Компрессорно-конденсаторные агрегаты. Chiller. AQH DCI 20 to 30. Air Cooled Water Inverter Heat Pump Engineering Data Manual. 20 to 30 kw.

Similar documents
SyScroll Air EVO NEW

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SyScroll 40 to 75 Air NEW

SyScroll 20 to 35 Air NEW

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

LZA High efficiency air to water heat pumps with HP compressor

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

CHAPTER 6 CONDENSING UNITS

Advance Split

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

LZT High efficiency air to water heat pumps with E.V.I. compressors

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

PRODUCT GUIDE

Air cooled industrial chillers

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

Aquaflair TRAC-TRAF-TRAH

AQUASNAP JUNIOR 30RHV

PYXIS U PYXIS U. rcgroupairconditioning

pyxis u pyxis ua NEW rcgroupairconditioning

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

NEMO A Split-system liquid chillers for indoor installation. Cooling Capacity: 5 26 kw

kw COOLING kw HEATING

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

KELVIN Clim F497. Kelvin air conditioning

pyxis pyxisa NEW rcgroupairconditioning

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

GLIDER EVO GLIDER EVO. rcgroupairconditioning

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

WSK WSK. Water to water chillers and heat pumps VERSIONS ACCESSORIES

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

Chiller, Close control and Water terminals. Air Conditioning. Light Commercial, Commercial and Industrial

Modular Air-cooled Chillers

unico pf unico pf rcgroupairconditioning

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

WZH Ground source heat pumps

LZT High efficiency air to water heat pumps with E.V.I. compressors

LDN Series. Trattamento dell aria SELECTION, INSTALLATION AND MAINTENANCE MANUAL

SYSEFTYS - SYSHRW THE. Water Source Heat Pumps Range N E W. Water cooled. Refrigerant R407C. from 2.1 to 30.0 kw. from 2.7 to 38.1 kw. models.

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

nemo a hp rcgroupairconditioning R410A

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

FRIGO SCREW CLA PLUS Packaged water cooled liquid chillers in A+ class energy efficiency for indoor installation. Cooling Capacity: kw

kw. technicalcatalogue

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

HT V2 HT Split

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

glider evo cla glider evo cla A-CLASS rcgroupairconditioning

kw. technicalcatalogue

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

unico turbo FL unico turbo FL LOW NOISE A-CLASS INVERTER rcgroupairconditioning

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

TECHNICAL MANUAL FOR AIR-COOLED CONDENSING UNITS MTE

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

UNICO TURBO FL FREE UNICO TURBO FL FREE HIGHEFFICIENCY INVERTER ACLASS FREECOOLING LOWNOISE. rcgroupairconditioning

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

Blue Box Epsilon Echos +

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

Superchiller Product Documentation. English. cod rev Issued by TDS

44,9 202,0 kw. technicalcatalogue

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

High temperature air-to-water heat pumps

Commercial and Technical Data

MACH N-407 Heat Pump Air-Cooled Chiller

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

Transcription:

1 Компрессорно-конденсаторные агрегаты Chiller AQH DCI 20 to 30 Air Cooled Water Inverter Heat ump Engineering Data Manual 20 to 30 kw 20 to 30 kw

Specifications 3 AQH DCI Finned coil optimized in ing mode. Brazed late Heat Exchanger counter-flow in ing mode. Bi-flow electronic expansion valve as standard: - Excellent control of supering. - Higher effi ciency at partial load. Fan speed control, hase Sequencer control and pump as standard. Leaving water temperature control logic. The new air ed water pump with inverter driven compressor has been designed for R410A refrigerant fluid. AQH DCI is equipped with a pump as standard and can operate with low water volume, thanks to the microprocessor that implements an auto-adaptive control logic ensuring a total protection of the compressors at different load or water volume conditions. Main features New 3 phase inverter control. Very low water volume operation thanks to inverter technology and new logic. Strength oints Variable capacity: down to 30% of nominal capacity. Great accuracy in maintaining the desired water temperature. Refrigerant: R410A. Unit optimized in ing mode for both fan coil and floor application. High CO (class A) for both application: fan coil and floor ing. High performance at partial load; High SCO values calculated according to new standard EN14825. Wide operating limits in ing mode: - Min outdoor ambient temperature: -15 C. - Max leaving water temperature: +55 C. High accessibility & serviceability inside the unit. General AQH DCI units are one-block type with one refrigerant circuit. They are intended to down the water required for any air-conditioning application as well as any other fluid, such as for example glycol water. These units are completely assembled at works. They are equipped with all the refrigerating connections and the internal electrical wiring required for a rapid installation on the field. An operation test is performed after assembly, with water flowing through the refrigerant/water exchanger in order to make sure that refrigerating circuit is properly working. The refrigerating circuits of every unit are pressure tested before inspection, drained and charged with R410A. A low noise level is the result of a careful study. It is achieved on chillers by using technologically advanced components without negatively affecting the operation performances and limits of the units. AQH DCI models can down chilled water at a temperature between + 18 and - 8 C and warm up water at a temperature between 25 C and 55 C. Compressors AQH DCI units are equipped with a scroll compressors, with brushless direct current motor (BLDC) type. Compressors are assembled on rubber shock orbers. They are ed down by the refrigerant gas. Compressors are powered on and off by the microprocessor of the unit control system which is intended to control the delivery of the thermal refrigerating capacity. Evaporators Evaporators are made of stainless steel plates. They are thermally insulated by means of a thick flexible insulating mattress with closed cells. The maximum operating pressures correspond to 10 bar for the water side and to 45 bar for the refrigerant side. Antifreeze protection for the water in the exchangers is ensured by electrical ers and differential pressure switches. The water side of these exchangers is connected by manifolds which will provide for the connection to the plant by means of one single 1 1/2 gas threaded attachment. Conformity with standards The units are in conformity with the following standards: Machine Directive: 2006/42/EC. Low Voltage Directive: 2006/95/EC. Electromagnetic Compatibility Directive: 2004/108/EC. ressure Equipment Directive: 97/23/EC.

4 Specifications Condensing coils Condensers are coils made of copper tubes arranged in staggered rows and mechanically expanded inside an aluminium finned pack with blue fins treatment as a standard. The maximum operating pressure on the refrigerant side of the condensing batteries is 45 bar Condenser fans The condenser fans are of a helical type. They are directly coupled and have an impeller with wing contoured aluminium blades. Each fan is equipped with a galvanised steel accidentprevention protection which is painted after manufacture. The fans motors are completely closed. They have an I54 protection degree and a protection thermostat embedded in the windings. Refrigerant circuit Each unit has a single refrigerating circuit equipped with an external service valves intended to measure the refrigerant pressure and charge, a sight glass with a humidity indicator, a dryer filter and a electronic expansion valve. Refrigerating circuits are also complete with a high and low pressure switch as well as a high and low transducer. Fans Control All models are equipped with a single-phase voltage fan speed controller using the principle of phase control to adjust the effective voltage output to the load, based on the phase of the WM control signal according the pressure measured on the exchanger. Hydraulic circuit All units are supplied with a circulating pump as standard. The head of the pump is insulated with 10 mm insulation to avoid condensation on it. A water filter is also supplied as standard. A safety valve and an expansion tank are located on the suction side of the pump. Both high and low pressure sides are equipped with 3/8 fittings which allow water to be drained and manometer to be connected during service operations. Water connections are of 1 1/2 male gas threaded type. Safety and control devices Each unit is complete with the following safety and control devices: Safety: Fan motor overload protection; Compressor motor overload protection; Water differential pressure switch; ump motor overload protection; High pressure switch; Low pressure switch; High and low pressure transducers; Evaporator antifreeze electric er; Crankcase oil electric er. Control: Entering water temperature sensor; Leaving water temperature sensor; Coil temperature sensor; Discharge temperature sensor; Air temperature sensor; Suction temperature sensor; Suction and discharge pressure transducers. Standard option Stepless capacity control S (inverter); Soft starter (SS) S (inverter); Fan Speed Controller (FSC); Electronic Expansion Valve (EEV); Counter-fl ow air-to-refrigerant HE; DHW function (future release); Leaving water temp up to 55 C; Blue fin treatment (BFC). ModBus protocol kit for BMS; Field-installed accessories No pump kit; Gauge kit; Hydro kit 112 litres; Flow switch; In/out valve kit; Remote On/Off control; Sequencer for up to 4 chillers installation. Control panel

Refrigerant Flow Diagram 5 Refrigerant Flow Diagram - AQH 20-30 DCI R410A SH M K AT A INVERTER 1 2 ON 3 20 20 9 H BT SL B D 20 20 EXV CONTROL UNIT CONTROL 8 F C 5 4 7 6 S ELECTRONIC EXANSION VALVE E COMONENTS 1 Inverter driven scroll compressor (S=41,5 bar) 2 4-way valve (S=45 bar) 3 Air ed condenser (S=45 bar) 4 Biflow filter drier (S=45 bar) 5 Sight glass 6 Expansion valve 7 Liquid receiver (S=45 bar) 8 late exchanger (S=45 bar) 9 Suction accumulator (S=31 bar) SAFETY/CONTROL DEVICES A High pressure switch (40,5 bar) AT High pressure transducer B Low pressure switch (2 bar) BT Low pressure transducer C Water differential pressure switch (105 mbar) D Air temperature sensor E Outlet water temperature sensor F Inlet water temperature sensor H Defrost temperature sensor M Discharge temperature sensor ST Suction temperature sensor S 5/16 Shrader valve (charging point) K Discharge temperature thermostat SL 5/16 Low pressure shrader valve SH 5/16 High pressure shrader valve ipe connection with shrader valve robes

6 Operating Limits AQH 20-30 DCI Cooling operation / Nominal capacity AQH 20 DCI Cooling operation / Max capacity AQH 25-30 DCI Cooling operation / Max capacity Outdoor air temperature OAT I 50 45 40 35 30 25 20 15 10 5 0-5 -10-15 -10 Water+Glycol Water -8-6 -4-2 0 2 4 6 8 10 12 14 16 18 20 Outdoor air temperature OAT I 50 45 40 35 30 25 20 15 10 5 0-5 -10-15 -10 Water+Glycol Water -8-6 -4-2 0 2 4 6 8 10 12 14 16 18 20 Evaporator Evaporator AQH 20-30 DCI Heating operation / Nominal capacity AQH 25-30 DCI Heating operation / Max capacity AQH 20 DCI Heating operation / Max capacity (----) Condenser 60 55 50 45 40 35 30 25 20-20 -15-10 -5 0 5 10 15 20 25 Outdoor air temperature Condenser 60 55 50 45 40 35 30 25 20-20 -15-10 -5 0 5 10 15 20 25 Outdoor air temperature

Correction factors 7 Correction factors Fouling factors - Evaporator Fouling factor (m 2. C/kW) Cooling capacity factor ower input factor 0.044 1.000 1.000 0.088 0.987 0.995 0.176 0.964 0.985 0.352 0.915 0.962 Fouling factors - Condenser Fouling factor (m 2. C/kW) Cooling capacity factor ower input factor 0.044 1.000 1.000 0.088 0.987 1.023 0.176 0.955 1.068 0.352 0.910 1.135 Correction factors for water ΔT different from 5 K Models Water temperature in/out Cooling capacity ower input 17/7 (10) 95% 98% AQH 14/7 (7) 97% 99% 12/7 (5) 100% 100% 10/7 (3) 103% 101% Altitude factors Altitude (m) Cooling capacity factor ower input factor 0 1.000 1.000 600 0.987 1.010 1.200 0.973 1.020 1.800 0.958 1.030 2.400 0.943 1.040

8 hysical Data hysical Data AQH 20-30 DCI R410A Model AQH DCI 20 25 30 NET 5 Data @ Eurovent LC/A/CHF conditions 1 Heating capacity (min/nom/max) kw 7,01 18,1 26,0 9,61 21,7 31,9 10,5 25,1 33,4 ower input kw 2,31 4,64 7,63 2,52 5,37 8,63 2,73 6,42 9,34 CO kw/kw 3,03 3,90 3,41 3,81 4,04 3,70 3,84 3,90 3,58 Cooling capacity (min/nom/max) kw 10,4 20,2 28,8 12,8 25,0 32,5 14,0 29,4 34,1 ower input kw 2,01 3,88 6,69 2,25 5,09 7,85 2,61 6,80 8,34 kw/kw 5,17 5,20 4,30 5,69 4,92 4,14 5,37 4,33 4,08 NET 5 Data @ Eurovent LC/A/AC conditions 2 Heating capacity (min/nom/max) kw 6,08 18,1 22,9 8,45 21,7 28,6 9,24 25,1 29,9 ower input kw 2,39 6,21 8,18 2,99 7,13 10,3 3,24 8,50 10,7 CO kw/kw 2,55 2,92 2,79 2,83 3,04 2,78 2,85 2,95 2,80 Cooling capacity (min/nom/max) kw 7,05 20,2 25,6 8,87 25,0 30,4 10,1 29,3 31,8 ower input kw 1,98 6,01 8,46 2,16 7,45 10,2 2,47 9,43 10,6 kw/kw 3,56 3,35 3,02 4,10 3,36 2,98 4,08 3,11 3,02 NET ES kw/kw 4,50 4,83 4,63 Number of refrigerant circuits 1 art load steps % Stepless ower supply V/ph/Hz 400/3+N/50 Startup type Inverter Maximum corrent (FLA) A Refer to eletrical data Startup corrent (LRA) A Refer to eletrical data Refrigerant Type R410A Compressor Number 1 Type Scroll (BLDC Motor) Crankcase er W 40 Evaporator Number 1 Type Brazed plate Water flow rate l/h Refer to hydraulic circuit data Water pressure drop ka Refer to hydraulic circuit data Antifreeze er W 35 Coil Number 1 Frontal surface mm 1.350x1.500 1.350x1.500 1.350x1.500 Rows 2 3 3 Fans Number 2 Air flow rate m 3 /h 12.220 11.400 11.400 Speed rpm 630 630 630 Input power kw 0,6 0,6 0,6 ump Number 1 Input power kw 0,65 0,65 0,65 Water flow rate l/s Refer to hydraulic circuit data Available static pressure ka Refer to hydraulic circuit data Water connections Type Male gas threated Inlet diameter inch 1 1/2 Outlet diameter inch 1 1/2 Water drain connection inch 3/8 Weight Shipping kg 269 285 285 Operating kg 262 279 279 Dimensions Lenght mm 1.477 1.477 1.477 Width mm 538 538 538 Height mm 1.625 1.625 1.625 Acoustic data Sound power level db(a) 74 75 75 Sound pressure level 6 db(a) 43 44 44 1 Eurovent LC/A/CHF conditions in ing mode: water exchanger EWT/LWT 30 C/35 C, OAT 7 C db/6 C WB. Eurovent LC/A/CHF conditions in ing mode: water exchanger EWT/LWT 23 C/18 C, OAT 35 C. 2 Eurovent LC/A/AC conditions in ing mode: water exchanger EWT/LWT 40 C/45 C, OAT 7 C db/6 C WB. Eurovent LC/A/AC conditions in ing mode: water exchanger EWT/LWT 12 C/7 C, OAT 35 C. 5 According EN 14511-2011 standard. 6 Sound pressure calculated at 10 m. Values refers to ISO Standard 3744 with parallepiped shape.

Electrical & Sound Data 9 Electrical Data AQH 20-30 DCI R410A Units* Size Unit electrical data* 20 25 30 Maximum power input 13 16 16 Maximum current input (A) 27 32 32 Start-up corrent (A) 5 5 5 * Data referring to the unit with pump. Compressors Compressor electrical data (400V/3/50Hz) ower input at maximum cond. per comp. Current at max cond. per comp. FLA Start up current LRA Resistenza carter olio comp. Sizes kw A A W 20 COM 1 ANB42 12 22,0 0,0 40 W 25 COM 1 ANB52 14,4 27,0 0,0 40 W 30 COM 1 ANB52 14,4 27,0 0,0 40 W Fans Fans electrical data (230V/1/50Hz) Size Fan number Nominal power/fan Max. running current/fan (A) Total fan power Total max fan current (A) 20 2 0,3 1,8 0,6 3,6 25 2 0,3 1,8 0,6 3,6 30 2 0,3 1,8 0,6 3,6 ump ump electrical data (400V/3/50Hz) Size Nominal power Max. running current (A) 20 0,85 1,6 25 0,85 1,6 30 0,85 1,6 Sound Data AQH 20-30 DCI R410A Sizes Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Sound power level db Sound power level db(a) Sound pressure level* db(a) 20 84 68 71 70 70 65 59 54 74 42 25 88 70 73 71 69 66 61 53 75 43 30 86 69 72 71 70 66 59 56 75 43 * Sound pressure level at 10 m. Values refers to ISO Standard 3744 with parallelepiped shape.

10 erformances Nominal performances / ing operation - AQH 20 DCI AQH 20 DCI 25 30 35 40 45 5 20,2 4,57 4,42 20,2 5,43 3,72 20,2 6,38 3,16 20,2 7,17 2,82 20,2 9,60 2,10 7 20,2 4,06 4,97 20,2 4,70 4,30 20,2 6,01 3,36 20,2 6,89 2,93 20,2 9,53 2,12 10 20,2 3,48 5,80 20,2 4,19 4,81 20,2 5,03 4,01 20,2 6,40 3,15 20,2 7,76 2,60 15 20,2 3,13 6,44 20,2 3,53 5,72 20,2 3,91 5,17 20,2 5,22 3,87 20,2 6,82 2,96 18 20,2 2,78 7,25 20,2 3,24 6,22 20,2 3,88 5,20 20,2 4,78 4,22 20,2 6,01 3,36 Maximum performances / ing operation - AQH 20 DCI AQH 20 DCI 25 30 35 40 45 5 26,8 6,83 3,93 25,3 7,47 3,39 23,6 8,18 2,89 21,9 8,94 2,45 20,2 9,77 2,07 7 29,0 7,06 4,10 27,3 7,73 3,53 25,6 8,46 3,02 23,8 9,25 2,57 21,8 10,1 2,16 10 32,4 7,41 4,37 30,6 8,14 3,76 28,6 8,91 3,21 26,6 9,74 2,73 24,5 10,6 2,31 15 29,7 5,22 5,68 28,0 5,79 4,83 26,2 6,39 4,10 24,5 7,03 3,48 22,7 7,70 2,95 18 32,5 5,46 5,96 30,6 6,06 5,05 28,8 6,69 4,30 26,9 7,35 3,65 25,0 8,06 3,10 Nominal performances / ing operation - AQH 20 DCI AQH 20 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 15,2 7,10 2,13 16,9 7,29 2,32 18,1 7,39 2,45 18,1 6,16 2,94 18,1 5,32 3,40 18,1 4,64 3,90 18,1 3,94 4,60 40 14,4 7,43 1,94 15,9 7,56 2,11 17,1 7,63 2,24 18,1 6,30 2,87 18,1 5,92 3,06 18,1 4,93 3,67 18,1 5,02 3,61 45 13,6 7,69 1,77 15,3 8,01 1,90 15,7 7,49 2,10 17,2 6,90 2,50 18,1 6,81 2,66 18,1 6,21 2,92 18,1 5,64 3,22 50 6,41 3,94 1,63 14,4 8,08 1,78 15,3 8,13 1,88 17,2 8,21 2,10 18,1 8,17 2,22 18,1 7,13 2,54 18,1 6,01 3,01 55 - - - 10,1 6,01 1,69 14,6 8,34 1,74 16,2 8,42 1,93 17,8 8,49 2,10 18,1 7,60 2,38 18,1 6,82 2,66 Maximum performances / ing operation - AQH 20 DCI AQH 20 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 15,2 7,10 2,13 16,9 7,29 2,32 18,1 7,39 2,45 20,6 7,50 2,75 23,0 7,55 3,05 26,0 7,63 3,41 29,6 7,67 3,85 40 14,4 7,43 1,94 15,9 7,56 2,11 17,1 7,63 2,24 19,4 7,72 2,52 21,7 7,77 2,78 24,2 7,85 3,08 27,4 7,91 3,47 45 13,6 7,69 1,77 15,3 8,01 1,90 15,7 7,49 2,10 17,2 6,90 2,50 20,2 7,94 2,54 22,9 8,18 2,79 25,8 8,16 3,16 50 6,41 3,94 1,63 14,4 8,08 1,78 15,3 8,13 1,88 17,2 8,21 2,10 19,1 8,27 2,30 21,3 8,34 2,55 24,0 8,41 2,85 55 - - - 10,1 6,01 1,69 14,6 8,34 1,74 16,2 8,42 1,93 17,8 8,49 2,10 19,8 8,56 2,31 22,2 8,63 2,58

erformances 11 Nominal performances / ing operation - AQH 25 DCI AQH 25 DCI 25 30 35 40 45 5 25,0 5,92 4,23 25,0 6,76 3,70 25,0 7,93 3,15 25,0 9,09 2,75 19,7 7,88 2,50 7 25,0 5,40 4,64 25,0 6,24 4,01 25,0 7,45 3,36 25,0 8,74 2,86 21,1 8,36 2,53 10 25,0 4,65 5,38 25,0 5,42 4,62 25,0 6,37 3,93 25,0 7,60 3,29 23,5 8,52 2,75 15 25,0 4,27 5,86 25,0 4,70 5,33 25,0 5,73 4,37 25,0 7,04 3,56 25,0 7,80 3,21 18 25,0 3,63 6,90 25,0 4,53 5,53 25,0 5,09 4,92 25,0 6,14 4,08 25,0 7,11 3,52 Maximum performances / ing operation - AQH 25 DCI AQH 25 DCI 25 30 35 40 45 5 31,8 8,34 3,81 30,2 9,00 3,35 28,5 9,70 2,94 26,8 10,1 2,64 19,7 7,88 2,50 7 33,9 8,36 4,05 32,2 9,16 3,52 30,4 10,2 2,98 28,6 10,9 2,62 21,1 8,36 2,53 10 37,3 8,24 4,53 35,5 9,20 3,87 33,6 10,0 3,35 31,7 11,0 2,88 23,5 8,52 2,75 15 33,2 6,41 5,18 31,7 6,53 4,85 30,1 7,49 4,02 28,5 8,49 3,35 26,7 8,51 3,14 18 35,9 6,02 5,96 34,3 7,21 4,75 32,5 7,85 4,14 30,8 8,24 3,73 29,0 8,69 3,33 Nominal performances / ing operation - AQH 25 DCI AQH 25 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 20,7 8,32 2,49 21,7 8,09 2,68 21,7 7,97 2,72 21,7 7,16 3,03 21,7 6,20 3,50 21,7 5,37 4,04 21,7 4,59 4,72 40 19,2 8,55 2,24 20,9 8,63 2,42 21,7 8,92 2,43 21,7 7,58 2,86 21,7 6,98 3,11 21,7 5,82 3,73 21,7 5,23 4,15 45 13,7 6,68 2,05 19,7 10,5 1,88 20,8 10,2 2,03 21,7 9,78 2,22 21,7 8,50 2,55 21,7 7,13 3,04 21,7 6,40 3,39 50 4,52 3,43 1,32 18,7 10,8 1,73 19,8 10,9 1,82 21,7 11,2 1,94 21,7 9,69 2,24 21,7 8,26 2,63 21,7 7,39 2,93 55 - - - 9,09 5,77 1,58 19,0 11,4 1,67 21,0 11,4 1,84 21,7 11,1 1,95 21,7 9,23 2,35 21,7 8,28 2,62 Maximum performances / ing operation - AQH 25 DCI AQH 25 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 20,7 8,32 2,49 22,3 8,37 2,67 23,5 8,77 2,68 25,9 8,97 2,89 28,4 8,59 3,30 31,9 8,63 3,70 36,2 8,66 4,19 40 19,2 8,55 2,24 20,9 8,63 2,42 22,0 9,09 2,42 24,5 8,72 2,81 26,8 9,05 2,97 29,9 8,88 3,37 33,9 9,19 3,69 45 13,7 6,68 2,05 19,7 10,5 1,88 20,8 10,2 2,03 23,2 10,68 2,17 25,4 10,4 2,45 28,6 10,26 2,78 32,3 10,67 3,03 50 4,52 3,43 1,32 18,7 10,8 1,73 19,8 10,9 1,82 22,0 11,4 1,93 24,1 11,1 2,18 27,0 11,13 2,43 30,4 11,44 2,66 55 - - - 9,09 5,77 1,58 19,0 11,4 1,67 21,0 11,4 1,84 22,9 11,9 1,92 25,5 11,39 2,24 28,7 11,63 2,46

12 erformances Nominal performances / ing operation - AQH 30 DCI AQH 30 DCI 25 30 35 40 45 5 29,3 7,41 3,96 29,3 8,61 3,41 29,3 10,2 2,89 28,1 11,1 2,54 20,7 8,36 2,47 7 29,3 6,67 4,40 29,3 7,79 3,77 29,3 9,43 3,11 29,3 11,2 2,63 22,1 8,59 2,57 10 29,3 5,75 5,10 29,3 6,79 4,32 29,3 8,06 3,64 29,3 9,70 3,03 24,6 8,96 2,74 15 29,3 5,32 5,51 29,3 5,83 5,03 29,3 7,21 4,07 29,3 8,90 3,30 28,0 9,56 2,93 18 29,4 4,64 6,35 29,4 5,87 5,02 29,4 6,80 4,33 29,4 7,96 3,70 29,4 9,19 3,21 Maximum performances / ing operation - AQH 30 DCI AQH 30 DCI 25 30 35 40 45 5 33,2 8,52 3,90 31,6 9,31 3,40 29,8 10,2 2,93 28,1 11,1 2,54 20,7 8,36 2,47 7 35,5 8,80 4,03 33,7 9,60 3,51 31,8 10,6 3,02 30,0 11,6 2,59 22,1 8,59 2,57 10 39,1 9,26 4,22 37,2 10,1 3,68 35,2 11,1 3,17 33,2 12,1 2,74 24,6 8,96 2,74 15 34,8 6,64 5,24 33,2 7,28 4,56 31,5 7,99 3,95 29,8 8,75 3,41 28,0 9,56 2,93 18 37,6 6,93 5,42 35,9 7,61 4,72 34,1 8,34 4,08 32,2 9,12 3,53 30,3 9,95 3,05 Nominal performances / ing operation - AQH 30 DCI AQH 30 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 21,7 9,40 2,31 23,4 9,40 2,49 24,6 9,39 2,62 25,1 8,69 2,88 25,1 7,45 3,36 25,0 6,42 3,90 25,1 5,47 4,58 40 20,1 9,58 2,10 21,9 9,71 2,25 23,1 9,78 2,36 25,1 9,03 2,78 25,1 8,35 3,00 25,1 6,97 3,60 25,1 6,21 4,04 45 14,3 7,38 1,94 20,6 10,2 2,01 21,8 10,3 2,11 24,3 10,5 2,31 25,1 10,1 2,47 25,1 8,50 2,95 25,1 7,57 3,31 50 4,61 3,21 1,44 19,6 11,0 1,78 20,8 11,1 1,86 23,1 11,3 2,04 25,1 11,5 2,18 25,1 9,86 2,54 25,1 8,70 2,88 55 - - - 9,52 5,87 1,62 19,9 12,1 1,65 22,0 12,2 1,80 24,0 12,3 1,95 25,1 10,8 2,31 25,1 9,60 2,61 Maximum performances / ing operation - AQH 30 DCI AQH 30 DCI -15-10 -7-2 2 7 12 CO CO CO CO CO CO CO 35 21,7 9,40 2,31 23,4 9,40 2,49 24,6 9,39 2,62 27,2 9,37 2,90 29,7 9,36 3,17 33,4 9,34 3,58 37,9 9,35 4,06 40 20,1 9,58 2,10 21,9 9,71 2,25 23,1 9,78 2,36 25,6 9,87 2,60 28,1 9,92 2,83 31,3 9,97 3,14 35,5 10,0 3,54 45 14,3 7,38 1,94 20,6 10,2 2,01 21,8 10,3 2,11 24,3 10,5 2,31 26,6 10,6 2,51 29,9 10,7 2,80 33,8 10,8 3,15 50 4,61 3,21 1,44 19,6 11,0 1,78 20,8 11,1 1,86 23,1 11,3 2,04 25,2 11,4 2,21 28,3 11,5 2,45 31,9 11,6 2,75 55 - - - 9,52 5,87 1,62 19,9 12,1 1,65 22,0 12,2 1,80 24,0 12,3 1,95 26,7 12,4 2,15 30,0 12,5 2,40

ump available pressure / Input power 13 ump available pressure / Input power AQH 20-30 DCI R410A Available static pressure / late exchanger pressure drop 350 325 300 275 250 225 [ka] 200 175 150 125 25-30 20 100 75 50 25 20 25-30 0 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 Water flow rate [l/s] Input power 700 675 650 20-25-30 625 600 [ka] 575 550 525 500 475 450 425 400 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 Water flow rate [l/s]

14 Dimensions Dimensions AQH 20-30 DCI I L Top view Side view 149 200 30 703 713 766 813 1625 Ø30 Ø30 E 35 1408 27 H 538 Top view 457 510 A D C 18 1441 1477 B F G NOTES A Water inlet ø 1 1/2 gas male B Water outlet ø 1 1/2 gas male C Auxiliary lines D Electrical power supply E Sight glass inspection F High pressure tap G Low pressure tap H Gauge kit (optional) I Main switch L Control keypad/display

Dimensions 15 Dimensions external hydrokit for AQH 20-30 DCI A Front view 43 Side view C B 390 186 92 Top view 4 holes Ø9 33 434 33 62.5 1352 62.5 1477 500 NOTES A Water inlet ø 1 1/2 gas male B Water outlet ø 1 1/2 gas male C Tank fill ø 1/2 gas male Dimensions in mm.

16 Clearences Clearences AQH 20-30 DCI R410A 200 mm 200 mm 200 mm 400 mm 800 mm

Notes 17 Notes

18 Notes Notes

Systemair AC srl Via XXV Aprile, 29 20825 Barlassina (MB) Italy Tel. +39 0362 680 1 Fax +39 0362 680 693 infoac@systemair.it www.systemair.com Systemair AC June 2012 EDM AQHDCI410-S.1GB/06.12 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.