Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Similar documents
FLOAT BATTERY CHARGERS

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

AT10.1 Series Microprocessor-Controlled Float Battery Charger (single phase input)

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

LORAIN CIP 4890/48120 DC Power System

LORAIN CSP DC Power System

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

SECTION AUTOMATIC TRANSFER SWITCHES

FDF Foam Pump Controllers Features

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Commercial and Light Industrial Fire Alarm Control Panel

Installation Guide for models:

B. Section Transfer Switches: Automatic transfer switch.

Public Safety DAS Annunciator Panel

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Spectron LSN (Life Safety Network) Suggested Specifications

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

DIESEL Engine Fire Pump Controllers Features

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

Loadstar AC/DC Systems

Installation Guide for models:

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

Pioneer-R16 Gas Monitor Operator s Manual

Model 4001 Series Single Channel Controller

ILLUMINATOR EM. CENTRAL LIGHTING INVERTER 1000 VA/W through 2800 VA/W 98% Efficiency!

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Remote NAC Power Supply D7038

Utility Battery Chargers DC Power Systems Custom Design

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. HZM-Series-Class I, Div 2 Battery Unit. Instalation instructions

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

LC2200 Level Controller Installation and Maintenance Instructions

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

ANALOX 3000 Carbon Monoxide Monitor

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Constant voltage 3-phase rectifier.

ESSEX ENGINEERING CORPORATION

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation, Operating and Maintenance Manual

SECTION AUTOMATIC TRANSFER SWITCHES

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. 3LERHZ Series Class I, Div 2 Combo Unit. Installation instructions

RE-PR3-E-27 3-Phase Panel Mount 27kW

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Table of Contents. Protective Relays

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

MR-2602 Two Zone Fire Alarm Control Panel

ECC-50/100C. Emergency Command Center

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

Dale Power Solutions Ltd

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

Fire Control/Communicator

CONTENTS AUTOMATIC TRANSFER SWITCHES

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. NXM Series - Survive-All. Emergency Light Unit

Booster Power Supply Manual

SECTION POWER SUPPLIES AND DISTRIBUTION

Across-the-Line SERIES MP300 Combined Manual and Automatic

Soft Start Series MP700 Solid State, Reduced Voltage

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

Constant voltage charger. Type UP 610. »We store the world's energy« Network

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

# amp # amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL. 4202/4MA, Rev. E 0804

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

AL800ULADA. NAC Power Extender. Installation Guide

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

APC BC300 Series 40kW 208/450/480V User Guide

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

TECHNICAL DATA OBSOLETE

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

July 14, 1999 DF C-100.

Series. Access Power Controllers. Installation Guide

Transcription:

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input April 2006

SCR-SCRF Utility & General Industry Switchgear Alarm Systems Engine Starting Railroad Emergency Lighting Marine Communication & Telecommunications Radio Telephone Telemetering Microwave Saft's SCR/SCRF Series of industrial float chargers is designed to automatically control charging rates for a wide variety of battery types and to simultaneously provide full rated output for both continuous and intermittent DC loads. The chargers are constant voltage devices with automatic current limiting. Voltage regulation and current limiting are controlled by solid state integrated circuitry to assure maximum performance in minimum space. The SCR/SCRF Series is ideally suited to utility, communications and other stationary charger applications. Design Features Component Selection Electronic and electrical components are substantially derated to assure long life and reliability. Typical MTBF is 30,000 hours minimum. Components are selected or designed to provide a system life expectancy of 20 years. Modular Construction Control circuits, alarm circuits and electrical subassemblies are printed circuit board wired or modularized with plug and socket connections for easy serviceability. Standard Subassemblies Control modules and many electrical subassemblies are standardized across the entire range of charger sizes. This minimizes spare parts inventory and simplifies maintenance. Durable Front panels are recessed to prevent accidental damage to meters and controls. Standard cabinets are NEMA-1 enclosures of heavy gauge phosphatized steel with an attractive, long lasting acrylic enamel finish. Easy Troubleshooting A complete service manual, color-coded wiring, test point identification and circuit symbol labeling of internal components make troubleshooting easy. Ease of Adjustment Tap adjustments are not required. Output float voltage, equalize voltage, current limit and alarm levels are potentiometer adjustable. Ease of Access Internal components and connections are easily accessible and/or removable through a hinged front door that opens approximately 180 degrees for easy serviceability. Ease of Installation Cabinets are floor, wall or rack mountable and equipped with knockouts for cable or conduit entrance. Input, output and remote alarm connections are wired to easily accessible, internal terminal blocks. Environmental Specifications Operating Ambient Temperature 32 F to 122 F (0 C to 50 C) without derating. Storage Temperature -40 F to 185 F (-40 C to 85 C). Operating Altitude 3300 feet (00 meters) above sea level without derating. Relative Humidity 5% to 95% (without condensation). Audible Noise Less than 65 dba at any point 5 feet from any vertical surface of enclosure. Typical values measure 55 to 60 dba at 0% load. Ventilation Units rated 300 Adc output or less are convection cooled via NEMA-1 vent openings in cabinet. Units rated 400 Adc output or greater have fan-assisted convection cooling with overheat audible alarm and remote alarm contacts. (Automatic charger shutdown due to overheat is optional.) Electrical Specifications AC Input Standard transformers are available with taps for nominal voltages as listed below. Single Phase Voltages: 120/220-240V 47-63Hz 480V 57-63Hz 120/208-240V 47-63Hz (optional) Three Phase Voltages: 208/240V 57-63Hz 380-416V 47-63Hz 480V 57-63Hz Chargers are wired and circuit protected for one nominal input voltage and frequency (to be specified at time of order). Output Regulation ±0.5% of DC voltage setting maintained with input line variations of ±% voltage and/or ±5% frequency. ±0.5% of DC voltage setting maintained with load variations from no load to full load. ±1.0% of DC voltage setting maintained against the combined variations of line, load and temperature.

SCR-SCRF Output Transient Response & Recovery ±5.0% max. of DC voltage setting maintained with step load changes from 20% to 0% load. Recovery to ±2.0% of DC voltage setting, typically 200msec. Recovery to steady state DC voltage setting, typically 500msec. Overshoot of DC Voltage setting is not present at turn-on due to soft-start feature. Output Current Limit The electronic current limiting circuitry is factory set at 1% of rated output. It is continuously adjustable from 90% to 120% of rated load. Output Ripple and Electrical Noise* Unfiltered (SCR Series): Output ripple voltage is less than % rms for single phase input SCR units. Output ripple voltage is less than 3% rms for three phase input SCR units. Filtered (SCRF Series): Output ripple voltage is 30mVrms or less for all SCRF units. Electrical voice band noise is less than 32dBrnC using C-message weighting network. *Measure when connected to a battery with an 8hr Amp-Hour rating of 4 times the full load current rating of the charger. Random Parallel Operation SCR/SCRF Series Chargers may be random parallel operated with other chargers of similar regulation and current limit characteristics. Equal load sharing by two SCR/SCRF chargers requires the addition of the forced load sharing option. Battery Eliminator Operation SCRF Series Chargers will operate as DC power supplies without batteries. Addition of the Filtered Battery Eliminator option (SCRF units only) will reduce ripple when used as a battery eliminator. DC Output Fuses Two-pole, fast acting, current limiting rectifier type. AC and DC Surge Supressors - MOV Type AC Withstand 240Vac or less: 1500Vpk - 1.2 x 20 μsec pulse Over 240Vac or less: 3000Vpk - 1.2 x 20 μsec pulse DC Withstand All DC outputs: 4000Vpk - 1.2 x 20 μsec pulse DC Output Ammeter and Voltmeter Front panel, 2% accuracy, 3.5 inch case. Manual Float/Equalize Switch Front panel toggle switch. Float and Equalize Adjustment Potentiometers Two front panel mounted, lockable adjustment potentiometers. Current Limit Adjustment Potentiometer Internally mounted, with easily accessible adjustment. DC Output Blocking Diode Standard SCRF series feature prevents battery from discharging back through the filter and rectifier when charger is off due to AC power failure or charger malfunction. Standard SCR Series design provides the same protection on unfiltered units. DC Output Protection Diode Prevents damage to charger and battery due to reversed polarity connections. Color-Coded Internal Wiring 600 Volt, color-coded, polyvinylchloride (PVC) wiring is standard. Standard Accessories AC On Indicating Light Green front panel indicator AC Input Circuit Breaker Single Phase Input: Two-pole, 5000 A.I.C., UL Listed 0A-Frame Three Phase Input: Three-pole, 5000 A.I.C., UL Recognized 0A-Frame Three-pole, 25000 A.I.C., UL Listed 225A-Frame Three-pole, 30000 A.I.C., UL Listed 400A and 600A-Frame

Floa S (Time Unregulated AC Input 1φ or 3φ Typical SCR/SCRF Series One-Line Circuit Diagram AC Input Circuit Breaker Input Surge Protection AC On Indicating Light Power Isolation Transformer SCR/Diode Rectifier Bridge Filter S (SCR o Remot Remote Alarm Signal AC Power Failure Alarm (optional) Remot Control Power Remot Internal Alarm Signal (e.g., HVA) Charger Shutdown (optional) Control (Trigger) Module w/current Limit Adjustment Battery charger DC Output Table Vdc Nominal Float Adjustment Range (Vdc) Equalize Adjustment Range (Vdc) Adc Size Range Available* Lead-Acid Cell Capability** (No. of cells) Ni-Cd Cell Capability*** (No. of cells) 1φ Input 3φ Input Normal Reduced Normal Reduced 12.5-14.5 11.3-16 6 to 0 60 to0 5-6 ---- 8 - ---- 24 23-30 24-32 6 to 0 50 to 600 11-13 ---- 17-20 [21] 48 46-60 48-64 6 to 0 50 to 600 22-26 [27] 34-40 [42] 130 115-140 124-150 6 to 50 25 to 600 55-62 [63] 86-94 [98] 260 230-280 245-300 6 to 25 16 to 300 1-124 [126] 172-188 [196] * The discrete Adc sizes offered within the ranges listed above are: 6, 12, 16, 20, 25, 30, 35, 40, 50, 60, 75, 0, 125, 150, 175, 200, 250, 300, 400, 500, 600Adc. All sizes are rated at 0% load. Some current ratings are not available on certain chargers. Consult factory or current priced list for exact offerings. ** Based on Lead-Acid Float of 2.15 to 2.25V/Cell and Equalize of 2.25 to 2.40V/Cell. *** Based on Ni-Cd Float of 1.35 to 1.45V/Cell and Equalize of 1.50 to 1.60V/Cell. Greater cell capability indicated by [xx] can be obtained by slightly reducing float and equalize settings.

Section only) Reverse Current Polarity Protection Output Fuse Protection DC Output Circuit Breaker (optional) Output Surge Protection Regulated DC Output ote Alarm Signal Charger Failure Alarm (optional) ote Alarm Signal Hi-Low Voltage Alarm (optional) ote Alarm Signal Ground Detection Alarm (optional) Current Sense oat/equalize Selection er is Optional) Voltage Sense & Adjustment Typical Performance Curves 2.5 Output Regulation - Lead-Acid Batteries 0 Conversion Efficiency - Single Phase Charger 2.4 2.3 2.2 2.1 Equalize Calcium-Float Antimony-Float 90 80 70 60 2.0 50 1.9 40 1.8 30 1.7 20 Vdc/cell 1.6 0 20 30 40 50 60 70 80 90 0 1 120 % Load Current limit adjustment 1.7 Output Regulation - Ni-Cd Batteries Vdc/cell 0 20 30 40 50 60 70 80 90 0 1 120 % Load Conversion Efficiency - Single Phase Charger 0 1.6 1.5 1.4 1.3 1.2 1.1 1.0 Equalize Float 90 80 70 60 50 40 30 20 Vdc/cell 0 20 30 40 50 60 70 80 90 0 1 120 % Load Current limit adjustment Vdc/cell 0 20 30 40 50 60 70 80 90 0 1 120 % Load Note: No load loss is 5% or less of DC output power at 0% load. Values shown are for nominal AC input and typical DC output voltage settings.

OPTIONAL ACCESSORIES Alarm Relays for Remote Indication* Available with or without front panel alarm indicating lights. AC Power Failure Alarm: Provides alarm state when AC power fails or AC breaker is open. DC Ground Detection Alarms: Provides alarm state when a ground fault has occurred at either the + or - output terminal. High-Low DC Voltage Alarms: Provides high alarm state when battery is being overcharged and low alarm state when battery is near end of discharge. Charger Failure Alarm (No DC Current): Provides alarm state when charger output current is less than 2% of rated output for 30 seconds or more. Will also activate with AC power failure and/or DC breaker or fuse open. Battery Discharging Alarm: Provides alarm state when battery discharge current exceeds the charger recharge current. End of Discharge Alarm: Provides alarm state when battery has discharged to lowest system voltage limit. DC Current Limit Alarm: Provides alarm state when charger output current reaches the current limit setting. Common (Summary) Alarm: Provides a single alarm state when any one or all monitored alarm conditions exist on charger. *Alarm circuits provide one (1) set of dry form C contacts (SPDT) wired to a terminal strip for customer termination. Alarm circuits with two (2) sets of dry from C contacts (DPDT) are available without indicating lights at additional cost. Standard relay contacts are rated for resistive loads of: 1A @ 120Vac, 2A @ 28Vdc, 1A @ 52Vdc, 0.1A @ 130Vdc. Auxiliary relays are available for use with alarm circuits when alarm load exceeds the standard contact rating. Auxiliary relay contacts are rated for resistive loads of: 5A @ 120Vac, 5A @ 28Vdc, 2A @52Vdc, 0.5A @ 130Vdc. Combined Alarm Status Charger Monitor* The following alarm relays are available combined together on a single board. Each relay has one (1) set of isolated, dry form C contacts (SPDT) wired to a terminal strip for customer connection. Two (2) sets of form C contacts (DPDT) are available at additional cost. High-Low AC Voltage Alarm Relay: With High and Low Indicating Lights, 15 second Time Delay on Alarm, Auto Reset. High DC Voltage Alarm Relay: With Indicating Light, 15 second Time Delay on Alarm, Auto Reset. Low DC Voltage Alarm Relay: With Indicating Light, 15 second Time Delay on Alarm, Auto Reset. Ground Detection Alarm Relay: With (+) Ground Detection Indicating Light and (-) Ground Detection Indicating Light, 15 second Time Delay on Alarm, Auto Reset. Charger Failure Alarm Relay: With Indicating Light, 30 second Time Delay on Alarm, Auto Reset. Common Alarm Relay: Summary Alarm Relay for any one or all alarms on this board. *Alarm contacts are rated for 0.5A @120V AC or DC. Indicating lights are red LED s front panel mounted. A Lamp Test switch is provided for verifying operation of indicating lights. Customer terminal strip is rated 15A @ 120V AC or DC to accommodate #14AWG maximum wire. This option may be ordered without Ground Detection for DC systems that are referenced to ground. DC Ground Detection for Local Indication Ground Detection Switch for Front Panel DC Voltmeter Indication: Measures voltage from + or - output terminals to common ground. Ground Detection Indicating Lights with Ground Test & Lamp Test Switch: Front panel lamps indicate + or - output ground fault with switch in Ground Test position. In Lamp Test position both lights are verified as operational. Equalize Timers 0-72hr Manual Equalize Timer w/ or w/o Float Equalize Indicating Lights: Replaces Float/Equalize Switch. Charger automatically switches from Equalize to Float at end of set time interval. 0-72hr Line Failure Auto-Equalize Timer w/float Equalize Indicating Lights: Charger is switched to equalize for a set time interval after power is interrupted for seconds or more. Equipped with Float Reset and Equalize override switches. 0-72hr Current Limit Auto-Equalize Timer w/float Equalize Indicating Lights: Charger is switched to equalize for a set time interval after charger is in current limit for seconds or more. Equipped with Float Reset and Equalize override switches. DC Circuit Breaker Two pole DC Breaker is installed with one-pole standard fuse: 5000 A.I.C., UL Listed 0A-Frame 000 A.I.C., UL Listed 250 & 400A-Frame 14000 A.I.C., UL Listed 600 & 800A-Frame Forced Load Sharing Chargers operating in parallel share load to within 2% of output current of each charger. High DC Voltage Charger Shutdown A contact closure from a High DC Voltage Alarm activates the shutdown circuit and charger output current goes to zero. Filtered Battery Eliminator Output ripple voltage is 30mVrms or 0.06% of nominal output voltage, whichever is higher, without battery connected. Input Lightning Arrestors Provides additional input protection against lightning induced transients. Surge Withstand Capability Additional surge protection to meet performance requirements of IEEE-472 SWC Specification. AC Input Voltmeter and/or Ammeter Front panel, 2% accuracy, 3.5-inch case. Additional Optional Accessories Special input voltages and frequencies Special High Interrupting Capacity (A.I.C.) circuit breakers 1% accuracy panel or switchboard meters Alarm buzzer Device nameplates Fungus proofing (Tropicalization) Drip-proof cabinet shields Cabinet heater strips Special paint NEMA-4 or NEMA-12 cabinets Special SIS or Hypalon internal wiring Export packing

SCR-SCRF TYPICAL INTERNAL CONSTRUCTION DETAIL 1. DC Ammeter 2. DC Voltmeter 3. AC Power On Light 4. Equalize Adjust POT 5. Float Adjust POT 6. Equalize Timer (optional) Float/Equalize Switch (standard) 7. DC Circuit Breaker (optional) 8. DC Fuse(s) 9. AC Circuit Breaker. DC Surge Supressor 11. Status Indicating Lights & Switches 12. Power Isolation Transformer w/ac Reconnection T.B. 13. AC Surge Suppressors 14. SCR Rectifier/Heat Sink Assembly 15. Polarity & Blocking Diode Assembly(s) 16. Filter Choke(s) 17. Bleeder Resistor 18. Filter Capacitor(s) 19. Alarm Relay(s) (optional) 20. Alarm Control Module(s) (optional) 21. Control Module 22. Current Limit Adjust POT 23. Input Line & Ground Terminals (TB1) 24. Output Terminals (TB2) 25. Remote Alarm Terminals (TB3) Note: Component placement may vary due to options selected. Style 1A Cabinet Construction Style 1B Cabinet Construction 17 18 12 17 18 20 22 12 13 15 14 20 25 19 21 23 22 15 13 14 16 16 24 11 11 7 4 8 1 2 3 4 6 5 9 1 2 3 11 5 6 9 23 21 25 24 19 7 8 3 2 1 11 7 8 11 6 Style 2 Cabinet Construction 5 4 17 20 18 21 14 15 22 13 12 9 16 24 23 25

BATTERY CHARGER, SIZE & DATA TABLE 12Vdc 24Vdc 48Vdc 130Vdc 260Vdc AMPERE RATING Single Phase Input 6 70 1A 80 (36) 95 1A 90 (41) 170 1A 5 (48) 370 1B 125 (57) 670 2 230 (4) 12 135 1A 90 (41) 200 1A 5 (48) 330 1A 120 (54) 740 1B 160 (73) ---- ---- ---- 16 180 1A 98 (44) 260 1A 115 (52) 440 1B 135 (61) 990 1B 2 (95) 1790 2 320 (145) 20 230 1A 5 (48) 320 1A 125 (57) 540 1B 160 (73) 1230 1B 220 (0) ---- ---- ---- 25 290 1B 120 (54) 400 1B 135 (61) 680 1B 170 (77) 1540 1B 230 (4) 2790 3 490 (222) 30 340 1B 130 (59) 480 1B 150 (68) 8 1B 190 (86) 1850 1B 250 (113) ---- ---- ---- 35 400 1B 135 (61) 560 1B 160 (73) 950 1B 2 (95) 2150 2 340 (154) ---- ---- ---- 40 460 1B 145 (66) 640 1B 180 (82) 80 1B 220 (0) ---- ---- ---- ---- ---- ---- 50 570 1B 160 (73) 800 1B 190 (86) 1350 2 245 (111) 3080 2 440 (200) ---- ---- ---- 60 680 2 185 (84) 960 2 2 (95) ---- ---- ---- ---- ---- ---- ---- ---- ---- 75 850 2 205 (93) 1200 2 245 (111) 2020 2 330 (150) ---- ---- ---- ---- ---- ---- 0 1130 3 280 (127) 1600 3 320 (145) 2700 3 440 (200) ---- ---- ---- ---- ---- ---- Three Phase Input 16 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1260 2 350 (159) 20 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 25 ---- ---- ---- ---- ---- ---- ---- ---- ---- 1260 2 300 (136) 1960 3 5 (231) 30 ---- ---- ---- ---- ---- ---- ---- ---- ---- 15 2 330 (150) ---- ---- ---- 35 ---- ---- ---- ---- ---- ---- ---- ---- ---- 1760 2 355 (161) 2750 3 560 (254) 40 ---- ---- ---- ---- ---- ---- ---- ---- ---- 20 2 380 (172) ---- ---- ---- 50 ---- ---- ---- 740 2 2 (95) 1230 2 255 (116) 25 3 500 (227) 3920 3 590 (268) 60 600 2 215 (98) 880 2 240 (9) 1480 2 320 (145) 30 3 520 (236) ---- ---- ---- 75 750 2 240 (9) 10 2 275 (125) 1850 2 350 (159) 3760 3 550 (249) 5880 4 890 (404) 0 990 3 315 (143) 1470 3 360 (163) 2460 3 460 (209) 50 3 680 (308) 7840 4 00 (454) 125 ---- ---- ---- 1840 3 425 (193) 3080 3 500 (227) 6260 3 750 (340) ---- ---- ---- 150 ---- ---- ---- 2200 3 480 (218) 3690 3 540 (245) 75 4 915 (415) 11800 5 1480 (671) 175 ---- ---- ---- 2570 3 5 (231) 4300 3 600 (272) 8760 4 (458) ---- ---- ---- 200 ---- ---- ---- 2940 3 550 (249) 4920 3 650 (295) 0 4 10 (680) 15700 5 16 (730) 250 ---- ---- ---- 3670 4 600 (272) 6150 4 750 (340) 12600 4 1400 (635) ---- ---- ---- 300 ---- ---- ---- 4400 4 7 (322) 7380 4 860 (390) 150 5 1500 (680) 23600 5 1950 (885) 400 ---- ---- ---- 5870 4 780 (354) 9830 4 950 (431) 200 5 1650 (748) ---- ---- ---- 500 ---- ---- ---- 7340 4 850 (386) 12300 5 1350 (612) 250 5 1820 (826) ---- ---- ---- 600 ---- ---- ---- 8800 4 925 (420) 14800 5 1500 (680) 300 5 1950 (885) ---- ---- ---- * Heat loss in BTU/HR is stated for nominal number of cells at float voltage and 0% DC load current. Ordering Information Specify: Charger Model #XSCRX XXX - XXX - X 1 for 1 phase 3 for 3 phase Omit for unfiltered F for filtered 012, 024, 048, 130 or 260 nominal Vdc output Nominal input (Vac) and frequency (Hz) Number and type of battery cells All optional accessories required on charger Omit if not required E for filtered battery eliminator (SCRF units only) 006 to 600 rated Adc output Cabinet Dimensions* 1A 1B 2 3 4 5 Mounting Type Wall** Wall** Floor** Floor Floor Floor H Dimensions 15 26 ¼ 37 ⅜ 49 62 80 in M.M. W 18 ¼ 19 20 ⅜ 32 42 58 (inches) D 12 ⅛ 15 ½ 14 ¾ 24 24 30 ** Rack mounting cabinet is optional for these styles. Saft 3 Powdered Metals Drive North Haven, CT USA 06473 TEL 203.239.4718 FAX 203.234.7598 Doc N o XXXXX-X-XXXX Edition: April 2006 Data in this document is subject to change without notice and becomes contractual only after written confirmation. www.saftbatteries.com