FEATURES: Bright/sunlight readable 7.0 LCD touch screen. Displays large, easy to read values, set points, room status, modes and alarms Up to six fully configurable Icons including: Environmental points Point or room status Point or room mode Display point values, set points, point status or space mode Local and remote audible and visual alarms Local set point, status and mode change Analog and digital input and outputs for point values, modes or status indicator Network for values, modes or status points Password protection and configurable user access restrictions Set point, status and mode networked or hardwired All parameters/settings saved in non/volatile memory Field configurable, easy, and intuitive menus. Easy and quick installation Input and output diagnostic screen Network communication debug screen TABLE OF CONTENTS Overview 1 Specification 2 Performance Characteristics 3 OVERVIEW: Multiview Monitor / Controller CRC-MVM The MultiVIEW is an advanced 7" LCD touchscreen display that is designed to be configured for any monitoring or sequencing application. Its core function is to give local access to critical information in an easy to read display. It's versatile design allows any of its on board analog, digital inputs, or network connections to drive the information being displayed on the screen. Additionally, any of the on board analog outputs or relays can be setup to drive a signal out to a BAS or peripheral device such as a valve or VFD. The MultiVIEW supports up to six (6) fully configurable graphical icons. The six graphical icons allow the facility user to view and/or make changes to point values, modes, status, set points, and alarms. The icons can be independently configured to retrieve their value from an analog input (0 5v, 0 10v, 4 20mA), digital input, or network communication. Typical Wiring 4 BaCnet Point Map 5-6 Additional Screens/ Installation 7-9 menclature/ordering 10 To support virtually any sequencing scenario, the four on board analog outputs and relays can also be configured to be driven by a point's alarm status, audible alarm status, current value, or set point value. The CRC MultiVIEW is excellently suited for any location where clear indication and user interface with critical information is required. CRC-MVM DATA SHEET 1 CRITICAL ROOM CONTROL
DISPLAY: Description: 7" Full color LED TFT 18 bit (262,144) color depth, sunlight viewable, 400cdm brightness, touch screen interface resistive touch (will work with gloved finger). Screen is capable of wipe down cleaning and water spray and dust resistant meeting (IP 54) Listing: CSA, RU(us), UL 60950, UL 94 V 0 (Enclosure) Main Screen: Display, alarm, and adjust set points for up to six environmental points COMMUNICATION: Connection: RS-485 Supported Protocol: BACnet MS/TP: Modbus, Johnson Controls Incorporated N2 & LON with optional card Network Debug: Network Setup: CONTROLLER I/O: Network communication diagnostics Baud rate, MAC address and instance ID configured via touch screen I/O Diagnostic: Graphical display of controller analog inputs/outputs and digital inputs/outputs Mounting: Low profile surface Analog Inputs: 4 total analog inputs AIN1 & AIN2 are selectable (4-20mA, 0-10V, or 0-5V) POWER REQUIREMENTS: Input Power: Power Draw: Primary: Class: 22 to 26VAC; 50/60Hz, fully isolated 20 VA 24 VAC Input Class 2 Energy Limiting, Class 130 (B) Insulation, Class 2 not wet, Class 3 wet Listing: CSA (c), RU (us) ANSI/UL 506, 508 1, 508 2 PRESSURE ALARMS: Audible: Visual: 1 (pressure alarm & remote alarm) 1 (amber (loss of pressure), red (alarm) ENVIRONMENTAL CHARACTERISTICS: AIN3 & AIN4 are (0-10V) (software selectable) Analog Outputs: 4: 0 10V or 0 5V (software selectable) Digital Inputs: 4 Relays: Terminals: Enclosure: Communication: Onboard power: 4 (normally closed - 0.5 A at 125 VAC; 2 A at 30 VDC) Removable screw terminals (18ga - 26ga wire) Fire retardant, extruded acrylic/pvc Alloy UL94V RS-485 10vdc (80mA max.), 5vdc (80mA max.), and onboard loop power circuit 22VDC (80mA max.) Temperature Limits: Storage: -40 to 180 Operating: +0 to 160 Compensated Range: +35 to 130 Temperature Coefficients: Zero: Span: Listing: ±0.03%F.S./ F ±0.03%F.S./ F UL-94-5VA CRC-MVM DATA SHEET 2 CRITICAL ROOM CONTROL
Instance Id Object Name Object Name Network changes saved in EEPROM AV 0 Current Value - Point 1 AV 1 Current Value - Point 2 AV 2 Current Value - Point 3 AV 3 Current Value - Point 4 AV 4 Current Value - Point 5 AV 5 Current Value - Point 6 AV 6 Set Point - Point 1 YES AV 7 Set Point - Point 2 YES AV 8 Set Point - Point 3 YES AV 9 Set Point - Point 4 YES AV 10 Set Point - Point 5 YES AV 11 Set Point - Point 6 YES AV 12 Alarm Status - Point 1 AV 13 Alarm Status - Point 2 AV 14 Alarm Status - Point 3 AV 15 Alarm Status - Point 4 AV 16 Alarm Status - Point 5 AV 17 Alarm Status - Point 6 CRC-MVM DATA SHEET 3 CRITICAL ROOM CONTROL
Instance Id Object Name Value Type Network chances saved in EEPROM AV 18 Alarm Low - Point 1 YES AV 19 Alarm Low - Point 2 YES AV 20 Alarm Low - Point 3 YES AV 21 Alarm Low - Point 4 YES AV 22 Alarm Low - Point 5 YES AV 23 Alarm Low - Point 6 YES AV 24 Alarm High - Point 1 YES AV 25 Alarm High - Point 2 YES AV 26 Alarm High - Point 3 YES AV 27 Alarm High - Point 4 YES AV 28 Alarm High - Point 5 YES AV 29 Alarm High - Point 6 YES AV 30 Point 1 AV 31 Point 2 AV 32 Point 3 AV 33 Point 4 AV 34 Point 5 AV 35 Point 6 AV 36 Analog Input 1 AV 37 Analog Input 2 AV 38 Analog Input 3 AV 39 Analog Input 4 BV 0 Digital Input 1 Read BV 1 Digital Input 2 Read BV 2 Digital Input 3 Read BV 3 Digital Input 4 Read CRC-MVM DATA SHEET 4 CRITICAL ROOM CONTROL
Additional Screens: CRC-MVM DATA SHEET 5 CRITICAL ROOM CONTROL
Installation Overview: The CRC-MultiVIEW is a two part system designed to reduce installation costs and eliminate problems that occur when wiring and pneumatic tubing have to be run down a wall. The two components are the CRC-LCD and the pressure transmitter/controller (CRC-DPT/CONT). te: Follow all local and federal electrical codes. Included Parts: (1) CRC-MultiVIEW-LCD w/faceplate (1) CRC-MultiVIEW-Control Unit (1) CRC-MultiVIEW-MB (Mounting Bracket) (1) CRC-RJ12 Crossover Cable (1) CRC-MultiVIEW Set Screw Installer Supplied Parts (t Included): (1) Three gang electrical box 24 VAC Power (18AWG recommended) Signal Wire (22AWG recommended) Mounting of the Monitor: The CRC-MultiVIEW-LCD and associated back plate (CRC-MultiVIEW-MB) is designed to be mounted directly to the wall using a standard three gang electrical box. The electrical box should be mounted flush relative to the face of the wall. The mounting bracket (CRC-MultiVIEW-MB) should be attached to the three gang electrical box. The CRC-MultiVIEW- LCD shall be slid down over mounting bracket and screwed in from the bottom. CRC-MVM DATA SHEET 6 CRITICAL ROOM CONTROL
Mounting of the CRC-MultiVIEW-Control Unit: The CRC-MultiVIEW-Control Unit is designed to be mounted remote from the monitor typically above the ceiling). The CRC-MultiVIEW-Control Unit is powered by 24VAC. CRC-MVM DATA SHEET 7 CRITICAL ROOM CONTROL
DIMENSIONS: 8.56 1.48 6.04 ORDERING NOMENCLATURE: ADDITIONAL PRODUCT INFORMATION: Please contact us at: Web: www.criticalroom.com Phone: 414.324.8978 Address: Critical Room Control 6643 West Mill Road Milwaukee, WI 53218 CRC-MVM DATA SHEET 8 CRITICAL ROOM CONTROL