1 Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY This report will describe the existing lighting system of the specific spaces of my redesign the auditorium, the atrium, the outdoor plaza and the 4 th level, representative of each of the lower levels. Included in the description is the lighting hardware, control devices and daylighting elements. Space properties such as surface materials, reflectances and furniture arrangement are also discussed. The existing system will be evaluated against the IES design criteria and ASHRAE Standard 90.1, From this report, I concluded that the lighting system of the auditorium meets the design criteria established. Additionally, the offices, design labs and editing rooms have appropriate lighting designs that exceed the lighting levels of IESNA. However, the atrium s track lighting system is ineffective, requiring too many fixtures to meet the recommended lighting levels. The results of the evaluation of the 4 th floor showed the need for a system to adjust the light levels in response to the amount of daylighting contributing to the space. The system would reduce the energy costs for the building.
2 Lighting Existing Conditions and Design Criteria Report The Maryland Institute College of Art is one of the nation s leading centers for digital art and design. The Brown Center reflects this idea in everything from it s unique structural frame to it s lighting system. This report will describe both the College s general lighting system and more specifically, the lighting systems of the four spaces I will be redesigning. The design criteria according to IESNA will be evaluated along with the power allowances according to ASHRAE/IESNA 90.1, Based on these criteria, I will evaluate the current system to determine the areas to improve in my redesign. Auditorium EXISTING LIGHTING SYSTEMS The 4,600 square foot auditorium holds 550 seats. Entrance to the space is through two sets of double doors at the rear of the auditorium. The doors empty on to the two aisle flanking each side of the seating and leading to the stage running along the angled south wall. (Figures 1.1 and 1.2) The space is able to hold a variety of functions. The stage will be used for small scale performances in dance and music. In addition, a 14 x 26 projection screen can be brought down over the stage to showcase the students work in digital mediums. The lighting system will need to adapt to both of these different functions. Figure 1.1: Auditorium Plan View
3 Figure 1.2: Auditorium Section The structure of the building is left exposed throughout the space. The ceiling and columns are the exposed concrete structure, while the concrete floor is sealed. The walls are composed of decorative concrete masonry units with acoustical panels mounted at various positions along the walls. Refer to Figure 1.3 for the surface materials and reflectance. Figure 1.3: Surface materials and reflectance SURFACE MATERIAL REFLECTANCE Ceiling Exposed concrete structure 35% Walls Decorative CMU 35% Acoustic Panels Floor Sealed Concrete 35% (IESNA, 9 th Edition, Figure 136, page 122) The overall lighting system of the auditorium consists of 9 rows of luminaires spaced 10 on center along the length of the auditorium ceiling. The 4 rows of fixtures closest to the stage are attached to pipe batton. This allows for flexibility of the lighting system with fixtures added or removed as needed. (5) 32 lengths of track run east to west at the north end of the auditorium, including (3) over the balcony. Each row contains (5) 100W PAR 38 accent lights spaced 7 on center. (Type A, Figure 1.4) Each luminaire is directed south towards the stage.
4 (3) 32 lengths of pipe batton follow the track sections. In addition to the (5) accent lights, each pipe batton contains extra theater lighting. The (5) 575W halogen spotlights are positoned at various spots along each pipe. The beam spreads vary between 26, 36 and 50. (Types B B3, Figure 1.4) (1) 24 length of pipe batton runs directly over the stage. This pipe holds (4) 100W accent lights and (6) 575W spotlights (3) directed north towards the audience and (3) directed south towards the projection screen. 28 above the auditorium floor are 2 rows of (9) pendant mounted 350W halogen asymmetric wallwashers spaced 5 on center. (Type C, Figure 1.4) A row of fixtures is positioned above each aisle from the rear entrance doors to the middle of the auditorium. Along the interior aisle walls, spaced 6 on center are recessed compact fluorescent steplights. (Type D, Figure 1.4) Finally, (2) 10 vertical pipe battons are mounted to the walls on each side of the stage. The initial design does not specify any luminaries mounted here, but the pipes were installed for future use. Figure 1.4: Auditorium Lighting Fixture Schedule TYP DESCRIPTION WATT VOLT MTNG LAMP FEATURES BALLAST A Halogen djustable accent light clamp (1)100W halogen PAR38 Fl 5 diameter cross baffle sheild B B1 B2 Halogen variable beam spot light Halogen ellipisoidal reflector Halogen ellipisoidal reflector clamp (1) 575 GLC, 115v Specular alzak reflector, 4 lens set VNSP, NSP, MFL, WFL clamp (1) 575 GLC, 115v 26 beam spread 6 diameter specular alzak reflector clamp (1) 575 GLC, 115v 36 beam spread 6 diameter specular alzak reflector
5 B3 C Halogen ellipisoidal reflector Halogen asymmetric wallwasher clamp (1) 575 GLC, 115v 50 beam spread 6 diameter specular alzak reflector pendant (1) 350 W HIR 8 x AFF aluminum reflector D Steplight wall 7W compact fluorescent 8 x 4 flush louvered faceplate 18 AFF High power factor ballast Atrium The atrium is the prominent entrance lobby of the Brown Center. It has the footprint of a right triangle with the two legs of the triangle being the glass curtain wall rising 60 feet. The hypotenuse of the triangle is clear glass, separating the atrium from the main corridor of each of the upper levels. (Figures 1.5 and 1.6) The atrium serves two functions. First, it is the building s central circulation space. The main staircase is located just beyond the entrance doors. The open concrete staircase can be seen escalating to each of the upper three levels. In addition, access to the elevator, auditorium and lower auditorium lobby leads off from this space. Secondly, the atrium hold the building s reception desk, positioned just left of the revolving doors. Figure 1.5: Atrium Plan View
6 Figure 1.6: Atrium Section Since the glass curtain wall slopes in at 27 degrees, it becomes both a wall of the atrium and the ceiling. The steel framed curtain wall is composed of a translucent white glass with a white frit pattern to allow light to pass through while blocking glare. The floors are the sealed concrete seen in the auditorium. Surafce materials and reflectances and transmittance are summarizes in Figure 1.7 below. Figure 1.7: Surface materials and reflectance/transmittance SURFACE MATERIAL REFLECTANCE/ TRANSMITTANCE Ceiling/Exterior White glass 80% Walls Interior wall Clear glass 95% Floor Sealed Concrete 35% (IESNA, 9 th Edition, Figure 136, page 122) Because the atrium is composed almost entirely of glass, daylighting is the primary lighting system used. For times when additional light is needed, a simple system of two rows of fixtures is used. The first track is attached to the sloped wall of the atrium across from the 3 rd level. Three 20 sections of track run the entire length of this wall. (4)150W halogen wallwashers and (2) 100W halogen accent lights are positioned along each of the three tracks. (Types F and A1, respectively, Figure 1.8) Identical to this system is a second row of tracks across from the 4 th level.
7 A triangular system of track lighting is used to highlight the reception desk and pathway to the elevator lobby and the lower auditorium lobby. Three 8 sections of track form an equilateral triangle to which the luminaries are attached. On each section, (1) 100W accent light is directed towards the center of the triangle (Type A1, Figure 1.8) and (2) 150W wallwashers are directed outwards. (Type F, Figure 1.8). Other fixtures in this space include the monopoint mounted 100W accent lights. (Type A2, Figure 1.8) A row of three fixtures are mounted to the underside of the stairs at each landing. These will provide emergency lighting for the means of egress. Figure 1.8: Atrium Lighting Fixture Schedule TYP DESCRIPTION WATT VOLT MTNG LAMP FEATURES BALLAST A1 Halogen djustable accent light track (1)100W halogen PAR38 Fl 5 diameter cross baffle sheild A2 F Halogen djustable accent light Halogen wallwasher Mono point (1)100W halogen PAR38 Fl track (1) frosted Q150DC 5 diameter cross baffle sheild 7 x 6 cross baffle shield Plaza An outdoor plaza is formed by the intersections of the existing Fox building and the Brown Center and the avenues of West Mount Royal and West Lafayette. This 9,600 square foot space serves as a gathering spot for people visiting the two buildings. Two side walks cut through the plaza one for access to the Brown Center from Lafayette Avenue and the other linking the Brown Center to the Fox Building. Benches line the sidewalks and the paths are joined by a large water feature. (Figure 1.9)
8 Figure 1.9: Plaza Plan View The lighting of the plaza is fairly minimal. A row of (3) 95 W single metal halide pole top luminaries line the main walkway between Lafayette Avenue and the Brown Center. (Type G, Figure 1.10) The building façade is illuminated by a series of direct burial uplights spaced 10 on center and 2 from the building. (Type H, Figure 1.10) These 400 W uplights are an alternative to flood lights to highlight the architecture. To illuminate the entrance to the building, a cluster of 40W inground adjustable uplights are positioned near the doors. (Type J, Figure 1.10) Figure 1.10: Plaza Lighting Fixture Schedule TYP DESCRIPTION WATT VOLT MTNG LAMP FEATURES BALLAST G Metal Halide pole (1)MHC95/U/M/3 Pole top K H J Direct burial uplight Adjustable uplight In ground In ground (1)MH 400/U (1) CDM35/PAR20/M /Fl 22 diameter 180º side lighting 12 pole 27 deep housing 10º lamp tilt 7.5 diameter 14 recess F can type ballast Integral encapsulated
9 4 th Level The 4 th level houses a variety of spaces including classrooms, design labs, offices, and a resource library. The main corridor runs along the exterior wall of the building, encircling the central classroom spaces. Although each level has a few unique spaces, the lighting system of this floor is typical for the remaining two levels. The surface materials of the 4 th floor are similar to those in the auditorium and the atrium. Concrete columns are left exposed throughout the entire 4 th floor. Ceilings in the elevator lobby, corridors, production studios, seminar labs and mechanical room are the exposed concrete structure. Ceilings in offices, editing rooms and restrooms are acoustical ceiling paneling. All floors are sealed concrete. All exterior walls are the white glass of the curtain wall system. All interior walls are gypsum board painted white. See Figure 1.11 for a summary of the surface materials and reflectances. Figure 1.11: Surface materials and reflectance/transmittance SURFACE MATERIAL REFLECTANCE/ TRANSMITTANCE Ceiling Exposed concrete structure 35% Acoustical ceiling panels 75% Exterior Walls White glass 80% Interior walls Gypsum board, 80% Painted white Floor Sealed Concrete 35% (IESNA, 9 th Edition, Figure 136, page 122) CORRIDORS: Since one wall along the length of the corridors is the glass curtain wall, daylight will be the primary means of lighting this circulation space. A 104W direct/indirect fluorescent fixture runs the length of the corridor for use when extra light is needed. (Type K, Figure 1.12) The 8 long fixtures are spaced 10 on center and suspended 2 6 from the ceiling. ELEVATOR LOBBY: From the exposed concrete ceiling hangs a wire frame. Between the 2 x 2 squares of the frames, cylindrical compact fluorescent downlights are pendant mounted. (Type L, Figure 1.12) Eight fixtures illuminate this space, space 6 on center.
10 GALLERY: A small gallery space is located just off the elevator lobby. It is open to the main corridor. The largest wall of the gallery is the glass wall that separates the atrium from this level, so daylight will contribute a significant amount of light. In addition, the track lighting system used in other areas of the building is applied here. (2) 28 lengths of track run along each wall. A combination of 100W accent lights and 150 W wallwashers are used to highlight the artwork. (Types A1 and F, Figure 1.14) RESOURCE LIBRARY: Two walls of the library are exterior, so daylighting will provided the majority of light for this space. In order to provide light for the bookshelves positioned in the interior corner, (5) 8 fluorescent direct/indirect fixtures are hung 18 below the ceiling. (Type K, Figure 1.12) OFFICES/EDITING: The offices and editing rooms on this floor have no exterior walls; therefore, these spaces rely solely on the direct/indirect fluorescent fixtures for lighting the space. (Type K, Figure 1.12) The lengths of these fixtures vary between 4 and 8 depending on the size of the space. SEMINAR: The seminar rooms are lined up along the south side of the building, so they have one exterior wall. Daylight will be sufficient to light the space under most circumstances; however, the direct/indirect fixture is used for additional lighting. (Type K, Figure 1.12) Figure 1.12: 4 th Level Lighting Fixture Schedule TYP DESCRIPTION WATT VOLT MTNG LAMP FEATURES BALLAST A1 Halogen adjustable accent light track (1)100W halogen PAR38 Fl 5 diameter cross baffle shield F Halogen wallwasher K 8 Direct/Indirect fluorescent L Compact fluorescent downlight track (1) frosted Q150DC 7 x 6 cross baffle shield pendant (2) F54T5/830/HO Opal acrylic diffusers pendant (2) PL@13/ diameter low iridescent reflector, cross baffle Integral electronic HPF magnetic ballast
11 DESIGN CRITERIA Auditorium Horizontal Illuminance: 10 fc Color appearance: important Lamps with a CRI greater than 80 should be chosen for good color appearances of skin tones and objects on stage System Control and Flexibility: very important Since the space will house a variety of functions from performances to digital media, lighting controls are very important to adapt the lighting levels to each of the functions POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Audience seating = W/ft 2 Area: 4,600 ft 2 Watts: 44 x 100 = 4400 watts 27 x 575 = 15,525 watts 24 x 7 = 168 watts 16 x 350 = 5,600 watts Total = 25,693 watts Power Density: 25,693 watts/ 4,600 ft 2 = 5.59 W/ ft 2 Atrium Horizontal Illuminance: 10 fc Vertical Illuminance: 3 fc Appearance of Space and Luminaires: very important Since this is the first space a person visiting the college will see, it should be visually appealing. Visual cues can be used to lead the visitors throughout the space Daylighting Integration and Control: very important Daylighting is effective to use in this area because it will be a source of ambient lighting. Since there are little tasks to be preformed in this space, the variability of the sun will not be a concern Modeling of Faces or Objects: important Points of Interest: very important
12 Lighting can be used to draw visitors to various points of interest around the space the reception desk, the auditorium and the elevator POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Lobby = 1.0 W/ ft 2 Area: 1,600 ft 2 Watts: 24 x 150 = 3,600 Watts 12 x 100 = 1,200 Watts Total = 4,800 Watts Power Density: 4,800 watts/1,600 ft 2 = 3.0 W/ ft 2 Plaza BUILDING ENTRANCE (Active) Horizontal Illuminance: 5 fc Vertical Illuminance: 3 fc Appearance of Space and Luminaires: very important Color Appearance: very important Direct Glare: very Important Light Pollution: very important Modeling of Faces or Objects: very important Peripheral Direction: very important Points of Interest: very important Light can be used to attract people to the main entrance of the building Reflected Glare: very important Bright reflections would be uncomfortable for people approaching the building and may deter them away Shadows: very important Shadows should be avoided because they could interfere with the entrance. The entrance doors should be free from any dark areas Source/Task Eye Geometry: very important Surface Characteristics: very important
13 POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Entrance without canopy = 30W/lin ft of door opening Door Opening: 18 lin ft Watts: 4 x 40 = 160 watts Power Density: 160 watts/ 18 lin ft = 8.89 W/ lin ft PLAZA GENERAL LIGHTING Horizontal Illuminance: 5 fc Vertical Illuminance: 2 fc Appearance of Space and Luminaires: very important The plaza should be visually appealing to encourage people stay and enjoy the space rather than just walking through it Color Appearance: very important Light Distribution on Surfaces: very important Modeling of Faces or Objects: very important Points of Interest: very important The plaza should function to direct people from the roadways into the buildings. This can be achieved through lighting by increasing the light levels as one walks towards the Brown Center Source/Task Eye Geometry: very important Surface Characteristics: very important POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Landscaped areas = 0.10 W/ft 2 Area: 9,600 ft 2 Watts: 3 x 95 = 285 watts 4 x 400 = 1600 watts Total = 1885 watts Power Density: 1885 watts/9,600 ft 2 = W/ft 2 4 th Level MULTIMEDIA LABS (Mixed CAD and Paper Tasks): Horizontal Illuminance: 30 fc Vertical Illuminance: 3 fc
14 Direct Glare: very important Since a variety of tasks will be performed in this space, care should be taken to avoid excessive glare from the fixtures Flicker and Strobe: very important Light Distribution on Surfaces: very important Uneven patterns of light should be avoided since they would make it difficult to perform the various tasks Light Distribution on Task Plane: important Reflected Glare: very important There should be no glare from the computer screens Shadows: very important Source/Task Eye Geometry: very important POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Labs = 2.10 W/ft 2 Area: 340 ft 2 Watt: 2 x 104 = 208 Watts Power Density: 208/340 = W/ft 2 CORRIDOR: Vertical Illuminance: 10 fc Daylighting Integration and Control: very important The corridors lead from the exterior spaces, completely lit with daylight, to the interior spaces, completely void of daylight. The corridors can be used to transition between the two extremes Direct Glare: very important Light Distribution on Surfaces: very important Modeling of Faces and Objects: very important Since corridors are high traffic spaces, a good distribution of light is important for good facial renderings Points of Interest: very important POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Corridor = 0.8 W/ft 2 Area: 240 ft 2 Watts: 5 x 104 = 520 watts Power Density: 520/240 = 2.17 W/ft 2
15 GALLERY (Flat Displays on Vertical Surfaces): Vertical Illuminance: 30 fc Appearance of Space and Luminaires: important Color Appearance: very important Daylighting Integration and Control: very important Light Distribution on Task Plane: very important Avoid patterns of light on the wall that may distract from the featured pieces Luminance of Room Surfaces: important Reflected Glare: very important Shadows: very important Proper luminaire placement can eliminate shadows from the frames of the pictures Source/Task Eye Geometry: very important The fixtures must be positioned at the appropriate angles to reduce glare on the artwork and enhance the contrast SEMINAR ROOMS (Meeting): Horizontal Illuminance: 30 fc Vertical Illuminance: 5 fc Appearance of Space and Luminaires: very important Direct Glare: very important Modeling of Faces or Objects: very important Since the seminar rooms are a place for meetings, lamps that enhance skin tones are important Reflected Glare: important Surface Characteristics: important POWER DENSITY REQUIREMENTS: ASHRAE/IESNA : Meeting = 1.5 W/ft 2 Area: 440 ft 2 Watts: 4 x 104 = 416 Watts Power Density: 416 watts/440 W/ft 2 = W/ft 2
16 EVALUATION OF EXISTING CONDITIONS Auditorium The pipe batton system of lighting the auditorium works well to provide the flexibility that this space needs. The uniform layout of the 100W accent lights provides the suggested light levels on the seats of the auditorium. The 575W adjustable spotlights can be turned on and positioned as needed for the differing performances. The power consumption for the space is twice that of the ASHRAE Standard 90.1, but the system will not be running continuously. The higher power density can be compensated by the fact that all the luminaries will only be on for a few hours at a time. Atrium Although the lighting system in the atrium will rarely be needed, I believe the existing design is ineffective. Since the accent lights are mounted 40 to 50 above the entrance lobby floor, a large number of fixtures are needed to achieve the desired lighting level. Output from these lamps is lost in the corridors of the upper levels, where additional light is not needed. This causes the power factor to be three times that of ASHRAE Standard Additionally, the two tracks of spotlights mounted high in the atrium would cause an uneven appearance of bright spots and dark areas on the façade at night. Bringing the luminaries down closer to the entrance level would reduce both the number of required fixtures and the power consumption. Additionally, little is done to use the lighting as a means of guiding visitors through the space. Increasing the light levels of areas surrounding the space would lure people from the entrance lobby to other points of interest, such as the auditorium, the elevator and the access to the lower lobby. Plaza The lighting system of the exterior plaza is sufficient to meet the requirements for both power density and the recommended illuminance values; however, the current design is not enough to create an environment to stop and linger. While currently only the path is lit, other features in this plaza should be illuminated to draw attention off of the main walkway. The large water fountain should be highlighted as one of these features. Although the lighting of the fountain should
17 be minimal as to not detract from the building s façade, some fixtures need to be added to mark the element. The building appears as a large uniform geometric block. Without the current lighting system, it is difficult to determine the break in this block to enter the building. The entrance is marked by four inground uplights. Additional luminaries, either mounted in the interior or on the exterior, would help to emphasize the grand entrance to this unique structure. 4 th Level Overall, the lighting system for the 4 th floor is very effective. The direct/indirect fluorescent fixtures in the office and design labs work well to provide sufficient light while reducing glare and shadows. The track lighting in the gallery will effectively highlight the work on the walls. The daylight spilling in from the atrium will add to appearance of the selected pieces. Improvement of the design would come by added a control system to adjust to the amount of daylight provided. On sunny days no additional lighting is needed for the corridors, seminar room and resource library. As the level of daylighting varies throughout the day, the amount of additional light needed will also vary. A dimming system could measure the amount of daylight in a given space and then adjust the room luminaries until the space meets the set illuminance level. Although this system has a higher initial cost, it would result in a significant decrease in energy since the system would be using only the energy that it needed.
Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY
Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY The Lighting Existing Conditions and Design Criteria Report will examine the existing lighting conditions in the (in general and
More informationLindsey Beane. Executive Summary
Executive Summary The purpose of this technical assignment is to compile lighting information and make an analysis about the existing spaces. This report will include a list of the equipment used, required
More informationSurface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile
Genetics Laboratory Space Description The Genetics Laboratory is located on the second floor of the laboratory building. The main functions of this space are as a learning and research area. There is a
More informationLighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03
Lighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03 Executive Summary The existing lighting conditions and design criteria report describes
More informationLighting Existing Conditions and Design Criteria Report
page 1 of 19 Lighting Existing Conditions and Design Criteria Report The lighting in the includes very general lighting used in buildings with an office type setting. The fixture schedule for the Hall
More informationJennifer Mers. Rio Hondo Library and Learning Resource Center. Executive Summary. General Building. Lighting/Electrical Option
Executive Summary This assignment goes into depth into the existing lighting conditions of the Rio Hondo Library and Learning. The lobby, Reference Stacks and Microfilm Area, the Stack Area on the second
More informationThesis Proposal. Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA
Thesis Proposal Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA New Addition s Functions Auditorium Entrances located on ground and basement floors Museum Art
More informationTechnical Report One
Technical Report One Yale Sculpture Building Lighting Conditions and Design Criteria Report: Technical Report 1 10.05.06 Prepared for: Dr. Richard Mistrick CC: Ted Dannerth Date: October 6, 2006 Executive
More informationLIGHTING EXISTING CONDITIONS SUMMARY EXECUTIVE SUMMARY Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA
LIGHTING EXISTING CONDITIONS SUMMARY EXECUTIVE SUMMARY Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA 11.4.2002 Contained in this report is a summary of the lighting existing conditions
More informationTechnical Assignment I
WHEELOCK COLLEGE CAMPUS CENTER AND STUDENT RESIDENCE 200 THE RIVERWAY, BOSTON, MA 02215 Technical Assignment I Lighting Existing Conditions and Design Criteria E X E C U T I V E S U M M A R Y The lighting
More informationUniversity Park, PA. The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr.
University Park, PA The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr. Martin Moeck A Building Overview The main spaces include: Convenience Store
More informationHARRY RANSOM HUMANITIES RESEARCH CENTER
HARRY RANSOM HUMANITIES RESEARCH CENTER EXPANSION AND RENOVATION THE UNIVERSITY OF TEXAS AT AUSTIN SCHEMATIC LIGHTING DESIGN LIGHTING / ELECTRICAL OPTION DR. RICHARD MISTRICK, ADVISOR THE HARRY RANSOM
More informationTECHNICAL ASSIGNMENT #3: SCHEMATIC LIGHTING DESIGN
TECHNICAL ASSIGNMENT #3: SCHEMATIC LIGHTING DESIGN Jason Weaver 12/13/2007 Background The central role of a college is to help students develop a worldview. The three things one needs to understand in
More informationCafé DUSON- Overview
Café DUSON- Overview Café DUSON is a study lounge with seating and tables to seat approximately 65 people in an area of about 1850 SF. The café is a double high space with full height windows on the North
More informationUniversity of California Santa Barbara. Student Resource Building
Student Resource Building Technical Assignment 1 October 16 th, 2006 1 Executive Summary The following report seeks to address the conditions of the proposed lighting system at the Student Resource Building
More informationLighting Design Criteria: Codes and Standards
EXTERIOR LIGHTING Lighting Design Criteria: Codes and Standards IESNA Lighting Handbook 10 th Edition RP-33-14 Lighting for Exterior Environments ASHRAE/IES Standard 90.1-2010 IBC 2012 2 Site Lighting
More informationLobby Lighting Design
Lobby Lighting Design The main lobby in Duques is hall is located on the first and second floor of the building. It is the main pathway in and out of the building for the more important spaces, such as
More informationEric Anderson. Technical Report 1. Existing Lighting Conditions
Eric Anderson Technical Report 1 Existing Lighting Conditions Executive Summary: The contents of Technical Report One include the evaluation of the lighting design and basic features of The Web Shop: The
More informationOverview. The Reading Room
Overview The library for is the largest space in the George E. Bello Center. This space not only houses all the school s books and reference material, but there are computer terminals set up for students
More informationSchematic Design Ideas for the Westlake Recreation Center. Presented by: Summer Padgett At Lutron Electronics On December 9, 2003
Schematic Design Ideas for the Westlake Recreation Center Presented by: Summer Padgett At Lutron Electronics On December 9, 2003 The Westlake Recreation This facility serves as a park and recreation center
More informationLobby Lighting Redesign
Lobby Lighting Redesign Description of Space The lobby is located on the first floor of the building. Upon entering the building through the curved façade that features large expanses of glass, one would
More informationLighting Existing Conditions and Design Criteria Report
The building was constructed a few years ago to act as both a Headquarters and to be a display of what the product they manufacture can accomplish when put to work. The architecture of the building was
More informationLighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1
Lighting Proposal Angela Nudy Lighting/Electrical Dr. Mistrick 12.16.2006 Lighting Proposal Memo 1 Executive Summary I have chosen to redesign the lighting for four interior spaces and one exterior space
More informationLighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ
Lighting Depth: Courtyard Courtyard Overview: The perimeter buildings of the Franklin Care Center wrap around the central two story building creating two courtyard areas. The courtyard is entered through
More informationMain Lobby Area (North Vestibule thru South Vestibule):
Main Lobby Area (North Vestibule thru South Vestibule): Overview of Space: This is the entrance level from both the North, city street entrance, and the South, campus entrance. The space is 190 x 30 x
More informationLighting Depth Part 1: Exterior Space
Lighting Depth Part 1: Exterior Space Metaphor and Ideas: The first space of my lighting redesign is the front façade of the Recreation Center shown below. Metaphorically, I want the front porch to act
More informationLord Stirling Community School
Lord Stirling Community School Schematic Design Proposal AE Senior Thesis Nehal M. Youssef About the Building A new face for an old town The building of the Lord Stirling Community School was the beginning
More informationDuke Tower Main Entrance Lobby Overview
Duke Tower Main Entrance Lobby Overview This is the main entrance to the building that is located in the prominent tower portion of the building. The floor of this lobby has the Duke University School
More informationSMEAL COLLEGE OF BUSINESS BUILDING University Park, PA
SMEAL COLLEGE OF BUSINESS BUILDING University Park, PA Yena K. Han The Pennsylvania State University Architectural Engineering, Lighting/Electrical Faculty Advisor: Richard G. Mistrick, Ph.D., P.E., FIES
More informationExterior Façade Lighting Design
Exterior Façade Lighting Design Duques Hall is located on George Washington campus in downtown Washington DC. It is located amidst some other university buildings, however, the façade is very visible from
More informationINDEPENDENCE VISITOR CENTER PHILADELPHIA, PA
The trellis lines the east wall of the independence visitor center. It has brick columns with a white painted wooden trellis that is covered in ivy. The trellis is built on top of a brick walkway. The
More informationHawthorn Building. Penn State Altoona Campus Altoona, PA. Walter Nichols. Lighting/Electrical Option Faculty Advisor: Dr.
Hawthorn Building Penn State Altoona Campus Altoona, PA Walter Nichols Lighting/Electrical Option Faculty Advisor: Dr. Richard Mistrick 58,800 sq.ft. 2 Stories above grade Steel frame with curtain wall
More informationDorrance H. Hamilton Building
Dorrance H. Hamilton Building Josh Kreutzberger Penn State Architectural Engineering Technical Report 3 Advisor: Dr. Mistrick Site Overview Martin Building December 2006 Scott Library & Administrative
More informationSteve Neimeister 8 October 2003 AE 481W AstroPower Headquarters Newark, Delaware Lighting/Electrical Option Consultant: M. Moeck
EXECUTIVE SUMMARY The will examine the existing lighting conditions in the (in general and specifically in the five spaces that will be redesigned) and compare it with respect to the IESNA lighting design
More informationCenter for Health Research and Rural Advocacy
CHRRA Angela Nudy Pennsylvania State University Lighting/Electrical Option Faculty Advisor: Dr. Mistrick Images Compliments of Ewing Cole Brief Overview Location: Geisinger Health System Campus in Danville,
More informationTechnical Report #1 Existing Lighting Conditions and Design Criteria
Technical Report #1 Existing Lighting Conditions and Design Criteria Lighting/Electrical Faculty Consultant: Table of Contents Executive Summary 1 Classroom A 2 Firing Range Area 8 Lobby and Corridors
More information2.0 Lighting Depth Introduction
2.0 Lighting Depth Introduction The lighting for four different spaces, the business news open office, first floor cafeteria seating, east lobby, and east façade, were analyzed and redesigned. The existing
More informationHARRY RANSOM HUMANITIES RESEARCH CENTER
HARRY RANSOM HUMANITIES RESEARCH CENTER Additions and Renovations MICHAEL ANTHONY LOMBARDI Lighting/Electrical Emphasis Dr. Richard Mistrick, Advisor The Pennsylvania State University HARRY RANSOM HUMANITIES
More informationHoly Cross Hospital North Addition. Fall 2005 Phil Mackey
Holy Cross Hospital North Addition Fall 2005 Phil Mackey 1 Existing Design 2 Existing Design Building Functions: 1 st floor consists of the new main entrance/lobby, concourse, conference center with multi-purpose
More informationExecutive Summary. CNBC Global Headquarters Christine Cajilig
Executive Summary This report contains information about the existing lighting conditions for the CNBC Global Headquarters in Englewood Cliffs, New Jersey, including hardware, controls, power density,
More informationUniversity of California, San Diego Cal IT 2 Brian Smith. Schematic Design Presentation 06 December 2005
University of California, San Diego Cal IT 2 Brian Smith Schematic Design Presentation 06 December 2005 Building Overview Location: University of California, San Diego Size: 220,000 s.f. Architect: NBBJ
More informationShepherd University Wellness Center AE 481 Thesis Lighting Technical Report 1
A E 481 THESIS TECHNICAL REPORT ONE Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 1 Shepherdstown, West Virginia Lighting/ Electrical Option Dr. Houser October 14, 2010 Contents
More informationThe New York University Concourse Project. New York City. Existing Conditions and Design Criteria
The New York University Concourse Project New York City Existing Conditions and Design Criteria Kevin Hsia Lighting/Electrical Option Advisor: Dr. Richard Mistrick September 29, 2008 executive summary
More informationMarie Ostrowski Lighting/Electrical Dr. Mistrick Science Building Phase 1 Buffalo State College Buffalo, NY Monday, October 5, 2009 Technical Report
2009 Marie Ostrowski Lighting/Electrical Dr. Mistrick Science Building Phase 1 Buffalo State College Buffalo, NY Monday, October 5, 2009 Technical Report 1 Executive Summary The Science Building addition
More informationby elliptipar wall and uplighting for every space
by elliptipar wall and uplighting for every space great performance small package ceramic metal halide M105 fluted compact, yet powerful ceramic metal halide for warm color, great color rendering, long
More informationSpertus Institute of Jewish Studies
2 Kanis Glaewktgarn Spertus Institute of Jewish Studies Lighting/Electrical Option 610 S Michigan Ave Chicago, IL Lighting Consultant: Dr. Kevin Houser September 29, 2008 Executive Summary This report
More informationThe Children s storytelling area
Purpose of Space The Children s storytelling area This area has a circular seating pattern, in different levels going up. Its intended use is for librarians, parents, or young adults to read to children.
More informationQuality of the Visual Environment
Quality of the Visual Environment IES Illuminating Engineering Society The IES is the recognized technical authority on illumination. For over ninety years its objective has been to communicate information
More informationREVISIONS Summary of Change. 6/1/12 All Replaced entire document with new revision
Revision Date Section REVISIONS Summary of Change 6/1/12 All Replaced entire document with new revision REV 6/12 1 of 5 UNIVERSITY CONTACT: EXTERIOR LIGHTING Electrical Services, Maintenance & Operations
More information1.1.0 Exterior Facade
1.1.0 Exterior Facade 1.1.1 Introduction As a primary marketing tool for potential residents unfamiliar with the Rochester area, the façade lighting calls for aesthetic appeal that meets the requirements
More informationGathering Space. Function and Orientation. Space Characteristics Gregory Wolfe 2004 Senior Thesis Lighting / Electrical
Gathering Space Function and Orientation The gathering space and reception area on the first floor is the first space you encounter upon entering the Westwood Community Church. As such, its purpose is
More informationLight Fixtures: A Lamp in a Box. Light fixtures are MORE than a decorative object.
1 Light Fixtures: A Lamp in a Box Light fixtures are MORE than a decorative object. 2 What defines a Light Fixture? Keyless Porcelain Socket Keyed (pull chain) Porcelain Socket Specifications: Method of
More informationThesis Proposal Update #2
Thesis Proposal Update #2 Princeton Theological Seminary Library Princeton, NJ Stephanie Deckard Lighting Electrical Faculty Advisor Dr. Kevin Houser 3/11/2013 Executive Summary The Princeton Theological
More informationExisting Area Description: The area is an angle around the North point of the building. It is a wide patio wrapping the façade of the building.
Exterior Street Entrance: Overview of Space: The street entrance is the main entrance for the members of the community who are entering the library. The purpose of this space is to effectively and aesthetically
More informationLighting System Conceptual Design
Kevin Michael Danna Penn State Architectural Engineering Senior Thesis BUILDING OVERVIEW One Christina Crescent is a six story office building located in Wilmington, Delaware and is home to Barclays Bank
More informationLIGHTING NORTH FAÇADE AND PLAZA
LIGHTING NORTH FAÇADE AND PLAZA The main entry to UCI Natural Science Unit II is marked by a four-story glass curtain wall, an outdoor stair feature and a 5875 square foot landscaped plaza. Trees are located
More informationAdvances in Non-Residential Lighting Technologies
Advances in Non-Residential Lighting Technologies CABEC conference San Diego, CA October 21, 2011 Steven Mesh, LC, IESNA Lighting Education & Design 140 Gardenside Drive, #304 San Francisco, CA 94131 415-516-8126
More informationTechnical Report I. jack risser lighting/electrical. s. good the nerman museum. overland park, kansas sept 16 th, 2013.
Technical Report I jack risser lighting/electrical s. good the nerman museum overland park, kansas sept 16 th, 2013. 2 Executive Summary: The Nerman Museum of Contemporary Art was selected for this technical
More informationGregory A. Wolfe Lighting / Electrical
Executive Summary: This report was created to study the existing lighting system present in the Westwood Community Church. Specifically, the purpose of this report is to analyze luminaire choice, power
More informationLighting Depth CAL IT 2. Brian Smith. Introduction
Introduction Lighting Depth The University of California, San Diego Cal IT 2 building is a large research, academic building. As stated earlier, the building is used for lectures, laboratory experiments,
More informationAbbey Beresik. Executive Summary. Ronald Reagan Presidential Library Simi Valley, California
Executive Summary This report is an analysis of the existing lighting conditions for the Mulitpurpose Room, Reagan Country Café, Exhibition Hall and Presidential Learning Center of The Ronald Reagan Presidential
More informationUSG LIBRETTO GMS CEILING ILLUMINATION OPPORTUNITIES
01 June, 2007 USG LIBRETTO GMS CEILING ILLUMINATION OPPORTUNITIES The Libretto GMS ceiling system allows for a wide variety of creative illumination opportunities. Lighting can be integrated from both
More informationTechnical Report 1 Part 2
Technical Report 1 Part 2 John Conley Lighting + Electrical Option Thesis Advisor Shawn Good Oakland University Engineering Center Rochester, MI 09.19.2014 Lighting calculation 3dsMax files can be found
More informationShepherd University Wellness Center AE 481 Revised Thesis Proposal
A E 481 REVISED THESIS PROPOSAL Shepherd University Wellness Center AE 481 Revised Thesis Proposal Shepherdstown, West Virginia Lighting/ Electrical Option Dr. Houser and Professor Dannerth March 24, 2011
More informationTHE COMPLETE GUIDE TO OUTDOOR WALL LIGHTS
THE COMPLETE GUIDE TO OUTDOOR WALL LIGHTS CONTENTS 1. INTRODUCTION 2. TYPES OF OUTDOOR WALL LIGHTS 3. LIGHT SOURCES IN OUTDOOR WALL LIGHTS 4. FACTORS IN SELECTING OUTDOOR WALL LIGHTS 5. SUMMARY lighting
More informationNew LED Product Offerings
New LED Product Offerings from we know light. TCP LED NEW Product Offerings LED Indoor Lighting PL Lamps EdgeLit Downlights HID DirecT8/DirecT5 T8/T5 Tubes Liscio by TCP Linear Accent Lighting Luxterior
More informationJamie Devenger Senior Thesis Princeton University Sherrerd Hall 1 Lighting Proposal Memo September 11, 2009
Jamie Devenger Senior Thesis Princeton University Sherrerd Hall 1 I am proposing to study five spaces for the lighting portion of my thesis. The spaces to be analyzed and redesigned are as follows: Large
More informationAdvanced Lighting For Office
Advanced Lighting For Office Open-Plan Office Applications High-Density 1 This High-Density 1 lighting application module presents alternative energy effective lighting design options for open-plan offices.
More informationLighting Depth Study. Exterior Departure/Canopy Area
Lighting Depth Study Exterior Departure/Canopy Area Overview The Exterior of the Indianapolis International Airport is consisted of 2 levels of traffic circulation. The lower level is the Arrival pick
More informationSchematic Design Presentation December 15, 2006 David Smith
Schematic Design Presentation December 15, 2006 David Smith Overview Located in Lancaster, PA 65,000 square feet 4 stories, 3 above grade Architect of record is Philip Johnson-Alan Ritchie Architects Ground
More information13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES
Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES R. Ries,
More informationCOMMERCIAL LIGHTING DESIGN GUIDE
COMMERCIAL LIGHTING DESIGN GUIDE WHAT SETS US APART INNOVATION We combine the latest energy efficient technology and design styles to create an extensive range of attractive and sustainable luminaires.
More informationSouth Nassau Communities Hospital North Addition
1 South Nassau Communities Hospital North Addition Carl Speroff Lighting Electrical Faculty Advisor: Dr. Kevin Houser 4 October 2010 AGI files located on Y Drive folder CAS Thesis 2 Executive Summary The
More informationShepherd University Wellness Center AE 481 Thesis Proposal
A E 481 THESIS PROPOSAL Shepherd University Wellness Center AE 481 Thesis Proposal Shepherdstown, West Virginia Lighting/ Electrical Option Dr. Houser and Professor Dannerth December 10, 2010 Executive
More informationCosmetology Lab Redesign
Cosmetology Lab Redesign Shane A. Semple - 25-4/5/2005 Design Concept: The Cosmetology Lab is a space that will be used for teaching students the trades of cutting hair, applying make-up, and doing manicures.
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Lighting. Basis of Design
Basis of Design This section applies to the design and installation of lighting systems. Design Criteria Select interior lighting to achieve initial system efficiencies greater than 64 lumens per watt.
More informationL ig h t in g Dept h 8
Ligh t in g Dept h 8 Lighting Depth The Woolly Mammoth Theatre Company is a very unique group. They have a mission to provide new and edgy productions to the community. Therefore, when designing their
More informationSacramento Republic FC Stadium. Stadium Specialty Ligh ng Concept Package. 100% Schema c Design. 13 May 2016
Stadium Specialty Ligh ng Concept Package 00% Schema c Design (BEHIND) Fixture: LED landscape floodlight. Applica on: Two narrow beam floodlights for each large shard, mounted behind fabric on structural
More information2. Measurements are to be made at ground level, with the light-sensor portion of the meter lying flat on the ground, pointing upward.
12.0 SITE LIGHTING 12.1 Applicability 1. A permit for the construction, reconstruction, or expansion of any structure or use of land shall be issued only if the site plan (or construction plan) is in compliance
More information1.0 Introduction to Lighting Depth. 1.1 Hotel Tower Facace and Porte Cochere
1.0 Introduction to Lighting Depth Dover Downs is primarily used for entertainment for the wealthy. When people go somewhere to spend money expectations are higher than usual. The lighting design for Dover
More informationDuke University Medical School. Duke School of Nursing
Duke School of Nursing Lighting and Electrical Depth Proposal and Breadth Topics Proposal for Spring 2008 Semester December 18 th, 2007 Table of Contents Executive Summary....................................
More informationChandler City Hall Chandler, Arizona
Chandler City Hall Chandler, Arizona Thesis Proposal AE481W: Architectural Engineering Senior Thesis Friday December 10 th, 2010 Stephanie Romanias Lighting/Electrical Faculty Consultants: Dr. Kevin Houser
More informationMomo Sushi. Robert Blecker ABS 643
Robert Blecker ABS 643 Building Information: -Momo Sushi is a Japanese restaurant that specializes in sushi. -The restaurant is located in Henderson on Stephanie St. and it was chosen because of its unique
More informationTechnical Report 1. Wentz Concert Hall and Fine Arts Center 171 E. Chicago Avenue Naperville, IL 60540
Technical Report 1 Lighting Existing Conditions and Design Criteria Will Lesieutre Lighting/Electrical Option Faculty Consultant: Dr. Mistrick Wentz Concert Hall and Fine Arts Center 171 E. Chicago Avenue
More informationNon-Cutoff and Semi-Cutoff Wall Pack Primary Use and Edits to Outdoor Wall-Mounted Luminaire Primary Use
Non-Cutoff and Semi-Cutoff Wall Pack Primary Use and Edits to Outdoor Wall-Mounted Luminaire Primary Use DLC proposes to include non-cutoff and semi-cutoff (or "open face") wall packs in the Technical
More informationFranklin Square Hospital Center
Franklin Square Hospital Center Baltimore, MD Thesis Proposal Cassandra Watson + Electrical Electrical Advisor Professor Dannerth Advisor Dr. Mistrick 16 December 2009 Table of Contents Executive Summary...
More informationLIGHTING DESIGN STANDARDS SECTION City of Maryland Heights ZONING CODE
SECTION 25-18 City of Maryland Heights ZONING CODE The Zoning Code text contained in the Interpretive Version is current as of Ordinance #2018-4308 adopted on February 15, 2018. The City Planner comments
More informationMultipurpose Room. Existing Conditions General Overview. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC
Multipurpose Room ` N Figure 1: 1 st Floor Plan Multipurpose Room Location Existing Conditions General Overview The Multipurpose Room, as the name implies, serves as a multifunctional space for the Assisted
More informationSF LINEAR FLOURESCENT T5 WITH HALOGEN MR 16 SAJ HALOGEN DOWNLIGHT FULLY ADJUSTABLE. Sept [Type text] Page 1
Executive Summary The Frederick College of Cardiology This report more clearly defines criteria and considerations I Arlington Heights, IL Will applying to the redesign process of The Frederick College
More informationstudent National Lighting Design Competition Winners 2010
student National Lighting Design Competition Winners 2010 winner student Hiroki Usui Project: FUEL Convenience Store/Gas Station School: Washington State University, Spokane, WA Cooper Lighting s 34th
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationSchematic Design Proposal Presentation
Steven A. Neimeister 9 December 2003 Architectural Engineering 481W AstroPower Headquarters Newark, Delaware Lighting/Electrical Option Consultant: Dr. M. Moeck Introduction to AstroPower Welcome to AstroPower!
More informationThe Bahen Centre for Information Technology. Meeting Room Lighting Redesign. Introduction. University of Toronto ~ Toronto, Ontario, Canada
Meeting Room Lighting Redesign Meeting Room #4287 Introduction The Meeting Room (room #4287) is located on the fourth floor within the grand spiral staircase in the atrium. The room is shaped like half
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Lighting. Basis of Design
Basis of Design This section applies to the design and installation of lighting systems. Design Criteria Select interior lighting to achieve initial system efficiencies greater than 64 lumens per watt.
More informationLighting depth. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC. Introduction
Introduction Grand Oaks is an Assisted Living Facility in the Washington, D.C. area that gives its residents the support they need while maintaining a home like environment. So, when I set out to develop
More informationRESIDENTIAL LIGHTING DESIGN GUIDE
RESIDENTIAL LIGHTING DESIGN GUIDE WHAT SETS US APART INNOVATION We combine the latest energy efficient technology and design styles to create an extensive range of attractive and sustainable luminaires.
More informationDUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD
DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD LIGHTING FIXTURES AND CIRCUITRY & SWITCHING SECONDARY SCHOOLS 1. GENERAL 1.1.1. Consultants MUST prepare a Summary of Fixtures which will include catalogue
More informationBUILDING DESIGN STANDARDS FACILITIES MANAGEMENT AND ANCILLARY SERVICES EXTERIOR IMPROVEMENTS DIVISION 32 Exterior Lighting
PART 1 GENERAL 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying exterior lighting for landscape use. These standards are not intended to restrict or replace professional
More informationCity of Green Administration Building. Brian Koze November 12, Lighting Schematic Design Presentation
City of Green Administration Building Brian Koze November 12, 2010 Lighting Schematic Design Presentation Building Statistics Location City of Green, Ohio Occupant City of Green Administration Size 53,671
More informationTechnical Assignment One. Existing Conditions Analysis. Prepared By: Brian Franco
Technical Assignment One Existing Conditions Analysis Prepared By: Brian Franco Table of Contents Executive Summary 3 Overview of existing conditions in the Performance Hall..4-6 Performance Hall Furniture
More information