AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW. Row Cooling Precision Air Conditioner. Cooling Capacity: 26.2kW~68.6kW

Similar documents
Chilled Water Precision Air Conditioner for Critical Application

Precision Air Conditioner For Critical Application

AIRSYS-P-SC-MOBILECOOL-INDOOR-E1507V01.2 MOBILECOOL-INDOOR. Air Conditioner for Telecommunication Base Station. Cooling Capacity: 3.4~13.

AIRSYS-P-SC-MOBILECOOL-OUTDOOR-E1509V01.5 MOBILECOOL-OUTDOOR. Air Conditioner for Telecommunication Base Station. Cooling Capacity: 3.5kW-13.

AIRSYS-P-SC-TELECOOL-E1511V01.3 TELECOOL. Cabinet Cooling Unit. Cooling Capacity:500W-3000W

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

Precision Cooling. DataMate3000 Series Precision Cooling Systems for Small Equipment Room IT Application

Vertical self-contained air conditioner

Aquaflair TRAC-TRAF-TRAH

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

2013 Product Range Precision Air Conditioners (CRAC)

kw COOLING kw HEATING

DATASHEET CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

Precision air handling cabinets Ciatronic MICRO/EXPAIR

Air Cooled Scroll Chiller

Flexible and efficient: Close Climate Control for IT equipment

DAIKIN Modular Inverter Air Cooled Chiller

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

Flexible & Innovative. Cooling Solutions

NEXT DL NEXT DL. rcgroupairconditioning

Guide Specifications for InRow Direct Expansion

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

50CO. Close Control Unit. Wide range of chilled water cabinets. Compact and attractive design. EC motor for energy savings. Auto-adaptive control

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

CoolTeg Plus XC40. AC-TXC Direct expansion Air-conditioning unit with integrated compressor

gforce Units Data Aire and Data Temp Series

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

york airside products Tailored air conditioning solutions Introducing the YORK YPRE range of custom air-to-air packaged roof top units

next p dw next p dw rcgroupairconditioning

Refrigerant Type Heat Recovery Unit for Temperature & Humidity Control Room

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Blower-YEFB-020-3R-1maxVel

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

LZA High efficiency air to water heat pumps with HP compressor

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

LZT High efficiency air to water heat pumps with E.V.I. compressors

3 0 H X C A - H P 2

Liebert HIROSS for Telecom

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

20-120RT Multi-functional Modular Combination High Efficiency & Energy Saving Keeping Technology Cool

8-101kW. AlphaCool close control range ADDITIONAL CAPACITIES. NOW AVAILABLE Plus EC fan option kW. Typical applications

Multi-Denco. » Precision Climate Control. Air Conditioning & Heating. Multi-DENCO

AHU Plus. DX Air Handling Units

HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Close control air conditioning

next DX.U.S* 052.Z2.H6.DC

44,9 202,0 kw. technicalcatalogue

30HXC-HP Water-to-water Screw Heat Punp. Nominal cooling capacity: 460~1283 kw Nominal heating capacity: 498~1591 kw

NA G µair CONNECT 2

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

IT COOLING CLOSE CONTROL AIR CONDITIONERS PRECISION AIR CONDITIONERS WITH INVERTER TECHNOLOGY FOR STABLE ROOM CONDITIONS

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

F series close control air conditioners exploit the indirect FREE COOLING system with adiabatic cooling to ensure high system energy savings.

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

GHE Dehumidifiers for radiant cooling systems with heat recovery

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GHE GHE. Dehumidifiers for radiant cooling systems with heat recovery VERSIONS ACCESSORIES

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

STULZ CyberAiR Floor Mounted Systems. Engineering Manual. Floor Mounted Air Conditioners

ACMVTECH HIGH EFFICIENCY UNITARY AHU

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

SIMPLICITY BY DESIGN M52 CONTROLLER

CAREL heatersteam Electric Element Steam Humidifiers

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

next evo cw next evo cw rcgroupairconditioning

DC Inverter Smart VRF Products(R410A)

MODULAR CHILLER. R410a R22

MODEL NUMBER: SRCOOL60KCW

SCA 620C AIR COOLED SCREW CHILLER

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

kw. technicalcatalogue

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C

21,8 222 kw COOLING 25,2 236 kw HEATING

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

GEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion

Modular Air Cooled Scroll Chillers

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode

Be sustainable while protecting your business

Transcription:

AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW Row Cooling Precision Air Conditioner Cooling Capacity: 26.2kW~68.6kW

CHILLROW is installed closely with the server cabinets and refrigerating independently. The unit takes away the high density heat load through horizontal air supply scheme. Installed closely with the heat source, the unit can increase the cooling capacity of the cooling system. It is a new solution to increase energy efficiency for data centers. Unit Identification CHILLROW. F. DXA 24 V1 C1 R410. 380/3/50. XXX Code for Custom Design 3 alphabetic and numerical code Separator Character. Power Source Voltage/Phase/Frequency Separator Character. Refrigerant R410=R410A Cabinet Size Code CHILLROW adopt C cabinet with 2 sizes C1, C2. 1 Hermetic DC inverter scroll compressor Nominal Cooling Capacity: kw Cooling scheme DXA Direct expansion with air cooled condenser CW Chilled water cooling single coil Separator Character. Air Supply Scheme FRONT Horizontal front air supply, abbr. as F. Separator Character. Product Series CHILLROW: Abbr. as CRW.

Working Range and Control Accuracy CHILLROW.DXA Operating Range Outdoor Temperature: -40 ~+55 (special options are available for extreme temperature condition) Piping Length: Total length of 30 meters of gas and liquid refrigeration piping loop (consult Airsys sales representative for specific installation condition) Piping Vertical Distance: Condenser above indoor unit: max. 20m Condenser below indoor unit: max. 5m (consult Airsys sales representative for specific installation condition) Control Accuracy Temperature Range and Accuracy Range: 15~35, Accuracy: ±1 ; Humidity Range and Accuracy Range: 35~80%, Accuracy: ±5%. CHILLROW.CW Operating Range Water pressure: Higher than overall system pressure drop, lower than 1,250KPa. Control Accuracy Temperature Range and Accuracy Range: 15~35, Accuracy: ±1 ; Humidity Range and Accuracy Range: 35~80%, Accuracy: ±5%. Application Middle and high telecommunication exchange room Middle and big data center and computer room Museum and library Precision machining equipment center

Working Principle CHILLROW.DXA 1 2 12 3 13 11 4 5 10 6 7 8 9 1 Indoor 2 Outdoor 3 Compressor 4 Indoor Fan 5 Evaporator 6 Expansion Valve 7 Sight Glass 8 Filter Dryer 9 Receiver 10 Condenser 11 Outdoor Fan 12 Supply Air 13 Return Air CHILLROW.CW 1 2 8 5 3 4 6 1 Indoor 2 Electric valve 3 Supply fan 4 Evaporator 5 Supply air 6 Return air 7 Water in 8 Water out 7

Advantages High Flexibility Take away huge heat load separately through each unit installed closely to cabinet with horizontal air supply scheme, unit layout flexible; Available for places no matter with raised floor or not, also available for both newly built data center and reconstruction project; Scalable, the customer can scale the cooling capacity easily as demand grows to reduce initial investment pressure. Saving Operation Cost CHILLROW is installed between server cabinets, closely with heat load, avoiding hot and cold air mixture. The system efficiency will be increased by 30% to 45% compared with traditional cooling system; Short supply airflow path, decreasing fan power consumption. Easy Maintenance It is easy to maintain the unit for the easy configuration. Units are independent. The system can still run normally when one unit fails. High Lights Matching Appearance CHILLROW provides two widths (300mm and 600mm) for flexibility. The dimension is similar to standard server cabinet and matches with the server cabinets well. Supply Air Scheme Horizontal front air supply and back air return; air supply path is short in order to reduce fan power consumption. Cooling Scheme CHILLROW include 2 cooling schemes: CW and DXA. CW is applicable when the customer can provide Chiller while DXA can eliminate water leakage risk. The customer can choose the unit according to their demand. Eco-friendly Refrigerant R410A is used for DXA units. Convenient Maintenance Front and rear service access. Don t need to remove the unit at maintenance and don t influence other normal working units. It is important to data center s normal operation. CRW.F.CW25C1 and CRW.F.DXA24C1 have 5 hot swappable fans which can be controlled independently. Convenient Installation The unit has four composite castors and height adjustable fixed legs. It makes it easier to remove and install the unit. Besides, top or bottom pipe and line connection can be chosen according to customer s demand.

Unit Configuration CHILLROW.DXA Standard Configuration Standard Configuration CRW.F.DXA24V1C1 CRW.F.DXA38V1C2 Black powder painted steel base, internal frame and top frame Black powder painted steel panel with inside thermal and acoustic insulation DC powered EC centrifugal fan AC powered EC centrifugal fan Compressor inverter Hermetic DC inverter scroll compressor Copper tube aluminum fin coil Thermal expansion valve Sight glass Dry filter Liquid receiver High pressure transducer Pressure switch for high/low pressure protection Condensing water tray Washable nylon air filter Temperature sensor at supply air inlet Temperature sensor at return air inlet Installation support stand with adjustable legs Composite castor Microprocessor control system Electrical control panel Note: standard configuration, no option available. CHILLROW.DXA Optional Configuration Optional Configuration CRW.F.DXA24V1C1 CRW.F.DXA38V1C2 Air pressure switch for clogged filter alarm Floor water leakage alarm kit RS232 communication card RS485 communication card Pcoweb card Clock card Phase sequence protection relay for power supply Note: optional configuration.

Unit Configuration CHILLROW.CW Standard Configuration Standard Configuration CRW.F.CW25C1 CRW.F.CW65C2 Black powder painted steel base, internal frame and top frame Black powder painted steel panel with inside thermal and acoustic insulation DC powered EC centrifugal fan AC powered EC centrifugal fan Copper tube aluminum fin coil Condensing water tray Washable nylon air filter Motorized 2-way valve Temperature sensor at supply air inlet Temperature sensor at return air inlet Air pressure switch for supply fan protection Installation support stand with adjustable legs Composite castor Microprocessor control system Electrical control panel Note: standard configuration, no option available. CHILLROW.CW Optional Configuration Optional Configuration CRW.F.CW25C1 CRW.F.CW65C2 Motorized 3-way valve Air pressure switch for clogged filter alarm Floor water leakage alarm kit RS232 communication card RS485 communication card Pcoweb card Clock card Phase sequence protection relay for power supply Note: optional configuration.

Microprocessor Control System Indicative Parameters for Unit Working Status Temperature Return air temperature Supply air temperature Working Status Supply fans Compressor Condenser fan Humidifier water filling and drain valves Dehumidification activation valve 2 stages electric heater working status Automatic or manual status High pressure of refrigeration system Working Hours of Every Main Component Supply fans Compressor Humidifier Heaters working hours Alarm Display Display effective alarms, store and track up to 100 historical alarms (including alarm code, date, time and alarm description) Other Control Functions Self-diagnosis The microprocessor will continuously monitor its own circuit and shut off automatically in case of malfunction. Pressure Protections for Compressors Double protection on high pressure by both high pressure transducer and pressure switch. Protection on low pressure by pressure switch. Motor Overload Alarm for Compressor, Supply Fan, Electric Heater and Condenser Fan Prevent damages of component motor from voltage unbalance, low voltage and phase loss. On-off Control Of Compressor By setting the start-up relay time, minimum working time, minimum on-off interval and number of start-ups per hour to assure the reliability and to prolong the life of the compressor. Sensor Failure Alarm The microprocessor will shut down the unit and send out alarm signal in case of any failure of temperature sensor and pressure transducer. Power Supply Failure Alarm The microprocessor will shut down the unit and send out alarm signal in case of any failure of the power supply such as phase loss, phase sequence mistake, and voltage out of range. Unit Random Insertion The units can start-up automatically after the power recovery. The microprocessor has 2~60 seconds of random insertion to avoid current shock caused by multiple unit start-up at the same time. Floor Water Leakage Alarm When detecting the water on the floor with the water leakage alarm kit, the microprocessor will send out an alarm. Humidification System Alarm Microprocessor provides various alarms to the humidification system, such as high/low current, high/low water level, cylinder life, high/low conductivity, to assure the reliability and to prolong the life of the humidifier. Condenser Pressure Control Microprocessor monitor the compressor discharge pressure and control the steadily control the pressure by changing the speed of the condenser fan. This feature enable more stable operation, low noise, energy saving and low ambient temperature start-up and operation. Manual Control It is able to manually switch on/off all the major components during the commissioning and service of the unit. Operating Scheduling This function allows the user to set daily or weekly operating schedule. Multi-unit Group Control When multiple units are installed in one room, the operating strategy such as rotation, standby, can be achieved by group networking. Acoustic and Optical Alarm Signaling The room temperature, humidity and working status of all the components are displayed on the controller. When a failure occurs, acoustic buzzer is energized and the failure message is displayed on the controller display. 4 Levels of Password Unit has 4 password dedicated to different operation and maintenance jobs, this will prevent the unit from wrong or unauthorized operation.

Modified Parameter Basic Running Parameter Basic Running Parameters can be modified by customers according to the customer need, for example: temperature and humidification setting Routine Parameter The default parameters can be modified by service engineer during regularly maintenance, for example: temperature and humidity range, precision adjustment, temperature and humidity dead zone setting, highest and lowest temperature and humidity setting, high pressure alarm setting, start and stop schedule setting. Advanced Parameter For example: alarm delay adjustment, backup rotation setting, condensing fan working point setting, the compressor minimum start interval setting The unit can be initialized if necessary Note: more details, please refer to the User Manual. Remote Control and Monitoring Network The unit can be remote controlled or monitored by many kinds of methods as follows: 3 kinds of local direct cable connection 3 kinds of LAN network connection 4 kinds of wireless network connection Wireless connection types Local area network connection type Wireless connection 1 wireless router wireless communication network LAN connection 1 Cooling unit & Comm. card N1 RS485 card MODBUS protocol RS485-TCP/IP converter with 16 ports Ethernet network cable RS485 Bus N2 Wireless connection 2 Wireless router Wireless connection 3 Mobile phone GSM Mobile communication network GSM module The computer is installed with TCP/IP card RS485 card RS232 card and IntelliVision plus software N16 N1 Wireless connection 4 LAN connection 2 Mobile phone GSM module RS485 Bus N2 GSM communication network Monitoring Computer N16 Single unit direct connection types Direct connection 1 Units direct connection type Direct connection 2 RS485-RS232 Converter RS485-RS232 Converter N1 RS232 cable RS485 Bus N2 Direct connection 3 Single port RS485-TCP/IP converter Direct connection 4 N16

Technical Parameters CHILLROW.DXA Model CRW.F.DXA24V1C1 CRW.F.DXA38V1C2 Supply air scheme F Cooling Capacity Total(1) kw 26.5 41.3 Sensible(1) kw 26.5 41.3 Total(2) kw 24.2 38.7 Sensible(2) kw 24.2 38.7 Total(3) kw 22.3 36.3 Sensible(3) kw 22.3 36.3 Total(4) kw --- 25.9 Sensible(4) kw --- 23.9 Refrigerant R410A Compressor Type Hermetic DC Inverter Scroll Type Max. power input kw 8.1 12.5 Max. current input kw 17.2 24.8 Supply fan Type DC Powered EC Centrifugal Fan AC Powered EC Centrifugal Fan Qty. of fan n. 5 3 Air volume m 3 /h 4560 11600 Power input kw 1.2 3.1 Air filter Washable nylon net air filter Electric heater(5) Electric heater capacity kw --- 9 Working steps n. --- 2 Humidifier(5) Type Electrode Humidification capacity kg/h --- 3 Power input kw --- 2.3 Outdoor Condenser Model CRM10 CME15 Qty. n. 1 1 Power supply Power source 380V/3Ph/50Hz Unit max. operating power input(6) kw 9.8 25.3 Unit max. operating current input(6) A 26.2 46.6 Unit piping connection Humidifier water supplyφ in --- 1/2 Condensing water drainageφ in 3/4 3/4 Refrigerant discharge lineφ mm 19 22 Refrigerant liquid lineφ mm 16 16 Unit dimensions and weight Width mm 300 600 Depth mm 1180 1180 Height mm 2000 2000 Weight kg 140 370 (1) Return air dry bulb temperature 40,RH 20%, outdoor dry bulb temperature 35 ; (2) Return air dry bulb temperature 37,RH 25%, outdoor dry bulb temperature 35 ; (3) Return air dry bulb temperature 35,RH 30%, outdoor dry bulb temperature 35 ; (4) Return air dry bulb temperature 24,RH 50%, outdoor dry bulb temperature 35 ; (5) --- means none; (6) Maximum operating power and current input means: return air dry bulb temperature 40, RH 20%, outdoor dry bulb temperature 45,dehumidification mode, electric heater operates at full load. 10

Technical Parameters CHILLROW.CW Unit Model CRW.F.CW25C1 CRW.F.CW65C2 Supply air scheme F Cooling capacity Total(1) kw 26.2 68.6 Sensible(1) kw 26.2 68.6 Total(2) kw 24.1 63.1 Sensible(2) kw 24.1 63.1 Cooling coil Water flow(1) m 3 /h 4.4 11.5 Water pressure drop(with coil and valve)(1) kpa 68.1 62.9 Water flow(2) m 3 /h 4.0 10.6 Water pressure drop(with coil and valve)(2) kpa 55.4 55.2 Supply fan Type DC Powered EC Centrifugal Fan AC Powered EC Centrifugal Fan Qty. n. 5 3 Air volume m 3 /h 4560 11600 Power input kw 1.1 2.8 Air filter Washable nylon net air filter Power supply 230V/1Ph/50HZ 380V/3Ph/50HZ Unit piping connection Condensing waterφ in 3/4 3/4 Chilled water outlet/inletφ in 1 1-1/2 Unit dimensions and weight Width mm 300 600 Depth mm 1180 1180 Height mm 1950 1950 Weight kg 135 330 (1) Return air dry bulb temperature 37, RH25%, water inlet/outlet temperature 10 /15 ; (2) Return air dry bulb temperature 35, RH30%, water inlet/outlet temperature 10 /15. 11

AIRSYS is a cooling product and solution provider for ICT (Information & Communication Technology) industry. The products include: Air conditioner and Chiller for IT room and large data center Intelligent Control system (BAS) for IT room and data center Air conditioning equipments for telecom shelters Intelligent control system for shelter cooling. Air conditioner and heat exchanger for telecom cabinets. The solution include: Cooling system design System integration Installation and Commissioning Operation and Maintenance AIRSYS is also a global leader in providing cooling solution for Medical Imaging System. AIRSYS Refrigeration Engineering Technology (Beijing) Co. Ltd. Add: No.28, LuGuDong Str., Shijingshan District, Beijing, China Post code: 100040 Tel:+86-10-6865 6161 Fax:+86-10-6865 2453 Callcenter :+86-400-820-5515 www.air-sys.com