MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE Tuesday June 8, 2010 Mandalay Bay Convention Center Las Vegas, NV

Similar documents
1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])

Maryland State Fire Marshals Office Rep. International Fire Marshals Association (IFMA)

HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA

MINUTES. HEALTHCARE INTERPRETATIONS TASK FORCE 7 JUNE 2005 Mandalay Bay: North Convention Center Las Vegas, NV

Heathcare Interpretations Task Force

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE DECEMBER 8, 2006

FINAL MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE. Tuesday June 11, 2013

HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA

Healthcare Interpretations Task Force AGENDA Mandalay Bay Convention Center Meeting Room Oceanside G Las Vegas, NV

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

3. Review / Approval of December 2006 Minutes (See Enclosure A page 3)

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

First Revision No NFPA [ Section No ]

MINUTES. HEALTHCARE INTERPRETATIONS TASK FORCE 6 JUNE 2006 Orange County Convention Center Room S210D Orlando, FL

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

Report on First Revisions with Statement June 2014 NFPA 101

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

ASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development

FHCA 2014 Annual Conference & Trade Show

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT

Developing a Healthcare Facility Fire Door Inspection Program

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

SAF-BCF SECOND REVISIONS WITH STATEMENTS

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Report on First Revisions with Statement June 2014 NFPA 101

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

The Physical Environment Portal: Module 5, LS Leadership

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

Iowa State Fire Marshal

NFPA 80 Overview January 21, 2016

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Lauzon Life Safety Consulting

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

New Facilities. Minimum Requirements

REPRESENTING. Honolulu Fire Dept., Rep. International Association of Fire Fighters. API/Petroleum Safety Consultants

NFPA 101 Life Safety Code Culture change 2012

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

Code Technology Committee Meeting #31 March 31-April 1, 2015 Care_WTC Recommendations/Elevators

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

Field Guide for Healthcare Facilities

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

TECHNICAL COMMITTEE ON FIRE CODE

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Center for Clinical Standards and Quality /Survey & Certification Group

TECHNICAL COMMITTEE MEMBERS PRESENT

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Correlating Committee on Automatic Sprinklers

Retain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry)

E25 (D) Automatic controls for general means of egress lighting

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

Life Safety - Means of Egress/Exits NFPA 101

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Agency for Health Care Administration

The Healthcare Environment Update

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

Amend Base Code. Amend Base Code. Amend Base Code. Disposition. (Statute, Rule, FBC, Industry) Y/N

For additional information regarding R-3.1 residential care facilities please contact (951)

Fire Department Fire Prevention Inspection Services. HIGH RISE STRUCTURE Fire Inspection Program

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Circulation Report for SIG-TMS Comments Document # 72

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

NFPA 550 ROP Meeting Minutes

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

Agency for Health Care Administration

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX

Report on First Revision June 2014 NFPA 5000

November 17, Sent Via Electronic and Regular Mail

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

Chapter 2: Definitions

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

BCAC Egress Work Group

Report on First Revision June 2014 NFPA 101

Transcription:

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE Tuesday June 8, 2010 Mandalay Bay Convention Center Las Vegas, NV 1. The meeting was called to order at 1:25 PM. (See Enclosure A [Agenda]) 2. Introduction of members and guests was completed. Those in attendance included: MEMBER Ken Bush* Lewis Faulkner* Skip Gregory* Philip Hoge * Thomas Jaeger James Merrill* Robert Solomon Chad Beebe* (ALT to J. Gregory) Dave Dagenais (ALT to D. Erickson) John Fishbeck* (ALT. to G. Mills) Gregory Harrington (ALT R. Solomon) Peter Larrimer* (ALT to D. Klein) Richard Strub (ALT to T. Jaeger) * Voting AHJ Member REPRESENTING Maryland State Fire Marshals Office Rep. International Fire Marshals Association (IFMA) IHS Division of Engineering Services Rep. Indian Health Services (IHS) State of Florida Agency for Health Care Administration Rep. Agency for State of Florida Healthcare Administration U. S. Army Corps of Engineers Rep. Department of Defense (DoD) Jaeger and Associates, LLC Rep. American Health Care Association (AHCA) U.S. Dept. of Health & Human Services Rep. Centers for Medicare/Medicaid Services (CMS) National Fire Protection Association Washington State Department of Health Rep. Washington State Department of Health Wentworth-Douglas Hospital Rep. American Society for Healthcare Engineering (ASHE) The Joint Commission Rep. The Joint Commission National Fire Protection Association U.S. Department of Veterans Affairs Rep. Department of Veterans Affairs (VA) American Health Care Association (AHCA) Rep. American Health Care Association (AHCA) Page 1 of 13

GUESTS REPRESENTING Bruce Abell U.S. Army Corps of Engineers (MX) Tim Adams ASHE Don Bender Loma Linda University Medical Center Lyn Bentley American Health Care Association Mark Berger Securitech Group/BHMA Jeff Coombs Cleveland Clinic A. Richard Fasano Russell Phillips & Associates Jerry Gervais Joint Commission Virgil Hall U.S. Department of Veterans Affairs George Johnston Loma Linda University Health Services James Lathrop Koffel Associates, Inc. Peter Leszczak Department of Veterans Affairs (VA) Nancy McNabb National Fire Protection Association Tom Scheidel Compliance Management Service W. Thomas Schipper Providence/LCM Hospitals David Seitz HCF Management, Inc. & NCAL Kenneth Sun CMS 3. Review of Questions. A. Sprinkler Clearance. This subject involves the sprinkler clearance rules in NFPA 13 and if the shelving that is positioned against the wall has to be secured to the wall. The HITF members agreed that a. Shelving isn t even required for the storage. b. There is no correlation between the shelving, the clearance and the need to secure any shelving. The HITF issued a response to this item (See Enclosure B-1 [Issued Interpretation]). B. Fire Pins in Fire Doors. This subject includes the use of thermal pins that are installed in certain fire rated doors that are used as egress/exit doors. Once exposed to a certain temperature, typically 400 o F, the thermal pins actuate and preclude the door from being operated/opened. The discussion about these devices noted, among other things, that these devices are relatively new and that based upon the operating temperatures of the device, that the door would not be usable any way. The HITF revised the question as follows and developed a qualified response. Question: Are rated fire doors required to be operable after the door is exposed to a fire that is representative of the test conditions used to obtain the rating of the door? Answer: NO. The HITF notes that a door that is exposed to these test conditions is no longer likely to be available as an egress path. (See 7.2.1.5.1 of NFPA 101 2000 edition). Page 2 of 13

In addition, the HITF notes the following: NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2008 Edition: Section 7.1.7.2 does not require the door hardware to be operable after the test. NFPA 101, 2012 edition (proposed) has a specific proposal that has been acted on to explicitly account for use of the thermal pins. See ROP proposal 101-75. Although the 2000 edition did not explicitly consider the use of these devices, the proposed change for NFPA 101 is obviously considering and recognizing the use of these devices. For convenience, the text of the proposal is as follows: 7.2.1.5 Locks, Latches, and Alarm Devices. 7.2.1.5.1 Door leaves shall be arranged to be opened readily from the egress side whenever the building is occupied. 7.2.1.5.2* The requirement of 7.2.1.5.1 shall not apply to door leaves of listed fire door assemblies after exposure to elevated temperature in accordance with the listing based on laboratory fire test procedures. 7.2.1.5.3 Locks, if provided, shall not require the use of a key, a tool, or special knowledge or effort for operation from the egress side. 7.2.1.5.4 The requirements of 7.2.1.5.1 and 7.2.1.5.3, shall not apply where otherwise provided in Chapters 18 through 23. A.7.2.1.5.2 Some fire door assemblies are listed for use with fire pins or fusible links that render the door leaf release inoperative upon exposure to elevated temperature during a fire. The door leaf release mechanism is made inoperative where conditions in the vicinity of the door opening become untenable for human occupancy and such door opening no longer provides a viable egress path. (Proposed new language underlined) (See Enclosure B-2 [Issued Interpretation]) C. Exit Access from Suites. This subject concerns exit access corridors and their proximity to a suite and if an exit stair can be substituted for the exit access corridor. The HITF noted that the reason you need to gain access to an Exit Access Corridor is so the patient(s) can be relocated across a smoke barrier such that the defend in place concept can be executed. Only having access to an exit stair would require a much greater effort to relocate a patient. The HITF issued a response to the first two questions as follows: Answer 1: YES. See NFPA 101: 19.2.5.1, Exception #3 concerning suites. Answer 2: NO. (See Enclosure B-3 [Issued Interpretation]) Page 3 of 13

D. Inventory Management Systems. This subject concerns use of the modular cabinet units that are becoming more popular. These devices are used to store large quantities of basic nursing supplies. The concern is does the space or area, such as a nurses station, become categorized as a storage area if the space is over 50 square feet. The HITF determined that a response on this subject cannot be developed. Factors such as what is the area housing the Inventory Management System being used for? What is being stored in the Inventory Management system? The HITF determined that there are too many unknowns with regard to determining how to classify the space where the storage device is located. HITF members Ken Bush, Dave Dagenais, Tom Jaeger and Pete Larrimer will look at the issue more closely and see if there might be a proposal for the 2012 edition of NFPA 101 that can be used to clarify use of this equipment. Addressing this type of storage system is more appropriate for inclusion in the Code rather than by being addressed by the HITF. E. Two Hour Floor/Ceiling Assembly. This was a supplemental agenda item. The issue involves a 2 hour rated floor/ceiling assembly being used to serve as an occupancy separation in a healthcare occupancy. Some jurisdictions (perhaps because of their state code provisions) apparently have been disallowing this type of assembly from being used as a proper barrier to provide the occupancy separation. The NFPA Life Safety Code has contained specific language allowing such assemblies to be used. This same subject was discussed as far back as 2004 by the HITF (November 16, 2004 Minutes) and given that the issue was so clear (and still is) in the Life Safety Code, an HITF position was not issued. Since this item continues to be problematic in some jurisdictions, the following response was issued. Question: May a 2-hour floor/ceiling assembly be used as the required membrane for occupancy separation as set forth in Section 19.1.2.1 of the 2000 edition of the Life Safety Code? Answer: YES. (See Enclosure B-4 [Issued Interpretation]) F. Projections Along Corridor Walls. This was a supplemental agenda item. This question raised the potential interpretation issues caused by the presence of multiple elements/devices placed along the corridor. NFPA 101: 18.2.3.4/19.2.3.4 provides very specific criteria for placement of projections along the corridor. The essence of this question is at what point do the number, length, width and thickness of any components create excessive encroachment thus causing a violation of the Code. The NFPA 101 rule requires a 48 inch separation between devices or components attached to the wall. The example provided in the question considered a series of chart stations, ABHR dispensers and fire alarm pull boxes. The question becomes can multiple devices be positioned less than 48 inches apart from one another? The HITF determined there are too many variables to respond to a question based on this rule for example, it is not known if groupings of projections can be considered within the 48 inch separation rule. Also, the HITF considered what happens if a sign with a 1/16 inch or 1/8 inch Page 4 of 13

thickness is installed on the wall. Would that be a contributor to the projection rules? The HITF noted that Proposal 101-265a for the 2012 edition of NFPA 101 is looking at the broad topic of items in the corridor. This proposal might be used by a member of the HITF (if they so choose) to introduce a public comment to try and further clarify the placement of the other devices/components. 4. New Business a. An update was given on the ITM Summit held at NFPA at the end of May. The summit was convened to determine how NFPA 72 could better correlate some of its ITM criteria with related documents. As an example, the testing frequency for a smoke damper (NFPA 80) and the testing frequency for the detector and motorized equipment to close the damper (NFPA 72) were cited as one example of where the two documents could be better coordinated. The published report from the summit will be used by the NFPA 72 committee to work towards consistency with the affected NFPA Codes and Standards. b. Health Care Summit Arrangements for this summit are being finalized. This summit will focus on trends in delivery of healthcare and how NFPA technical committees should start to look at those trends. 5. Old Business. None. 6. Next Meeting. A date for the next meeting of the HITF will not be determined until October 2010. HITF members must submit any planned agenda items to NFPA not later than Friday, October 1, 2010. If a sufficient number of items are received, an HIFT meeting will be held in December 2010. The meeting would be held right before or right after the NFPA 1 ROC meeting in Orlando, FL. Tentative meeting dates would be December 13 or December 16, 2010. If a sufficient number of agenda items are not received by October 1 st, consideration will be given to holding a conference call meeting. Otherwise, the next meeting would be deferred until June 2011 during the NFPA Conference in Boston, MA 7. Adjournment. The meeting was adjourned at 4:55 PM. Minutes prepared by Robert E. Solomon Page 5 of 13

ENCLOSURE A AGENDA Page 6 of 13

ENCLOSURE A HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA JUNE 8, 2010 Mandalay Bay Convention Center South Convention Center Level 2 - Reef C 3950 Las Vegas Boulevard South Las Vegas, NV 89119 1:00 P.M. 6:00 P.M. 1. Call to order 1:00 P.M. 2. Introduction of Members and Guests. 3. Review of Questions A. 18 in. Sprinkler Clearance - American Society for Healthcare Engineering (ASHE) - (See Enclosure A-1 Page 3) B. Door Pin - American Society for Healthcare Engineering (ASHE) - (See Enclosure A-2 Page 4) C. Exit Access from Suites - American Society for Healthcare Engineering (ASHE) - (See Enclosure A-3 Page 5) D. Storage Areas - American Society for Healthcare Engineering (ASHE) - (See Enclosure A-4 Page 6) 4. New Business ITM Summit May, 2010 Health Care Summit July, 2010 5. Old Business 6. Date / Location for Next Meeting 7. Adjournment (by 6:00 P.M.) Page 7 of 13

ENCLOSURE B INTERPRETATIONS Page 8 of 13

ENCLOSURE B-1 HITF INTERPRETATION JUNE 2010 NO. 1 Agenda Item 3.A. (D. Dagenais) Document to be interpreted: NFPA 13, 1999 edition, 5-8.5.2.1; 2002 edition, 8.6.6; and 2002 edition, A.8.6.6. Edition: 1999 and 2002 Background Information (optional): 18 Sprinkler Clearance In a healthcare setting many organizations use perimeter walls for storing items. This storage is accomplished with the use of wire racks that may be free standing on the floor or have wheels so they can be moved to facilitate cleaning. Some AHJs are requiring that perimeter wall shelving be fastened to the wall. NFPA 13 (2002) A.8.6.6 states shelving on a wall or shelving against. The word against seems to imply a free standing unit set against the wall is permitted without fastening. Question 1: Is it required that perimeter wall shelving that extends to the ceiling be fastened to the wall? Answer 1: NO a. Shelving isn t even required for the storage. b. There is no correlation between the shelving, the clearance and the need to secure any shelving. Page 9 of 13

ENCLOSURE B-2 HITF INTERPRETATION JUNE 2010 NO. 2 Agenda Item 3.B. (D. Dagenais) Document to be interpreted: NFPA 101, 2000 edition, 4.5.3.1, 4.5.3.2. Edition: 2000 Background Information (optional): Fire Pins in Fire Doors In recent months, hospitals, during routine inspections have been presented inspection citations as a result of employing thermally fused pins in fire door assemblies with less-bottom-rod (LBR) exit devices. These citations are issued because the door will fail to operate as a means of egress, as defined by the Life Safety Code, when the thermally fused pins are activated. Thermally fused fire pins have long been used in fire door assemblies when LBR exit devices are installed. The thermally fused fire pin is an integral part of the fire door assembly and without it, the assembly cannot be fire rated. Thermal pins are activated only when their core temperature exceeds approximately 400 F, at which point temperatures on the fire side of the door assembly are in excess of 1200 F. At these temperatures there is no longer an egress requirement from the fire-side of any opening at these elevated temperatures. Regardless of the use of a thermally fused pin, the door assembly will not function as a means for egress at these temperatures because the door will have expanded so forcefully into the frame it will not open. Secondly, there are additional thermal pins used in nearly every type of fire rated latching hardware, including the top latch of the very same LBR exit device your inspectors are rejecting. The fire door assembly in a pathway of egress serves two purposes, a means for egress, and a fire barrier. We submit to you that when the fire barrier function of the assembly is required, the egress function is moot and irrelevant. Question 1: Are rated fire doors required to be operable after the door is exposed to a fire that is representative of the test conditions used to obtain the rating of the door? Page 10 of 13

ENCLOSURE B-2 Answer 1: NO The HITF notes that a door that is exposed to these test conditions is no longer likely to be available as an egress path. (See 7.2.1.5.1 of NFPA 101 2000 edition). In addition, the HITF notes the following: NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2008 Edition: Section 7.1.7.2 does not require the door hardware to be operable after the test. NFPA 101, 2012 edition (proposed) has a specific proposal that has been acted on to explicitly account for use of the thermal pins. See ROP proposal 101-75. Although the 2000 edition did not explicitly consider the use of these devices, the proposed change for NFPA 101 is obviously considering and recognizing the use of these devices. For convenience, the text of the proposal is as follows: 7.2.1.5 Locks, Latches, and Alarm Devices. 7.2.1.5.1 Door leaves shall be arranged to be opened readily from the egress side whenever the building is occupied. 7.2.1.5.2* The requirement of 7.2.1.5.1 shall not apply to door leaves of listed fire door assemblies after exposure to elevated temperature in accordance with the listing based on laboratory fire test procedures. 7.2.1.5.3 Locks, if provided, shall not require the use of a key, a tool, or special knowledge or effort for operation from the egress side. 7.2.1.5.4 The requirements of 7.2.1.5.1 and 7.2.1.5.3 shall not apply where otherwise provided in Chapters 18 through 23. A.7.2.1.5.2 Some fire door assemblies are listed for use with fire pins or fusible links that render the door leaf release inoperative upon exposure to elevated temperature during a fire. The door leaf release mechanism is made inoperative where conditions in the vicinity of the door opening become untenable for human occupancy and such door opening no longer provides a viable egress path. (New proposed text is underlined) Page 11 of 13

ENCLOSURE B-3 HITF INTERPRETATION JUNE 2010 NO. 3 Agenda Item 3.C. (D. Dagenais) Document to be interpreted: NFPA 101, 2000 edition, 19.2.6.2.4 Edition: 2000 Background Information (optional): Exit Access From Suites In many cases within a healthcare setting there are suites built and designed with stairwells within them. These stairwells provide similar or greater protection than exit access corridors. In some cases AHJs are enforcing travel distance limitations to exit access corridors even though there is a valid exit stairwell within the suite. Question 1: Is it the intent of 101 (2000-19.2.6.2.4) to require every sleeping suite to have access to an Exit Access Corridor? Answer 1: YES See NFPA 101: 19.2.5.1.1, Exception #3 concerning suites. Question 2: If the answer to question 1 is yes, is a stairwell within the suite allowed to be substituted as an exit access corridor? Answer 2: NO Page 12 of 13

ENCLOSURE B-4 HITF INTERPRETATION JUNE 2010 NO. 4 Supplemental Agenda Item (D. Klein) Document to be interpreted: NFPA 101, 2000 edition, 19.1.2.1 Edition: 2000 Background Information (optional): Two Hour Floor/Ceiling The issue includes a 2 hour rated floor/ceiling assembly being used to serve as an occupancy separator in a healthcare occupancy. Some jurisdictions (perhaps because of their state code provisions) apparently have been disallowing this type of assembly from being used as a proper barrier to provide the occupancy separation. The NFPA Life Safety Code has contained specific language allowing such assemblies to be used. This same subject was discussed as far back as 2004 by the HITF (November 16, 2004 Minutes) and given that the issue was so clear (and still is) in the Life Safety Code, an HITF position was not issued. Since this item continues to be problematic in some jurisdictions, the following response was issued. Question 1: May a 2-hour floor/ceiling assembly be used as the required membrane for occupancy separation as set forth in Section 19.1.2.1 of the 2000 edition of the Life Safety Code? Answer 1: YES Page 13 of 13