Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Size: px
Start display at page:

Download "Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96"

Transcription

1 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

2 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response Option (10 msec ) LED Zone Display Upon Entry 40 Second Dialer Delay on Stay For All Zones 6 Programmable User Codes 4 Selectable Emergency Keypad Conditions False Alarm Reduction Features 2 Programmable Trigger Output C/S Test Timer Offset 2 Alarm Event History Log Bell Supervision For NFPA 72 LED or LCD Keypad Compatible 2 Programmable Entry Delay Times Unattended and On-Line Downloading

3 XL-2G Gold Terminal Connections Zone Zone Zone Zone Zone Zone # 1 # 2 # 3 # 4 # 5 # 6 2.2K 2.2K 2.2K 2.2K 2.2K 2.2K Zones 1(+) &2(-) Zone 1 (requires 2.2k EOL resistor) 2(-) & 3(+) Zone 2 (requires 2.2k EOL resistor) 4(+) & 5(-) Zone 3 (requires 2.2k EOL resistor) 5(-) & 6(+) Zone 4 (requires 2.2k EOL resistor) 7(+)& 8(-) 8(-)& 9(+) Zone 5 (requires 2.2k EOL resistor) Zone 6 (requires 2.2k EOL resistor) Maximum loop resistance 100 ohms Programmable loop response 10ms. or 280ms.

4 Panic Circuit or Keyswitch 8 10 NON SUPERVISED Panic Normally open, NON-SUPERVISED 24 hour hardwired panic circuit can be programmed as audible or silent. A momentary device recommended. (max. 3 feet from panel on UL installation) Terminals may also be used to connect a keyswitch which will toggle to arm and disarm the control panel Earth Ground Terminal # 11 Connect to cold water pipe utilizing #18 awg wire at 15 foot maximum.

5 Keypad Connections Neg. Data Data Pos. In Out Maximum of 4 keypads, max. loop length is 500 ft. with 22 awg wire 4600SM 4600RM (LCD) 30mA current draw each Keypads should be connected prior to power up. Regulated Power Negative Positive 500 ma at VDC includes power used by keypads and smoke detectors.

6 Smoke Detector Power OR Trigger #1 Output Positive Negative Accepts 4 wire smoke detectors only, approximately 50mA of current for powering all smoke detectors and E.O.L. relay ( Recommended FBI model 620). *These terminals adhere to fire verification logic* * when used to power smoke detectors.* Two Trigger Outputs Terminals 15+ & 16- may also be used as trigger #1 output Trigger Outputs #1 & #2 may also be connected using the XL-2GTC trigger connector cable

7 Telephone Line Connections Green Red Brown Gray Telco Tip Telco Ring Home Tip Home Ring Plug into USOCRJ31X jack or CA31A(Canadian) Do not connect to phone line with call waiting, unless call waiting interrupt numbers are programmed into phone sequence. *Do not connect to phone line with Fax or modem in use* Constant DC Power Terminal # 21 Constant unregulated VDC, powers devices using constant DC voltage Connected to Bell fuse (F3)

8 Bell Output Positive Negative Total output 1 AMP VDC(Res.) or (comm.) Constant voltage for burglary and pulsed for fire. (750mA for UL) NFPA 72 Signaling Device Supervision For Mechanical Bells, Self Contained Siren/Speakers, Speakers Connected To Siren Driver Program Loop # 6 As a Fire Zone An Open Circuit (Not A Short) will initiate a Fire Trouble Condition

9 22+ NFPA 72 Signaling Device Supervision XL-2G FBII VS-299 Voice Siren Driver VS-299 Speaker Bell Output 23-10K 1/4Watt Siren Driver (+) (-) To 24 Hour Zone FBII 679S Siren Driver To 24 Hour Zone (+) 22+ Bell Output S Siren Driver 2.2K EOL (-)

10 Transformer Connect 12 VAC 20VA transformer, utilizing 18 awg wire max 15 feet from panel. Use unswitched 120 VAC outlet Backup Battery: Red(+) and Black(-) flying leads connected to 12VDC 4-6 AH gel cell. Battery test approx. every 4.5 minutes. Low battery condition occurs at 11VDC. Ground Start Recommended is the use of an FBII module 117. SYSTEM STABILIZATION ON POWER UP Two Minute Delay Reduces Motion Detector False Alarms

11 XL-2G Keypad Programming 01 Primary Telco # L5 L6 L7 L8 L9 L10 L11 L12 02 Secondary Telco# L5 L6 L7 L8 L9 L10 L11 L12 03 Callback # L5 L6 L7 L8 L9 L10 L11 L Valid B = * C = 3 Sec Pause E = *70 (Touch-tone) or 1170C (Rotary) F = 800 prefix

12 04 Dialer Options 1601 L1 Dialer Formats Dialing Format Pulse Touchtone CS Reporting Format 0 Standard Or 4 X 2 1 Standard Or 4 X 2 2 Extended 3 Extended 4 Partial Extended 5 Partial Extended 8 None No Dialer/ Local System

13 04 Dialer Options 1601 L2 Central Station Receiver Type E FBI, Rad Handshake Typical CS Format Pulse Speed Frequency Parity Receiver 10 PPS 20 PPS 40 PPS 1400 HZ 2300 HZ 0 FBI, Ademco,Silent Knight 1 FBI 2 FBI 3 FBI 4 FBI, Silent Knight, Adcor,Ademco 5 FBI, Radionics 6 FBI, Franklin,Sescoa,Dti,Varitech 7 FBI, Radionics 8 FBI 9 FBI A FBI B FBI, Radionics

14 04 Dialer options 1601 L3 Message length, swinger shutdown FBI, Rad CS Reporting Format Lenth Swinger Dialing Pulse Type 3 X 1 3 X 2 4 X 1 4 X 2 Shutdown U.S European A B C D E F * For UL installations swinger shutdown must not be selected*

15 04 Dialer Options 1601 L4 System options : Keypad panic silent/audible, C/S split reporting, C/S test, bell test Keypad Panic C/S Split Cancel Code Bell Ringback System Bell Audible / Silent Reporting Silent / Audible Test A B C D E F

16 05 Keypad Conditions 1270 L1 Enable: Keypad Panic(* & #), System Stay Mode- Dialer Delay, Stay Mode- Bell Instant Keypad Aux (1&3) Digit Keypad Stay Mode Stay Mode Keypad Auxiliary Panic Dialer Delay Bell Instant Audible / Silent A B C D E F

17 05 Keypad conditions 1270 L2 Panic/keyswitch, hard wired panic silent/audible, A/C Line Frequency, Keypad Quick Commands ZONE # 7 INPUT A/C Quick Panic Keyswitch Line Frequency Commands Digit (Audible / Silent) 50Hz / 60Hz Enabled A C D E

18 05 Keypad Conditions 1270 L3 C/S Test Timer Interval and European Ring Detect Digit C/S Test Time Interval European 1 Hour 24 Hour Weekly 27 Days 60 Days 90 Days Ring Detect A B C E F *All test time intervals are reset after a successful CS report *

19 05 Keypad conditions 1270 L4 Restore follows bell or loop, CS test ringback User on line, Instant Arming Enabled Digit Restore After User-On C/S Test Keypad Ringback Instant Bell Loop Line Silent Audible Arming A B C D E F

20 06 System Time-outs 665F L1 Entry delay #1: Zones 1-3 only 30 seconds L2 Exit delay System wide 60 seconds Digit Entry Time-outs 0 1 Second 1 5 Seconds 2 10 seconds 3 15 seconds 4 20 seconds 5 25 Seconds 6 30 Seconds 7 35 Seconds 8 40 Seconds 9 45 Seconds A 50 Seconds B 55 Seconds C 1 Minute D 1 Minute 5 Seconds E 1 minute 10 Seconds F 3 Minutes Digit Exit Time-outs 0 1 Second 1 10 Seconds 2 20 seconds 3 30 seconds 4 40 seconds 5 50 Seconds 6 1 Minute 7 1 Minute 10 Seconds 8 1 Minute 20 Seconds 9 1 Minute 30 Seconds A 1 minute 40 Seconds B 11minute 50 Seconds C 2 Minutes D 2 Minutes 10 Seconds E 2 Minutes 20 Seconds F 3 minutess

21 06 System Time-outs 665F L3 Burglary Bell Cutoff 15 Minutes L4 Fire Bell Cutoff Infinite Digit Burglary & Fire Bell Time-outs 1 3 Minutes 2 6 Minutes 3 9 Minutes 4 12 minutes 5 15 Minutes 6 18 Minutes 7 21 Minutes 8 24 minutes 9 27 Minutes A 30 minutes B 33 Minutes C 36 minutes D 39 Minutes E 42 minutes F Infinite

22 07 Miscellaneous 2C05 System Options L1 Entry Delay # 2 Zones 4-6 only ( Valid choices are selected from question # 6 ) L2 Ring Count for panel pick up for a remote communications session & dialer delay Digit Ring Count For Dialer Pickup Delay 0 Remote Communications Disabled 1 2 Rings 2 4 Rings 3 6 Rings 4 8 Rings 5 10 Rings 6 12 Rings 7 14 Rings 8 Remote Communications Disabled 9 2 Ringss A 4 Rings B 6 Rings C 8 Ring D 10 Rings E 12 Rings F 14 Rings

23 07 Miscellaneous 2C05 System Options L3 Smoke Power or Trigger #1 output types L4 Trigger # 2 output types Valid Entries Description of Operation 0 = Smoke power output Used in Fire verification to reset smokes 1 = Fire bell on Follows fire bell timer 2 = Burg bell on Follows burg bell timer 3 = Line seizure Follows line seizure relay 4 = Ready Follows ready LED 5 = Armed Follows armed LED (steady states only) 6 = Exit time ON during exit time 7 = Entry time ON during entry time 8 = Fire only latch Goes ON with Fire bell, OFF with code 9 = Burg only latch Goes ON with Burg bell, OFF with code A = Strobe B = Panic alarm C = Shock asterisk reset D = Shock code reset E = Duress Goes ON steady w/burg, pulse w/fire OFF with code Zone 7 (hardwired panic) ON with Alarm OFF with code * Activates for 2-6 seconds Normally sinking current: arming floats for 2-6 seconds Pulse 2-6 Sec. Following Duress Code

24 Unless otherwise specified, trigger output normally floats and actively sinks on activation 08 Account # 1 Valid entries: 0-9 & B - F 09 Account # 2 Valid entries: 0-9 & B - F

25 10 Zone programming 2031 L1 & L2 #1 Zone Type, L3 & L4 C/S Code Burglary (Controlled ) Zones Digit Zone Type Zone Options Instant Delay Int. Follower Chime Day Bypass In Stay Fast Zone 10 ( None W/O Options ) A 1B 1C 1D 20 ( None W/O Options ) ( None W/O Options ) C 4D 24 Hour Zone Types 24 Hour Zone Options 24 Hour Alarm Fire 24 Hour Trouble Audible Silent (Always Audible) 89 8A

26 11 Zone programming L1 & L2 Zone type for zone # 2 41 ( Interior ) L3 & L4 CS zone alarm code Zone programming L1 & L2 Zone type for zone # 3 10 ( Perimeter ) L3 & L4 CS zone alarm code Zone programming L1 & L2 Zone type for zone # 4 10 ( Perimeter ) L3 & L4 CS zone alarm code Zone programming L1 & L2 Zone type for zone # 5 10 ( Perimeter ) L3 & L4 CS zone alarm code Zone programming L1 & L2 Zone type for zone # 6 10 ( Perimeter ) L3 & L4 CS zone alarm code 36

27 16 Ambush/AC Loss L1 & L2 Ambush C/S code (user # 6) Immediate and non abortable L3 & L4 A/C Loss C/S code Reported 15 min. after detection AA AA 17 Panic/Low Battery L1 & L2 Panic C/S code (keypad & remote) 22 Immediate and non abortable L3 & L4 Low Battery C/S code AA Reported 4 min. after detection 18 Open/Close, 24 Hour test L1 Opening C/S code (1st digit of 4x2 code) 2nd digit is the user slot number 1-6 L2 Closing C/S code (1st digit of 4x2 code) 2nd digit is the user slot number 1-6 A A L3 & L4 C/S test code AA

28 19 Bypass, Restore, Trouble, Cancel L1 Bypass C/S code (1st digit of 4x2) A Reports zone bypass upon arming (2nd digit from zone code) L2 Restore C/S code (1st digit of 4x2) A Reports 24 hour and burglary zones(2nd digit from zone code) L3 Trouble C/S code (1st digit of 4x2) F Reports Fire trouble or Day trouble (2nd digit from zone code) L4 Cancel C/S code (1st digit of 4x2) 8 Sent if after a violation of a controlled zone, a user code is entered. If the zone is still violated, entry of a user code will transmit cancel code. If the zone is programmed for restoral, then restore code will be sent when loop restores. 20 Keypad Fire/Aux L1 & L2 Keypad fire C/S code (7 & 9) AA C/S Code can vary from any other fire zones L3 & L4 Keypad Auxiliary C/S code (1 & 3) AA

29 21 C/S Test Timer Offset L1 & L2 C/S Offset in Hours L3 & L4 C/S offset in Minutes AA AA Allows the setting of the time for C/S test to occur offset from the time at installation 00 Installer Code 2468 L1 - L4 This code is used to enter system keypad programming and may only be accessed directly

30 XL-2G Gold Zone Descriptor Programming Question # 22 (zone 1) through Question # 27 (zone 6) L5 L6 L7 L8 L9 L10 L11 L12 Quest: 22 Front Door 7 increments the character at the cursor * 7 scrolls forward (up) through character set 9 Decrements the character at the cursor # 9 scrolls backwards through character set 0 Inserts space and advances cursor Code Instant moves cursor to the left one space moves the cursor to the right one space Available Characters

31 ! #$%& ( )*+-./ ;=@ABCDEFGHIJKLMNOPQRSTUVWXYZ XL-2G Gold Summary Of System Keypad Programming Enter programming mode Code * (installer code) 1 Movement between questions * followed by question # ( i.e.: *06) Advance Between locations (Enter) # D Data entry 0-9 valid entries A T Ques : 11 Loc: 1 A Code 1 A B Code 2 Data: 5 C Code 3 Q D Code 4 U E Code 5 E F Code 6 S T +1 Arm +2 Stay +4 Instant +8 AC/LB Ready +1 Zone 1 +2 Zone 2 +4 Zone 3 +8 Zone Zone 5 Zone 6 Exit system program mode Stay button to exit

32 XL-2G Gold Keypad Installer Modes Installer Mode 1 (keypad programming) a) Pressing 1 & 3 together in this mode will default system to original factory program b) Pressing 7 & 9 together in this mode will default ONLY end user codes Installer Mode 2 ( system log view) a) View last 2 alarm memory conditions starting with oldest event, the # will advance to most recent event. Installer Mode 3 (unattended downloading) a) enter unattended download mode b) system enters keypad programming, proceed to question 03 and program Downloader phone number c) Proceed to question 02 and enter 6 digit computer designated account number d) Press the Stay button, the control panel will now perform the desired download operation. Installer Mode 4 (on line download) a) Call person at download computer using telco line connected to panel b) Verbally identify the panel account number to operator c) Enter [Code] [*] [installer] [4] or #9 (if programmed) d) Hang up telephone

33 XL-2G Gold User Functions Arming/Disarming Stay Arming Stay/Instant Arming [Enter any valid user code] [Stay] [Enter any valid user code] [Stay] [Instant] [Enter valid user code] Bypass [Bypass] [Enter valid user code][zone #] Quick Bypass [Bypass] [Zone #] User Code Programming [Code] [Enter master user code (slot #1)] [User slot # to program] [Enter 4 digit code] User Code Deletion [Code][Enter master user code][user #][*] Quick Arming [ # ] [ 1 ] Quick Forced Arming [ # ] [ 2 ] Toggle Chime [ # ] [ 6 ] On-Line Downloading [ # ] [ 9 ] Ambush [ Enter user code slot # 6 ] Keypad Panic [ * ] & [ # ] at the same time ** Keypad Fire [ 7 ] & [ 9 ] at the same time ** Auxiliary [ 1 ] & [ 3 ] at the same time ** ** Functions are used ONLY on the 6805, 6615 & 4600RM keypads

34

Property of Monitronics Inc

Property of Monitronics Inc Enter Program Press CODE key + * + 2468 + 1 (also try 2121) Installer Options Move to location Program location Exit Program Default Panel Hex Program Code + * + Installer Code + 1 = Enter Programming

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E...

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E... 5$1*(5( DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS General Description... 2 Standard and Optional Parts List... 2 Feature Definitions... 3 Comments about the 8600E... 4 Terminal

More information

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION...2 STANDARD AND OPTIONAL PARTS LIST...2 FEATURE DEFINITIONS...3 TERMINAL DRAWING AND SPECIAL NOTES...4

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program Program Location 1. Hold 8 key for 3 seconds, keypad will beep 2. Enter 4 5 6 7 8 9, display should show dash on display 1. Press [B/A] key display will show 3 dashs 2. Enter 3-digit location

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

GEM-P800 Programming Instructions

GEM-P800 Programming Instructions NOTE After 15 minutes of keypad inactivity the keypad will emit a steady tone indicating the panel has been left in Dealer Program Mode Enter Dealer Code to exit or press the key to return to Dealer Program

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

FBII Security System. Programming Guide. Version 2.X. N9967PRV3 4/04 Rev. A

FBII Security System. Programming Guide. Version 2.X. N9967PRV3 4/04 Rev. A FBII Security System OMNI -624 Version 2.X Programming Guide N9967PRV3 4/04 Rev. A CONTENTS INSTALLER MODE 1 COMMANDS... 3 INSTALLER MODE 1 (PROGRAMMING MODE)... 4 SUBMODE 1: SYSTEM OPTIONS... 4 Telephone

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

First Alert 1200C Installer Notes M. Leuck

First Alert 1200C Installer Notes M. Leuck First Alert 2C Installer Notes M. Leuck. Programming can done by standard keypads 2. Enter programming with Installer Code + 8 + + 3. Another method of entering programming: Power system down, then back

More information

Installation Instructions

Installation Instructions g 466-2339A October 2009 2009 GE Security, Inc. Introduction This is the GE. Installations should only be done by trained professionals. Use this document to install the system with default settings that

More information

D6500 reports are shown in typewriter style letters. For example, AC FAILED indicates the report sent when the panel reports an AC power failure.

D6500 reports are shown in typewriter style letters. For example, AC FAILED indicates the report sent when the panel reports an AC power failure. Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable. However, Radionics, Inc. assumes no responsibility for inaccuracies

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

INSTALLATION MANUAL & PROGRAM RECORD SHEET

INSTALLATION MANUAL & PROGRAM RECORD SHEET INSTALLATION MANUAL & PROGRAM RECORD SHEET TABLE OF DESCRIPTION CONTENTS PAGE WIRING MANUAL 2-6 MENU CHART 7 INSTALLER FUNCTIONS 8 MENU 1 SYSTEM TIMES 9 MENU 2 ZONE CONFIGURATION 10-14 MENU 3 SYSTEM OPTIONS

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

INSTALLATION MANUAL PC56O. Version 1.OA

INSTALLATION MANUAL PC56O. Version 1.OA INSTALLATION MANUAL PC56O Version 1.OA TABLE OF CONTENTS INTRODUCTION 3 Features... 3 Specifications... 3 INSTALLATION 4 Mounting the Control Panel... 4 Mounting the Keypad... 4 Wiring... 5 Burglary Zone

More information

NX-4V2 Control Panel Installation Instructions

NX-4V2 Control Panel Installation Instructions 4V2 Control Panel Installation Instructions Introduction This is the 4V2-Control Panel Installation Instructions. Installations should only be done by trained professionals. Use this document to install

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account

More information

FBII Security System. Installation and Setup Guide. Version 2.0. N9938V4 8/06 Rev. A

FBII Security System. Installation and Setup Guide. Version 2.0. N9938V4 8/06 Rev. A FBII Security System OMNI -848 OMNI -848EU Version 2.0 Installation and Setup Guide N9938V4 8/06 Rev. A THANK YOU for your purchase of the OMNI -848 Security System. The purpose of this manual is to give

More information

INSTALLATION MANUAL PC15OO

INSTALLATION MANUAL PC15OO INSTALLATION MANUAL PC15OO This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2)

More information

CC488. Quick Reference Guide Solution Ultima 880

CC488. Quick Reference Guide Solution Ultima 880 CC488 EN Quick Reference Guide Solution Ultima 880 CC488 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty

More information

Radionics D4112 Program Sheet

Radionics D4112 Program Sheet Programming only by downloading, 5200 Programmer or 5100 "Wand" Programmer Plug programmer in and momentarily short Reset Pin to Terminal 25 to enable program mode 1. Account Account # I I I I I (0 to

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

System Programming Guide

System Programming Guide & System Programming Guide Software Versions 4.4 (728ULT) and 4.1 (738ULT) Installer Code (Default - 728 Ultra: 282828; 738 Ultra: 383838) Full access to programming, except user access codes (PINs). No

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

AXI LED USER MANUAL (REV. 1.0)

AXI LED USER MANUAL (REV. 1.0) Security & Home Automation System AXI LED USER MANUAL (REV. 1.0) CONTENTS PREFACE FEATURES LED KEYPAD OUTLOOK 1.0 LIGHT INDICATION 1 2 4 6 CHAPTER 1: ALARM SYSTEM CONTROL 1.0 USING LED KEYPAD 1.0.1 ARMING

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

GEM-P800. Control Panel/Communicator. Installation Instructions

GEM-P800. Control Panel/Communicator. Installation Instructions GEM-P800 Control Panel/Communicator Installation Instructions NAPCO 2002 WI850C 9/02 WI850C GEM-P800 Installation Instructions Table of Contents General Information GEM-P800 Features General Information...

More information

CC408. Quick Reference Guide Solution 880

CC408. Quick Reference Guide Solution 880 CC408 EN Quick Reference Guide Solution 880 CC408 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

NetworX Series NX-4V2 Control Panel Installation and Startup

NetworX Series NX-4V2 Control Panel Installation and Startup NetworX Series NX-4V2 Control Panel Installation and Startup 2005 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every

More information

INSTALLATION MANUAL PC25OO

INSTALLATION MANUAL PC25OO INSTALLATION MANUAL PC25OO NOTES ON UL INSTALLATION This equipment is UL listed in accordance with UL standard 1023 (Household Burglar Alarm System Units), UL standard 985 (Household Fire Warning Units)

More information

ELECTRONICS LINE S TECHNICAL SUPPORT DEPARTMENT: (972)

ELECTRONICS LINE S TECHNICAL SUPPORT DEPARTMENT: (972) Summit 3208GLD Installation, Operation and Programming Electronics Line (E.L.) Ltd. www.elecline.com ELECTRONICS LINE S TECHNICAL SUPPORT DEPARTMENT: (972)-3-9211110 Electronics Line (E.L.) Ltd. reserves

More information

SECURITY SYSTEM 4110DL. Programming Form Programming Form Programming Form 4110DL-PRV3 10/96

SECURITY SYSTEM 4110DL. Programming Form Programming Form Programming Form 4110DL-PRV3 10/96 SECURITY SYSTEM 4110DL Programming Form Programming Form Programming Form 4110DL-PRV3 10/96 4110DL PROGRAMMING FORM FIELD FUNCTION [ ] = Default Value SYSTEM OPTIONS (*20-*28) *20 MASTER SECURITY CODE

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Quick Programmer s Manual

Quick Programmer s Manual Version 2.604 (31/03/05) p1 Quick Programmer s Manual 2005. Inner Range Pty. Ltd. Part Number: 630048V2 p2 Version 2.604 (31/03/05) TABLE OF CONTENTS. 1. PROGRAMMING FLOWCHART. The following flowchart

More information

Content. 1. Introduction to the IDS Features Installation and Wiring End-of-Line Resistors/Tamper per Zone...

Content. 1. Introduction to the IDS Features Installation and Wiring End-of-Line Resistors/Tamper per Zone... 1 2 Content 1. Introduction to the IDS 805... 7 1.1 Features...7 2. Installation and Wiring...8 3. End-of-Line Resistors/Tamper per Zone...9 4. Connecting the Telephone Communicator...10 5. Programmable

More information

EasyLoader. Integrated Alarm Control/Communicator. Year 2000 ready. Express Installation and Operation Manual. Edition II

EasyLoader. Integrated Alarm Control/Communicator. Year 2000 ready. Express Installation and Operation Manual. Edition II EasyLoader AV-2004, AV-2048 Integrated Alarm Control/Communicator Year 2000 ready Express Installation and Operation Manual Version 3.06 (with very slow zone) Edition II This product is subject to continual

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

2000 Series. Program Entry Guide. Control Panels

2000 Series. Program Entry Guide. Control Panels 2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control

More information

Training Manual Multi-Language with Wireless

Training Manual Multi-Language with Wireless Training Manual Multi-Language with Wireless Installer Training Firmware Version 2.3 X16 Stock Code: 860-1-473-X16 X64 Stock Code: 860-1-864-XS 2 Contents IDS X Series Training V2.3 Contents Contents 3

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

SPECIFICATIONS Control Panel Specifications Remote Keypad Specifications 21 zones including: (PC3000RK) Audible alarm output:

SPECIFICATIONS Control Panel Specifications Remote Keypad Specifications 21 zones including: (PC3000RK) Audible alarm output: SPECIFICATIONS Control Panel Specifications 21 zones including: 16 fully programmable supervised zones (EOL resistors) Supervised fire zone 1 auxiliary normally open zone 3 keypad activated zones Audible

More information

GEM-P801 Control Panel/Communicator For use with the GEM-RP8 or the GEM-K800 Keypads. Installation Instructions

GEM-P801 Control Panel/Communicator For use with the GEM-RP8 or the GEM-K800 Keypads. Installation Instructions 333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440 Publicly traded on NASDAQ Symbol: NSSC GEM-P801 Control Panel/Communicator For

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

NetworX Series NX-6 CONTROL PANEL. Installation and Startup

NetworX Series NX-6 CONTROL PANEL. Installation and Startup NetworX Series NX-6 CONTROL PANEL Installation and Startup 25 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every possible

More information

VISTA-100 Commercial Fire & Burglary Partitioned System

VISTA-100 Commercial Fire & Burglary Partitioned System VISTA-100 Commercial Fire & Burglary Partitioned System 4XLFN6WDUW Step-by Step Programming Procedure Single and Multiple Programming Forms System Worksheets FIRE FIRE * PULL VISTA-100PR Rev B 4/99 TABLE

More information

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher IMPORTANT WARNING:This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

System Introduction. 1.1 Specifications

System Introduction. 1.1 Specifications System Introduction S E C T I O N 1 1.1 Specifications Downloading Software Support PC585 uses DLS-1 v6.5 and up. Flexible Zone Configuration Four fully programmable zones; system expandable to eight zones

More information

R E G E N C Y Model 2615 Control/Communicator. Installation Manual. Part Number , Rev. A Initial Release Date: March 1995 Revised August 1998

R E G E N C Y Model 2615 Control/Communicator. Installation Manual. Part Number , Rev. A Initial Release Date: March 1995 Revised August 1998 R E G E N C Y Model 2615 Control/Communicator Installation Manual Part Number 150863, Rev. A Initial Release Date: March 1995 Revised August 1998 Interactive Technologies, Inc. TE CHNO LO G IES Security

More information

CC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom

CC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom CC880/LP880, SC8016 EN Operators Guide Solution-16, Solution-16 Safecom CC880/LP880, SC8016 Operators Guide EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch

More information

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging 1.1 Specifications System Introduction S E C T I O N 1 Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master,

More information

System Introduction. 1.1 Specifications S E C T I O N 1

System Introduction. 1.1 Specifications S E C T I O N 1 System Introduction S E C T I O N 1 1.1 Specifications Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 37 Access Codes: 32 User, 1 System Master, 2 Partition Master

More information

Installation Instructions

Installation Instructions Model S5832SG Control Panel 8 to 32 Zones Installation Instructions Table of Contents Table of Contents Compliance and Regulatory Information...i Installing and Connecting the Control Panel... 1-5 Sierra

More information

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1 1.1 PC5015 Specifications System Introduction S E C T I O N 1 Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master, 2 Duress and 1 maintenance

More information

Contact ID as of 2/2/2015

Contact ID as of 2/2/2015 Contact ID as of 2/2/2015 100 Medical Zone A non-specific medical exists 101 Personal Emergency Zone Emergency Assistance request 102 Fail to report in Zone A user has failed to activate a monitoring device

More information

Control Panel ICP-SOL2-P/ICP-SOL3-P. en User's Guide

Control Panel ICP-SOL2-P/ICP-SOL3-P. en User's Guide Control Panel ICP-SOL2-P/ICP-SOL3-P en User's Guide Control Panel Table of Contents en 3 Table of contents 1 Introduction 5 2 Specifications 6 3 Codepad Introduction 7 3.1 Codepad 7 3.2 Quick Codepad

More information

INSTALLATION MANUAL. PC3OOO Version 7.6W

INSTALLATION MANUAL. PC3OOO Version 7.6W INSTALLATION MANUAL This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device

More information

XT30/XT50 PROGRAMMING PART 2. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 2. Bell Options

XT30/XT50 PROGRAMMING PART 2. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 2. Bell Options Slide 1 XT30/XT50 Basic Training Programming- Part 2 Slide 2 Objectives After completing this course you will: 1) Understand how to prepare the panel for programming and how to access the built-in programmer.

More information

Summit 3208GLD USER MANUAL. Electronics Line

Summit 3208GLD USER MANUAL. Electronics Line Summit 3208GLD USER MANUAL Electronics Line Table of Contents 1: Introduction... 2 2: Overview... 3 3: Keypad Functions... 4 3.1: Keypads... 4 3.2: 3108 LCD Keypad Layout... 4 4: Basic System Operation...

More information

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand 6 Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd Operating Guide 1 Proudly Designed and Manufactured in New Zealand CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR

More information

EasyLoader AV-2004, AV Integrated Alarm Control/Communicator. Year 2000 ready. Express Installation and Operation Manual. Version 2.

EasyLoader AV-2004, AV Integrated Alarm Control/Communicator. Year 2000 ready. Express Installation and Operation Manual. Version 2. EasyLoader AV-2004, AV-2048 Integrated Alarm Control/Communicator Year 2000 ready Express Installation and Operation Manual Version 2.17 Edition II This product is subject to continual enhancement and

More information

FBII Security System. Programming Guide. Version 2.X. N9938PRV3 4/04 Rev. A

FBII Security System. Programming Guide. Version 2.X. N9938PRV3 4/04 Rev. A FBII Security System OMNI -848 OMNI -848EU Version 2.X Programming Guide N9938PRV3 4/04 Rev. A CONTENTS INSTALLER SUBMODE 1: SYSTEM OPTIONS... 4 Central Station Phone Numbers... 4 Pager Phone Numbers...

More information

Sentry 4 Zone Alarm Panel User Manual

Sentry 4 Zone Alarm Panel User Manual TM TM Sentry 4 Zone Alarm Panel User Manual PLEASE NOTE: A 16Vac / 16VA Transformer MUST be used with this product. Contents 1. Introduction. 2. Programming a Remote. 3. Deleting all Remote s. 4. The siren

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

IDS S E C U R I T Y IDS816. User Manual MANUAL NO C ISSUED APRIL 2005 VERSION 2.00

IDS S E C U R I T Y IDS816. User Manual MANUAL NO C ISSUED APRIL 2005 VERSION 2.00 INHEP DIGITAL IDS S E C U R I T Y IDS816 User Manual MANUAL NO. 700-283-01C ISSUED APRIL 2005 VERSION 2.00 Contents 1. Introduction to the IDS816... 4 2. Understanding the Keypad Indicators... 4 3. Programmable

More information

/10 Rev A

/10 Rev A VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev A Your Honeywell security system is designed for use with devices

More information

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A $'(0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHP 8VHU*XLGH N7003V3 5/04 Rev A 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...5 Fire Protection...6 Burglary Protection...6 Alarms...6

More information

Control Panel ICP-SOL2-P/ICP-SOL3-P. en User's Guide

Control Panel ICP-SOL2-P/ICP-SOL3-P. en User's Guide Control Panel ICP-SOL2-P/ICP-SOL3-P en User's Guide Control Panel Table of Contents en 3 Table of contents 1 Introduction 5 2 Specifications 6 3 Codepad Introduction 7 3.1 Codepad 7 3.2 Quick Codepad

More information

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98 USER'S GUIDE FA1220CV 2-Partition Security System N7003-1V2 7/98 SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Fire Protection... 4 Alarms... 5 Emergency

More information

Digiplex Control Panel (DGP-848) - V4.0

Digiplex Control Panel (DGP-848) - V4.0 Digiplex Control Panel (DGP-848) - V4.0 DGP-848 Reference and Installation Manual TABLE OF CONTENTS INTRODUCTION... 4 1.0 1.1 Features... 4 1.2 Specifications... 4 INSTALLATION... 5 2.0 2.1 Location &

More information

8-zone Expansion Module

8-zone Expansion Module 8-zone Expansion Module APR3-ZX8 SECTION [001] : General Options Option OFF ON [1] Tamper Recognition ON = Input 8 (Z8) becomes tamper input = Default setting Disabled Enabled [2] PGM Deactivation After

More information

ICP-CC408 ICP-CC408 EN. Control Panel. User s Guide

ICP-CC408 ICP-CC408 EN. Control Panel. User s Guide ICP-CC408 EN User s Guide ICP-CC408 Control Panel ICP-CC408 User's Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc, ( Bosch

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

4-PGM Expansion Module

4-PGM Expansion Module 4-PGM Expansion Module APR3-PGM4 = Default setting SECTION [001] : General Options SECTION [002] : PGM Options Option OFF ON Option OFF ON [1] Future Use N/A N/A [1] PGM1 Deactivation After Deactivation

More information

Solution-8248 Installation Manual ISSUE 1.16

Solution-8248 Installation Manual ISSUE 1.16 Solution-8248 Installation Manual ISSUE 1.16 MA880I Solution- 8248 This page has been included for you to cut out and insert into the spine of the folder Installation Manual ISSUE 1.16 www.dsworld.com

More information

Series. NX-4-EUR Control Panel. Installation manual

Series. NX-4-EUR Control Panel. Installation manual g GE Security NetworX TM Series NX-4-EUR Control Panel Installation manual CONTENTS CONTENTS...2 GENERAL INFORMATION...4 ORDERING INFORMATION...4 FEATURE DEFINITIONS...5 PROGRAMMING THE NX-4 KEYPADS...12

More information

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3

More information

Power Wave LCD Keypads. Users Operating and Programming Guide Version 2.00

Power Wave LCD Keypads. Users Operating and Programming Guide Version 2.00 Power Wave LCD Keypads CR-16S CR-16M Users Operating and Programming Guide Version 2.00 P/N 7102265 Rev. C N.A May 2003 Contents Introduction...4 Meet the PowerWave Alarm Control System... 4 Typical Alarm

More information

SMS8 Alarm Control Panel

SMS8 Alarm Control Panel SMS8 Alarm Control Panel 8 Zone Alarm Control Panel with LCD Keypad, Inbuilt Dialler for Back to Base Monitoring and SMS Messaging. Easy Operation Dialler SMS Messaging I n s t r u c t i o n s N517 Code

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction.

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction. INTRODUCTION The PC4020 is a highly flexible and versatile control which will enable the installer to meet the most demanding security requirements. The heart of the system is the main control panel, designated

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

MG Partition 64-Zone Wireless Console with GPRS/GSM Version 1.6. Section Programming Guide

MG Partition 64-Zone Wireless Console with GPRS/GSM Version 1.6. Section Programming Guide MG6250 2-Partition 64-Zone Wireless Console with GPRS/GSM Version.6 Section Programming Guide Things You Need to Know About this Programming Guide The MG6250 All-in-one Wireless Console can be programmed

More information

Elite 64 Version 64 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Elite 64 Version 64 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand 2 Elite 64 Version 64 Zone Controller Arrowhead Alarm Products Ltd Operating Guide Proudly Designed and Manufactured in New Zealand 1 CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR

More information

ICP-CC488 ICP-CC488 EN. Control Panel. User s Guide

ICP-CC488 ICP-CC488 EN. Control Panel. User s Guide ICP-CC488 EN User s Guide ICP-CC488 Control Panel ICP-CC488 User's Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc. ( Bosch

More information