Henderson Affilliation: Self Submittal Date: Wed Jun 29 15:07:07 EDT 2016

72 780 of /30/ :10 AM Public Input No. 250-NFPA [ Section No ]

73 781 of /30/ :10 AM

74 782 of /30/ :10 AM Spacing shall be in accordance with either Table (a) and Figure or Table (b). Table (a) Room Spacing for Wall-Mounted Visible Appliances Maximum Room Size ft m Minimum Required Light Output [Effective Intensity (cd)] One Light visible notification appliance per Room Four Lights visible notification appliances per Room (One Light per Wall) 15 NA 30 NA 34 NA NA: Not allowable. Table (b) Room Spacing for Ceiling-Mounted Visible Appliances Maximum Minimum Required Maximum Lens Height* Room Size Light Output (Effective Intensity); ft m ft m One Visible Notification Appliance Light (cd)

75 783 of /30/ :10 AM Maximum Minimum Required Maximum Lens Height* Room Size Light Output (Effective Intensity); ft m ft m One Visible Notification Appliance Light (cd) *This does not preclude mounting lens at lower heights. Figure Room Spacing for Wall-Mounted Visible Appliances. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term " visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell

76 784 of /30/ :10 AM Submittal Date: Wed Jun 01 09:27:20 EDT 2016

77 785 of /30/ :10 AM Public Input No. 267-NFPA [ Section No ] Visible notification appliances shall be installed in accordance with Table (a) or Table (b) using one of the following: (1) A single visible notification appliance. (2) * Two groups of visible notification appliances, where visual appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of strobes visible notification appliances operated by separate systems. (3) More than two visible notification appliances or groups of synchronized appliances in the same room or adjacent space within the field of view that flash in synchronization. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:49:17 EDT 2016

78 786 of /30/ :10 AM Public Input No. 457-NFPA [ Section No ] Any design that provides a minimum of lumens/ft 2 ( lumens/m 2 ) of illumination at any point within the covered area at all angles specified by the polar dispersion planes for wall- or ceiling-mounted visual mounted public mode visual appliances in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, Impaired ; ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories, or equivalent, as calculated for the maximum distance from the nearest visual notification appliance, shall be permitted in lieu of the requirements of , excluding UL, at the request of NEMA, harmonized the visual signaling requirements in UL 1971, UL 1638 and ULC S526 into a bi-national Standard ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories. Reference in NFPA 72 needs to be revised to include both UL 1971 and UL Submitter Full Name: Daniel Grosch Organization: UL LLC Submittal Date: Fri Jun 24 11:50:22 EDT 2016

79 787 of /30/ :10 AM Public Input No. 612-NFPA [ Section No ] Sleeping Areas Combination smoke detectors and visible notification appliances or combination smoke alarms and visible notification appliances shall be installed in accordance with the applicable requirements of Chapters 17, 18, and Combination carbon monoxide detectors and visible notification appliances or combination carbon monoxide alarms and visible notification appliances shall be installed in accordance with the applicable requirements of Chapters 17, 18, and * Table shall apply to sleeping areas. Table Effective 3 Effective Intensity Requirements for Sleeping Area Visible Notification Appliances Distance from Ceiling Minimum Intensity to Top of Lens (cd) in. mm <24 < Exception: Where the visible appliance is not used for fire alarm signaling but only carbon monoxide signaling, the effective intensity shall not be required to be greater than 110 cd For rooms with a linear dimension greater than 16 ft (4.87 m), the visible notification appliance shall be located within 16 ft (4.87 m) of the pillow. This revision is one of a numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change is recommended to provide recognition of use, application and/or installation requirement consistent with other device requirements in Chapter 18 and where such requirement is applicable to carbon monoxide detection devices. Related Public Inputs for This Document Related Input Public Input No. 609-NFPA [Section No ] Relationship CO requirements integration Submitter Full Name: Daniel O`Connor Organization: Jensen Hughes Affilliation: Task Group for the NFPA 720/72 consolidation

80 788 of /30/ :10 AM Submittal Date: Tue Jun 28 22:22:15 EDT 2016

81 789 of /30/ :10 AM Public Input No. 64-NFPA [ Section No ] * Table The minimum visible notification appliance intensity for sleeping areas shall comply withtable shall apply to sleeping areas after applying the relevant mounting height in accordance with the requirements of Chapters 17, 18, and 29. Table Effective Intensity Requirements for Sleeping Area Visible Notification Appliances in. Distance from Ceiling to Top of Lens mm Minimum Intensity (cd) <24 < The current table is not clear with respect to mounting height criteria of visible notification appliances. This language is more easily enforced. Submitter Full Name: Lynn Nielson Organization: City of Henderson Affilliation: none Submittal Date: Thu Jan 28 19:23:43 EST 2016

82 790 of /30/ :10 AM Public Input No. 688-NFPA [ Section No ] Location of Visible Notification Appliances for Wide Area Signaling. Visible notification appliances for wide- area signaling shall be installed in accordance with the requirements of the authority having jurisdiction, approved design documents, and the manufacturer s instructions to achieve the required performance. A Correlating Committee task group on language/terms reviewed the language of the Code for consistency and grammar. Editorial revision to align with the common usage elsewhere in the Code regarding hyphenating "wide-area." Submitter Full Name: Lawrence Shudak Organization: UL LLC Submittal Date: Wed Jun 29 14:19:03 EDT 2016

83 791 of /30/ :10 AM Public Input No. 189-NFPA [ Section No ] Speaker Textual Audible Notification Appliances Speaker Textual audible notification appliances shall comply with Section * The sound pressure level, in dba, of the tone produced by a signaling speaker textual audible notification appliance shall comply with all the requirements in (public), (private), or (sleeping) for the intended mode or shall comply with the requirements of (narrow band tone signaling). As part of the CC TG on terms, the term "Speaker" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to a person. In this section the term is for an appliance and the proper term "Textual Audible Notification Appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed May 18 08:24:16 EDT 2016

84 792 of /30/ :10 AM Public Input No. 772-NFPA [ Section No ] * Standard Emergency Service Interface. Where required by the enforcing authority; governing laws, codes, or standards; or other parts of this Code, annunciators, information display systems, and controls for portions of a system provided for use by emergency service personnel shall be designed, arranged, and located in accordance with the requirements of the organizations intended to use the equipment. This section should be deleted since there is no need for it. Different fire alarm system manufacturers are producing different types of listed fire alarm annunciators. Some of these annunciators could be customized per a specific Fire jurisdiction request. There is no need to include a "Standard Emergency Service interface" within the body of the NFPA 72 code. As a Fire AHJ, I'm not aware of such a "standard emergency service interface" - If such an interface does not exist and is not needed - it should be deleted from the code since it confuses many AHJs wondering how to require such an interface. Related Public Inputs for This Document Related Input Public Input No. 773-NFPA [Section No. A.18.11] Public Input No. 774-NFPA [Section No. A ] Public Input No. 775-NFPA [Section No ] Relationship Submitter Full Name: Sagiv Weiss-Ishai Organization: San Francisco Fire Department Affilliation: SFFD Submittal Date: Wed Jun 29 21:43:37 EDT 2016

85 1108 of /30/ :10 AM Public Input No. 195-NFPA [ Section No. A ]

86 1109 of /30/ :10 AM A Acoustically Distinguishable Space (ADS).

87 1110 of /30/ :10 AM All parts of a building or area intended to have occupant notification are subdivided into ADSs as defined. Some ADSs might be designated to have voice communication communications capability and require that those communications be intelligible. Other spaces might not require voice intelligibility or might not be capable of reliable voice intelligibility. An ADS might have acoustical design features that are conducive for voice intelligibility, or it might be a space where voice intelligibility could be difficult or impossible to achieve. Each is still referred to as an ADS. In smaller areas, such as those under 400 ft 2 (40 m 2 ), walls alone will define the ADS. In larger areas, other factors might have to be considered. In spaces that might be subdivided by temporary or movable partitions, such as ballrooms and meeting rooms, each individual configuration should be considered a separate ADS. Physical characteristics, such as a change in ceiling height of more than 20 percent, or a change in acoustical finish, such as carpet in one area and tile in another, would require those areas to be treated as separate ADSs. In larger areas, there might be noise sources that require a section to be treated as a separate ADS. Any significant change in ambient noise level or frequency might necessitate an area be considered a separate ADS. In areas of 85 dba or greater ambient sound pressure level, meeting the pass/fail criteria for intelligibility might not be possible, and other means of communication communications might be necessary. So, for example, the space immediately surrounding a printing press or other high-noise machine might be designated as a separate ADS, and the design might call for some form of effective notification but not necessarily require the ability to have intelligible voice communication communications. The aisles or operator s control stations might be separate ADSs where intelligible voice communication might be desired. Significant differences in furnishings, for example, an area with tables, desks, or low dividers, adjacent to an area with high shelving, would require separate consideration. The entire desk area could be a single acoustic zone, whereas each area between shelving could be a unique zone. Essentially, any noteworthy change in the acoustical environment within an area will mandate consideration of that portion of the area to be treated as an acoustic zone. Hallways and stairwells will typically be considered as individual acoustic zones. Spaces confined by walls with carpeting and acoustical ceilings can be deemed to be one ADS. An ADS should be an area of consistent size and material. A change of materials from carpet to hard tile, the existence of sound sources, such as decorative waterfalls, large expanses of glass, and changes in ceiling height, are all factors that might separate one ADS from another. Each ADS might require different components and design features to achieve intelligible voice communication. For example, two ADSs with similar acoustical treatments and noise levels might have different ceiling heights. The ADS with the lower ceiling height might require more ceiling-mounted speakers to ensure that all listeners are in a direct sound field (see Figure A.3.3.6). Other ADSs might benefit from the use of alternate speaker technologies, such as line arrays, to achieve intelligibility. An ADS that differs from another because of the frequency and level of ambient noise might require the use of speakers and system components that have a wider frequency bandwidth than conventional emergency communications equipment. However, designers should not use higher bandwidth speakers in all locations, unless needed to overcome certain acoustic and ambient conditions. This is because the higher bandwidth appliance will require more energy to perform properly. This increases amplifier and wire size and power supply requirements. In some spaces, it might be impractical to achieve intelligibility, and, in such a case, alternatives to voice evacuation might be required within such areas. Figure A Illustration Demonstrating the Effect of Ceiling Height. (Source: R. P. Schifiliti Associates, Inc.) There might be some areas of a facility where there are several spaces of the same approximate size and the same acoustic properties. For example, there might be an office space with multiple individual offices, each with one speaker. If one or two are satisfactorily tested, there is no need to test all of them for speech intelligibility.

88 1111 of /30/ :10 AM Additional Proposed Changes File Name Description Approved A pdf Terraview would not allow editing of this text as there is a figure as part of this section. I therefore had to upload this PDF. As part of the CC TG on terms, the term "Speaker" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to a person. In this section the term is for an appliance and the proper term "Textual Audible Notification Appliance" should be used. Where the term "speaker" is highlighted on the attached PDF the term should be changed to "textual audible notification appliance." Additionally; As part of the CC TG on terms, the term "communication(s) was reviewed throughout the entire document for proper use regarding reference to singular and plural use. The term should be plural use in this context. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed May 18 09:14:58 EDT 2016

89 Copyright 2015 National Fire Protection Association (NFPA). Licensed, by agreement, lor individual use and download on October 2, 2015 to Rodger Reiswig lor designated user Rodger Reiswig. No other reproduction or transmission in any lonm penmitted without written penmission 01 NFPA. For inquires or to report unauthorized use, contact NATIONAL FIRE ALARM AND SIGNALING CODE A Code. The decision to designate a standard as a "code" is based on such factors as the size and scope of the document, its intended use and form of adoption, and whether it contains substantial enforcement and administrative provisions. A Listed. The means for identifying listed equipment may vary for each organization concerned with product evaluation; some organizations do not recognize equipment as listed unless it is also labeled. The authority having jurisdiction should utilize the system employed by the listing organization to identify a listed product. A Acoustically Distinguishable Space (ADS). All parts of a building or area intended to have occupant notification are subdivided into ADSs as defined. Some ADSs might be designated to have voice communication capability and require that those communications be intelligible. Other spaces might not require voice intelligibility or might not be capable of reliable voice intelligibility. An ADS migh t have acoustical design features that are conducive for voice intelligibility, or it might be a space where voice intelligibility could be difficult or impossible to achieve. Each is still referred to as an ADS. In smaller areas, such as those under 400 ft 2 (40 m"), walls alone will define the ADS. In larger areas, other factors might have to be considered. In spaces that might be subdivided by temporary or movable partitions, such as ballrooms and meeting rooms, each individual configuration should be considered a separate ADS. Physical characteristics, such as a change in ceiling height of more than 20 percent, or a change in acoustical finish, such as carpet in one area and tile in another, would require those areas to be treated as separate ADSs. In larger areas, there might be noise sources that require a section to be treated as a separate ADS. Any significan t change in ambient noise level or frequency might necessitate an area be considered a separate ADS. In areas of 85 deaor greater ambient sound pressure level, meeting the pass/fail criteria for intelligibility might not be possible, and other means of communication might be necessary. So, for example, the space immediately surrounding a printing press or other high-noise machine might be designated as a separate ADS, and the design might call for some form of effective notification but not necessarily require the ability to have intelligible voice communication. The aisles or operator's control stations might be separate ADSs where intelligible voice communication might be desired. Significant differences in furnishings, for example, an area with tables, desks, or low dividers, adjacent to an area with high shelving, would require separate consideration. The entire desk area could be a single acoustic zone, whereas each area between shelving could be a unique zone. Essentially, any noteworthy change in the acoustical environment within an area will mandate consideration of that portion of the area to be treated as an acoustic zone. Hallways and stairwells will typically be considered as individual acoustic zones. Spaces confined by walls with carpeting and acoustical ceilings can be deemed to be one ADS. An ADS should be an area of consistent size and material. A change of materials from carpet to hard tile, the existence of sound sources, such as decorative waterfalls, large expanses of glass, and changes in ceiling height, are all factors that might separate one ADS from another. Each ADS might require different components and design features to achieve intelligible voice communication. For example, two ADSs with similar acoustical treatments and noise levels might have different ceiling heights. The ADS with the lower ceiling height might require more ceiling-mounted speakers to ensure that all listeners are in a direct sound field (see FigureA.3.3.6). Other ADSs might benefit from the use of alternate speaker technologies, such as line arrays, to achieve intelligibility. An ADS that differs from another because of the frequency and level of ambient noise might require the use of speakers and system components that have a wider frequency bandwidth than conventional emergency communications equipment. However, designers should not use higher bandwidth speakers in all locations, unless needed to overcome certain acoustic and ambient conditions. This is because the higher bandwidth appliance will require more energy to perform properly. This increases amplifier and wire size and power supply requirements. In some spaces, it might be impractical to achieve intelligibility, and, in such a case, alternatives to voice evacuation might be required within such areas. There might be some areas of a facility where there are several spaces of the same approximate size and the same acoustic properties. For example, there might be an office space with multiple individual offices, each with one speaker. If one or two are satisfactorily tested, there is no need to test all of them for speech intelligibility. A Average Ambient Sound Level. The term average ambient sound levelis also called the equivalent A-weighted sound level measured over t hours, where t is the time period over which the measurement is made. The standard industry symbol is L Aeg.,. Where a measurement is taken over a 24-hour time period, the designation would be LA.eq.24'!X' rr====rr=========nr=======~~========tr==~~ 117 ft (35.7 m) FIGURE A Illustration Demonstrating the Effect of Ceiling Height. (Source: R. P. SchifilitiAssociates, Inc.) 2016 Edition

90 1125 of /30/ :10 AM Public Input No. 197-NFPA [ Section No. A ] A Textual Audible Notification Appliance. An example of a textual audible notification appliance is a speaker an appliance that reproduces a voice message. As part of the CC TG on terms, the term "Speaker" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to a person. In this section the term is for an appliance and should be modified as shown. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed May 18 09:20:18 EDT 2016

91 1196 of /30/ :10 AM Public Input No. 743-NFPA [ New Section after A ] Annex MAterial: Public Mode Audible Requirements for CO. A The building s emergency response plan might specify occupant notification only in the area(s) of initiation and at the control panel. Whole building evacuation might not be specified in the emergency response plan.. To provide clarity to the body of the same section. For buildings other than those with dwelling units, due to the varying building size and use, the danger of carbon monoxide exposure is only in the area of coverage. Audible notification should be limited to that area to limit the evacuation and disruption to the entire building s operation or business, and is to be documented as such in the emergency response plan for the protected premises. The area of coverage as defined by NFPA ; Requirements for Carbon Monoxide Detectors Carbon monoxide detectors shall be installed as specified in the manufacturer s published instructions in accordance with (1) and (2), or (3): (1)*On the ceiling in the same room as permanently installed fuel-burning appliances (2)*Centrally located on every habitable level and in every HVAC zone of the building (3) A performance-based design in accordance with Related Public Inputs for This Document Related Input Public Input No. 742-NFPA [New Section after ] Relationship Body Submitter Full Name: Anthony Mucci Organization: Tyco Integrated Security Submittal Date: Wed Jun 29 16:35:32 EDT 2016

92 1197 of /30/ :10 AM Public Input No. 478-NFPA [ Section No. A ] A The typical average ambient sound level for the occupancies specified in Table A are intended only for design guidance purposes. The typical average ambient sound levels specified should not be used in lieu of actual sound level measurements. Table A Average Ambient Sound Level According to Location Location Average Ambient Sound Level (dba) Business occupancies Educational occupancies 45 Industrial occupancies Institutional occupancies 50 Mercantile occupancies 40 Mechanical rooms Piers and water-surrounded structures 40 Places of assembly Residential occupancies 35 Storage occupancies 30 Thoroughfares, high-density urban 70 Thoroughfares, medium-density urban 55 Thoroughfares, rural and suburban 40 Tower occupancies 35 Underground structures and windowless buildings 40 Vehicles and vessels 50 Sound levels can be significantly reduced due to distance and losses through building elements. Every time the distance from the source doubles, the sound level decreases by about 6 decibels (db). Audible notification appliances are typically rated by manufacturers' and testing agencies at 10 ft (3 m) from the appliance. Subsequently, at a distance of 20 ft (6.1 m) from an audible appliance rated at 84 dba, the sound level might be reduced to 78 dba. At a closed door, the loss might be about 10 db to 24 db or more depending on construction. If the opening around the door is sealed, this might result in a loss of 22 db to 34 db or more. The reference table in the Annex is a reference of expected and typical ambient sound levels in certain locations. This table has been in the Annex for multiple code cycles. Submitter believes this to be a useful reference for designers to determine audible requirements in a specific occupancy. As such, this table should be reviewed and updated as appropriate. The submitted updates are based upon recent published reports from the Department of Health and Human Services, Centers for Disease Control and Prevention and reflect current approximations for typical ambient sound levels in certain locations. In circumstances where multiple measurements were possible, submitter used an average but excluded the maximum and minimum values. In circumstances where two measurements were available, submitter selected value closest to existing measurement. Submitter Full Name: Thomas Hammerberg

93 1198 of /30/ :10 AM Organization: Automatic Fire Alarm Association Affilliation: Automatic Fire Alarm Association Submittal Date: Mon Jun 27 09:11:32 EDT 2016

94 1199 of /30/ :10 AM Public Input No. 280-NFPA [ Section No. A.18.5 ] A.18.5 The mounting height of the appliances affects the distribution pattern and level of illumination produced by an appliance on adjacent surfaces. It is this pattern, or effect, that provides occupant notification by visible appliances. If mounted too high, the pattern is larger but at a lower level of illumination (measured in lumens per square foot or foot-candles). If mounted too low, the illumination is greater (brighter) but the pattern is smaller and might not overlap correctly with that of adjacent appliances. A qualified designer could choose to present calculations to an authority having jurisdiction showing that it is possible to use a mounting height greater than 96 in. (2.44 m) or less than 80 in. (2.03 m), provided that an equivalent level of illumination is achieved on the adjacent surfaces. This can be accomplished by using listed higher intensity appliances or closer spacing, or both. Engineering calculations should be prepared by qualified persons and should be submitted to the authority having jurisdiction, showing how the proposed variation achieves the same or greater level of illumination provided by the prescriptive requirements of Section The calculations require knowledge of calculation methods for high-intensity strobes visible notification appliances. In addition, the calculations require knowledge of the test standards used to evaluate and list the appliance. As part of the CC TG on terms, the term "light" and strobe was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 14:05:11 EDT 2016

95 1200 of /30/ :10 AM Public Input No. 748-NFPA [ New Section after A ] Annex Material for Area of Coverage fo CO A The building s emergency response plan might specify occupant notification only in the area(s) of initiation and at the control panel. Whole building evacuation might not be specified in the emergency response plan. For providing clarity to body of the same section. For buildings other than those with dwelling units, due to the varying building size and use, the danger of carbon monoxide exposure is only in the area of coverage. Visible notification should be limited to that area to limit the evacuation and disruption to the entire building s operation or business, and is to be documented as such in the emergency response plan for the protected premises. The area of coverage as defined by NFPA ; Requirements for Carbon Monoxide Detectors Carbon monoxide detectors shall be installed as specified in the manufacturer s published instructions in accordance with (1) and (2), or (3): (1)*On the ceiling in the same room as permanently installed fuel-burning appliances (2)*Centrally located on every habitable level and in every HVAC zone of the building (3) A performance-based design in accordance with Related Public Inputs for This Document Related Input Public Input No. 746-NFPA [New Section after ] Relationship Body Submitter Full Name: Anthony Mucci Organization: Tyco Integrated Security Submittal Date: Wed Jun 29 16:42:24 EDT 2016

96 1201 of /30/ :10 AM Public Input No. 253-NFPA [ Section No. A ] A New research using lights visible notification appliances with longer pulse durations shows that the existing tables for indirect signaling [Table (a) and Table (b)] are inadequate to assure reliable notification. Until additional work is done and incorporated into this Code, lights visible notification appliances used for indirect signaling and having effective intensities specified in Table (a) or Table (b) need to be short duration, high intensity to be effective for the specified area of coverage. This limitation does not apply to direct signaling such as that used in corridors in accordance with For direct signaling in corridors ( ), longer pulse appliances (up to 100 ms), such as LED lights, have been shown to be effective. Longer pulse durations might also be effective in large volume spaces that use direct signaling, as discussed in A As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 09:47:56 EDT 2016

97 1202 of /30/ :10 AM Public Input No. 255-NFPA [ Section No. A ] A Effective intensity is the conventional method of equating the brightness of a flashing light to that of a steady-burning light as seen by a human observer. The units of effective intensity are expressed in candelas (or candlepower, which is equivalent to candelas). For example, a flashing light visible notification appliance that has an effective intensity of 15 cd has the same apparent brightness to an observer as a 15 cd steady-burning light source. Measurement of effective intensity is usually done in a laboratory using specialized photometric equipment. Accurate field measurement of effective intensity is not practical. Other units of measure for the intensity of flashing lights visible notification appliances, such as peak candela or flash energy, do not correlate directly to effective intensity and are not used in this standard. Strobe lights appliances might be used to signal fire or other emergencies and might be intended to initiate evacuation, relocation, or some other behavior. Lights Visible notification appliances intended to initiate evacuation due to fire are required by the Code to be clear or white. Colored lights visible notification appliancevisible notification appliances, such as amber/yellow lights appliances, might be used in a combination system for any emergency (fire, bomb, chemical, weather, etc.) when the intent is for the signal recipient to seek additional information from other sources (voice, text displays, and so on). Example Scenario 1: A building has a fire alarm system used for general evacuation. A separate mass notification system is used to provide voice instructions and information in the event of non-fire emergencies. The fire alarm system would have white/clear strobes strobe appliances intended to alert occupants of the need to evacuate. The mass notification system would have amber/yellow strobes strobe appliances that are intended to signal the need to get additional information from either audible voice announcements, text or graphical displays, or other information sources controlled or operated from the mass notification system. In the event that both systems are activated at the same time, the strobes visible notification appliances should be synchronized per Example Scenario 2: A building has a mass notification system that provides information and instructions for a variety of emergency situations, including fire. Fire alarm initiation might be by a stand-alone fire detection system or might be an integral part of the mass notification system. In the event of an emergency, textual audible appliances are used to provide information. Visible alerting could be accomplished using one set of clear or colored strobes visible notification appliances to indicate the need to get additional information. Visible textual information can be provided by text or graphic display or other visible information appliances. The content of the audible and visible messages will vary depending on the emergency. As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:03:10 EDT 2016

98 1203 of /30/ :10 AM Public Input No. 281-NFPA [ Section No. A ] A Effective intensity is the conventional method of equating the brightness of a flashing light to that of a steady-burning light as seen by a human observer. The units of effective intensity are expressed in candelas (or candlepower, which is equivalent to candelas). For example, a flashing light that has an effective intensity of 15 cd has the same apparent brightness to an observer as a 15 cd steady-burning light source. Measurement of effective intensity is usually done in a laboratory using specialized photometric equipment. Accurate field measurement of effective intensity is not practical. Other units of measure for the intensity of flashing lights, such as peak candela or flash energy, do not correlate directly to effective intensity and are not used in this standard. Strobe lights Visible notification appliances might be used to signal fire or other emergencies and might be intended to initiate evacuation, relocation, or some other behavior. Lights Visible notification appliances intended to initiate evacuation due to fire are required by the Code to be clear or white. Colored lights, such as amber/yellow lights, might be used in a combination system for any emergency (fire, bomb, chemical, weather, etc.) when the intent is for the signal recipient to seek additional information from other sources (voice, text displays, and so on). Example Scenario 1: A building has a fire alarm system used for general evacuation. A separate mass notification system is used to provide voice instructions and information in the event of non-fire emergencies. The fire alarm system would have white/clear strobes intended to alert occupants of the need to evacuate. The mass notification system would have visible notification appliances with amber/yellow strobes lenses that are intended to signal the need to get additional information from either audible voice announcements, text or graphical displays, or other information sources controlled or operated from the mass notification system. In the event that both systems are activated at the same time, the strobes visible notification appliances should be synchronized per Example Scenario 2: A building has a mass notification system that provides information and instructions for a variety of emergency situations, including fire. Fire alarm initiation might be by a stand-alone fire detection system or might be an integral part of the mass notification system. In the event of an emergency, textual audible appliances are used to provide information. Visible alerting could be accomplished using one set of clear or colored strobes visible notification appliances to indicate the need to get additional information. Visible textual information can be provided by text or graphic display or other visible information appliances. The content of the audible and visible messages will vary depending on the emergency. As part of the CC TG on terms, the term "light" and strobe was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 14:06:52 EDT 2016

99 1204 of /30/ :10 AM Public Input No. 256-NFPA [ Section No. A ]

100 1205 of /30/ :10 AM A

101 1206 of /30/ :10 AM The prescriptive requirements of Section 18.5 assume the use of appliances having very specific characteristics of light color, intensity, distribution, and so on. The appliance and application requirements are based on extensive research. However, the research was limited to typical residential and commercial applications such as school classrooms, offices, hallways, and hotel rooms. While these specific appliances and applications will likely work in other spaces, their use might not be the most effective solution and might not be as reliable as other visible notification methods. For example, in large warehouse spaces and large distribution spaces such as super stores, it is possible to provide visible signaling using the appliances and applications of this chapter. However, mounting strobe lights visible notification appliances at a height of 80 in. to 96 in. (2.03 m to 2.44 m) along aisles with rack storage subjects the lights visible notification appliances to frequent mechanical damage by forklift trucks and stock. Also, the number of appliances required would be very high. It might be possible to use other appliances and applications not specifically addressed by this chapter at this time. Alternative applications must be carefully engineered for reliability and function and would require permission of the authority having jurisdiction. Tests of a system in large warehouse/super stores designed using the prescriptive approach of showed that high ambient light levels resulted in both indirect and direct signaling effects. The signalto-noise ratio produced by the operating visible notification appliances was low in many locations. However, with visible notification appliances located over the aisles or unobstructed by stock, indirect and some direct notification was sometimes achieved. Direct notification occurs even when occupants do not look up toward the ceiling-mounted visible notification appliances due to the extended cone of vision shown in Figure A (a). The visible notification appliance intensity and spacing resulting from the prescriptive design was generally sufficient for occupant notification by a combination of direct and indirect signaling. Testing showed that the best performance was achieved where visible notification appliances were directly over aisles or where visible notification appliances in adjacent aisles were not obstructed by stock. The performance-based design method will almost always result in aisles not having a line of visible notification appliances in them, because the spacing of visible notification appliances can be greater than the spacing of aisles. Also, it is recognized that aisles might be relocated after installation of the system. Good design practice is to place visible notification appliances over aisles, especially those that are likely to remain unchanged such as main aisles, and over checkout areas. Where reorganization of aisles results in visible notification appliances not in or over an aisle, or where that is the base design, it is important to have a clear view from that aisle to a nearby visible notification appliance. See Figure A (b). Some spaces might have marginal visible notification appliance effect (direct or indirect). However, occupants in these large stores and storage occupancies move frequently and place themselves in a position where they receive notification via the visible notification appliances. In addition, complete synchronization of the visible notification appliances in the space produced a desirable effect. Visible notification using the methods contained in is achieved by indirect signaling. This means the viewer need not actually see the appliance, just the effect of the appliance. This can be achieved by producing minimum illumination on surfaces near the appliance, such as the floor, walls, and desks. There must be a sufficient change in illumination to be noticeable. The tables and charts in Section 18.5 specify a certain candela-effective light intensity for certain size spaces. The data were based on extensive research and testing. Appliances do not typically produce the same light intensity when measured off-axis. To ensure that the appliance produces the desired illumination (effect), it must have some distribution of light intensity to the areas surrounding the appliance. ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, specifies the distribution of light shown to provide effective notification by indirect visible signaling. Figure A (a) Extended Cone of Vision. (Courtesy of R. P. Schifiliti Associates, Inc.) Figure A (b) Visible Notification Appliances in Stores. (Courtesy of R. P. Schifiliti Associates, Inc.)

102 1207 of /30/ :10 AM As part of the CC TG on terms, the term "light" was reviewed throughout the entire document for proper use. In some cases it refers to a physical appliance while other sections use it to refer to the output of an appliance. In this section the term is for an appliance and the proper term "visible notification appliance" should be used. Submitter Full Name: Rodger Reiswig Organization: Tyco SimplexGrinnell Submittal Date: Wed Jun 01 11:07:35 EDT 2016

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Item Review Dates and Times for Future Meetings/Conference Calls

Item Review Dates and Times for Future Meetings/Conference Calls Agenda Technical Committee on Protected Premises Fire Alarm and Signaling Systems (SIG-PRO) First Draft Meeting Salt Lake City, UT July 25-27, 2016 Item 16-7-1. Call to Order Item 16-7-2. Roll Call and

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Technical Committee on Record Protection (REA-AAA)

Technical Committee on Record Protection (REA-AAA) Technical Committee on Record Protection (REA-AAA) DATE: September 8, 2015 TO: FROM: M E M O R A N D U M Principal and Alternate Members of the Technical Committee on Record Protection (REA-AAA) Audrey

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Daniel O Connor (SIG-IDS), Jensen Hughes Robert Schifiliti (SIG-NAS), R.P. Schifiliti Associates William Koffel (SIG-ECS), Koffel

More information

Remove the "Exception" text to be consistent with direction provided in the MOS.

Remove the Exception text to be consistent with direction provided in the MOS. of 37 1/11/2017 7:38 AM Public Input No. 9-NFPA 88A-2015 [ Global Input ] Remove the "Exception" text to be consistent with direction provided in the MOS. The current language in 88A has numerous section

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Second Revision No. 1 NFPA [ Chapter 2 ]

Second Revision No. 1 NFPA [ Chapter 2 ] Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM of 496 10/20/2016 11:03 AM First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017.

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017. NFPA 72 SIG-PRO Meeting Minutes NFPA Technical Committee on Protected Premises Fire Alarm Systems (SIG-PRO) Second Draft Meeting, July 17 19, 2017 Charlotte, North Carolina 17-7-1 Call to Order Chair Jack

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Report on First Revision June 2014 NFPA 101

Report on First Revision June 2014 NFPA 101 101- Log #62 SAF-BSF Final Action: (9.2.3) Submitter: Doug Hohbein, Northcentral Regional Fire Code Development Committee Recommendation: Revise to read: 9.2.3 Commercial Cooking Equipment Operations.

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly

More information

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM 3 of 326 11/21/2013 1:03 PM First Revision No. 88-NFPA 72-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2011 2014 edition. NFPA 96, Standard

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

NFPA Changes

NFPA Changes Chapter 18, Notification Appliances Summary. Chapter 18 was Chapter 7 in NFPA 72-2007. Voice intelligibility moved to Annex D, Speech Intelligibility. Metric units followed by English units reversed to

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET)

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) Item No. Subject 10-10-1 Call to Order (10:00 A.M.) 10-10-2 Roll Call 10-10-3 Staff Remarks 10-10-4

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope

More information

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF FIRST DRAFT REPORT Document: NFPA 110 (EPS-AAA) Revision Cycle: A2018 Meeting Date(s):

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Change all instances of flame resistant (hypobaric) to Limited-Combustible (material) in all instances in the document. 1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Committee Input No. 1-NFPA [ Chapter 2 ]

Committee Input No. 1-NFPA [ Chapter 2 ] of 35 11/4/2016 6:18 PM Committee Input No. 1-NFPA 80-2016 [ Chapter 2 ] The committee will review and update the editions of the referenced publications to the correct edition at the Second Draft meeting.

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-26992-0 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by SABS Standards Division 1 Dr Lategan Road Groenkloof

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA

Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA Item No. Subject 14-6-1 Call to Order (8:00 A.M) 14-6-2 Roll Call 14-6-3 Approval of Agenda 14-6-4 Approval

More information

Second Correlating Revision No. 21-NFPA [ Global Input ]

Second Correlating Revision No. 21-NFPA [ Global Input ] Second Correlating Revision No. 21-NFPA 72-2017 [ Global Input ] Change "published manufacturer's instructions" and "manufacturer's instructions" to "manufacturer's published instructions" in accordance

More information

NFPA 720. Standard for the. Installation of Carbon Monoxide (CO) Warning Equipment in. Dwelling Units Edition

NFPA 720. Standard for the. Installation of Carbon Monoxide (CO) Warning Equipment in. Dwelling Units Edition NFPA 720 Standard for the Installation of Carbon Monoxide (CO) Warning Equipment in Dwelling Units 2005 Edition Copyright 2005, National Fire Protection Association, All Rights Reserved This edition of

More information

First Draft Meeting (F2017) Agenda Friday, March 11 th, :30 AM 4:00 PM ET

First Draft Meeting (F2017) Agenda Friday, March 11 th, :30 AM 4:00 PM ET NFPA 170 Technical Committee on Fire Safety and Emergency Symbols First Draft Meeting (F2017) Agenda Friday, March 11 th, 2016 9:30 AM 4:00 PM ET 1. Call to Order: 9:30 AM 2. Introductions and Attendance

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

Questions/Comments for Richard Roux from Webinar on 7/11/13

Questions/Comments for Richard Roux from Webinar on 7/11/13 Questions/Comments for Richard Roux from Webinar on 7/11/13 Below are the questions and comments from the July 11, 2013 webinar 2013 NFPA 72: Design and Installation Requirements for Mass Notification

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO

Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO Item No. Subject 13-9-1 Call to Order (8:00 A.M) 13-9-2 Roll Call 13-9-3 Approval of Agenda 13-9-4

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Protected Premises

More information

Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA

Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA Item No. Subject 14-6-1 Call to Order (8:00 A.M) 14-6-2 Roll Call 14-6-3 Approval of Agenda 14-6-4 Approval

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information