Description/ Application

Similar documents
WARNING WARNING FOR YOUR SAFETY. Gas Conversion Kit Instructions. Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings

SEPARATED COMBUSTION. General WARNING

Models F and B Size Option Package by Option Designation, Model Size, Voltage, and P/N

IMPORTANT WARNING CAUTION

Series Unit Heaters (Fan Models)

UNIT HEATER CATALOG. Form C-UH-0516 COMMERCIAL/INDUSTRIAL HEATERS RESIDENTIAL GARAGE HEATERS. FUEL Natural Gas Propane Fuel Oil

UNIT HEATER CATALOG. Form RZ-NA-C-UH (Version F)

NOTICE: The information contained on the following page(s) was produced prior to May 1, On that date Reznor became part of Nortek, Inc.

OPTION CA1, CA2, AND CA3 POWER VENTERS

Installation Instructions

POWER VENT. Standard Power Vent, Fan Type Unit Heaters: Standard Power Vent, Blower Type Unit Heaters: General WARNING WARNING. Model UDAP & Model APD

WARNING CAUTION 50T INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS. Integrated Furnace Control

! WARNING: FIRE OR EXPLOSION HAZARD

Mini-Combo id. Model MCH. Installation and Operation Instructions. Induced Draft Residential Gas-Fired Space/Water Heater

Series Fan-Type Unit Heaters

Typical Mount Height. Combustion Chamber

Insert Manual. RHT Series WARNING. For Your Safety

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

Applies to: Models F, B, FE, and BE FOR YOUR SAFETY

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

Multi-Function Cooktop

ELECTRONIC FIREPLACE DAMPER

SEPARATED COMBUSTION. General

ELECTRIC WALL OVEN INSTALLATION INSTRUCTIONS

ELECTRONIC FIREPLACE DAMPER

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

TO DO IF YOU SMELL GAS

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

CQS ! WARNING: FIRE OR EXPLOSION HAZARD. Installation / Operation / Maintenance Applies to: Model F and Model B Gas-Fired, Gravity-Vented Unit Heaters

Installation, Operation & Service Manual

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

REPLACEMENT PARTS LIST

CSD-1 COMMERCIAL BOILER CONTROLS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

Installation Instructions Part No , Part No Part No

Automatic Digital Humidifier Control

Installation / Operation. Applies to: Standard Power Vent Unit Heaters: Separated Combustion Unit Heaters:

Insert Manual. DET3 Series WARNING. For Your Safety

Model UDAP. Power Vented, Low Static Axial Fan Commercial/Industrial Unit Heaters DESCRIPTION STANDARD FEATURES OPTIONAL FEATURES - FACTORY INSTALLED

CATALOG: HVAC - Gas Space Unit Heating

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY:

NOTICE: The information contained on the following page(s) was produced prior to May 1, On that date Reznor became part of Nortek, Inc.

ASSEMBLY INSTRUCTIONS - NXS SERIES. INFRARED RADIANT TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

P/N _B September Field Installed Dual Temp Operation E P R Controlled (Evaporator Pressure Regulator)

INSTALLATION INSTRUCTIONS FOR FREESTANDING DUAL FUEL

Installation Instructions Part No

FOR YOUR SAFETY. Applies to: Models RIH, RIHV, RIHVN, and RIHVL Gas-Fired High-Intensity Infrared Heaters. Models RIH/RIHV

LOW VOLTAGE CONTROL CIRCUIT WIRING

UNIT HEATER CATALOG. Form RZ-NA-C-UH (Version F)

GAS COOKTOP INSTALLATION INSTRUCTIONS BEFORE YOU BEGIN. IMPORTANT Save these instructions for local electrical inspector s use.

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

Effective october 14, 2014

PVK-80 Power Vent - Installation Instructions -

INSTALLATION GUIDE. AAN & AEN Series - Manufactured Housing Electric Furnace. 1. Safety Instruction. 2. Inspection ! CAUTION CAUTION `!

Effective february 9, 2015

Some models are supplied with a protective film on steel and aluminium parts. This film must be removed before installing/using the appliance.

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded

Installation Instructions

AFUE 95% Heating Input 50,000 to 200,000 Btuh

SUBMITTAL SCHEDULE & DATA

ASYSTAT625A Humidity Control

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

! WARNING: FIRE OR EXPLOSION HAZARD. Applies to: Model SC, Separated-Combustion Duct Furnace. Model SC INSTALLATION / OPERATION / MAINTENANCE

KG6TE Series. High Efficiency / Direct Vent or Non Direct Vent 2-Stage Condensing Gas Furnace with Variable Speed Blower TECHNICAL SPECIFICATIONS

24 VAC SYSTEM CONTROL KIT

Gas Conversion Kits and Instructions

INSTALLATION INSTRUCTIONS FAN COIL PROGRAMMABLE DIGITAL THERMOSTAT. Meets California Title 24

Installation Instructions

PE MODEL WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SEPARATED COMBUSTION WARNING

RL with INNOVATOR Doors

ARM SERIES Switching Relays With Priority

FG6T(C,L) Series. High Efficiency / Direct Vent or Non Direct Vent 2-Stage Condensing Gas Furnace with Variable Speed Blower TECHNICAL SPECIFICATIONS

Heating & Ventilation Product Line

INSTALLATION INSTRUCTIONS

LUMINOUS A PATIO HEATER LIKE NO OTHER

Installation Instructions

Type 300 Series Bench Electrode Stabilization Ovens

Min. Mount Height. Min. Mount Height. Length Weight

COOKTOP, BURNER AND GRATE PARTS For Model: JGRP548WP00 (Stainless)

Insert Manual. DES Series WARNING. For Your Safety

Installation Instructions

INSTALLATION INSTRUCTIONS APARTMENT FAN COIL UNIT FMA4X, FMA4P

INSTALLATION INSTRUCTIONS

! WARNING. Before using product, read and understand instructions.

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model MICROGENUS PLUS. R EN - Edition 02-01/04/2007

Installation, Operation and Service Instructions RS RANGE RESIDENTIAL INFRARED HEATERS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

Advantium TM. Built-In. Speedcook Ovens. Installation. Instructions

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

A. Product Data: Include rated capacities, furnished specialties and accessories.

OPTIONAL THERMOSTATIC BLOWER ASSEMBLY No. SC18T

COMMERCIAL MODELS: XTHERM 1005 THROUGH 2005

MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS

Applies to: Model REC Evaporative Cooling Module

Transcription:

Form I-OPT-MH (2-16) Obsoletes Form I-OPT-MH (Version D.2) Installation of Multiple Heater Control, Options CL31 and CL32 Applies to: Models LDAP, UDAP, APD, UDAS, UDBP, UDBS, UEAS, F, B, V Description/ Application These options are designed to permit the control of up to six heaters (one "Primary" heater and one to five "Secondary" units; see note for LDAP limitations) with one single-stage thermostat or with a time clock and single or multiple single-stage thermostats. For maximum safety, the multiple control is done in the low voltage circuit. (Interruption of the supply voltage is not recommended.) Wiring lengths may not exceed those shown in the table on page 8. DO NOT use these multiple heater control options with a two-stage gas valve or a two-stage thermostat. Application by Voltage & Model Model LDAP 115/1 N/A 208/1 CL31 for both the Primary and 1st Secondary Heater plus a CL32 each for the 2nd, 3rd, 4th, and 5th Secondary Heaters. * Models UDAP, APD, UDAS, UDBP, UDBS, and UEAS** CL31 for both the Primary and 1st Secondary Heater plus a CL32 each for the 2nd, 3rd, 4th, and 5th Secondary Heaters. Models F, B, and V CL31 for both the Primary and 1st Secondary plus a CL32 each for 2nd, 3rd, 4th, and 5th Secondary Heaters. Application by Voltage & Model 230/1 208/3 N/A CL32 for the Primary Heater plus CL32 each for 1st, 2nd, 3rd, 4th, and 5th Secondary Heaters. 230/1 208/3 230/3 N/A 230/3 460/3 N/A 460/3 575/3 N/A CL31 for both the Primary and 1st Secondary plus a CL32 each for 2nd, 3rd, 4th, and 5th Secondary Heaters. 575/3 * Model LDAP 400 can have five secondary heaters; Model LDAP 800 can have a maximum of three secondary heaters; and Model LDAP 1200 can have a maximum of two secondary heaters. ** Model UEAS is 115 volt only. 115/1 208/1 Kit Components by Model Check the components against the list for the model being installed. Model LDAP Model UDAP & APD Model UDAS Model UDBP Model UDBS Model UEAS Model F Model B Model V Kits for Model LDAP Option CL31 for LDAP - Pkg P/N 208366 for Primary and One Secondary Unit 2 208365 elay Assemblies each consisting of one P/N 18549 relay, with attached 42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with terminals. 2 208185 Wiring Diagram Label Option CL32 for LDAP - Pkg P/N 208367 for each Additional Secondary Unit 1 208365 elay Assemblies each consisting of one P/N 18549 relay, with attached 42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with terminals. 1 208185 Wiring Diagram Label Kits for Models UDAP, APD, UDAS, UDBP, UDBS, UEAS Opt CL31 for UDAP/ APD/UDAS/UEAS - Pkg P/N 197155 for Primary & One Secondary Heater 1 194808 Transformer 40VA 2 197157 elay Assemblies each consisting of one P/N 18549 relay, wired and 2 195249 Self-drilling screw for attaching relay bracket 2 16228 Cable Clamp 3/16" 2 197164 Wiring Diagram Label 1 197160 Wiring Harness Assembly (brown wires) Form I-OPT-MH, P/N 102247 8, Page 1

Kit Components by Model (cont'd) Kits for Models UDAP, APD, UDAS, UDBP, UDBS, and UEAS (cont'd) Opt CL31 for UDBP/UDBS Pkg P/N 202958 for Primary & One Secondary Heater 2 197157 elay Assemblies each consisting of one P/N 18549 relay, wired and 2 195249 Self-drilling screw for attaching relay bracket 2 16228 Cable Clamp 3/16" 2 197164 Wiring Diagram Label 1 197160 Wiring Harness Assembly (brown wires) Opt CL32 for UDAP/APD/UDAS/UDBP/UDBS/UEAS Pkg P/N 197156 for Each Additional Secondary Heater 1 197157 elay Assembly consisting of one P/N 18549 relay, wired and 1 195249 Self-drilling screw for attaching relay bracket 1 16228 Cable Clamp 3/16" 1 197164 Wiring Diagram Label Kits for Model V Option CL31 for V Pkg P/N 205685 for Primary and One Secondary Heater 2 102243 elay Assemblies each consisting of one P/N 18549 relay, wired and 1 194808 Transformer 40VA 1 16354 Twist-on Wire Connector (Orange) 4 98872 Spacers 4 121033 Screws #8 x 1" lg 2 16228 Cable Clamp 3/16" 2 197164 Wiring Diagram Label Option CL32 for V Pkg P/N 205686 for Each Additional Secondary Heater 1 102243 elay Assembly consisting of one P/N 18549 relay, wired and 2 98872 Spacers 2 121033 Screws #8 x 1" lg 1 16228 Cable Clamp 3/16" 1 197164 Wiring Diagram Label Kits for Models F and B Option CL31 for Models F & B Pkg P/N 102248 for Primary and One Secondary Heater 1 102708 Transformer 35VA Basler #BE141640-AK 2 103152 Sheetmetal Screws, #6 x 1-1/2 long (for transformer) 2 111233 Tinnerman Clips, #C1110-62 (for transformer screws) 2 102243 elay Assemblies each consisting of one P/N 18549 relay, wired and 2 16228 Cable Clamp 3/16" 2 131127 Wiring Diagram Label Option CL32 for Models F & B Pkg P/N 102249 for Each Additional Secondary Heater 1 102243 elay Assembly consisting of one P/N 18549 relay, wired and 1 16228 Cable Clamp 3/16" 1 131127 Wiring Diagram Label Form I-OPT-MH, P/N 102247 8, Page 2

WANING Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury, or death. ead the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment. Installation Instructions Flame ollout Switch (UDAP and UDAS Sizes 30-125 only) These instructions are designed to assist a qualified electrician in installing this multiple heater control kit. All electrical wiring and connections, including electrical grounding, MUST be in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in Canada, with the Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 In addition, the installation must comply with local ordinances and applicable gas company requirements. Follow the instructions that apply to the option and model of heater. 1. Turn off the gas and electric power. 2. Change the Transformer (does not apply to Model LDAP, UDBP, or UDBS) applies to OPTION CL31 installation on the "Primary" unit only efer to the illustration (FIGUE 1A, 1B, or 1C) for the unit being serviced. emove or open panels as required and locate the factory-installed transformer. Mark and disconnect the wires. emove the transformer. Using the same screws (except Models F and B; see FIGUE 1C), install the 35 or 40 VA transformer from the kit. Connect the wires. Close the panel. FIGUE 1A - Control Compartment showing Transformer Location, Models UDAP, APD, UDAS, and UEAS "Primary" Heater The transformer is mounted on the control board on the bottom of the control compartment. Flame Sensor Pressure Switch - Sizes 30-125 High Temperature Limit Control Venter Motor (Size 30-75 illustrated. Venter motor is in the same location for all models, but appearance is different.) UDAS, UEAS, and UDBS have a collar for the combustion air pipe (not shown) Burner Assembly Gas Valve Door Switch - UDAS, UEAS, and UDBS only Fan Motor Terminal Board (24V) TANSFOME Circuit Board (DSI Integrated Control Module) Ignitor Control Panel Assy located on the Control Compartment Bottom UDAP/S 30-125 UDAP/S 150-400 All UEAS - On the cabinet bottom; control locations are slightly different. Optional Fan Motor Capacitor (used with 208/230V and Option AL14) TANSFOME Circuit Board (DSI Integrated Control Module) Electrical Box - UDAS and UDBS only emove cover to connect supply and access disconnect switch wires. Always replace cover. Pressure Switch (Sizes 150-400) Venter Motor Capacitor Fan Motor Capacitor Disconnect Switch - UDAS, UEAS, and UDBS only Form I-OPT-MH, P/N 102247 8, Page 3

Installation Instructions (cont'd) 2. Change the Transformer (cont'd) FIGUE 1B - Bottom View showing Transformer Location, Model V "Primary" Heater Spark Electrode Burner Pressure Switch Ignition Controller Ground Screw Gas Valve elay (Optional) TANSFOME 24V Terminal Board Burner Section Control Section (Open this side only to change transformer.) FIGUE 1C - Transformer Location, Model F or B "Primary" Heater emove the left outer side panel (left when facing the rear of the heater), exposing the inner side panel and the wiring. Locate the factory-installed transformer. Mark and disconnect the wires. emove the transformer. Through the large hole in the side panel (for mounting the transformer), slide the Tinnerman clips over the new transformer. Attach with the screws included in the kit. Connect the wires to the new transformer. eplace the outer side panel. ear View Transformer Terminal Strip Form I-OPT-MH, P/N 102247 8, Page 4

3. Install a elay or elay Bracket Assembly on the Primary Unit and all Secondary Units Option CL31 and Option CL32. Select the appropriate FIGUE (2A, 2B, 2C, or 2D) for the Model of Heater. FIGUE 2A - Model LDAP emove the access panel from the main heat section. Locate the position on the control panel for the new relay. Attach the relay with the screws provided in the kit. 24V Thermostat Terminal Board Vent Permissive elay (Models emote Destrat (Fan Control) elay 800 and 1200) Destrat (Fan Conrol) elay Disconnect Switch elay (primary and secondary units) Transformer DSI Control (Circuit Board) Burner Assembly Fan Permissive elay Heat Permissive elay (Models 800 and 1200) FIGUE 2B - Models UDAP, APD, UDAS, UDBP, UDBS, UEAS Model UD Sizes 30, 45, 60, 75, 100, 125 - On the rear of the heater, position the bracket as illustrated. emove the screws from the edge of the cabinet bottom. e-insert the screws attaching the relay bracket. Model UD Sizes 150, 175, 200, 225, 250, 300, 350, 400 and all UEAS - On the rear of the heater, position the bracket as illustrated. emove the screw on the left from the edge of the cabinet bottom. e-insert the screw attaching the bracket. Secure the other side of the bracket with the self-drilling screw in the kit. Cable Clamp All model sizes use existing screw. elay Bracket Assembly Model UD Sizes 30-125 use existing cabinet screw. Model UD Sizes 150-400 and all UEAS use self-drilling screw in the kit. Form I-OPT-MH, P/N 102247 8, Page 5

Installation Instructions (cont'd) 3. Install a elay or elay Bracket Assembly (cont'd) FIGUE 2C - Model V On the end of the burner/control box, remove and discard the screws holding the thermostat terminal strip. Use the screws and spacers in the option package to attach the relay bracket and to re-attach the terminal strip. Follow the sequence below, starting at the burner/ control box - first the terminal strip, - second the spacers, - third the relay bracket, - and fourth (on the left side only) put the blue and brown wires through the plastic cable clamp and position the cable clamp on top of the relay bracket. NOTE: The spacers are required to allow the access door to open. Screw (remove and discard) elay Bracket Assembly Cable Clamp Place Wiring Diagram Label at this location. Terminal Strip Screw (remove and discard) Spacers furnished with kit Use screws furnished in the kit. FIGUE 2D - Model F or B On the rear of the heater, remove the screws that hold the thermostat terminal strip. Slide the relay bracket underneath the terminal strip. e-insert the screw on the right side. Put the blue and brown wires into the plastic cable clamp, and on the left end of the terminal strip, position the cable clamp on top. Fasten with the other screw. NOTE: The 1" long screws and the spacers in the option package will not be used. Screw (remove to install) Terminal Strip Place wiring diagram on lower right corner of the outer side panel. Screw (remove to install) elay Bracket Assembly Cable Clamp Form I-OPT-MH, P/N 102247 8, Page 6 4. Wiring Diagram Label All Heaters See FIGUE 3A, 3B, or 3C for Option CL31 and CL32 wiring diagram. Model FIGUE Label LDAP...3A...208185 UDAP & APD...3B...197164 UDAS...3B...197164 UDBP...3B...197164 UDBS...3B...197164 UEAS...3B...197164 V...3B...197164 F...3C...131127 B...3C...131127 Select the wiring diagram for the model of heater being installed. Check the appropriate box on each diagram for the heater function (Primary or Secondary). Adhere the label in the location specified below for the model of heater. Packaged Model LDAP Position the label (P/N 208185) on the inside of the access panel. Wipe the area with a clean, dry cloth. emove the backing and adhere the wiring diagram. Unit Heater Models UDAP, APD, UDAS, UDBP, UDBS, and UEAS Position the label (P/N 197164) on the bottom rear corner of the access panel. Wipe the area with a clean, dry cloth. emove the backing and adhere the wiring diagram. Infrared Heater Model V Position the label on the rear of the burner box above the terminal strip. Wipe the area with a clean, dry cloth. emove the backing and adhere the wiring diagram.

Unit Heater Models F and B Position the label (P/N 131127) in the lower right corner of the outer left side panel (left when facing the rear of the heater). Wipe the area with a clean, dry cloth. emove the backing and adhere the wiring diagram. 5. Control Wiring - All Models Follow the diagram label to wire the controls. FIGUE 3A- Multiple Heater Control Wiring Diagram Label for Model LDAP, P/N 208185 CHECK APPOPIATE BOX: PIMAY HEATE SECONDAY HEATE SECONDAY HEATE 7 PIMAY HEATE For future identification, check appropriate box on each wiring diagram label. W1 W1 2 4 3 1 4 1 2 3 B W W OPTIONAL TIME CLOCK CONTACTS O OTHE CONTOL DEVISE TO ADDITIONAL SECONDAY HEATES B B B B B FIELD WIING HAVING A MINIMUM TEMPEATUE ATING OF AT LEAST 105 DEGEES C. SHALL BE USED. SUPPLY CICUIT WIING SHALL HAVE A MINIMUM SIZE OF 18 AWG. FIELD SUPPLIED WIING CIMP TEMINAL THEMOSTAT O OTHE CONTOL DEVICE WD# 189578 Label 208185 FIGUE 3B - Multiple Heater Control Wiring Diagram Label for Models V, UDAP, APD, UDAS, UDBP, UDBS, and UEAS, P/N 197164 PIMAY HEATE SECONDAY HEATE SECONDAY HEATE PIMAY HEATE TO COMMON SIDE OF TANSFOME For future identification, check appropriate box on each wiring diagram label. TO COM ON DSI CONTOL (NOTE: V Models do not have a "W2" terminal. Splice between the DSI control "COM" and 24V on the transformer and use the twist-on wire connector provided to connect the wires. TO ADDITIONAL SECONDAY HEATES THEMOSTAT O OTHE CONTOL DEVICE Label 197164 Form I-OPT-MH, P/N 102247 8, Page 7

Installation Instructions (cont'd) FIGUE 3C - Multiple Heater Control Wiring Diagram Label for Models F and B, P/N 131127 For future identification, check appropriate box on each wiring diagram label. 5. Control Wiring (cont'd) PIMAY HEATE SECONDAY HEATE CHECK APPOPIATE BOX: SECONDAY HEATE PIMAY HEATE GD STIP ON G77 O G67 W1 W1 B NOTE #1 2 4 3 1 W B B W 4 1 2 3 OPTIONAL TIME CLOCK CONTACTS O OTHE CONTOL DEVISE TO ADDITIONAL SECONDAY HEATES B B B B THEMOSTAT O OTHE CONTOL DEVICE FIELD WIING HAVING A MINIMUM TEMPEATUE ATING OF AT LEAST 105 DEGEES C. SHALL BE USED. SUPPLY CICUIT WIING SHALL HAVE A MINIMUM SIZE OF 18 AWG. NOTE #1: ON STANDING PILOTS MODELS, ATTACH TO BOWN WIE ON GAS VALVE. FIELD SUPPLIED WIING EV #2 131127 Do not exceed the control wire lengths shown in the table. Field Control Wiring (Length and Gauge) Wire Type Wire Gauge Maximum Wire Length* Maximum Distance TEW 18 500 ft (152M) 250 ft (76M) TEW 14 1300 ft (457M) 650 ft (198M) TEW 12 2100 ft (640M) 1050 ft (320M) *Wire length equals wire for circuit going plus wire for returning circuit. CAUTION: Be careful not to short thermostat leads to a metal surface. Doing so will cause the transformer to fail, requiring it to be replaced. 6. Turn on the electric power and the gas. Follow the lighting instructions to operate the heater. Check the control system for proper and safe operation. Form I-OPT-MH, P/N 102247 8, Page 8 Specifications & illustrations subject to change without notice and without incurring obligations. Nortek Global HVAC, LLC 2016. All rights reserved. All marks are the property of their respective organizations. O Fallon, MO I Printed in U.S.A. (2/16) Form I-OPT-MH (2-16)