109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

Size: px
Start display at page:

Download "109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:"

Transcription

1 109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr #500 rth Miam FL (305) Owner s Address: _ Owner's Phone Number: Property Being Evaluated: E1 Shoppes At Lago Mar SW 72nd St Miami FL Property Address: Valter Perez Technician : Certified: Yes Certification Type: FASA Issued: Approving Agency : Contact:Telephone: Miami Dade County Fire Rescue _ (786) Time Of Inspection: 11:00 am 07/05/2016 Date: SYSTEM TYPE Remote Station Local Proprietary Central Station Date Issued: Security Partners Name: UL Certificate.: Expires: SERVICE Monthly Quarterly Semiannually Annually Other (Specify) MONITORING ENTITY Telephon e: (188) Monitori ng Account Ref..: TYPE TRANSMISSION Built in UDACT Digital RF Slave Dialer Type: AES 7788F Battery Size: 8ah Visual Functional Pass Fail Control Unit Control Unit Manufacturer: Silent knight Model.: 5104 Software Rev: Number of Circuits: 1 Style: Last Date System Had Any Service Performed: 02/2014 Last Date Software or Configuration Was Revised: Serial :_ SYSTEM POWER SUPPLIES (a) Primary (Main): minal Voltage: 120 VAC Amps: 2.0 Overcurr ent Protectio n: Type: Breaker Amps: 20 Location (of Primary Supply Panelboard): Disconnecting Means Location: DYNA-4793 Breaker Lock Present: Breaker Labeled: (b) Secondary (Standby): Storage Battery Amp-Hr Rating: Calculated capacity to operate system, in hours: Engine-driven generator dedicated to fire alarm system: Location of fuel storage: SPRINKLER SYSTEM Inspection Completed on: 07/2016 Red Tag Green Tag Monthly Quarterly Semiannually Annually Completed by (Company Name): DynaFire SYSTEM COMPONENTS Yes Networked System: Network Functions: Remote Annunciator: Annunciator Functions: NAC Panels: NACs Function: Beside FACP Circuit #8 Yes 8 Ah 24 Hours Battery Size: Voice Evacuation: Remote Microphone: Microphone Functions: TYPE BATTERY Visual: Functional: BattQty: Pass: Quantity of nodes:_ Type: Type: Qty: Type: Qty: Fail: Type:_ Dry Cell Sealed Lead-Acid Other (Specify):_ Nickel Cadmium Lead-Acid (c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply: Emergency system described in NFPA 70, Article 700: Legally required standby described in NFPA 70 Article701: Optional standby system described in NFPA 70 Article 702, which also meets the performance requirements of Article 700 or 701.: FORM ID: SERV01 FP EF Florida PE NICET IV FPC

2 Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1): N/A Property Name: E1 Shoppes At Lago Mar Cust..: Pg 2 of 4 Quantity: Style(s): INITIATING DEVICES AND CIRCUIT INFORMATION Quantity Circuit Style Visual Functional Alarm Supervisory Latching n-latching Pass Fail View Report Pull Station Ion Detectors Photo Detectors Duct Detectors Heat Detectors 1 B Water Flow Switches Gas Detectors CO Detector Tamper Switches Fire Pump Power Fire Pump Running Pump Phase Reversal Pump Auto Position Pump Trouble Generator Auto Position Generator Trouble Switch Trouble Generator Engine Run Lock Box Ansul/ Hood System Disabled Alarm Verification feature is: ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION Quantity Circuit Style Visual Functional Factory Setting Measured Setting Pass Fail View Report Strobes Horns Horn Strobes Speakers Speaker Strobe Chimes Chime Strobes Bells 1 115vac Water Flow Bell Other (Specify)

3 . of alarm notification appliance circuits: N/A Are circuits monitored for integrity?: NOTIFICATIONS ARE MADE Yes Who Time Monitoring Entity Building Occupants Building Management Other (Specify) AHJ tified of Any Impairments Security Partners TYPE Visual Functional Comments Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring SECONDARY POWER TYPE Battery Condition Load Voltage Discharge Test Charger Test TRANSIENT SUPPRESSORS Property Name: E1 Shoppes At Lago Mar Cust..: Pg 3 of 4 PRIOR TO ANY TESTING SYSTEM TEST AND INSPECTION Passed 13.65v Comments 11:00 am NOTIFICATION APPLIANCES Audible Visible Speakers Voice Clarity Comments: EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Simulated Operation Pass Fail View Report Comments Qty: Phone Set Phone Jacks Off Hook Indicator Call-in Signal INTERFACE EQUIPMENT Suppression Systems Type: Qty: Smoke Aspirating Type: Qty: Releasing Panels Type: Qty: Other: Qty: RELAY INTERFACE AHU Shutdown Door Holders Gas Valve Shutoff Sound System Shutoff Other: Addressable Conventional Qty: Qty: Qty: Qty: Qty: ELEVATOR INTERFACE Primary Recall Alternate Recall Shunt Trip Battery Backup Floor: Floor: SMOKE CONTROL Active Passive Other: Special Procedures:

4 E1 Shoppes At Lago Mar Property Name: Cust..: Pg 4 of 4 Comments: SUPERVISING STATION MONITORING Yes Time Comments Alarm Signal Alarm Restoration Trouble Signal Supervisory Signal Supervisory Restoration 11:01 am 11:02 am 10:55 am 10:49 am 11:25 am MISCELLANEOUS ITEMS Yes Log Book Onsite Panel Tags Updated Manuals Onsite FACP Inside Sign on Door As-Built Drawings Onsite UL Certificate Previous Years Inspection Form Onsite NOTIFICATIONS THAT TESTING IS COMPLETE Building Management Monitoring Agency Building Occupants Other (Specify) Fire Watch Needed Yes Time Who 11:45 am Security Partners The following did not operate correctly: Breaker #8 for FACP A/C power is missing breaker lock. FACP piezo will not ring from waterflow alarm. System restored to normal operation: Date:_ 07/05/ :45 THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS. Valter Perez Name of Inspector: Time: Signature: Name of Owner/Representative : Date: Time: 07/05/ :45 Signature: Date: Time: 07/05/ :45 DEFICIENCY RESOLUTIONS Date Part # & Deficiency Resolution

5 109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr #500 rth Miam FL (305) Owner s Address: _ Owner's Phone Number: Property Being Evaluated: E1 Shoppes At Lago Mar SW 72nd St Miami FL Property Address: Valter Perez Technician : Certified: Yes Certification Type: FASA Issued: Approving Agency : Contact:Telephone: Miami Dade County Fire Rescue _ (786) Time Of Inspection: 9:00 am 07/05/2016 Date: SYSTEM TYPE Remote Station Local Proprietary Central Station Date Issued: Security Partners Name: UL Certificate.: Expires: SERVICE Monthly Quarterly Semiannually Annually Other (Specify) MONITORING ENTITY Telephon e: (188) Monitori ng Account Ref..: TYPE TRANSMISSION Built in UDACT Digital RF Slave Dialer Type: AES 7788F Battery Size: 7ah Visual Functional Pass Fail Control Unit Control Unit Manufacturer: Silent knight Model.: 5104 Software Rev: Number of Circuits: 1 Style: Last Date System Had Any Service Performed: 12/2015 Last Date Software or Configuration Was Revised: Serial :_ SYSTEM POWER SUPPLIES (a) Primary (Main): minal Voltage: 120 VAC Amps: 2.0 Overcurr ent Protectio n: Type: Breaker Amps: 20 Location (of Primary Supply Panelboard): Disconnecting Means Location: DYNA-4794 Breaker Lock Present: Breaker Labeled: (b) Secondary (Standby): Storage Battery Amp-Hr Rating: Calculated capacity to operate system, in hours: Engine-driven generator dedicated to fire alarm system: Location of fuel storage: SPRINKLER SYSTEM Inspection Completed on: 07/2016 Red Tag Green Tag Monthly Quarterly Semiannually Annually Completed by (Company Name): DynaFire SYSTEM COMPONENTS Yes Networked System: Network Functions: Remote Annunciator: Annunciator Functions: NAC Panels: NACs Function: Beside FACP Circuit #28 7Ah 24 Hours Battery Size: Voice Evacuation: Remote Microphone: Microphone Functions: TYPE BATTERY Visual: Functional: BattQty: Pass: Quantity of nodes:_ Type: Type: Qty: Type: Qty: Fail: Type:_ Dry Cell Sealed Lead-Acid Other (Specify):_ Nickel Cadmium Lead-Acid (c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply: Emergency system described in NFPA 70, Article 700: Legally required standby described in NFPA 70 Article701: Optional standby system described in NFPA 70 Article 702, which also meets the performance requirements of Article 700 or 701.: FORM ID: SERV01 FP EF Florida PE NICET IV FPC

6 Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1): N/A Property Name: E1 Shoppes At Lago Mar Cust..: Pg 2 of 4 Quantity: Style(s): INITIATING DEVICES AND CIRCUIT INFORMATION Quantity Circuit Style Visual Functional Alarm Supervisory Latching n-latching Pass Fail View Report Pull Station Ion Detectors Photo Detectors Duct Detectors Heat Detectors 1 B Water Flow Switches Gas Detectors CO Detector Tamper Switches Fire Pump Power Fire Pump Running Pump Phase Reversal Pump Auto Position Pump Trouble Generator Auto Position Generator Trouble Switch Trouble Generator Engine Run Lock Box Ansul/ Hood System Disabled Alarm Verification feature is: ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION Quantity Circuit Style Visual Functional Factory Setting Measured Setting Pass Fail View Report Strobes Horns Horn Strobes Speakers Speaker Strobe Chimes Chime Strobes Bells 1 115vac Water Flow Bell Other (Specify)

7 . of alarm notification appliance circuits: N/A Are circuits monitored for integrity?: NOTIFICATIONS ARE MADE Yes Who Time Monitoring Entity Building Occupants Building Management Other (Specify) AHJ tified of Any Impairments Security Partners 9:00 am TYPE Visual Functional Comments Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring SECONDARY POWER TYPE Battery Condition Load Voltage Discharge Test Charger Test TRANSIENT SUPPRESSORS Property Name: E1 Shoppes At Lago Mar Cust..: Pg 3 of 4 PRIOR TO ANY TESTING SYSTEM TEST AND INSPECTION Failed- See Report 13.7v Comments NOTIFICATION APPLIANCES Audible Visible Speakers Voice Clarity Comments: EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Simulated Operation Pass Fail View Report Comments Qty: Phone Set Phone Jacks Off Hook Indicator Call-in Signal INTERFACE EQUIPMENT Suppression Systems Type: Qty: Smoke Aspirating Type: Qty: Releasing Panels Type: Qty: Other: Qty: RELAY INTERFACE AHU Shutdown Door Holders Gas Valve Shutoff Sound System Shutoff Other: Addressable Conventional Qty: Qty: Qty: Qty: Qty: ELEVATOR INTERFACE Primary Recall Alternate Recall Shunt Trip Battery Backup Floor: Floor: SMOKE CONTROL Active Passive Other: Special Procedures:

8 E1 Shoppes At Lago Mar Property Name: Cust..: Pg 4 of 4 Comments: SUPERVISING STATION MONITORING Yes Time Comments Alarm Signal Alarm Restoration Trouble Signal Supervisory Signal Supervisory Restoration 9:46 am 9:46 am 9:50 am 9:29 am 10:00 am MISCELLANEOUS ITEMS Yes Log Book Onsite Panel Tags Updated Manuals Onsite FACP Inside Sign on Door As-Built Drawings Onsite UL Certificate Previous Years Inspection Form Onsite NOTIFICATIONS THAT TESTING IS COMPLETE Building Management Monitoring Agency Building Occupants Other (Specify) Fire Watch Needed Yes Time Who 10:20 am Security Partners The following did not operate correctly: FACP battery is faulty. (1) 12v 7ah Breaker #28 for FACP A/C power is not labeled and missing breaker lock. FACP piezo will not ring from waterflow alarm. System restored to normal operation: Date:_ THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS. 07/05/ :30 Valter Perez Name of Inspector: Time: Signature: Name of Owner/Representative : Date: Time: 07/05/ :30 Signature: Date: Time: 07/05/ :30 DEFICIENCY RESOLUTIONS Date Part # & Deficiency Resolution

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

Facilities Management

Facilities Management Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department

Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA 93010 Purchasing Department TO: All Jobwalk Attendees July 19, 2018 FROM: Janice Kisch, Purchasing

More information

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:

More information

Fire Alarm System Inspection and Testing Report

Fire Alarm System Inspection and Testing Report Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

VSC Fire & Security, Inc.

VSC Fire & Security, Inc. JOB#: 12775876 VSC Fire & Security, Inc. 10640 Iron Bridge Road, Suite G Jessup MD 20794 (301) 575-1500 www.vscfs.com Important: Deficiencies, Comments and Explanations any FAIL or NEGATIVE responses are

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16720 - ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection

More information

FIRE ALARM SYSTEM INSPECTION

FIRE ALARM SYSTEM INSPECTION 13555 Wellington Center Circle Suite 123 Gainesville, VA 20155 T: 1-888-883-2867 F: 703-468-6070 www.vectorsecurity.com FIRE ALARM SYSTEM INSPECTION Upon arrival, contact Vector Security Service Dept.

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION Underwriters Laboratories Inc. FIRE ALARM SYSTEM PRE-INSPECTION DATA SHEETS PLEASE RETURN COMPLETED FORMS TO UL PRIOR TO INSPECTION PROTECTED PROPERTY City: State: Zip Code: ALARM SERVICE COMPANY File

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant

More information

USAutomatic Sprinkler Corporation

USAutomatic Sprinkler Corporation Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION

More information

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax: Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi 38671 Phone: 662-393-7466 Fax: 662-280-6521 Fire Alarm Maintenance Guide The City of Southaven enforces the 2012

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights 1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights These 1 Exam Prep Highlights are based on the Fire Alarm Signaling Systems, 4th Edition. Each Tabs sheet has five rows of tabs. Start with the

More information

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,

More information

Final EC Inspection Report 03/2010

Final EC Inspection Report 03/2010 2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Building Name: Our Lady of Sorrows Date: July 10, 2013

Building Name: Our Lady of Sorrows Date: July 10, 2013 1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

July 14, 1999 DF C-100.

July 14, 1999 DF C-100. www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,

More information

Fire - Rescue. November 2016

Fire - Rescue. November 2016 Fire - Rescue Fire Alarm and Central Station Monitoring Plan Submittal Guidelines November 2016 Plan Submittal Guidelines are provided based on the 2015 International Fire Code, Policies, and Local Amendments.

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

INSPECfiON AND TESTING FORM PROPERTY NAME (USER) APPROVING AGENCY. Contact: Telephone:

INSPECfiON AND TESTING FORM PROPERTY NAME (USER) APPROVING AGENCY. Contact: Telephone: ... SIEMENS SIEMENS BUILING TECHNOLOGIES, INC. FIRE SAFETY IVISION INSPECfiON AN TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) ATE: 3-9-16_ TIME: 1: Name: _Si_em_en_s_B_u_ild_in_g._T_ec_hn_o_log

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

CONTACT ID REPORT CODES

CONTACT ID REPORT CODES CONTACT ID REPORT CODES PREFIX - E - ACTIVATION PREFIX - R - RESTORAL 100 Medical Zone 101 Personal Emergency Zone 102 Fail to report in Zone Fire Alarms 110 110 Fire Zone 111 Smoke Zone 112 Combustion

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

June 10, 2002 DF C S2424

June 10, 2002 DF C S2424 GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

Sheetz Inc. Fire Protection Service Guidelines

Sheetz Inc. Fire Protection Service Guidelines Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate

More information

SECTION FIRE ALARM

SECTION FIRE ALARM SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Release Control Fire Alarm Systems

Release Control Fire Alarm Systems SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POWER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Doc. No Part No Rev. U * T*

Doc. No Part No Rev. U * T* Doc. No. 430545 Part No. 579-357 Rev. U *0579357T* Blank Page- Back of Front Cover Copyrights and Trademarks 2005-2018 Johnson Controls. All rights reserved. Specifications and other information shown

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Residential Fire Sprinkler Inspection

Residential Fire Sprinkler Inspection Residential Fire Sprinkler Inspection Hickory, NC 88.38.6363 Charleston, SC 843.78.08 Greensboro, NC 336.373.3973 Columbia, SC 803.99.00 Raleigh, NC 99.834.9644 Greenville, SC 864.458.7070 Charlotte, NC

More information

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response

More information

Signature Series Auto-Sync Output Module (CC1S)

Signature Series Auto-Sync Output Module (CC1S) Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

ECC-50/100C. Emergency Command Center

ECC-50/100C. Emergency Command Center ECC-50/100C Emergency Command Center Canadian DF-60815:B Emergency Communications General Fire-lite s ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification

More information

Valuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work:

Valuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work: PERMIT FEE: $ 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the following information. Please PRINT).

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information