Compressor Confusion: Field Findings on the Role of Supplemental Cooling in a Commercial Indirect Evaporative Air Conditioner

Similar documents
Would You Bolt A Swamp Cooler To Your DX Rooftop Unit? [not exactly.]

ENGINEERING AND CONSTRUCTION BULLETIN

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Evaporative Cooling in a Hot-Dry Climate

Displacement Ventilation in Classrooms

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

A/C Cooling Load calculation and measurement

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

INDUSTRIAL DEHUMIDIFICATION DRYING OF SOFTWOODS

Field Tests of Specially Selected Air Conditioners for Hot Dry Climates

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

CTI Sponsored Educational Program

ENGINEERING. Edition No. 13 October 2002

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Climate Wizard Indirect Evaporative Cooler - TriTool

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Designing Energy Efficient Outdoor Air Systems

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

100% Outdoor Air Dehumidification Methods

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Fundamental Principles of Air Conditioners for Information Technology

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

SPACE CONDITIONING IN RESIDENTIAL BUILDINGS

Dehumidifying with Dedicated Outdoor Air

Oxyvap Evaporative Cooling Applications

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Section 4 of 6 DOAS Core Technologies

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Trane Voyager DC Hybrid Rooftop Unit Performance: Western Cooling Challenge Laboratory Test Results

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

Customer Advanced Technologies Program Technology Evaluation Report. The Coolerado

99.503A. Prepared by: (415) Drains: Power. Prepared for: ACEE. Final Report Contributors: Danny Parkerr. Me!

Application of Air Source Variable Refrigerant Flow in Cold Climates

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Energy Recovery Ventilation

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

SPLIT-SYSTEM RESIDENTIAL HEAT PUMP WITH SEPARATE DEHUMIDIFICATION OPERATING MODE

FIELD TEST OF HYBRID ROOFTOP UNIT PHASE 1

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

SUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer

Indirect Evaporative Air Conditioning FACTORY INSTALLATION (CW-160)

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Pthey are comfortable. In regions with hot

Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Air Conditioning Clinic

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

VariCool VAV. (Variable Air Volume) 9 to 70 tons Variable Air Volume Water-Cooled and Chilled Water. Unique Solutions for All-Indoor HVAC Projects

HVAC Field Evaluation

HVAC DISTRIBUTION and DELIVERY SYSTEMS

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TECHNICAL NOTE ON EVAPORATIVE COOLING. Renato Lazzarin, President of the IIR s Commission E1

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Efficient Motor-Driven Appliances Using Embedded Adjustable-Speed Drives

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

Modelling Appliance Loads in Multi-Unit Residential Buildings

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Desiccant Cooling with Solar Energy

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Psychrometric Engineering Applications

Field Test and Performance Verification: Integrated Active Desiccant Rooftop Hybrid System Installed in a School

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

CHAPTER 4. HVAC DELIVERY SYSTEMS

Comfort and health-indoor air quality

Southwest Air Conditioning

Dehumidification: Energy Efficiency Comparisons

Presented By: John Dolan, P.E.

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Energy Efficiency Potential of Heat Pump Water Heaters in Commercial Buildings

MAXIMIZING FACILITY PERFORMANCE WITH INNOVATIVE HVAC & IRRIGATION SYSTEMS

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

ASHRAE JOURNAL ON REHEAT

PACKAGE AIR CONDITIONER

Sound Performance Rating of Outdoor Unitary Equipment

Variable Refrigeration Flow Systems Overview 10/11/2016

Submittal Data Performance Data Electrical Data

Introduction. Motor Types

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Adding More Fan Power Can Be a Good Thing

HVAC Water chiller selection and optimisation of operation

Transcription:

Compressor Confusion: Field Findings on the Role of Supplemental Cooling in a Commercial Indirect Evaporative Air Conditioner Cathy Higgins and Howard Reichmuth, New Buildings Institute ABSTRACT The market trends for low-energy cooling and green building technologies are driving new approaches to air conditioning. Indirect evaporative systems offer significantly reduced energy and demand while providing greater amounts of outside air. Yet a key question in product development and system design involves the need for and use of a vapor compression system to supplement the indirect heat exchanger. This paper is based on two years of field research results on a new hybrid air conditioner the Desert CoolAire TM (CoolAire) which combines a 100% outside air indirect evaporative core with a compressor. The indirect evaporative core consistently provided air at 65-70 F without the use of the compressor, regardless of the outdoor temperature. Although this output matches well with mild cooling periods and new high performance buildings with low loads, monitoring data shows a critical role for supplemental cooling of 5-10 F to meet comfort conditions in most climates and typical spaces with standard duct sizing. The paper provides important guidance on compressor need, sizing and optimization for integration in various hybrid air-conditioning systems, particularly 100% outside air systems.. Findings on the actual field energy use pattern of a digitally controlled scroll compressor which differ significantly from the anticipated performance are also presented. Introduction In 2005, the Northwest Energy Efficiency Alliance (NEEA), recognizing the need for new approaches to reducing commercial cooling energy use, funded a performance investigation of a prototype package air-conditioning system the Desert CoolAire in the Northwest. The research was extended to the California market through participation of the Sacramento Municipal Utility District (SMUD), with support from the American Public Power Association Demonstration of Energy-Efficient Developments (DEED) Program. The 2006-2007 field research showed a highly promising new indirect evaporative cooler (IEC) that demonstrated 50% demand savings and significant energy savings, increased capacity compared with standard air conditioners during times of summer peak, provided pre-compressor cooling at temperatures that allow for aggressive compressor lock-out, and delivered 100% outside air throughout the cooling season. This combination of significant demand savings, energy control potential and indoor air quality benefits were compelling rationale for continued investigation of the CoolAire s performance, and refinements of component operations and design. Review of the CoolAire Final Report 1 is necessary to understand the full project objectives, equipment specs and airflow configuration, outcomes and product status. 1 The Desert CoolAire Package Unit Technical Assessment 2006 Final Report and 2007 Addendum are available at http://www.newbuildings.org/mechanical.htm. 3-156

A fundamental design question for the research and product development of indirect evaporative cooling concerns the use of a supplemental compressor subsystem. Is it necessary, and if so, how big must it be, and how can it best be integrated? This paper presents the field findings on the CoolAire that address these key design questions concerning the compressor. Design Intent The original design intent for the prototype CoolAire units was to provide a cooling capacity equivalent to a nominal 5-ton capacity packaged rooftop unit (RTU) air conditioner at typical outdoor air design conditions. Accordingly, a 4-ton direct expansion compressor (DX) refrigeration system was selected to complement a 100% outside air (OA) indirect evaporative heat exchanger (HMX) 2 designed for a 5-ton cooling load. Although there have been systems designed to retrofit existing RTUs with evaporative coolers (DualCool 2008) to create a hybrid air conditioner with greater energy efficiency and many applications for larger built up systems (NBI 2006) 3 there is no currently available pre-integrated hybrid commercial product small package system. The underlying design rationale for development of this product was based on three primary drivers in the market place. First, RTUs now are the most widely used means of commercial heating and cooling with single-package DX cooling systems accounting for over 47% of commercial space conditioning and the 5-ton unit being the most commonly sold system (Jacobs 2003). Second, the field performance of standard RTUs, particularly during hot conditions when utility systems are stressed, is poor. More efficient cooling in this market can reasonably be a large offset to peak load. Figures 1 and 2 present the impacts of high outdoor temperatures on efficiency and on system capacity of RTUs respectively. In Figure 1 the efficiency of a 13 EER RTU dropped by approximately 20% between outside temperatures of 85 F and 105 F. Figure 2 shows that the same system loses almost 5,000 btus of cooling capacity over this temperature range. However, for 100% OA evaporative systems the performance advantage increases with outdoor dry bulb temperature because of the greater wet bulb (WB) depression at higher outdoor temperatures and the increasing ventilation air precooling benefit (Davis Energy Group 2002). In essence, evaporative cooling can serve as a hedge against peak cooling loads caused by hot weather. 2 The heat exchangers were invented by Dr. Valeriy Maisotsenko and are patented by Coolerado/Idalex Corporation. Manufacturing rights belong to Coolerado/Idalex Corporation and Delphi Corporation. 3 See the Southern California Edison report prepared by NBI on the residential and commercial market products and prototypes associated with evaporative cooling including the DualCool, Freus, OAsys, Champion/Essek, AdobeAire, SpecAir Acer etc.(nbi 2006) 3-157

Figure 1. Impact of Outdoor Temperature on Energy Efficiency Rating (EER) for Small Package HVAC Systems EER (Btu/hr/watts) 13.5 13.0 12.5 12.0 11.5 11.0 10.5 10.0 9.5 9.0 8.5 8.0 7.5 7.0 6.5 6.0 85F 90F 95F 100F 105F 110F 115F 120F 125F 130F Outdoor Temperature ( o F) Standard Unit High Efficiency Unit Poly. (High Efficiency Unit) Poly. (Standard Unit) Source: CEC PIER Integrated Design of Package Rooftop Units 2003 73,000 Figure 2. Impact of Outdoor Temperature on Cooling Capacity for Small Package HVAC Systems Gross Cooling Capacity (Btu/hr) 68,000 63,000 58,000 53,000 48,000 85F 90F 95F 100F 105F 110F 115F 120F 125F 130F Outdoor Temperature ( o F) Standard Unit High Efficiency Unit Poly. (High Efficiency Unit) Poly. (Standard Unit) Source: CEC PIER Integrated Design of Package Rooftop Units 2003 The third design driver is the growing interest and demand for green technologies. An indirect evaporative RTU does not add moisture to the supply air and the 100% OA provides improved indoor air quality and ventilation to benefit occupants and qualifies for credits in many local and national green building programs. The Role of the Compressor The field findings on the role of the DX proceed from measurement of the evaporative performance of the unit in the field, and simulations of the evaporative performance in several western climates, in order to estimate the required supplemental DX capacity. 3-158

In general, monitoring showed that the DX components were over-sized and utilized inefficiently. The field research assessment clearly showed that supplemental cooling of 5-10 F beyond the capacity of the indirect evaporative cooler was necessary to maintain a discharge air temperature in the low 60s during humid periods in the Northwest and in Central California (Sacramento). Evaporative Performance Central to the field findings is the thermal performance of the indirect evaporative heat exchanger, referred to here as the core. The performance of all evaporative cooling is expressed in terms of the achieved reduction in the dry bulb (DB) temperature of the inlet air as a ratio of the difference in the inlet air dry bulb and wet bulb temperatures. 4 In this work this evaporative performance measure will be referred to as the dry bulb effectiveness. Figure 3 shows this effectiveness as a function of outdoor temperature as observed in the field results. Figure 3. Dry Bulb Effectiveness Dry Bulb Effectiveness - Site 13 Aug '07 Dry Bulb Effectiveness Factor 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 80.0 85.0 90.0 95.0 Inlet Dry Bulb Temperature, deg F Figure 3 shows a dry bulb effectiveness of between 0.85 and 0.90, which increases slightly with higher outdoor temperatures. Note in this figure that the evaporative performance is observable as a very coherent function of inlet air dry bulb temperature. Effectively, this means that the DB temperature of the inlet air can be cooled 80-90% of the way to the WB temperature of the inlet air. In most western locations the inlet air wet bulb temperature during the hot part of typical summer days remains in the mid 60s F. Thus, in practice, the evaporative cooler tends to discharge air with a dry bulb temperature in the mid 60s regardless of the temperature of the inlet air. This performance is typical of the proper operation of this type of 100% OA IEC. The field testing also showed examples where the performance was lower than this because of inadequate 4 For example, if an evaporative cooler reduces the inlet dry bulb temperature sufficiently that the dry bulb temperature of the cooled air from the cooler is now as low as the inlet air wet bulb temperature it is considered to have a dry bulb effectiveness factor of 1. This is alternatively referred to as an evaporative efficiency of 100%. 3-159

water flow or inadequate air flow. But for the purposes of this analysis, a DB effectiveness of 0.87 is a reasonable performance assumption and well within the design potential of this core as investigated by others (Wicker 2003). Meeting Comfort Conditions The field testing showed that a very predictable performance could be achieved from the evaporative core. But this performance measure alone does not describe the more complex situation that determines the comfort in the cooled space. It is well known that the cooling comfort in a space will depend on both the internal gains, sensible and latent, of the cooled space and on the conditions, temperature and humidity, of the air supplied to the space. For most commonly occupied spaces, the internal gains are modest and a very significant determinant of comfort is the condition of the air supplied to the space. Therefore, we approached this fundamental question by reviewing the site weather conditions with reference to a climate performance screen. An example of this performance screen is shown in Figure 4. The performance screen shows the prevailing outdoor air conditions for a site as defined by TMY2 5 (NREL 1995) as well as the conditions of the cooled air exiting the indirect evaporative cooler into the cooled space. The exit conditions were estimated using empirical performance measures derived from the field monitoring (Higgins & Reichmuth 2007) and represent the performance of an indirect evaporative cooler with a dry bulb effectiveness of 0.90. The example in Figure 4 is for Sacramento, California. The conditions for the month of July reasonably represent the required upper limits of cooling performance for the system. Figure 4. Climate Performance Screen for Central California (Sacramento) Cooling Conditions Sacramento - July TMY2 Wet Bulb Temperature, deg F 85 80 75 70 65 60 55 50 45 40 40 50 60 70 80 90 100 Dry Bulb Temperature, deg F OSA Comfort saturation indirect evap limit evap exit Note in Figure 4 that the wide range of initial outside air conditions (open diamonds) result in a much tighter cluster of conditions emerging from the evaporator cooler (star points). About one-third of these exit condition points lay within the green comfort zone (box); the rest 5 Typical Meteorological Year 2 (TMY) data 3-160

are cooler than the comfort zone, in the 60-70 F range. The exit points in the comfort zone have little further cooling capacity for the internal gains. This argues for some additional cooling capability to lower the supply air temperature by a few more degrees. The saturation line in Figure 4 is a very important physical limit. The typical western air conditions represent a borderline situation such that it will be necessary to de-humidify air in order to get it from a supply air temperature of 60 down to 55 F. Thus, the last small increment of cooling necessary can have an exaggerated energy cost if it involves latent heat removal. Figure 5 shows the maximum summer conditions typical for Portland, Oregon. This figure shows that a significant portion of the outside air conditions at Portland are already in the comfort zone, without the need for further conditioning, and it shows that most of the evaporative core exit conditions are cooler than the comfort conditions and very suitable for space cooling. Boise, Idaho, (not shown) has conditions even more favorable than Portland s for indirect evaporative cooling. Figure 5. Climate Performance Screen for the Northwest (Portland OR) Cooling Conditions Portland - July TMY2 Wet Bulb Temperature, deg F 85 80 75 70 65 60 55 50 45 40 40 50 60 70 80 90 100 Dry Bulb Temperature, deg F OSA Comfort saturation indirect evap limit evap exit In the apparently dry southwest climate, there are some short-term seasonal conditions that prevail in the quickly growing regions of Southern California and Phoenix, Arizona that are distinctly humid. Figure 6 shows the Phoenix July conditions. 3-161

Figure 6. Climate Performance Screen for Phoenix Cooling Conditions Phoenix - July TMY2 Wet Bulb Temperature, deg F 85 80 75 70 65 60 55 50 45 40 60 70 80 90 100 110 120 Dry Bulb Temperature, deg F OSA Comfort saturation indirect evap limit evap exit In Figure 6, note that about one third of the evaporative cooler exit condition points are more humid than is comfortable. Note also that the majority of the points lie in the comfort zone box but have little extra capability of removing the internal gains. This situation again argues for the use of auxiliary cooling, both to remove moisture from the ventilation air, and to counter internal gains. In the above figures it is apparent that the supply air temperatures exiting the evaporative cooler are generally in the 60-70 F temperature range for almost all western sites. Higher elevation (and dryer) sites such as Boise showed even lower supply air temperatures, and these sites can be cooled by indirect evaporative cooling alone without the need for additional cooling. But for most other western locations, sensible cooling of up to 10 F to the supply air stream would be occasionally necessary to maintain a discharge air temperature in the low 60s during humid periods. Green Design and Indirect Evaporative Cooling These 60-70 F discharge temperatures from IECs are cool enough to remove moderate amounts of internal gain, but even in an ideal case, they are above the recommended 55 F commonly used as the design cooling temperature for conventional duct sizing. This recommended cooling design temperature has emerged from a practical compromise leading to moderately sized ducts and moderately efficient cooling unit performance. But that compromise emerged when evaporative cooling was not a contender. It can be argued that in new green-designed buildings an indirect evaporative cooler will be used in conjunction with highly efficient spaces with low internal gains and larger, lowerresistance ductwork. This would allow a higher supply temperature, up to approximately 65 F. A further green design approach involves displacement ventilation, where the ventilation air is supplied low and drives the heat gain out through the high-mounted exhaust without heating up by mixing with the room air. Although these design features may permit a higher supply temperature compatible with the supply air temperatures of a dedicated IEC, the analysis 3-162

consistently suggests that a small amount of additional cooling will still be necessary to properly condition the air under all circumstances. So, the research conclusion on the first design question Is a compressor necessary to supplement the indirect evaporative cooler? is yes in most climates and applications. But how big should the DX system be? Integrating the Dx This field work has showed that indirect evaporative cooling is an efficient alternative in cooling applications that involve 100% outside air, and that the Dx is essential and plays a critical support role. This highlights the importance of system design integration and operations. The integration of these two components in the prototype CoolAire was suboptimal and the field research provides valuable guidance for next generation systems. Sizing the Supplemental DX Capability Although the majority of the time the air from the evaporative cooler is directly suitable for cooling it is the extreme conditions that require compressor assist. The extreme conditions of the output air from an evaporative cooler cluster within a tight temperature range. Under the observed and anticipated extreme conditions the output DB temperature is almost always 75 F or less, and the WB ranges from a low of 63 to a high of 70 F. From these extreme conditions, a modest 10 F increment of cooling is all that is required of the DX subsystem. In the case of the lower WB temperature, 63 F, this incremental cooling is mostly sensible cooling, but in the case of the higher WB temperature, 70 F, the cooling is mostly latent cooling. In spite of the tight cluster of air exit conditions, the nature of the compressor assist ranges widely from predominant sensible cooling to predominant latent cooling. There are also other considerations in the sizing of the compressor system to facilitate: A wide variety of application conditions, Significant cooling when the evaporative cooler is in winterized mode and shoulder season cooling may be necessary, and Designed cooling capacity when actual internal gain or outdoor wet bulb temperature is higher than design conditions. We applied the field data on output supply temperatures and system integration to assess design needs on sizing. To bracket the sizing range we did an initial sizing estimate for an application with a cooling load that includes cooling of 100% OA. The initial sizing is done with reference to the fundamental psychrometrics of the situation and includes consideration of both the sensible and latent cooling requirements. Table 1 shows the extreme cooling loads for the expected high (Phoenix) and low (Sacramento) range of cooling supplement conditions, although most of the supplemental DX will be much less than shown in the table. 3-163

Path Ambient conditions dry/wet Table 1. Extreme Cooling Loads Final design Full Cooling condition Load dry/wet Enthalpy Evaporative Contribution btu/lb Required DX supplement % of cooling load btu/lb Low Cooling 100/72 62/57 11.2 7.1 37% High Cooling 95/75 62/57 14.1 4.4 69% Table 1 shows a supplemental DX capacity of 37% of full cooling load for the low cooling path and 69% of the full cooling load for the high cooling path. The low cooling path is mostly sensible cooling and the high cooling path is mostly latent cooling. Note also the low cooling path starts with a higher ambient DB temperature than the high cooling path. The high cooling path starts with a higher ambient WB temperature and a DB temperature of 95 F that is characteristic of the humid situations. In practice, Table 1 should be understood in the context of a control hierarchy contributing to the following conclusions: at all western locations, at least 60% of the cooling will require no DX supplement; 30-40% of cooling will require a DX supplement with a maximum capacity of 37% of the full cooling capacity. And at humid sites 10%-20% of the cooling will require a DX supplement with a maximum capacity of 69% of the full cooling capacity. Note that traditional extreme design conditions may not be extreme from the perspective of an evaporative cooler and that the real extreme for the evaporative cooler is the high WB situation shown in Table 1. 6 We take from this initial sizing that most of the DX supplemental cooling will be at a low capacity, less than 40% of the nominal unit capacity, and a minority portion will be at a higher capacity, 70% of nominal capacity. The manufacturer, for market and production purposes, needs to determine a single total amount of DX supplement to provide with each capacity line and the highest additional potential need (70%) is a likely choice. This, in combination with the desire for a nearly full backup system for their prototype, is clearly the basis for the single 4-ton DX in the CoolAire. The variation in the range of additional DX need does, however, argue strongly for the ability to split the load through the use of a 2-stage compressor and attention to careful control staging in order to maintain the best energy efficiency. Achieving Efficient Compressor Operation The field monitoring showed that the realized efficiency of the compressor operations was very poor. The 2006 CoolAire Report presents the findings associated with the low 6 For example the ASHRAE 1% design condition for Phoenix is 108 DB, 70 WB. This ASHRAE extreme has about 15% humidity and a reasonably low absolute humidity of about.007 lbs water/lb air and would only need a small DX supplement. In the site screening analysis for Phoenix, TMY2 weather conditions were used to examine the full range of conditions. The high WB situations were always associated with a more moderate DB (90-95 F) which is the local monsoon condition. In spite of the un-dramatic dry bulb, this monsoon condition has an absolute humidity of about.014 lbs water/lb air - twice the amount of water in the air as in the ASHRAE 1% condition. This monsoon condition is the real challenge for the evaporative cooler because the high WB limits the evaporative effectiveness, and the low DB does not leave much room for the sensible cooling that the evaporative cooler is so good at. Under this non-obvious extreme the evaporative cooler cannot remove much heat from the air and the DX supplement must shoulder a larger load. 3-164

compressor efficiency, which was approximately half that expected 7. These performance issues can be summarized as: The 4-ton compressor operates primarily at very low loads, The variable speed scroll compressor selected reduces output but does not proportionally reduce electric energy input, and Low purge airflow through the condenser contributed to un-necessarily high head pressures and high compressor power. This field research work has showed several areas of investigation regarding an improvement to compressor system operations used in this context. Evaporator coils. In the case of almost all IECs, the compressor system will be operating on air that has already been cooled and is reasonably close to its saturation condition. The extent of further cooling must be carefully considered because under these conditions, excess cooling of the air will involve unnecessary extraction of moisture from the air resulting in a low sensible heat ratio and low cooling efficiency. In order to avoid this unfavorable efficiency situation, the evaporator coils should be somewhat oversized relative to the capacity of the compressor (which would be the case for a two stage compressor operating on low stage). This will allow the evaporator coil to provide the required cooling at a higher temperature and to minimize the energy losses associated with excess condensation. That is, the system operates at a higher and more efficient sensible heat ratio. Variable speed compressor. The very practical design problem is to devise a control scheme that can deliver a highly variable small quantity of additional cooling from hour to hour, all while maintaining compressor operation at its highest efficiency. The use of multiple compressors is the common approach to this, and was considered for the field tested units, but excluded for cost reasons. Instead a 4-ton variable output scroll compressor was used. In the field test units, the output of such a compressor is modulated with an un-loader valve that can alter the output from full to zero while the compressor continues to spin at its design rotations per minute (rpm). In operation, this un-loader cycles several times a minute as necessary to control the average output of the compressor. But the research uncovered a common misunderstanding regarding variable speed scroll compressors: the output of these compressors can be precisely reduced from full output through the use of the un-loader mechanism, but the input electric energy is not proportionally reduced. Therefore, when the compressor is operating at less than its full load, it will be operating at a significantly reduced efficiency. This resulted in very low compressor operating efficiencies at the predominant part load conditions encountered in the field test. Thus a variable speed compressor is not an efficiency improvement to the design. Air flow. The air flow through the condenser coils of the compressor subsystem can also have a significant effect on the operating efficiency of the system. In the field test units, the air flow through the condenser could be varied by a damper, and in cases where the flow was too limited (in an effort to conserve on fan power), the compressor would be driven to high head pressures, 7 The compressor efficiency reported in the 2006 report is EER of 6-8. 3-165

high enough in some cases, to cause the compressor to trip off line. This problem was significant enough that the site monitoring for the 2007 cooling season was upgraded at two sites in-order to develop more detailed insight into compressor operation. The field findings in Figures 7 and 8 show, as expected, that the compressor head pressure is dependent on the air flow through the condenser. Figure 7. Condenser Pressure at Different Condenser Air Flows Condenser Pressure Condenser Pressure, psig 350 300 250 200 150 100 50 60 70 80 90 100 Outside Air Temperature, deg F Low Flow Higher Flow In Figure 7 observations at two different field sites with different air flow settings are presented. At the Higher Flow site, purge flow was higher than supply flow, but at the Low Flow site, the purge driving pressure was 60% lower and the purge flow was less than the supply flow. During this comparison interval, the evaporator flow and temperatures were similar yet it is apparent that the condenser pressure (and compressor head pressure) is increased by the lower air flows through the condenser. In operation, this low flow case tripped off line when the outdoor temperatures reached above 105 F and the condenser pressure reached 375 pounds per square inch (psi) - the high pressure limit. A low purge air flow has a two-fold effect on the condenser. The low purge flow leads to a relatively higher purge core exit temperature and thus to a higher temperature increase through the condenser because the lower flow cannot carry away the discharged heat as effectively. Together these effects contribute about equally to a 20 F condenser air temperature difference observed between sites. These higher condenser air temperatures are the predominant reason for the higher condenser pressures observed in Figure 7 and to the higher energy use shown in Figure 8 in the low air flow case. 3-166

Figure 8. Compressor Power at Different Condenser Air Flows Compressor kw vs Outside Air Temperature Compressor Power, kw 4.5 4 3.5 3 2.5 2 1.5 1 0.5 0 60 70 80 90 100 Outside Air Temperature, deg F Low Flow Higher Flow Optimizing compressor operations is strongly dependant on establishing the proper system sizing, maintaining adequate airflow, reducing the air temperature through the condenser coils, and effective control. Theoretically, the prime air source for the condenser is the exhaust air from the cooled space. It is the nature of an evaporative cooler to pressurize the cooled space with the 100% outside air, and stabilizing the building pressure requires providing an exhaust air flow about equal in magnitude to the supply air flow. If the exhaust air path were directed through the condenser, the condenser would have a good air flow rate at the lowest available temperature, which is the best operating condition for the DX subsystem. Summary The two-year field test of the hybrid indirect evaporative/compressor cooling system has led to the following results and design recommendations: The 100% OA indirect evaporative core can provide a very predictable performance with core exit air in the mid-60s F even under high outdoor temperature conditions. Supplemental compressor based cooling of 5-10 F beyond the capacity of the indirect evaporative cooler will be necessary for limited times at many western sites in order to maintain consistent comfort conditions. Compressor control will have a significant effect on overall compressor operating efficiency. A modulating scroll compressor should be avoided because, although the output can be precisely reduced from full output through the use of the un-loader mechanism, the input electric energy is not proportionally reduced. The capacity of the supplemental compressor system should be 50% of the design capacity of the overall hybrid system in moderate cooling regimes such as Portland, Boise and even Sacramento. But the capacity needs to be up to 70% of design capacity in partially humid cooling situations such as Phoenix and the Southern California deserts, inland empire. 3-167

A 2-stage compressor should be used to allow for optimization of the more frequent need to low amounts of supplemental cooling. The design operating conditions for a supplemental compressor system are different than for a full compressor based cooling system. High operating efficiency of the compressor system will depend on minimizing unnecessary condensation. This is best achieved by using an oversized evaporator coil relative to the compressor capacity. Monitoring demonstrated that average condenser exit air temperature and compressor system efficiency are highly sensitive to the purge air flow, with lower purge air flows reducing efficiency. For best compressor system efficiency, the airflow through the condenser should be as high as possible and the temperature of the air should be as low as possible. Conducting the exhaust air from the building through the condenser will give an adequate air flow and at a temperature usually much less than the outside air temperature. This configuration will give compressor efficiencies that are much better than could be expected from a stand alone compressor cooling system. References Davis Energy Group. 2002. DualCool Monitoring and Evaluation Report. San Francisco, Cal. Pacific Gas and Electric DualCool. 2008. Equipment Specifications. On web page at: http://dualcool.net/details.html Higgins, Cathy, and Reichmuth. 2007. Desert CoolAire Package Unit Technical Assessment. White Salmon, Wash.: Northwest Energy Efficiency Alliance and Sacramento Utility District. Jacobs, Peter. 2003. Small HVAC System Design Guide. CEC #500-2003-82-A-12. Sacramento, Calif.: California. California Energy Commission. National Renewable Energy Laboratory (NREL). 1995. User's Manual for TMY2s (Typical Meteorological Years), NREL/SP-463-7668, and TMY2s, Typical Meteorological Years Derived from the 1961-1990 National Solar Radiation Data Base, June 1995, CD-ROM. Golden, Colo.: National Renewable Energy Laboratory. New Buildings Institute. 2006. Assessment of Market-Ready Evaporative Technologies for HVAC Applications. Irwindale, Cal. Southern California Edison. Wicker, K., 2003. Life below the Wet Bulb: the Maisotsenko Cycle. Houston, Tex.: Power, November/December 2003. 3-168