MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING
|
|
- Christine Atkinson
- 5 years ago
- Views:
Transcription
1 MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING 32 HARD WIRED ZONES CAN BE NORMALLY-OPEN OR NORMALLY-CLOSED ZONE WIRING RUNS CAN BE AS FAR AS 10,000 FEET FROM CONTROL CABINET UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO A SYSTEM CONTROL CABINET CONNECTED TO CONSOLE WITH FOUR WIRE CABLE REMOTE CONSOLE CAN BE LOCATED UP TO 1000 FEET FROM CONTROL CABINET BUILT-IN AUDIBLE SIGNAL, SOUND LEVEL IS 3 FEET SIXTEEN FOUR DIGIT ACCESS CODES ALL ZONE CONTROL AND ZONE STATUS ON REMOTE CONSOLE ZONE BY-PASS CAPABILITY, ZONE BY-PASS OUTPUT, DAY ZONE BYPASS THIRTY-TWO RED LED ZONE STATUS INDICATORS LOW STAND-BY BATTERY OUTPUT, AC POWER FAILURE OUTPUT ALL FIELD WIRING TERMINATED IN CENTRALLY LOCATED CONTROL CABINET ALARM CONTROLS CORPORATION
2 MODEL ZAC-32 ZONE STATUS INDICATORS LED OFF - ZONE SECURE LED FLASHING - ZONE BYPASSED LED ON - ZONE VIOLATED DIGITAL KEYPAD THE DIGITAL KEYPAD IS USED TO ACCESS AND CONTROL ALL SYSTEM FUNCTIONS: ANNUNCIATOR RESET, ZONE MEMORY RESET, DAY ZONE MODE AND ZONE BYPASSING VALID CODE INDICATOR WHEN LED IS ON A VALID CODE HAS BEEN ENTERED DAY ZONE INDICATOR WHEN LED IS ON ALL DAY ZONES ARE BYPASSED LOW BATTERY INDICATOR WHEN LED IS ON STANDBY BATTERY IS LOW POWER FAILURE INDICATOR WHEN LED IS ON AC POWER HAS FAILED, SYSTEM IS OPERATING ON STANDBY BATTERY AUDIBLE SIGNAL ATTENTION GETTING 85 db BUZZER SPECIFICATIONS VOLTAGE INPUT: 12 VOLT AC, USE 20 VA TRANSFORMER INCLUDED STANDBY BATTERY: 12 VOLT 4AH RECHARGEABLE BATTERY INCLUDED POWER CONSUMPTION: ZAC-32 CONTROL 30MA., REMOTE ANNUNCIATOR 25MA.IN, 150MA. MAX. TOTAL OUTPUT CURRENT: NOT TO EXCEED 800MA. FROM ALL OUTPUTS ZONES: NORMALLY-OPEN, NORMALLY-CLOSED, SUPERVISED ZONE MODEL AVAILABLE ZONE LENGTH: 10,000 FEET 18 GA., 5000 FEET 20 GA., 2500 FEET 22 GA., 2 CONDUCTOR WIRE DESKTOP ANNUNCIATOR: CONECTED TO CABINET WITH 22 GA. SHEILDED 4 CONDUCTOR WIRE DESKTOP ANNUNCIATOR SIZE: 16.2 L x 8 W x 2.8 D CABINET SIZE: 13 H x W x 3.5 D RACK MOUNTED ANNUNCIATOR: STANDARD 19 RACK, 8.75 W ALARM CONTROLS CORPORATION QUALITY SECURITY EQUIPMENT SINCE BRANDYWINE DRIVE, P.O. BOX 280, DEER PARK, NEW YORK FAX INFO@ALARMCONTROLS.COM
3 TABLE OF CONTENTS ZONE ANNUNCIATOR/CONTROLLER INSTALLATION INSTRUCTIONS SUBJECT PAGE INTRODUCTION 1 SYSTEM FEATURES 1 POWER REQUIREMENTS 2 AC POWER 2 STANDBY BATTERY 2 EARTH GROUND 2 ZONE INPUTS ZAC-32 2 ZONE INPUTS ZAC-32S 3 ZONE TERMINAL DESIGNATIONS 3 CONNECTING PROCESSOR TO PRINTER INTERFACE 4 AUXILIARY VOLTAGE OUTPUTS 4 EXTERNAL STATUS OUTPUTS 4 EXTERNAL STATUS DESCRIPTION 5 CONNECTING DISPLAY TO PROCESSOR 5 SPECIFICATIONS 6 FCC COMPLIANCE 7 WARRANTY 7
4 ZONE ANNUNCIATOR/ CONTROLLER MODEL ZAC-32 INSTALLATION INSTRUCTIONS I. INTRODUCTION THE ZAC-32 ZONE ANNUNCIATOR/ CONTROLLER IS A TWO COMPONENT SYSTEM COMPRISED OF A CENTRAL ZONE PROCESSOR AND A REMOTE DISPLAY/CONSOLE. THE SYSTEM PROVIDES TOTAL ZONE MONITORING AND CONTROL AT A FULL FEATURED REMOTE DISPLAY CONSOLE. THE SYSTEM IS CAPABLE OF ZONE EXPANSION IN THIRTY- TWO ZONE MULTIPLES, AN OPTIONAL REMOTE PRINTER PROVIDES A HARD COPY OF ALL ZONE ACTIVITY BY AN IDENTIFYING AUTHORIZED CODE NUMBER IN ADDITION TO TIME AND DATE. THE REMOTE CONSOLE THE REMOTE CONSOLE CONTROLS AND DISPLAYS ALL THIRTY-TWO ZONES. THE CONDITION OF EACH ZONE IS CLEARLY DISPLAYED ON THE FUNCTIONALLY DESIGNED CONSOLE. THE DIGITAL KEYPAD IS USED TO ALLOW AUTHORIZED PERSONNEL ACCESS TO THE SYSTEM BY AN IDENTIFYING ACCESS CODE AND TO PERFORM VARIOUS SYSTEM FUNCTIONS. ALL ZONE DATA AND ZONE CONTROL FUNCTIONS ARE TRANSMITTED TO THE ZONE PROCESSOR FROM THE REMOTE CONSOLE OVER A FOUR-CONDUCTOR CABLE. UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO THE SYSTEM FOR ANNUNCIATION AND CONTROL AT MULTIPLE LOCATIONS. REMOTE CONSOLES CAN BE LOCATED IN EXCESS OF 1000 FEET FROM THE ZONE PROCESSOR. THE ZONE PROCESSOR CABINET THE ZONE PROCESSOR CABINET CONTAINS THE SYSTEM LOGIC CIRCUITRY, POWER SUPPLY AND STANDBY POWER SOURCE. ALL FIELD WIRING IS TERMINATED IN THE ZONE PROCESSOR CABINET. A FOUR CONDUCTROR CABLE CONNECTS THE ZONE PROCESSOR TO THE REMOTE CONSOLE. II. SYSTEM FEATURES 32 ZONES CAN BE WIRED NORMALLY- FOUR WIRE REMOTE ANNUNCIATOR OPEN OR NORMALLY-CLOSED DISPLAY CONSOLE UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO A SYSTEM BUILT-IN AUDIBLE SIGNAL, 80 3 FT. THIRTY-TWO ZONE STATUS INDICATORS OPTIONAL PRINTER FOR COMPLETE RECORD OF SYSTEM ACTIVITY OPTIONAL THIRTY-TWO ZONE VOLTAGE OUTPUT MODULE DIGITAL KEYPAD FOR SYSTEM SECURITY FOUR SYSTEM FUNCTION INDICATORS POWER FAILURE AND LOW BATTERY INDICATION OPTIONAL SUPERVISED ZONE MODULE OPTIONAL EIGHT ZONE RELAY MODULE SIXTEEN FOUR DIGIT ACCESS CODES COMMON ANNUNICATOR VOLTAGE OUPUT PAGE 1
5 II. POWER REQUIREMENTS A. AC POWER TERMINALS 11 & 12 CONNECT THE 12 VOLT 20 VA. UL LISTED PLUG-IN TRANSFORMER TO THESE TERMINALS. DO NOT CONNECT TO A RECEPTACLE CONTROLLED BY A SWITCH. CAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK, DISCONNECT POWER TO RECEPTACLE BEFORE INSTALLING OR REMOVING THE TRANSFORMER. WHEN REMOVING THE RECEPTACLE COVER SCREW, COVER MAY FALL ACROSS PLUG PINS OR RECEPTACLE MAY BECOME DISPLACED. USE ONLY A DUPLEX RECEPTACLE HAVING A CENTER SCREW. SECURE TRANSFORMER IN PLACE WITH SCREW SUPPLIED. B. STANDBY BATTERY TERMINALS 9 (+) & 10 (-) CONNECT THE 12 VOLT RECHARGEABLE BATTERY, TO TERMINALS 9 AND 10 WITH THE BATTERY LEADS PROVIDED OBSERVING POLARTIY. CAUTION: BATTERY POLARITY MUST BE STRICTLY OBSERVED. IF BATTERY POLARITY IS REVERSED BATTERY FUSE WILL BLOW. REPLACE WITH CORRECT FUSE, (SOC SS2 3A), UNIT DOES NOT HAVE STANDBY POWER IF FUSE IS BLOWN. THE BATTERY FUSE IS LOCATED TO THE RIGHT OF TERMINAL 7 ON THE PRINTED CIRCUIT BOARD. C. EARTH GROUND THIS UNIT HAS EFFECTIVE LIGHTNING PROTECTION ONLY WHEN GROUNDED ACCORDING TO THE FOLLOWING INSTRUCTIONS: CONNECT TERMINAL 13 TO A METAL COLD WATER PIPE OR BURIED GROUND ROD WITH NOT LESS THEN 16 GA SOLID COPPER WIRE. CLEAN SURFACE OF METAL PIPE OR GROUND ROD AND SECURE WITH SUITABLE CLAMP. DO NOT GROUND TO A GAS PIPE. NOTE: IF THE ZONE PROCESSOR CIRCUIT BOARD IS REMOVED FROM THE CABINET ALL FOUR MOUNTING SCREWS MUST BE REPLACED TO INSURE PROPER GROUNDING TO AVOID LIGHTNING DAMAGE. IV. ZONE INPUTS (MODEL ZAC-32) THE ZONE PROCESSOR HAS 32 NON-SUPERVISED ZONE INPUTS WHICH CAN BE CONNECTED FOR NORMALLY-OPEN OR NORMALLY-CLOSED SWITCH CONTACT CONFIGURATIONS. A NORMALLY-OPEN ZONE INPUT REQUIRES A 10K OHM RESISTOR CONNECTED BETWEEN THE POSITIVE TERMINAL AND THE ZONE TERMINAL AS SHOWN. N/C ZONE TERMINALS N/O ZONE TERMINALS POS ZONE POS NEG ZONE N / 0 N/C CONTACT /\ /\ 10 K RES. PAGE 2
6 V. ZONE INPUTS (MODEL ZAC-32S) THE ZAC-32S ZONE PROCESSOR HAS 32 ZONE INPUTS WHICH ARE SUPERVISED WITH A 10K OHM END OF LINE RESISTOR. NORMALLY-CLOSED OR NORMALLY-OPEN SWITCH CONTACTS CAN BE CONNECTED TO THE SAME ZONE INPUT. ALL NORMALLY-OPEN DEVICES ARE CONNECTED IN PARALLEL AND ALL NORMALLY-CLOSED DEVICES ARE CONNECTED IN SERIES. THE END OF LINE RESISTOR IS CONNECTED IN SERIES WITH THE LAST NORMALLY- CLOSED DEVICE OR IN PARALLEL WITH THE LAST NORMALLY-OPEN DEVICE. NOTE: A SHORT OR OPEN IN A SUPERVISED ZONE WILL INDICATE A ZONE VIOLATION. N/O ZONE CONTACTS N/O & N/C ZONE N/C ZONE CONTACTS +POS ZONE +POS ZONE +POS ZONE N/C N/0 N/O N/C CONTACT CONTACT CONTACT / \ / \ / \ / \ / \ / \ 10K RES. 10K RES. 10K RES. VI. ZONE TERMINAL DESIGNATIONS ZONE N/C N/O ZONE N/C N/O TERMINALS TERMINALS LOCATION TERMINALS TERMINALS LOCATION 1 19, 21 20, , 45 44, , 22 20, , 46 44, , 23 20, , 47 44, , 24 20, , 48 44, , 27 26, , 51 50, , 28 26, , 52 50, , 29 26, , 53 50, , 30 26, , 54 50, , 33 32, , 57 56, , 34 32, , 58 56, , 35 32, , 59 56, , 36 32, , 60 56, , 39 38, , 63 62, , 40 38, , 64 62, , 41 38, , 65 62, , 42 38, , 66 62, 66 PAGE 3
7 VII. CONNECTIONS TO ZAP-256 PRINTER INTERFACE, (SEE ZAP-256 INSTRUCTIONS FOR FURTHER DETAILS) ZONE ANNUNCIATOR TO PRINTER INTERFACE TERMINALS TERMINALS 1 (RED) 1 OR 6 (RED) 2 (GREEN) 2, 3, 4, 5, 7, 8, 9, 10 (GREEN) 3 (YELLOW) 11 OR 12 (YELLOW) 4 (BLACK) 13 OR 14 (BLACK) NOTE: THE RED WIRE FROM EACH ZONE ANNUNCIATOR MAY BE CONNECTED TO EITHER TERMINAL 1 OR 6 ON THE PRINTER INTERFACE. TERMINALS 1 AND 6 ARE INTERNALLY CONNECTED. DUAL TERMINALS ARE PROVIDED TO LIMIT THE NUMBER OF CONNECTIONS ON EACH TERMINAL. THE GREEN WIRE FROM EACH ZONE ANNUNCIATOR MAY BE CONNECTED TO EITHER TERMINAL 2,3,4,5,7,8,9,10 ON THE PRINTER INTERFACE. VIII. AUXILIARY VOLTAGE OUTPUTS 12 VOLTS DC THE ZONE ANNUNCIATOR HAS EIGHT SETS OF AUXILIARY VOLTAGE OUTPUT TERMINALS. EACH SET OF OUTPUT TERMINALS IS FUSED WITH A 500 MA., 5 MM FUSE, (ACC P/N SS2-5). THE MAXIMUM TOTAL CURRENT AVAILABLE FROM THESE OUTPUTS IS 700 MA. THIS TOTAL OF ALL OUTPUTS SHOULD NOT BE EXCEEDED. USE THE PROVIDED CHART TO TOTAL THE SUM OF THE OUTPUTS. VOLTAGE OUTPUT TERMINALS CURRENT USED 19 + & 20- MA & 26- MA & 32- MA & 38- MA & 44- MA & 50- MA & 56- MA & 62- MA. TOTAL NOT TO EXCEED 700 MA. IX. EXTERNAL STATUS OUTPUTS THE ZONE ANNUNCIATOR HAS FOUR EXTERNAL STATUS OUTPUTS. THESE OUTPUTS WILL SUPPLY MA. TO AN EXTERNAL DEVICE. THE EXTERNAL STATUS OUTPUTS SWITCH GROUND WHEN ACTIVE. THE OUTPUT MUST BE CONNECTED TO THE NEGATIVE SIDE OF THE DEVICE TO BE OPERATED. ALL EXTERNAL STATUS OUTPUTS CAN BE CONNECTED TOGETHER TO COMBINE FUNCTIONS. EXTERNAL STATUS OUTPUT ANNUNCIATE (ANN) BYPASS (BYP) LOW BATTERY (LBT) AC POWER FAILURE (PFL) TERMINALS 15 & ANY POSITIVE TERMINAL 16 & ANY POSITIVE TERMINAL 17 & ANY POSITIVE TERMINAL 18 & ANY POSITIVE TERMINAL PAGE 4
8 X. EXTERNAL STATUS OUTPUT DESCRIPTION ANNUNCIATE- WHEN ANY ZONE IS VIOLATED THE ANNUNCIATE OUPUT TURNS ON. WHEN THE AUDIBLE SIGNAL IS SILENCED THE ANNNICATE OUTPUT WILL TURN OFF. BYPASS- THE BYPASS OUTPUT WILL TURN ON WHEN ANY ZONE IS BYPASSED. THE BYPASS OUTPUT WILL TURN OFF WHEN ALL ZONES ARE UN-BYPASSED. THIS OUTPUT IS NOT AFFECTED BY THE USE OF THE DAY ZONE FEATURE. LOW BATTERY- WHEN A LOW BATTERY CONDITION IS DETECTED THE LOW BATTERY OUTPUT WILL TURN ON. THE OUTPUT WILL REMAIN ON UNTIL THE LOW BATTERY CONDITION IS CORRECTED. AC POWER FAILURE WHEN AC POWER FAILS THIS OUTPUT TURNS ON. THE OUTPUT WILL REMAIN ON UNTIL AC POWER IS RESTORED. XI. CONNECTING THE REMOTE DISPLAY CONSOLE TO THE ZONE PROCESSOR UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO THE SYSTEM. EACH REMOTE CONSOLE IS POWERED FROM THE ZONE PROCESSOR. ALLOW 150 MA. FOR EACH REMOTE DISPLAY CONSOLE WHEN CALCULATING THE TOTAL CURRENT USED BY THE SYSTEM. THE REMOTE CONSOLE IS TERMINATED WITH AN EIGHT CONDUCTOR MODULAR CORD. AN EIGHT CONDUCTOR MODULAR JACK IS SUPPLIED TO TERMINATE THE CABLE RUN BETWEEN THE ZONE PROCESSOR AND THE REMOTE DISPLAY CONSOLE. A MINIMUM OF FOUR CONDUCTORS MUST BE USED. IF THE CABLE RUN BETWEEN THE ZONE PROCESSOR IS IN EXCESS OF 100 FEET; SHEILDED CABLE SHOULD BE USED. THE MAXIMUM CABLE RUN BETWEEN THE ZONE PROCESSOR AND THE REMOTE DISPLAY CONSOLE IS 1000 FEET. TWO CONDUCTORS OF THE MODULAR CORD CAN BE USED FOR A TAMPER CIRCUIT WHICH CAN BE CONNECTED TO THE N/C INPUT OF A CONVENTIONAL ALARM SYSTEM. THE USE OF THE TAMPER CIRCUIT REQUIRES A SIX CONDUCTOR SHEILED CABLE. IF SHEILDED CABLE IS USED, CONNECT TO THE GRAY AND BROWN TERMINAL ON THE MODULE JACK. REMOTE DISPLAY TO ZONE PROCESSOR JACK TERMINALS TERMINALS RED 5 GREEN 6 YELLOW 7 BLACK 8 GRAY & BROWN 13 TO SHEILD BLUE & ORANGE TAMPER CIRCUIT TO ALARM SYSTEM TAMPER INPUT NOTE: A RACK MOUNTED OR GRAPHIC DISPLAY IS CONNECTED USING THE SAME COLOR CODE AS THE REMOTE DISPLAY CONSOLE. PAGE 5
9 XII. SPECIFICATIONS POWER INPUT: 12 V.A.C., 20 VA., CLASS 2 PLUG-IN TRANSFORMER, (ACC P/N BE12V20) STANDBY: 12 VOLT, 4 A.H. RECHARGEABLE BATTERY, (YUASA P/N NP4-12) POWER CONSUMPTION ZAC-32 ZONE PROCESSOR: 30 MA. ZAR-32 REMOTE ANNUNCIATOR: 25 MA. MINIMUM, 150 MA. MAXIMUM POWER OUTPUT ANNUNCIATOR OUTPUT: MA. ZONE BYPASS OUTPUT: MA. LOW BATTERY OUTPUT: MA. POWER FAILURE OUTPUT: MA. AUXILIARY POWER OUTPUT: MA. NOTE: TOTAL CURRENT FROM ALL OUTPUTS NOT TO EXCEED 800 MA. FUSES BATTERY FUSE: 2.5 SB 3 AG AUXILIARY POWER FUSES: 5 x 20MM 500MA ZONE PARAMETERS LOOP RESPONSE TIME: 250 MS. TO ACTIVATE, 125 MS. TO RESTORE LOOP RESISTANCE: 10,000 OHMS MAXIMUM LOOP LENGTH: FEET WITH 18 AWG. 2 CONDUCTOR WIRE 5000 FEET WITH 20 AWG. 2 CONDUCTOR WIRE 2500 FEET WITH 22 AWG. 2 CONDUCTOR WIRE REMOTE ANNUNCIATOR PARAMETERS AUDIBLE SIGNAL: 80 3 FEET WIRE TYPE: 22 AWG., 4 CONDUCTOR SHEILDED LENGTH: 1000 FEET MAXIMUM DIMENSIONS CONTROL CABINET: 13H x 11.75W x 3.5D DEST TOP CONSOLE: 16.2L x 8W x 2.8D RACK MOUNTED ANNUNCIATOR: STANDARD 19 INCH x 8.75 PAGE 6
10 FCC COMPLIANCE THIS EQUIPMENT GENERATES AND USES RADIO FREQUENCY ENERGY AND IF NOT INSTALLED AND USED PROPERLY, THAT IS IN STRICT ACCORDANCE WITH THE MANUFACTURER S INSTRUCTION, MAY CAUSE INTERFERENCE TO RADIO AND TELEVISION RECEPTION. IT HAS BEEN TYPE TESTED AND FOUND TO COMPLY WITH THE LIMITS FOR A CLASS B COMPUTING DEVICE IN ACCORDANCE WITH THE SPECIFICATIONS OF SUBPART J OF PART 15 OF FCC RULES, WHICH ARE DESIGNED TO PROVIDE REASONABLE PROTECTION AGAINST SUCH INTERFERENCE IN AN INSTALLATION. HOWEVER, THERE IS NO GUARANTEE THAT INTERFERENCE WILL NOT OCCUR IN A PARTICULAR INSTALLATION. IF THIS EQUIPMENT DOES CAUSE INTERFERENCE TO RADIO OR TELEVISION RECEPTION, WHICH CAN BE DETERMINED BY TURNING THE EQUIPMENT OFF AND ON. THE USER IS ENCOURAGED TO TRY TO CORRECT THE INTERFERENCE BY ONE OR MORE OF THE FOLLOWING MEASURES. 1. RE-ORIENT THE TV OR RADIO ANTENNA. 2. RELOCATE OR MOVE THE EQUIPMENT AWAY FROM THE RECEIVER. 3. PLUG THE TRANSFORMER FOR THE EQUIPMENT INTO A DIFFERENT OUTLET SO THAT THE RECEIVER AND THE EQUIPMENT ARE ON DIFFERENT BRANCH CIRCUITS. 4. IF NECESSARY, THE USER SHOULD CONSULT THE INSTALLER OR AN EXPERIENCED RADIO/ TELEVISION TECHNICAN FOR ADDITIONAL SUGGESTIONS. THE USER MAY FIND THE FOLLOWING BOOKLET PREPARED BY THE FEDERAL COMMUNICATION COMMISSION HELPFUL: HOW TO IDENTIFY AND RESOLVE RADIO/ TV INTERFERENCE PROBLEMS. THIS BOOKLET IS AVAILABLE FROM THE U.S. GOVERNMENT PRINTING OFFICE, WASHINGTON, DC 20402, STOCK # WARRANTY THE EQUIPMENT MANUFACTURED BY ALARM CONTROLS CORPORATION IS GUARANTEED TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP UNDER NORMAL USE AND SERVICE WHEN INSTALLED IN ACCORDANCE WITH ALARM CONTROLS CORPORATION S INSTALLATION INSTRUCTIONS. ALARM CONTROLS CORPORATION, WARRANTS TO REPLACE OR REPAIR, FREE OF CHARGE, THE EQUIPMENT COVERED BY THE WARRANTY WHICH HAS BEEN RETURNED TO THE FACTORY, TRANSPORTATION CHARGES PREPAID, WITHIN TWELVE MONTHS FROM RECEIPT OF THE EQUIPMENT AT ORIGINAL DESTINATION, AND WHICH, IN THE SOLE JUDGEMENT OF ALARM CONTROLS CORPORATION IS DEFECTIVE IN MATERIAL AND WORKMANSHIP. ANY MISUSE, MODIFICATION, REWORK, OR ADJUSTMENT ON EQUIPMENT BY ANY PERSON OTHER THAN AN AUTHORIZED REPRESENTATIVE OF ALARM CONTROLS CORPORATION SHALL VOID THE WARRANTY. THIS WARRANTY IS LIMITED ONLY TO THOSE PRODUCTS MANUFACTURED BY ALARM CONTROLS CORPORATION. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING THE WARRANTY OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE OR USE, AND IN NO EVENT SHALL ALARM CONTROLS CORPORATION BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES AS SAME ARE DEFINED IN THE UNIFORM COMMERCIAL CODE. PAGE 7
11
12 MODEL ZAC-32 OPERATING INSTRUCTIONS I. INTRODUCTION THE ZAC-32 ZONE ANNUNCIATOR/CONTROLLER IS A TWO COMPONENT SYSTEM COMPRISED OF A CENTRAL ZONE PROCESSOR AND A REMOTE DISPLAY CONSOLE. THE SYSTEM PROVIDES TOTAL ZONE MONITORING AND CONTROL AT THE FULL FEATURED REMOTE CONSOLE. THE SYSTEM IS CAPABLE OF ZONE EXPANSION IN THIRTY-TWO ZONE MULTIPLES. THE REMOTE CONSOLE CONTROLS AND DISPLAYS ALL THIRTY-TWO ZONES. THE CONDITION OF EACH ZONE IS CLEARLY DISPLAYED ON THE FUNCTIONALLY DESIGNED CONSOLE. A DIGITAL KEYPAD IS USED TO ALLOW AUTHORIZED PERSONEL ACCESS TO THE SYSTEM BY AN IDENTIFYING ACCESS CODE AND TO PERFORM VARIOUS SYSTEM FUNCTIONS. II. THE ZONE PROCESSOR THE ZAC-32 HAS 32 ZONES. EACH ZONE IS INDEPENDENT IN OPERATION. WHEN A ZONE IS VIOLATED THE ZONE INDICATOR AND THE AUDIBLE SIGNAL WILL TURN ON AND ZONE MEMORY WILL BE SET. IF THE VIOLATED ZONE IS RESTORED BEFORE IT IS ACKNOWLEDGED THE ZONE INDICATOR WILL REMAIN ON. THE ZONE PROCESSOR CONTAINS A POWER SUPPLY AND RECHARGEABLE BACK-UP BATTERY. THE AC POWER AND BATTERY ARE MONITORED FOR FAILURE. IF THE AC POWER IS INTERRUPTED OR THE BATTERY VOLTAGE DROPS BELOW A SAFE LEVEL THE SYSTEM INDICATORS AND AUDIBLE SIGNAL WILL REPORT THE TROUBLE CONDITION. WHEN AC POWER HAS BEEN RESTORED THE INDICATORS AND AUDIBLE SIGNAL WILL TURN OFF. III. THE REMOTE DISPLAY CONSOLE THE REMOTE CONSOLE DISPLAYS AND CONTROLS ZONE STATUS AND SYSTEM CONDITIONS. THE CONSOLE CONTAINS A DIGITAL KEYPAD, ZONE SYSTEM INDICATORS AND AN AUDIBLE SIGNAL.. A. DIGITAL KEYPAD - THE DIGITAL KEYPAD IS USED TO ACCESS AND CONTROL THE SYSTEM. B. ZONE ANNUNCIATION - THE ZONE INDICATORS DISPLAY COMPLETE ZONE STATUS. FLASHING - ZONE BYPASSED, OFF - ZONE SECURE OR IN A NON-VIOLATED CONDITION ON - ZONE VIOLATED OR IN ZONE MEMORY. C. SYSTEM INDICATORS - THE SYSTEM INDICATORS DISPLAY THE FOLLOWING INFORMATION. DAY MODE INDICATOR ON - ALL DAY ZONES ARE BYPASSED. ACCESS INDICATOR ON - A VALID CODE HAS BEEN ENTERED. LOW BATTERY INDICATOR ON - LOW BATTERY VOLTAGE HAS BEEN DETECTED. POWER FAILURE INDICATOR ON - AC POWER IS OFF. D. ANNUNCIATOR - AN AUDIBLE SIGNAL SOUNDS TO INDICATE A ZONE VIOLATION, SYSTEM TROUBLE OR WHEN A KEY IS PRESSED. IV. ZONE ANNUNCIATION/CONTROLLER SYSTEM OPERATION A. ACCESS CODE - A FOUR DIGIT ACCESS CODE MUST BE ENTERED BEFORE ANY FUNCTION CODE WILL BE ACCEPTED. ALL ACCESS CODES ARE PRESET AT THE FACTORY. A LIST OF ACCESS CODES IS INCLUDED WITH EACH UNIT. LISTED BELOW IS THE PROCEDURE FOR ENTERING AN ACCESS CODE. 1. LOAD A VALID FOUR DIGIT ACCESS CODE. PRESS EACH NUMBER OF THE CODE UNTIL A BEEP IS HEARD. 2. PRESS THE #,(POUND), KEY TO ENTER THE CODE. 3. ACCESS INDICATOR TURNS ON. NOTE: AFTER 60 SECONDS ACCESS IS AUTOMATICALLY TURNED OFF. B. FUNCTION CODES - THE ZONE ANNUNCIATOR/CONTROLLER HAS SIX FUNCTIONS. SYSTEM CONTROL CODE FUNCTION 1 ANNUNCIATION RESET 2 ZONE MEMORY RESET 3 DAY ZONE MODE 4 SYSTEM TEST PAGE 1
13 BYPASS CONTROL CODE FUNCTION 5 ZONE BYPASS ON 6 ZONE BYPASS OFF TO ENTER A SYSTEM CONTROL FUNCTION CODE 1. LOAD VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND), KEY TO ENTER CODE 2. ENTER THE SELECTED FUNCTION CODE, THEN PRESS #,(POUND), KEY TO ENTER CODE TO ENTER A BYPASS CONTROL FUNCTION CODE 1. LOAD VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND), KEY TO ENTER CODE 2. LOAD SELECTED BYPASS FUNCTION CODE, THEN PRESS,(STAR). KEY TO ENTER * 3. LOAD TWO DIGIT ZONE NUMBER,(01-32), THEN PRESS #,(POUND), KEY TO EXECUTE NOTE: ONLY ONE ZONE AT A TIME CAN BE BYPASSED OR UN-BYPASSED C. ANNUNCIATE RESET THE AUDIBLE ANNUNCIATOR WILL SOUND WHEN A ZONE HAS BEEN VIOLATED OR A SYSTEM TROUBLE SIGNAL IS DETECTED. NOTE: AFTER ACKNOWLEDGMENT OF THE ACTIVITY THE ANNUNCIATOR MUST BE RESET. TO RESET THE AUDIBLE ANNUNCIATOR 1. ENTER VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND), KEY TO ENTER 2. PRESS KEY 1 3. PRESS #,(POUND), KEY TO EXECUTE THE AUDIBLE ANNUNCIATOR WILL BE SILENCED WHEN KEYS ARE PRESSED. IF THE AUDIBLE ANNUNCIATOR IS NOT RESET, THE AUDIBLE SIGNAL WILL SOUND AFTER THE LAST KEY IS PRESSED. D. MEMORY RESET WHEN A ZONE HAS BEEN VIOLATED THE ZONE MEMORY IS SET. IN ORDER TO MONITOR THE ZONE STATUS THE ZONE MEMORY MUST BE RESET. TO RESET THE ZONE MEMORY 1. ENTER A VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND),KEY TO ENTER 2. PRESS KEY 2 3. PRESS #,(POUND), KEY TO EXECUTE THE ZONE MEMORY WILL RESET, THE ZONE INDICATOR WILL TURN OFF UNLESS THE ZONE IS STILL VIOLATED. E. DAY ZONE MODE THE DAY ZONE MODE IS ACTIVE WHEN THE DAY ZONE STATUS INDICATOR IS ON. ALL DESIGNATED DAY ZONES ARE BYPASSED WHEN THE DAY ZONE MODE IS ACTIVATED ALLOWING FREE ACCESS TO THOSE ZONES WITHOUT CAUSING A VIOLATION. TO ACTIVATE THE DAY ZONE MODE 1. ENTER VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND), KEY TO ENTER 2. PRESS 3 KEY 3. PRESS #,(POUND), KEY TO EXECUTE IF DAY ZONE MODE WAS OFF DAY ZONE MODE WILL TURN ON. IF DAY ZONE MODE WAS ON DAY ZONE MODE WILL TURN OFF. NOTE: ALL DAY ZONES ARE BYPASSED WHEN THE DAY MODE IS ON. F. SYSTEM TEST IT IS RECOMMENDED THAT THE SYSTEM TEST BE OPERATED AT LEAST ONCE A WEEK TO CHECK ALL ZONE STATUS, SYSTEM INDICATORS AND STAND-BY BATTERY CONDITION. PAGE 2
14 TO OPERATE SYSTEM TEST 1. ENTER A VALID FOUR DIGIT ACCESS CODE, THEN PRESS #,(POUND),KEY TO ENTER 2. PRESS KEY 4 3. PRESS #,(POUND), KEY TO EXECUTE ALL ZONE AND SYSTEM INDICATORS WILL TURN ON. AC POWER WILL BE DISCONNECTED AND THE AUDIBLE SIGNAL WILL SOUND. NOTE: IF A ZONE IS VIOLATED DURING THE TEST PERIOD THE TEST IS ABORTED AND NORMAL OPERATION RESUMES. IF A LOW BATTERY IS DETECTED DURING THE TEST ALL INDICATORS ARE RESTORED TO NORMAL. LOW BATTERY WILL STILL BE INDICATED UNTIL THE TEST IS COMPLETED, THEN AC POWER AND BATTERY VOLTAGE RESTORES. G. BYPASS CONTROL IF A PROBLEM DEVELOPS IN A ZONE OR FREE ACCESS IS DESIRED THE ZONE MUST BE BYPASSED. THE FOLLOWING IS AN EXAMPLE OF THE ZONE BYPASS FUNCTION: TO BYPASS ZONE NUMBER 2 1. LOAD A VALID FOUR DIGIT ACCESS CODE THEN PRESS #,(POUND), KEY TO ENTER 2. PRESS KEY 5 THEN PRESS,(STAR), KEY TO ENTER * 3. ENTER A ZONE NUMBER 02 THEN PRESS #,(POUND), KEY TO EXECUTE ZONE 2 INDICATOR WILL FLASH, BYPASS STATUS OUTPUT WILL TURN ON THE FOLLOWING IS AN EXAMPLE OF THE ZONE UN- BYPASS FUNCTION: TO UN-BYPASS ZONE NUMBER LOAD A VALID FOUR DIGIT ACCESS CODE THEN PRESS #,(POUND), KEY TO ENTER 2. PRESS KEY 6 THEN PRESS,(STAR), KEY TO ENTER * 3.ENTER A ZONE NUMBER 30 THEN PRESS #,(POUND), KEY TO EXECUTE ZONE 30 INDICATOR WILL DISPLAY ZONE OR MEMORY STATUS, BYPASS STATUS OUTPUT WILL TURN OFF H. ZONE VIOLATION WHEN A ZONE VIOLATION IS REPORTED DO THE FOLLOWING: 1. ENTER A VALID FOUR DIGIT ACCESS CODE 2. RESET AUDIBLE SIGNAL 3. ACKNOWLEDGE ZONE INDICATOR FOR LOCATION 4. RESET ZONE MEMORY TO INDICATE ZONE STATUS I. POWER FAILURE WHEN AC POWER FAILURE IS DETECTED DO THE FOLLOWING: 1. ENTER A VALID FOUR DIGIT ACCESS CODE 2. RESET AUDIBLE ANNUNCIATOR 3. ACKNOWLEDGE POWER FAILURE INDICATOR 4.CHECK AC POWER ALL INDICATORS ARE RESTORED TO NORMAL. J.LOW BATTERY WHEN A LOW BATTERY IS DETECTED DO THE FOLLOWING: 1. ENTER A VALID FOUR DIGIT ACCESS CODE 2. RESET AUDIBLE ANNUNCIATOR 3. ACKNOWLEDGE LOW BATTERY INDICATOR 4.CHECK STANDBY BATTERY ALL INDICATORS ARE RESTORED TO NORMAL. PAGE 3
15 ZAC-32 PROGRAMMED INFORMATION A. ACCESS CODES PROM # 111 ACCESS ID NUMBER ACCESS CODE B. ZONE DESIGNATIONS STANDARD ZONES # 1-24 DAY ZONES # ALARM CONTROLS CORPORATION 19 BRANDYWINE DRIVE DEER PARK, NY
MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES
MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES INDEPENDENT ZONE ANNUNCIATION WITH ZONE STATUS INDICATION EIGHT RED LEDS INDICATE ZONE STATUS SELECTABLE NORMALLY-OPEN,
More informationIndependent Zone Control (I.Z.C.)
Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics
More informationLong Range Radio Alarm Transmitter
TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in
More informationModel 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
More informationLong Range Radio Alarm Transmitter
W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM
More informationFigure 1. These Installation Instructions -1- K4866 4/00 OmniProx Reader Model Series OP-10/20/30/40
K4866 4/00 OmniProx Reader Model Series OP-10/20/30/40 Installation Instructions WHAT IS THE ADEMCO OmniProx READER? The OmniProx Reader is an RFID proximity card reader to be installed for use with access
More informationAPS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES
APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED
More informationCAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN THE LIGHTNING FLASH AND ARROW- HEAD WITHIN THE
THE LIGHTNING FLASH AND ARROW- HEAD WITHIN THE TRIANGLE IS A W ARNING SIGN ALERTING YOU OF "DANGEROUS VOLTAGE" INSIDE THE PRODUCT. CAUTION RISK OF ELECTRIC SHOCK DO NOT OP CAUTION: TO REDUCE THE RISK OF
More informationFire Control/Communicator
Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING
More informationFireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
More informationInstallation Instructions
Installation Instructions S E C U R I T Y S Y S T E M Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations
More informationCrypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL
Crypto-Lock Model CC-8521B Updated 7/17 Access Control System INSTRUCTION MANUAL MONITEQ, Inc. 2 TABLE OF CONTENTS 1. INTRODUCTION..4 2. SPECIFICATIONS.....6 3. SUPPLIED EQUIPMENT.. 6 4. FUNCTIONS OF CONTROLS
More informationEVO192 v3.0 Fire and Burglary What s New
EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They
More informationRMS/RPX Reader. User Manual
RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,
More informationRAM3 Remote Alarm Module
RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.
More informationLong Range Radio Alarm Transmitter
TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3 This manual is for the LINKS2150 software version 1.3 TABLE OF CONTENTS FEATURES 1 Keypad Programmable... 1 EEPROM Memory... 1 Static/Lightning
More informationSupplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual
Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised
More information0$; Installation Instructions. Computerized Control Panel '(6&5,37,21 63(&,),&$7,216 DE5011 1
0$; Computerized Control Panel Installation Instructions '(6&5,37,21 The MAX-5 is a highly reliable, cost effective control panel for residential and commercial applications. Besides being simple to install
More informationTECHNICAL DATA OBSOLETE
Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)
More informationINSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS
INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS MODEL XR5FC/XR5SL COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed
More informationINSTALLATION MANUAL PC25OO
INSTALLATION MANUAL PC25OO NOTES ON UL INSTALLATION This equipment is UL listed in accordance with UL standard 1023 (Household Burglar Alarm System Units), UL standard 985 (Household Fire Warning Units)
More informationTECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.
September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.
More informationPipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder
Pipo Communications Model ST-888 DTMF ANI/ENI Display Decoder 1516 Cassil Place Hollywood, California 90028-7106 Phone: 323-466-5444 Fax: 323-466-1520 www.pipo.cc Manual # 68-9888 May 1, 2002 Rev. 5/02
More informationInstallation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.
More informationDS7400Xi Addressable Control/ Communicator
DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems
More informationSection PERIMETER SECURITY SYSTEMS
Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security
More information16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5
Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series
More informationMODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS
MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS OPERATES ON 12 OR 24 VOLTS AC/DC, AUTO VOLTAGE SENSING FULLY PROGRAMMABLE FROM THE KEYPAD
More informationTABLE OF CONTENTS TABLE OF CONTENTS 1
TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2
More informationInstallation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp
More informationRELEASE DEVICE CONTROLS
RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a
More informationSEC 2000 Millenium Infrared Gas Detector
SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com
More information30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
More informationUsing Your GEM-P400 Security System H
Using Your GEM-P400 Security System H 1 2 3 4 AR MED STATU S 1 2 This page left blank intentionally Introduction Congratulations on your purchase of an advanced GEMINI-P400 Security System. Meticulously
More informationModel Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:
Model 2102 Gas Alarm Panel APPLICABILITY & EFFECTIVITY This manual provides instructions for the following Sierra Monitor products: Model Description 2102-00 Alarm Panel 2 Channel 2102-01 Alarm Panel 2
More informationMulti-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.
M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @
More informationIMPORTANT SAFETY INSTRUCTIONS
WARNING TO PREVENT FIRE OR SHOCK HAZARD, DO NOT USE THIS PLUG WITH AN EXTENSION CORD, RECEPTACLE OR OTHER OUTLET UNLESS THE BLADES CAN BE FULLY INSERTED TO PREVENT BLADE EXPOSURE. TO PREVENT FIRE OR SHOCK
More informationKT-100 Door Controller
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully
More informationHA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE
D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system
More informationMulti-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.
M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp
More informationEVAPORATIVE COOLER W
EVAPORATIVE COOLER 972-1003-W USER MANUAL INTRODUCTION READ AND SAVE THESE INSTRUTIONS! 1 Thanks for your support and choice of our unique tower fan, in order to help you use the product more conveniently,
More informationSelf-Setting Clock Radio
Self-Setting Clock Radio Just plug it in it sets itself TimeSmart table of contents Cautions and Warnings................................................. 2-6 Location of Controls....................................................
More informationWith Remote Control. English. Model
Digital Ceramic Heater With Remote Control, Owner s Manual English Model HPQ15F-E TABLE OF CONTENTS 2 INTRODUCTION Thank you for choosing the Hunter Ceramic Heater. This manual gives you complete instructions
More informationInstallation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev
Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control
More informationTABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover
TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad
More informationVoice Module Installation Guide. For use with ProSYS 16, ProSYS 40, ProSYS 128
Voice Module Installation Guide For use with ProSYS 16, ProSYS 40, ProSYS 128 Important Notice This guide is delivered subject to the following conditions and restrictions: This guide contains proprietary
More informationRANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...
More informationDATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D
DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.
More informationControl Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2
Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...
More informationFW-RA-LED Remote Multiplex Annunciator Panels
FW-RA-LED Remote Multiplex Annunciator Panels WIRING and INSTALLATION INSTRUCTION LNOTICE All information, documentation, and specifications contained in this manual are subject to change without prior
More informationInstallation Instructions
0$;0$; Computerized Multi-Function Alarm Control Panels Installation Instructions '(6&5,37,21$1'&$3$%,/,7,(6 The MAX-8 and MAX-16 are reliable, cost-effective control panels for residential and commercial
More informationUniversal Fan and Light Remote Control
Universal Fan and Light Remote Control Hand-Held Remote and Wall Cradle Owner s Guide and Installation Manual English Form# 41316-01 20100930 2010 Hunter Fan Co. 1 Welcome Table of Contents Read and Save
More informationGlobal Water Instrumentation, Inc.
Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 High Water Alarm WA400-DC WA400-AC WA400-BU WA400-FS WA400-AL 10/23/06 P/N: 01-527
More informationSentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.
Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3
More informationInstallation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control
More informationRAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE
Advanced Life Safety Solutions RAM-208 Remote Multiplex Annunciator Panel A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE LAMP TEST SYSTEM RESET Wiring & Installation Installation
More informationOwner s Manual. PIR-1 IR Learner
Owner s Manual PIR-1 IR Learner PIR-1 Owner s Manual 2010-2013 Universal Remote Control, Inc. The information in this owner s manual is copyright protected. No part of this manual may be copied or reproduced
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
More informationGROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer. Users Manual
GROUP OF COMPANIES MERLIN STEALTH Electric Fence Energizer Users Manual Revision 1.2 20 July 2011 : USERS MANUAL March 2007 Table of Contents FOREWORD.... 3 GUARANTEE.... 4 INTRODUCTION.. 5 OPERATION WITHOUT
More informationINSTALLATION GUIDE XTLN-WIFI PANEL
INSTALLATION GUIDE XTLN-WIFI PANEL MODEL XTLN-WiFi INSTALLATION GUIDE FCC NOTICE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of
More informationADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE
K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.
More informationINSTALLATION MANUAL PC56O. Version 1.OA
INSTALLATION MANUAL PC56O Version 1.OA TABLE OF CONTENTS INTRODUCTION 3 Features... 3 Specifications... 3 INSTALLATION 4 Mounting the Control Panel... 4 Mounting the Keypad... 4 Wiring... 5 Burglary Zone
More informationPERS-3600 PERSONAL EMERGENCY REPORTING SYSTEM INSTALLATION & OPERATION INSTRUCTIONS
PERS-600 PERSONAL EMERGENCY REPORTING SYSTEM BY BY INSTALLATION & OPERATION INSTRUCTIONS (760) 8-7000 USA & Canada (800) -587 & (800) 9-0 Toll Free FAX (800) 68-0 www.linearcorp.com CONTENTS CONTROL AREA
More informationNetworX Series NX-870E Fire Supervision Module Installation and Startup
NetworX Series NX-870E Fire Supervision Module Installation and Startup 2002 GE Interlogix All rights reserved. Printed in the USA. NetworX is a trademark of GE Interlogix. These instructions do not purport
More informationDATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D
DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.
More informationD2071A. Operation & Installation Guide Fire Alarm Control Panel
D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More information1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN
Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More information4100U City and Relay Cards Installation Instructions
4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting
More informationMODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
More informationInstallation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger
More information4500 THERMOSTAT INSTALLATION INSTRUCTIONS
4500 THERMOSTAT INSTALLATION INSTRUCTIONS N7970 7/97 Downloaded from: http://www.guardianalarms.net Table of Contents Section 1. GENERAL DESCRIPTION...1-1 Application and Description...1-1 4500 Specifications...1-2
More informationLUMA-NET 804CP / 808CP REMOTE CONTROL PANEL
LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL INSTALLATION AND OPERATION GUIDE INTRODUCTION The NSI 804CP and 808CP represents a key part of a state of the art, total lighting control system. Combined with
More informationXR10/XR20 Command Processor Panels Installation Guide
XR10/XR20 Command Processor Panels Installation Guide 10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator LT-0229 (5/97) MODEL XR10/XR20 COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationTECHNOLOGY CORP. Taking a bite out of energy costs. Instruction Manual for the ORKA Remote Thermostat/Humidity Controller.
ORKA TECHNOLOGY CORP. Taking a bite out of energy costs Instruction Manual for the ORKA Remote Thermostat/Humidity Controller Model # RFTH-100 Thank you for your purchase of Orka Technology s RFTH-100
More informationBooster Power Supply Manual
Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation
More informationSafety & Installation Instructions
Model 6303 & 6302 Zoned Comfort Control Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61001212A 6302-6303 Zoned Comfort Control Install.indd 1 TABLE OF CONTENTS SAFETY INSTRUCTIONS..........................................
More informationINSTALLATION MANUAL PC15OO
INSTALLATION MANUAL PC15OO This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2)
More informationTwin Bell Digital Clock
Twin Bell Digital Clock Model: V50-500 Instruction Manual PLEASE READ THIS INSTRUCTION MANUAL CAREFULLY BEFORE USE AND KEEP IT FOR FUTURE REFERENCE. SPECIFICATIONS... 1 SAFETY INSTRUCTIONS... 2 FUNCTIONS...
More informationModel 4001 Series Single Channel Controller
Model 4001 Series Single Channel Controller Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-Mail: sales@sierramonitor.com Web site:
More informationMR-2316-AT/Z Remote Annunciator
MR-2316-AT/Z Remote Annunciator Secutron LT-617SEC Rev.1 February 2011 Table of Contents Table of Contents 1.0 Introduction 7 1.1 Contact Us... 7 1.1.1 General Inquiries... 7 1.1.2 Customer Service...
More informationLED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.
LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels
More informationCONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA
CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with
More informationAL800ULADA. NAC Power Extender. Installation Guide
AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery
More informationOhm Metrics. Instruction Manual. Continuous Workstation Monitors Model CM1600. T r a n s f o r m i n g T e c h n o l o g i e s, L L C
O u t s t a n d i n g A l t e r n a t i v e s i n S t a t i c C o n t r o l T r a n s f o r m i n g T e c h n o l o g i e s, L L C Ohm Metrics Continuous Workstation Monitors Model CM1600 Instruction Manual
More informationInstallation Guide. Control/Communicator
Installation Guide Control/Communicator 33120G Page 2 Copyright 2001 Radionics Contents 1.0 Introduction... 5 1.1 Listings and Approvals... 5 1.1.1 Fire... 5 1.1.2 Burglary... 5 1.2 FCC Notice... 5 1.2.1
More informationExcel-EN Conventional Fire Control Panel
Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs
More informationAddressable NAC Output Module D327A
Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,
More informationBeacon 800 Gas Monitor Operator s Manual
Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be
More informationAMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.
AMC-RAM-4 Refrigerant Alarm Module USER MANUAL IMPORTANT: Please read the installation and operating instructions completely and carefully before starting. Filename: 3310405B, DOC, AMC_RAM4_Manual.doc
More informationHazardous Area Ringdown Telephone
Industrial Communications Worldwide Hazardous Area Ringdown Telephone Model EP701 Installation & Operation 7552-10th Street N.E. Calgary, Alberta, Canada T2E 8W1 Ph: 403.258.3100 \ email:info@guardiantelecom.com
More informationPSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
More informationAIM TECHNICAL MANUAL PATENT PENDING STOP REMEMBER TO ACTIVATE UNIT BEFORE TESTING. See page 9 for Activation Instructions
AIM TECHNICAL MANUAL AIM-1450WL WIRELESS PATENT PENDING STOP REMEMBER TO ACTIVATE UNIT BEFORE TESTING See page 9 for Activation Instructions AIM Technical Manual - AIM 1450WL AIM-1450WL WIRELESS ABOUT
More informationInstallation Manual Version 1.3. Long Range RF Transmitter. How to contact us:
How to contact us: Technical Support If you have questions or problems when using this product, you can call Technical Support. If you are within the United States or Canada, you can get support by dialing
More information52 BERKSHIRE CEILING FAN
52 BERKSHIRE CEILING FAN Owner s Manual Models #20223, 20224 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9
More informationBeacon 410A Gas Monitor Operator s Manual
Beacon 410A Gas Monitor Operator s Manual Part Number: 71-0397 Revision: F Released: 12/5/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be
More informationTowel Warmer MAKE EVERYDAY A SPA DAY
Towel Warmer MAKE EVERYDAY A SPA DAY TABLE OF CONTENTS Warnings and Cautions....1 FCC Information...4 Location of Parts and Controls...6 Set Up... 7 Using the Towel Warmer....8 Selecting the Timer...9
More information