West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Size: px
Start display at page:

Download "West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8"

Transcription

1 City of Ottawa Project No. CR Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire Marshall..2 National Fire Protection Association Standards: NFPA Reid Stenhouse Limited Standards.4 Insurer's Advisory Organization (IAO).5 Factory Mutual (FM).6 NFPA Contractors.1 Acceptable Contractors:.1 Grinnell.2 Ottawa Sprinkler.3 Escape Fire Protection 1.3 Description of Work.1 The work includes, but is not necessarily limited to the following:.1 Removal of all existing sprinkler piping distribution within the existing building, back to the sprinkler valve closet..2 Design and installation of a new sprinkler system to serve the existing and the new construction..3 Testing and commissioning of complete system. 1.4 Design Criteria.1 Sprinklers are to be hydraulically designed for the coverage and occupancy as indicated..2 Carry out flow test of water main and submit results for Engineer's review prior to submitting hydraulic calculations..3 Survey existing sprinkler system as required, and incorporate necessary information to the shop drawings..4 All sprinkler piping shall be installed to allow diffusers or lights to be relocated to any position within the ceiling grid for lay-in tile suspended ceilings.

2 City of Ottawa Project No. CR Page 2 of 8.5 Heads shall be located in the centre of the ceiling tiles in areas with suspended ceilings..6 The location of heads in all areas shall be coordinated with Architect and Engineer..7 All branch piping shall be installed in the joist space (where applicable) to minimize future interference..8 All sprinkler mains installed within areas with no suspended ceilings shall be installed as high as possible. Refer to architectural and structural drawing for general layouts and beam openings to install piping..9 Sprinklers in elevator machine rooms shall be sidewall type only, or where not possible, provide drain trays under all piping..10 Sprinkler system to be seismically restrained to Ontario Building Code and NFPA # 13 requirements. Shop drawings to be certified by a Professional Engineer..11 Provide the following zones:.1 Ground Floor..2 Second Floor.12 Design densities to be confirmed with IAO or FM as follows:.1 Library Areas: 0.1 gpm/sq.ft. over 1500 sq.ft..2 Mechanical Areas: 0.15 gpm/ sq.ft. over 1500 sq.ft. 1.5 Shop Drawings.1 Drawings and calculations shall be certified by a Professional Engineer registered in the Province of Ontario..2 Submit shop drawings and technical information for the review and approval of the Engineer. Two prints are required..3 Drawings are required for sprinkler heads, siamese connections, sprinkler layout, alarm valve, accessories, and hydraulic calculations. Drawing to incorporate the existing sprinkler valve and piping distribution system, including all necessary modifications to the existing system and equipment to complete the installation.

3 City of Ottawa Project No. CR Page 3 of 8.4 Sprinkler layout drawings shall be submitted at the same scale as the architectural drawings and must be on AutoCAD 2008 or later. Manual drawings will not be accepted..5 Submit hydraulic calculations for review, certified by a Professional Engineer in the Province of Ontario..6 Submit copies of all necessary information to the Client's insurance advisors and obtain their approval before proceeding with installation. Any modifications required to the installation to obtain this approval shall be to the contractor's account. 1.6 Coordination and Cooperation.1 This trade shall be responsible for fully coordinating his piping with those of the HVAC, plumbing, electrical and other contractors..2 Obtain drawings from HVAC contractor and super-impose these on sprinkler drawings where necessary to show areas of conflict..3 Survey existing systems and building conditions..4 Cooperate with all existing tenants to minimize the inconvenience during the installation of systems in occupied areas. 1.7 Maintenance Data.1 Provide maintenance data for sprinkler system, for incorporation into the maintenance manual in accordance with Division Earthquake Protection.1 Sprinkler system shall be restrained for earthquake protection in accordance with NFPA 13. PART 2 - PRODUCTS 2.1 Pipe, Valves and Fittings.1 Pipe, Valves and Fittings:.1 Up to NPS 2 shall be schedule 40 black steel, lightwall threadable pipe; to ASTM A-135, A-53, or A-795 with

4 City of Ottawa Project No. CR Page 4 of 8 threaded joints or style 005 firelock couplings with Vic plus gasket system..2 NPS 2-1/2 to NPS 4 shall be Schedule 40 black steel to ASTM A53 with mechanical cut grooved couplings, or engineered lightwall pipe with roll grooved couplings to ASTM A795 Type E Grade A complete with angle bolt pads..3 Schedule 10 black steel pipe to ASTM A53 may be used for NPS 2-1/2 to NPS 5 and schedule 20 for NPS 6 and over, with roll grooved couplings complete with angle bolt pads..4 Any below ground piping shall be either ductile iron Class 51 or if not also serving domestic water system may be black steel protected against corrosion with Denso tape applied with a minimum 50% overlap of the joints..5 Where a grooved system is used, all grooved end products shall be of one manufacturer..2 Fittings:.1 Shall be Class 125/150 for system pressures up to 1200 kpa (175 psig), and shall be Class 250/300 for system pressures over 1200 kpa (175 psig) and up to 2070 kpa (300 psig)..2 Up to NPS 2 shall be malleable iron threaded fittings Class 150 or 300 to ANSI B16.3, or cold drawn electroplated steel with integral O-ring seals..3 Over NPS 2 shall be cast iron flanged fittings Class 125 or 250 to ANSI B16.1 or malleable iron flanged fittings Class 150/300 to ASTM B16.5, with hex head nuts and bolts to ASTM A307 and 1.6 mm thick plain or cloth inserted red rubber gaskets to ANSI B16.20 and B16.2. Alternatively approved ULC listed mechanical grooved couplings may be used..3 Valves:.1 All valves shall be UL or ULC listed for fire protection service, and be FM approved..2 Up to NPS 2 valves shall be bronze to ASTM B61 outside screw and yoke style Crane No.459 or approved equal..3 Over NPS 2 gate valves shall be flanged cast iron body, bronze mount OS&Y bolted bonnet and yoke, bronze seat and disc, Crane No or approved equal up to 1375 kpa (200 psi) working pressure..4 Over NPS 2 butterfly valves shall be grooved end ductile iron polyphenylene coated body, with EPDM coated ductile iron disc, complete with weatherproof manual actuator, and

5 City of Ottawa Project No. CR Page 5 of 8 two prewired SPDT supervisory switches. Valve to be rated for not less than 1200 kpa (175 psi). Acceptable Material: Victaulic style 750W and Check valves shall be grooved end ductile iron body with spring loaded single disc check, and resilient EPDM seat rated for up to 1375 kpa (200 psi)..6 Inspectors test valves shall be Victaulic Style 720 or equal, rated 300 psi with sight glass..7 Floor by floor zones: A fully integrated device that combines the flow switch, pressure gauge and the Testmaster II into a single factory assembly. Acceptable Material: Victaulic 747 Riser Manifold..4 Backflow Preventers: For isolation of antifreeze systems use an RPP backflow preventer to CSA B64..5 Pipe Hangers: Shall be ULC listed for fire protection service and installed in accordance with NFPA Signs.1 Signs: fabricated from metal with chain suspension; white letters on red background. 2.3 Sprinkler Heads.1 All heads to be Factory Mutual approved..2 Heads in areas without ceilings to be brass upright, painted white. Temperature rating 74 C (165 F.)..3 Heads in areas with ceilings (suspended T-bar, drywall, or any other types of ceilings) shall be white concealed type, temperature rating 74 C (165 F.).4 Supply spare heads of each type and wrenches in a suitably marked cabinet in accordance with NFPA Siamese Connection.1 Provide new chrome plated brass siamese fire department connection as indicated to supply sprinkler system with two NPS 2-1/2 female hose connections fitted with caps and chains. Threads

6 City of Ottawa Project No. CR Page 6 of 8 of NPS 2-1/2 connection shall conform to those of local fire department. Acceptable Material: NFE Model Piping from connection shall be the same size as the sprinkler system. Include horizontal check valves and automatic drip discharging to nearest floor drain for connections..3 Identify pumper connections with sign having raised letters at least 25 mm in size cast on plate or fitting reading "AUTOMATIC SPRINKLER SYSTEM". 2.5 Supervisory and Alarm Switches.1 Supervisory switches for butterfly valves shall be Potter Electric Signal Co. Model PCVS-2..2 Supervisory switches for OS&Y gate valves shall be Potter Electric Signal Co. Model OSYSU-2..3 Waterflow switches shall be Potter Electric Signal Co.Model VSR-F..4 Supervisory and alarm pressure switches shall be Potter Electric Signal Co. Model PSS-40 for dry sprinkler systems and Model PSS-120 for wet sprinkler systems. 2.6 Wet Pipe System.1 Provide complete with following:.1 Alarm valve.2 Indicating control valves.3 Excess pressure pump and pressure switch.4 Water pressure gauges on inlet and discharge of alarm valve..5 Piping and fittings.6 Valves.7 Hangers.8 Floor and ceiling escutcheon plates..2 Provide alarm valve complete with excess pressure pump and standard accessories, drain valves, check valves, alarm connections and water gauges. Provide indicating type valves for controlling water supply and alarm shutoff.

7 City of Ottawa Project No. CR Page 7 of 8.3 Provide water flow alarm, valve tamper alarm, and low pressure supervisory alarm devices..4 Provide excess pressure pump capable of pumping system to 25 psi in excess of normal pressure within 30 min. Provide pump with supports, safety valve, gauge, starter and connections to wet pipe sprinkler system. Set safety valve 10 psi above operating pressure. Pump to be 110 volt, single phase. Acceptable Material: Albany. PART 3 - EXECUTION 3.1 Installation.1 Install horizontal valve with stems upright where space allows..2 Arrange drains so that they can be fully opened without flooding..3 Sprinkler mains to be installed within 12" of underside of steel joists, and all branch piping shall be in joist space..4 Piping shall run parallel to building grid lines..5 Mechanical contractor to isolate sprinkler system as required to perform work. Notify owner in advance of all shutdowns and follow owners procedures regarding draining and re-filling of system. Mechanical contractor to include all costs for de-activation and reactivation of fire alarm system as required to perform work. Fire alarm system shutdowns to coincide with sprinkler shutdowns. 3.2 Testing.1 Test systems in accordance with NFPA 13 and authorities having jurisdiction. 3.3 Protection of Completed Work.1 Provide red wire guards for sprinkler heads in elevator machine rooms, mechanical rooms, electrical rooms, Janitor s room, and in other areas subject to damage.

8 City of Ottawa Project No. CR Page 8 of Site Visit.1 The Engineer providing the certified design for the sprinkler layout drawings and calculations shall visit the site, as required, to provide a letter at the end of construction, indicating the installation is in accordance with the certified shop drawing submission and Ontario Building Code. The letter shall be stamped and signed with the Professional Engineer s seal, licensed in the Province of Ontario. END OF SECTION

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314W - AUTOMATIC SPRINKLER SYSTEMS (WET PIPE SYSTEMS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPRESSION SYSTEMS 21 1200 FIRE-SUPPRESSION DRY STANDPIPES 21 1313 WET PIPE SPRINKLER PROTECTION SYSTEM 21 1314 WET-PIPE AUTOMATIC SPRINKLER SYSTEM

More information

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13. 21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS SECTION 13900 FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Automatic wet-type, Class I, fire-suppression standpipes and branches for sprinklers. 2. Wet-pipe, fire-suppression

More information

2. Welding Materials and Procedures shall conform to the ASME Code.

2. Welding Materials and Procedures shall conform to the ASME Code. PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 211313 WET-PIPE SPRINKLER SYSTEMS PRT 1 GENERL 1.01 RELTED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals 1 General 1.1 Provide all material, labor, engineering and operations for the installation of complete and operable fire suppression systems as shown in the job scope and as specified herein. 1.2 Provide

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 21 13 13 FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS A. Furnish all labor, materials, equipment services and incidentals required to design and install properly

More information

A. This Section includes the following fire-suppression piping inside the building:

A. This Section includes the following fire-suppression piping inside the building: SECTION 211000 - WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following fire-suppression piping inside the building: 1. Automatic wet-type, standpipe systems.

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

SECTION AUTOMATIC SPRINKLER PIPING

SECTION AUTOMATIC SPRINKLER PIPING SECTION 15330 AUTOMATIC SPRINKLER PIPING ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of automatic sprinkler piping. Some piping is allowed

More information

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13930 WET-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete wet-pipe fire sprinkler system in new addition only as specified

More information

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS SUNY GENESEO 211310-1 PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

Design and Construction Standards SECTION FIRE SUPPRESSION

Design and Construction Standards SECTION FIRE SUPPRESSION SECTION 13900 FIRE SUPPRESSION PART 1 GENERAL 1.1 SCOPE A. The work under this section of the specifications consists of furnishing all materials, equipment, labor, testing, appurtenances, engineering

More information

SECTION FIRE SUPRESSION

SECTION FIRE SUPRESSION PART 1 GENERAL 1.1 SCOPE SECTION 21 00 00 FIRE SUPRESSION A. The work under this section of the specifications consists of furnishing all materials, equipment, labor, testing, appurtenances, engineering

More information

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6 Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

Mercury Plastics New Building February TABLE OF CONTENTS

Mercury Plastics New Building February TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 210500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 210548 VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 211300 WET PIPE FIRE SUPPRESSION SPRINKLERS

More information

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13935 DRY-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete fire sprinkler system as specified in Contract Documents. B.

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION FIRE SUPPRESSION SYSTEMS

SECTION FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2

More information

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum. Page 211200-1 SECTION 211200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

SECTION : FIRE PROTECTION SYSTEMS

SECTION : FIRE PROTECTION SYSTEMS SECTION 21 00 10: FIRE PROTECTION SYSTEMS 1. GENERAL A. This section applies to the design and performance information for fire protection and suppression systems. B. All fire protection materials and

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 13 16 DRY-PIPE SPRINKLER SYSTEMS SPEC WRITER NOTES: Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including NFPA references which are not

More information

SECTION FIRE-SUPPRESSION PIPING

SECTION FIRE-SUPPRESSION PIPING SECTION 211313 FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SECTION ELECTRIC-DRIVEN, FIRE PUMPS SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including

More information

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS FIRE PROTECTION BA SECTION 13910 - FIRE PROTECTION BASIC MATERIALS AND METHODS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler, standpipe and fire hose,

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION SYSTEMS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION SYSTEMS PART 1 - GENERAL SECTION 21 12 00 FIRE PROTECTION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211200 - FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Hose connections. 4. Fire-department connections.

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

SECTION FIRE PROTECTION SYSTEMS

SECTION FIRE PROTECTION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: SECTION 21 12 00 FIRE PROTECTION SYSTEMS A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY. Copyright 2016 by The American Institute of Architects (AIA) Exclusively published and distributed by AVITRU, LLC for the AIA This Product MasterSpec Section is licensed by AVITRU, LLC to Victaulic Company

More information

Facility Fire-Suppression Water-Service Piping

Facility Fire-Suppression Water-Service Piping University of New Hampshire University of New Hampshire Scholars' Repository Division 21 Fire Supression Chapter 5 Technical Construction and Renovation Standards 4-23-2015 211100 - Facility Fire-Suppression

More information

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL DESCRIPTION A. Furnish all materials and labor for the detailed design and installation for new fire sprinkler wet pipe systems for Buildings A through R hereafter referred

More information

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015 SECTION 211000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Related Documents: Drawings, Notice to Bidders, General Conditions, Project Coordination, RFP Format, Requested RFP Alternatives, Cutting and

More information

TABLE OF CONTENTS

TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 21 05 00 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 21 13 00 WET PIPE FIRE SUPPRESSION SPRINKLERS END TABLE

More information

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids. SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems

More information

May 2017 Middleton Heritage 09T SC DIVISION 21: FIRE SUPPRESSION END OF TABLE OF CONTENTS

May 2017 Middleton Heritage 09T SC DIVISION 21: FIRE SUPPRESSION END OF TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPPRESSION SYSTEMS 21 1313 Wet-Pipe Sprinkler Systems END OF TABLE OF CONTENTS Table of Contents - 1-21 0000 B L A N K P A G E Table of Contents

More information

Specialties Quality, Durability, Reliability. FIrE ProTECTIon

Specialties Quality, Durability, Reliability. FIrE ProTECTIon _specialties:pcsectiond_new 2/6/2012 4:46 PM Page -36 36 SECTIon Specialties Quality, Durability, Reliability FIrE ProTECTIon In addition to our plumbing business, LYNCAR has been a leading supplier to

More information

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.

More information

Addendum No. 2 to the Contract Documents

Addendum No. 2 to the Contract Documents Addendum No. 2 to the Contract Documents Lewis County Jefferson Community College Education Center Project CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL

More information

DIVISION 21: FIRE SUPPRESSION

DIVISION 21: FIRE SUPPRESSION DIVISION 21: FIRE SUPPRESSION 21 0500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 21 0553 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 21 1300 WET PIPE FIRE SUPPRESSION SPRINKLERS Kenworth Sales

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 PART I - GENERAL 1.01 WORK INCLUDED A. Furnish all labor, materials, tools, and equipment to complete the automatic fire sprinkler system as hereinafter described, ready for service to the

More information

New Rigby Elementary School February TABLE OF CONTENTS

New Rigby Elementary School February TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 21 0500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 21 0548 VIBRATION & SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING & EQUIPMENT 21 0553 IDENTIFICATION FOR FIRE SUPPRESSION PIPING

More information

Capital Projects Group Fire Protection Sprinkler System Specification

Capital Projects Group Fire Protection Sprinkler System Specification Capital Projects Group Fire Protection Sprinkler System Specification Specification 21 13 00 Revision 0 Date: August 2018 Fire Protection Sprinkler System Specification Specification 21 13 00 Publication

More information