PAYNE Heating & ELECTRIC CONDITIONER 710A (60 Hz) Sizes 018 thru 060 Model 710A Energy-Efficient Air Conditioners incorporate innovative technology to provide quiet, reliable summer cooling performance. Built into these units are the features most desired by homeowners today including SEER ratings of at least 10.0 when used with components as designated by manufacturer. All models are listed with UL, c-ul, ARI, and CEC. FEATURES UNIT DESIGN Copper tube, enhanced sine wave, aluminum fin coil is designed for optimum heat transfer. Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. Heat pump style base pan for easy removal of water, dirt, and leaves. ELECTRICAL RANGE Units are offered in 208-230v single phase. WIDE RANGE OF SIZES Available in nominal sizes from 018 through 060 to meet the needs of residential and light commercial applications. WEATHER-PROTECTIVE CABINET Steel is protected with a galvanized coating and treated with a layer of zinc phosphate. A coat of modified polyester powder coating is then applied and baked-on, providing each unit with a hard, smooth finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting, rustresistant, quality appearance. TOTALLY ENCLOSED FAN MOTOR Means greater reliability under rain conditions and dependable performance for many years. Permanent-split-capacitor-type motors provide more economical operation. APPLICATION VERSATILITY The 710A can be combined with a wide variety of evaporator coils and blower packages to provide quiet, dependable comfort. Unit can be installed on a roof or at ground level on a slab. EXTERNAL SERVICE VALVES Both service valves are brass, front seating type with sweat connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures. EASY SERVICEABILITY One access panel provides access to electrical controls. Removal of top gives access to fan motor, compressor, and condenser coil. COMPRESSOR PROTECTION Each compressor is protected with internal temperature- and current-sensitive overloads. An internal pressure relief valve provides high-pressure protection to the refrigerant system. WARRANTY Standard 1 year on parts. Additional 4 years on compressor. Form No. PDS 710A.18.3P
NOTES: 1. Allow 30 in. clearance to service side of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55 F max 125 F. 3. Series designation is the 14th position of the unit model number. 4. Center of gravity. A 3 / 8 IN. DIA TIEDOWN KNOCKOUTS (2) PLACES IN IN DISCHARGE IN J N P DISCHARGE DISCHARGE FIELD POWER SUPPLY CONN 7 / 8 IN. DIA HOLE WITH 1 1 / 8 IN. DIA KNOCKOUT AND 1 3 / 8 IN. DIA KNOCKOUT FIELD CONTROL SUPPLY CONN 7 / 8 IN. DIA HOLE 3 / 8 IN. DIA LIQUID LINE CONN B DISCHARGE IN 2 7 / 8 C E M F D DIA VAPOR LINE CONN 1 1 / 4 A937 DIMENSIONS UNIT 710A OPER. WT. A B C D E F J M N P SERIES Lb. In. In. In. In. In. In. In. In. In. In. 018 A 112 22-1/2 21-15/16 3-3/16 5/8 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 9-3/4 024 A 121 22-1/2 23-15/16 3-3/16 5/8 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 10-3/4 030 A 127 22-1/2 25-15/16 3-3/16 3/4 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-1/4 036 A 142 22-1/2 29-15/16 3-3/16 3/4 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-3/4 042 A 169 30 23-15/16 3-1/4 7/8 23-1/2 6-1/2 10 15-1/4 16 11 018 B 103 22-1/2 21-15/16 3-3/16 5/8 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 9-3/4 024 B 115 22-1/2 23-15/16 3-3/16 5/8 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 10-3/4 030 B 125 22-1/2 27-15/16 3-3/16 3/4 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-1/2 036 B 153 22-1/2 29-15/16 3-3/16 3/4 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-3/4 042 B 175 30 23-15/16 3-1/4 7/8 23-1/2 6-1/2 10 15-1/4 16 11 048 B 172 30 27-15/16 3-1/4 7/8 23-1/2 6-1/2 10 14-1/2 16 16 060 B 199 30 39-15/16 3-1/4 7/8 23-1/2 6-1/2 10 14-1/2 16 17 036 C 125 22-1/2 25-15/16 3-3/16 3/4 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-1/4 042 C 133 22-1/2 29-15/16 3-1/4 7/8 18-1/2 4-1/16 8-3/16 12-1/8 12-1/4 11-3/4 048 C 177 30 27-15/16 3-1/4 7/8 23-1/2 6-1/2 10 14-1/2 16 16 060 C 204 30 39-15/16 3-1/4 7/8 23-1/2 6-1/2 10 14-1/2 16 17 The data in this publication is displayed for all series, however, every series may not be available from manufacturer. UNITARY CONDITIONING MANUFACTURER CERTIFIED TO ARI AS COMPLYING WITH ARI EQUIPMENT STANDARD 210 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI. 2
CHECK-FLO-RATER CHART PISTON* UNIT SIZE-SERIES IDENTIFICATION NO. 018-A, B 52 024-A, B 59 030-A, B 67 036-A, B, C 73 042-A, B, C 78 048-B, C 84 060-B 93 060-C 96 * Piston listed is for any approved coil non-capillary tube combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil. SPECIFICATIONS UNIT SIZE 018 024 030 SERIES A/B A/B A/B ELECTRICAL Unit Volts Hertz Phase 208-230 60 1 Operating Voltage Range* 197 253 Compressor Rated Load Amps 9.6 10.9 15.3 Locked Rotor Amps 49.0 61.0 75.0 Condenser Fan Motor Full Load Amps 0.5 0.5 0.8 Min Unit Ampacity for Wire Sizing 12.5 14.1 19.9 Min Wire Size (60 C/75 F Copper) AWG 14/14 14/14 14/14 Max Wire Length (60 C/75 F) (Ft) 61/58 53/50 39/37 Max Branch Circuit Fuse Size** 15 20 30 COMPRESSOR & REFRIGERANT Compressor Manufacturer Copeland/Tecumseh Type Reciprocating Temperature and Current Protection Internal Line Break Refrigerant Type and Amount R-22 3.88 R-22 4.38 R-22 4.82 Refrigerant Tubes (In. OD) Vapor and Liquid (Up to 50 Ft) 5/8 and 3/8 3/4 and 3/8 CONDENSER COIL & FAN Coil Face Area (Sq Ft) 6.5 7.2 7.9 8.7 Fan Motor HP, Type, and RPM 1/12 PSC and 1125 1/10 PSC and 1125 Volts Hertz Phase 208/230 60 1 Condenser Airflow (CFM) 1900 1900 2100 OPTIONAL EQUIPMENT Short Cycle Protector KSACY0101AAA Start Assist PTC Type KAACS0201PTC Start Assist Capacitor/Relay Type KSAHS0601AAA/KSAHS0301AAA Low-Pressure Switch KAALP0101LPS High-Pressure Switch KSAHI0101HPS Sound Hood KSASH1101COP KSASH1301TEC KSASH1101COP KSASH1301TEC KSASH1101COP KSASH1301TEC Time-Delay Relay KAATD0101TDR Low-Ambient Controller KSALA0101AAA Winter Start Control KAAWS0101AAA Evaporator Freeze Thermostat KAAFT0101AAA Crankcase Heater KAACH1001AAA Liquid Line Solenoid Valve KAALS0101LLS Coastal Filter KAACF0401SML TXV Kit (RPB) KAATX0201RPB KAATX0301RPB KAATX0401RPB TXV (Hard Shutoff) KAATX0901HSO KAATX1001HSO KAATX1101HSO Thermostat, Auto Changeover, Non-Programmable, F/ C, TSTATPPNAC01-A Thermostat, Auto Changeover, 7-Day Programmable, F/ C, TSTATPPPAC01-A Thermostat, Manual Changeover, Non-Programmable, F, HH07AT212 Outdoor Sensor TSTATBBSEN01 See notes on page 5. 3
See notes on page 5. SPECIFICATIONS Continued UNIT SIZE 036 042 SERIES A/B C A/B C ELECTRICAL Unit Volts Hertz Phase 208-230 60 1 Operating Voltage Range* 197 253 Compressor Rated Load Amps 16.1 16.7 19.0 20.5 Locked Rotor Amps 82.0 95.0 105.0 115.0 Condenser Fan Motor Full Load Amps 1.4 1.4 1.4 1.4 Min Unit Ampacity for Wire Sizing 21.5 22.3 25.2 27.0 Min Wire Size (60 C/75 F Copper) AWG 12/12 12/12 10/10 10/10 Max Wire Length (60 C/75 F) (Ft) 57/54 55/52 77/73 74/70 Max Branch Circuit Fuse Size** 30 30 35 40 COMPRESSOR & REFRIGERANT Compressor Manufacturer Copeland/Tecumseh Millennium Copeland/Tecumseh Millennium Type Reciprocating Scroll Reciprocating Scroll Temperature and Current Protection Internal Line Break Refrigerant Type and Amount R-22 5.38 R-22 4.82 R-22 5.81 R-22 5.50 Refrigerant Tubes (In. OD) Vapor and Liquid (Up to 50 Ft) 3/4 and 3/8 3/4 and 3/8 7/8 and 3/8 7/8 and 3/8 CONDENSER COIL & FAN Coil Face Area (Sq Ft) 9.4 7.9 10.7 9.4 Fan Motor HP, Type, and RPM 1/4 PSC and 1125 1/4 PSC and 1125 1/4 PSC and 1125 1/4 PSC and 1125 Volts Hertz Phase 208/230 60 1 Condenser Airflow (CFM) 2500 2500 3000 2500 OPTIONAL EQUIPMENT Short Cycle Protector KSACY0101AAA Standard KSACY0101AAA Standard Start Assist PTC Type KAACS0201PTC KAAC60201PTC KAACS0201PTC KAACS0201PTC Start Assist Capacitor/Relay Type KSAHS0601AAA/ KSAHS0301AAA KSAHS0401AAA KSAHS0701AAA/ KSAHS0301AAA KSAHS0401AAA Low-Pressure Switch KAALP0101LPS High-Pressure Switch KSAHI0101HPS Sound Hood KSASH1101COP KSASH0801TEC KSASH0601COP N/A Time-Delay Relay KAATD0101TDR Low-Ambient Controller KSALA0101AAA Winter Start Control KAAWS0101AAA Evaporator Freeze Thermostat KAAFT0101AAA Crankcase Heater KAACH1001AAA KAACH1201AAA KAACH1001AAA KAACH1201AAA Liquid Line Solenoid Valve KAALS0101LLS Coastal Filter KAACF0401SML KAACF0501LRG KAACF0401SML TXV Kit (RPB) KAATX0501RPB KAATX0501RPB KAATX0501RPB KAATX0501RPB TXV (Hard Shutoff) KAATX1201HSO KAATX1201HSO KAATX1201HSO KAATX1201HSO Thermostat, Auto Changeover, Non-Programmable, F/ C, TSTATPPNAC01-A Thermostat, Auto Changeover, 7-Day Programmable, F/ C, TSTATPPPAC01-A Thermostat, Manual Changeover, Non-Programmable, F, HH07AT212 Outdoor Sensor TSTATBBSEN01 4
SPECIFICATIONS Continued UNIT SIZE 048 060 SERIES B C B C ELECTRICAL Unit Volts Hertz Phase Operating Voltage Range* Compressor Rated Load Amps 24.4 25 28.9 30.1 Locked Rotor Amps 140.0 132.2 165.0 175.0 Condenser Fan Motor Full Load Amps 1.4 1.4 Min Unit Ampacity for Wire Sizing 31.9 32.7 37.5 39.0 Min Wire Size (60 C/75 F Copper) AWG 8/10 8/8 Max Wire Length (60 C/75 F) (Ft) 97/59 94/58 82/78 80/76 Max Branch Circuit Fuse Size** 50 50 60 COMPRESSOR & REFRIGERANT Compressor Manufacturer Millennium Copeland Millennium Copeland Type Scroll Temperature and Current Protection Internal Line Break Refrigerant Type and Amount R-22 6.38 R-22 6.50 R-22 7.88 R-22 8.00 Refrigerant Tubes (In. OD) Vapor and Liquid (Up to 50 Ft) 7/8 and 3/8 7/8 and 3/8 1-1/8 and 3/8 CONDENSER COIL & FAN Coil Face Area (Sq Ft) 12.8 19.3 19.3 Fan Motor HP, Type, and RPM 1/4 PSC and 1125 Volts Hertz Phase 208/230 60 1 Condenser Airflow (CFM) 3300 OPTIONAL EQUIPMENT Short Cycle Protector Standard Start Assist PTC Type KAACS0201PTC Start Assist Capacitor/Relay Type KSAHS0801AAA Low-Pressure Switch KAALP0101LPS High-Pressure Switch KSAHI0101HPS Sound Hood N/A Time-Delay Relay KAATD0101TDR Low-Ambient Controller KSALA0101AAA Winter Start Control KAAWS0101AAA Evaporator Freeze Thermostat KAAFT0101AAA Crankcase Heater KAACH1201AAA Liquid Line Solenoid Valve KAALS0101LLS Coastal Filter KAACF0501LRG TXV Kit (RPB) KAATX0601RPB KAATX0701RPB TXV (Hard Shutoff) KAATX1301HSO KAATX1401HSO Thermostat, Auto Changeover, Non-Programmable, F/ C, TSTATPPNAC01-A Thermostat, Auto Changeover, 7-Day Programmable, F/ C, TSTATPPPAC01-A Thermostat, Manual Changeover, Non-Programmable, F, HH07AT212 Outdoor Sensor TSTATBBSEN01 * Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure. If wire is applied at ambient greater than 30 C (86 F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60 C (140 F) conductors, per the NEC (ANSI/NFPA 70) Article 336-36. Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time-delay fuse. Start assist capacitor and relay required when using liquid solenoid valve or hard shutoff TXV (except 048 and 060 Sizes). Do not use hard shutoff TXV with liquid solenoid valve. N/A Not applicable in this application. NOTE: 1. Control circuit is 24v on all units and requires external power source. 2. All motors/compressors contain internal overload protection. 3. Copper wire must be used from service disconnect to unit. 5
RATINGS AND PERFORMANCE UNIT SIZE-SERIES 018-A,B 024-A,B 030-A,B 036-A,B,C See notes on page 7. INDOOR MODEL TOT. CAP. BTUH FACTORY SUPPLIED ENHANCE- MENT STANDARD RATING FIELD-SUPPLIED ACCESSORY TDR TXV CC5A/CD5A/CD5BA018* 17,400 NONE 10.10 10.30 10.30 CD3(A,B)A018 17,000 NONE 10.00 10.20 10.20 CC5A/CD5A/CD5BA024 17,600 NONE 10.00 10.50 10.50 CC5A/CD5A/CD5BW024 17,600 NONE 10.00 10.50 10.50 CD3(A,B)A024 17,600 NONE 10.00 10.50 10.50 CE3AA024 17,800 NONE 10.00 10.50 10.50 CF5AA024 17,800 NONE 10.00 10.50 10.50 CG5AA024 17,800 TXV 10.00 10.50 F(A,B)4ANF018 16,800 TDR 10.00 10.00 F(A,B)4ANF024 17,600 TDR 10.50 10.50 FC4BNF024 17,600 TDR & TXV 10.50 FC4BNF033 18,000 TDR & TXV 11.00 FD3ANA018 17,100 NONE 10.00 10.20 10.20 FD3ANA024 17,600 NONE 10.00 10.50 10.50 FF1(A,B)NA018 17,200 TDR 10.50 10.50 FF1(A,B)NA024 17,600 TDR 10.50 10.50 FG3AAA024 17,500 NONE 10.00 10.20 10.20 FK4CNF001 17,500 TDR & TXV 12.00 FK4CNF002 17,500 TDR & TXV 12.00 CC5A/CD5A/CD5BA024* 22,200 NONE 10.00 10.30 10.30 CC5A/CDBA/CD5BW024 22,200 NONE 10.00 10.30 10.30 CD3(A,B)A024 22,200 NONE 10.00 10.20 10.20 CC5A/CD5A/CD5BA030 22,600 NONE 10.00 10.20 10.20 CC5A/CD5A/CD5BW030 22,600 NONE 10.00 10.20 10.20 CD3(A,B)A030 22,600 NONE 10.00 10.50 10.50 CE3AA024 22,400 NONE 10.00 10.50 10.50 CE3AA030 22,600 NONE 10.00 10.50 10.50 CF5AA024 22,200 NONE 10.00 10.20 10.20 CG5AA024 22,200 TXV 10.00 10.20 F(A,B)4ANF024 22,200 TDR 10.00 10.00 F(A,B)4ANF030 22,400 TDR 10.50 10.50 FC4BNF024 22,200 TDR & TXV 10.00 FC4BNF033 22,600 TDR & TXV 10.50 FC4BNF030 22,400 TDR & TXV 10.50 FD3ANA024 21,600 NONE 10.00 10.20 10.20 FD3ANA030 22,400 NONE 10.00 10.50 10.50 FF1(A,B)NA024 22,200 TDR 10.50 10.50 FF1(A,B)NA030 22,400 TDR 10.50 10.50 FG3AAA024 21,400 NONE 10.00 10.20 10.20 FK4CNF001 23,000 TDR & TXV 11.50 FK4CNF002 23,000 TDR & TXV 11.50 FK4CNF003 23,600 TDR & TXV 11.50 CC5A/CD5A/CD5BA030* 28,200 NONE 10.10 10.20 10.20 CC5A/CD5A/CD5BW030 28,000 NONE 10.00 10.10 10.10 CD3(A,B)A030 28,000 NONE 10.00 10.10 10.10 CC5A/CD5A/CD5BA036 29,000 NONE 10.00 10.10 10.10 CD5A/CD5BW036 29,000 NONE 10.00 10.10 10.10 CD3(A,B)A036 29,000 NONE 10.00 10.50 10.50 CE3AA030 27,800 NONE 10.00 10.50 10.50 CE3AA036 28,600 NONE 10.00 10.50 10.50 CF5AA036 28,800 NONE 10.00 10.10 10.10 CG5AA036 28,800 TXV 10.00 10.10 F(A,B)4ANF030 27,600 TDR 10.00 10.00 F(A,B)4ANF036 28,200 TDR 10.20 10.20 FC4BNF030 27,600 TDR & TXV 10.00 FC4BNF036 28,200 TDR & TXV 10.20 FC4BNF033 28,600 TDR & TXV 10.50 FD3ANA030 27,800 NONE 10.00 10.20 10.20 FF1(A,B)NA030 28,000 TDR 10.20 10.20 FG3AAA036 28,000 NONE 10.00 10.20 10.20 FK4CNF001 29,000 TDR & TXV 10.50 FK4CNF002 29,000 TDR & TXV 10.50 FK4CNF003 29,000 TDR & TXV 11.00 FK4CNF005 30,000 TDR & TXV 11.50 CC5A/CD5A/CD5BA036* 33,800 NONE 10.00 10.30 10.30 CD5A/CD5BW036 33,800 NONE 10.00 10.30 10.30 CD3(A,B)A036 33,800 NONE 10.00 10.30 10.30 CC5A/CD5A/CD5BA042 33,800 NONE 10.00 10.30 10.30 CD3(A,B)A042 33,800 NONE 10.00 10.30 10.30 CC5A/CD5A/CD5BW042 33,400 NONE 10.00 10.20 10.20 CE3AA036 33,400 NONE 10.00 10.20 10.20 CE3AA042 33,600 NONE 10.00 10.30 10.30 CF5AA036 33,600 NONE 10.00 10.20 10.20 CG5AA036 33,600 TXV 10.10 10.20 F(A,B)4ANF036 33,200 TDR 10.00 10.00 F(A,B)4AN(F,B)042 33,800 TDR 10.20 10.20 FC4BNF036 33,000 TDR & TXV 10.00 FC4BNF033 33,400 TDR & TXV 10.20 FC4BN(F,B)042 33,800 TDR & TXV 10.20 FC4BNF038 35,000 TDR & TXV 10.50 FC4BNB054 35,600 TDR & TXV 10.50 FG3AAA036 33,000 NONE 10.00 10.20 10.20 SOUND RATING W/O ACCESSORY SOUND BLANKET (dba) SOUND RATING W/ACCESSORY SOUND BLANKET (dba) 80 76 80 76 81 76 83 76 6
UNIT SIZE-SERIES 036-A,B,C 042-A,B,C 048-B,C 060-B,C INDOOR MODEL RATINGS AND PERFORMANCE Continued TOT. CAP. BTUH FACTORY SUPPLIED ENHANCE- MENT STANDARD RATING FIELD-SUPPLIED ACCESSORY TDR TXV FK4CNB006 35,000 TDR & TXV 11.00 FK4CNF001 33,000 TDR & TXV 10.50 FK4CNF002 33,000 TDR & TXV 10.50 FK4CNF003 33,600 TDR & TXV 10.50 FK4CNF005 35,000 TDR & TXV 11.00 CC5A/CD5A/CD5BA042* 40,000 NONE 10.00 10.30 10.30 CD3(A,B)A042 40,000 NONE 10.00 10.30 10.30 CC5A/CD5A/CD5BW042 40,000 NONE 10.00 10.30 10.30 CD5A/CD5BA048 40,500 NONE 10.00 10.30 10.30 CD3(A,B)A048 40,500 NONE 10.00 10.30 10.30 CC5A/CD5A/CD5BC048 40,000 NONE 10.00 10.00 CC5A/CD5A/CD5BW048 40,500 NONE 10.00 10.30 10.30 CE3AA042 40,000 NONE 10.00 10.30 10.30 CE3AA048 40,500 NONE 10.00 10.50 10.50 CF5AA048 40,500 NONE 10.00 10.30 10.30 CG5AA048 40,500 TXV 10.00 10.30 F(A,B)4AN(F,B)042 40,000 TDR 10.00 10.00 F(A,B)4AN(F,B)048 41,000 TDR 10.50 10.50 FC4BN(F,B)042 40,000 TDR & TXV 10.00 FC4BNF038 40,500 TDR & TXV 10.50 FC4BNB054 41,500 TDR & TXV 10.50 FC4BN(F,B)048 41,000 TDR & TXV 10.30 FG3AAA048 40,000 NONE 10.00 10.20 10.20 FK4CNB006 42,000 TDR & TXV 11.50 FK4CNF003 40,000 TDR & TXV 11.00 FK4CNF005 41,000 TDR & TXV 11.00 CD5A/CD5BA048* 46,000 NONE 10.00 10.40 10.40 CD3(A,B)A048 46,000 NONE 10.00 10.40 10.40 CC5A/CD5A/CD5BC048 45,500 NONE 10.00 10.40 10.40 CC5A/CD5A/CD5BW048 46,000 NONE 10.00 10.40 10.40 CC5A/CD5A/CD5BA060 46,500 NONE 10.20 10.50 10.50 CD3(A,B)A060 46,500 NONE 10.20 10.50 10.50 CC5A/CD5A/CD5BW060 47,500 NONE 10.20 10.50 10.50 CE3AA048 46,500 NONE 10.20 10.50 10.50 CE3AA060 47,500 NONE 10.20 10.50 10.50 CF5AA048 46,500 NONE 10.20 10.50 10.50 CG5AA048 46,500 TXV 10.40 F(A,B)4AN(F,B)048 47,000 TDR 10.40 10.40 F(A,B)4AN(F,B)060 47,500 TDR 10.50 10.50 FB4ANB070 48,000 TDR 10.50 10.50 FC4BN(F,B)048 47,000 TDR & TXV 10.40 FC4BNB070 48,000 TDR & TXV 10.50 FC4BN(F,B)060 47,500 TDR & TXV 10.50 FC4BNB054 47,000 TDR & TXV 10.50 FG3AAA048 45,000 NONE 10.00 10.40 10.40 FG3AAA060 47,000 NONE 10.20 10.50 10.50 FK4CNB006 48,000 TDR & TXV 11.00 FK4CNF005 47,500 TDR & TXV 11.00 CC5A/CD5A/CD5BW060* 57,000 NONE 10.00 10.20 10.20 CC5A/CD5A/CD5BA060 56,000 NONE 10.00 10.10 10.10 CD3(A,B)A060 56,000 NONE 10.00 10.10 10.10 CE3AA060 57,000 NONE 10.00 10.20 10.20 F(A,B)4AN(F,B)060 57,500 TDR 10.00 10.00 FB4ANB070 58,000 TDR 10.30 10.30 FC4BNB070 58,000 TDR & TXV 10.30 FC4BN(F,B)060 57,500 TDR & TXV 10.00 FC4BNB054 58,000 TDR & TXV 10.50 FG3AAA060 57,000 NONE 10.00 10.10 10.10 FK4BNB006 58,000 TDR & TXV 10.50 FK4CNB006 58,000 TDR & TXV 10.50 SOUND RATING W/O ACCESSORY SOUND BLANKET (dba) SOUND RATING W/ACCESSORY SOUND BLANKET (dba) 83 76 84 N/A 82 N/A 82 N/A * Tested Combination TDR is on all furnaces with the exception of 394HAD. N/A Not Applicable NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included. 2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures. 3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan-coil or furnace-coil literature. 4. Minimum outdoor operating ambient in cooling mode is 55 F (12.8 C), maximum 115 F (46.1 C). 5. The dashes ( ) appearing in the SEER WITH ACCESSORY TDR column indicate no improvement in efficiency due to time-delay function built into unit as manufactured (see table). 7
EVAPORATOR CFM EWB See notes on page 11. DETAILED COOLING CAPACITIES* CONDENSER ENTERING TEMPERATURES F 75 85 95 105 115 Sens Kw** Sens Kw** Sens Kw** Sens Kw** Sens 710A018-A,B Outdoor Section With CC5A/CD5A/CD5BA018 Section Kw** 72 21.2 10.1 1.68 20.0 9.60 1.81 18.8 9.15 1.94 17.6 8.71 2.06 16.5 8.26 2.17 525 67 19.2 17.3 12.4 14.6 1.65 1. 18.1 16.3 11.9 14.1 1.77 1.72 17.0 15.3 11.4 13.6 1.88 1.83 15.9 14.3 10.9 13.1 1.99 1.93 14.8 13.2 10.5 12.5 2.09 2.02 57 15.9 15.9 1.58 15.2 15.2 1.70 14.4 14.4 1.80 13.6 13.6 1.90 12.9 12.9 1.99 72 21.6 10.5 1.72 20.5 10.0 1.86 19.2 9.54 1.99 18.0 9.09 2.11 16.8 8.63 2.22 600 67 19.7 17.8 13.0 15.5 1.69 1.66 18.5 16.7 12.5 15.0 1.81 1.77 17.4 15.6 12.1 14.5 1.93 1.87 16.2 14.6 11.6 13.9 2.04 1.97 15.1 13.5 11.1 13.3 2.14 2.06 57 16.6 16.6 1.64 15.8 15.8 1.74 15.0 15.0 1.85 14.2 14.2 1.96 13.4 13.4 2.05 72 22.1 10.8 1.75 20.8 10.4 1.90 19.5 9.90 2.02 18.3 9.45 2.15 17.0 8.98 2.26 675 67 20.0 18.1 13.7 16.4 1.72 1.69 18.9 17.0 13.2 15.8 1.85 1.81 17.7 15.9 12.7 15.3 1.97 1.92 16.5 14.9 12.2 14.6 2.08 2.01 15.3 13.8 11.7 13.8 2.18 2.11 57 17.2 17.2 1.67 16.4 16.4 1.79 15.6 15.6 1.90 14.7 14.7 2.01 13.8 13.8 2.11 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ 018 1.00 1.00 FC4BNF 024 1.01 1.02 CD5BA 024 1.01 1.01 033 1.03 1.05 CC5A/CD5A/ FD3ANA 018 0.98 1.03 CD5BW 024 1.01 1.01 024 1.01 1.00 CD3(A,B)A 018 0.98 1.00 FF1(A,B)NA 018 0.99 0.98 024 1.01 1.01 024 1.01 1.00 CE3AA 024 1.02 1.01 FG3AAA 024 1.01 1.01 CF5AA 024 1.02 1.01 FK4CNF 001 1.01 0.94 CG5AA 024 1.02 1.01 002 1.01 0.94 F(A,B)4ANF 018 0.97 0.99 024 1.01 1.02 710A024-A,B Outdoor Section With CC5A/CD5A/CD5BA024 Section 72 26.7 12.9 2.20 25.3 12.4 2.34 23.9 11.9 2.48 22.5 11.4 2. 21.1 10.9 2.74 700 67 24.3 22.1 16.2 19.3 2.14 2.09 23.0 20.9 15.6 18.7 2.27 2.21 21.7 19.6 15.1 18.1 2.40 2.33 20.4 18.4 14.5 17.5 2.52 2.44 19.0 17.1 14.0 16.8 2.63 2.54 57 20.8 20.8 2.06 19.9 19.9 2.18 18.9 18.9 2.29 17.9 17.9 2.41 16.9 16.9 2.52 72 27.1 13.5 2.25 25.8 13.0 2.40 24.4 12.5 2.54 22.9 11.9 2.67 21.4 11.4 2.80 800 67 24.8 22.6 17.1 20.6 2.20 2.14 23.5 21.4 16.6 20.0 2.33 2.27 22.2 20.1 16.0 19.3 2.47 2.38 20.8 18.8 15.5 18.5 2.58 2.50 19.3 17.6 14.9 17.6 2.69 2.60 57 21.7 21.7 2.12 20.7 20.7 2.24 19.7 19.7 2.37 18.6 18.6 2.49 17.6 17.6 2.60 72 27.6 14.0 2.30 26.1 13.5 2.45 24.7 13.0 2.59 23.1 12.4 2.73 21.6 11.9 2.85 900 67 25.3 23.0 18.0 21.8 2.25 2.20 23.9 21.7 17.5 21.1 2.38 2.32 22.5 20.4 16.9 20.2 2.52 2.44 21.0 19.2 16.3 19.2 2.64 2.56 19.6 18.1 15.8 18.1 2.75 2.67 57 22.4 22.4 2.18 21.4 21.4 2.31 20.3 20.3 2.44 19.2 19.2 2.56 18.1 18.1 2.67 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ 024 1.00 1.00 FC4BNF 024 1.00 1.00 CD5BA 030 1.02 1.00 030 1.01 1.00 CD3(A,B)A 024 1.00 1.00 033 1.02 1.02 030 1.02 1.00 FD3ANA 024 0.97 0.97 CC5A/CD5A/ 024 1.00 1.00 030 1.01 1.01 CD5BW 030 1.02 1.00 FF1(A,B)NA 024 1.00 1.00 CE3AA 024 1.01 1.00 030 1.01 1.02 030 1.02 1.01 FG3AAA 024 0.96 1.00 CF5AA 024 1.00 1.00 FK4CNF 001 1.04 0.94 CG5AA 024 1.00 1.00 002 1.04 0.95 F(A,B)4ANF 024 1.00 1.00 003 1.06 0.93 030 1.01 1.00 8
EVAPORATOR CFM EWB See notes on page 11. DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING TEMPERATURES F 75 85 95 105 115 Sens Kw** Sens Kw** Sens Kw** Sens Kw** Sens 710A030-A,B Outdoor Section With CC5A/CD5A/CD5BA030 Section Kw** 72 34.0 16.4 2.82 32.2 15.7 3.00 30.4 15.1 3.17 28.6 14.4 3.30 26.8 13.7 3.51 875 67 31.0 28.1 20.5 24.4 2.73 2.64 29.3 26.6 19.8 23.7 2.90 2.80 27.7 25.0 19.1 22.9 3.06 2.95 26.0 23.5 18.4 22.1 3.20 3.10 24.3 22.0 17.7 21.2 3.38 3.25 57 26.4 26.4 2.59 25.2 25.2 2.75 24.0 24.0 2.91 22.8 22.8 3.00 21.6 21.6 3.23 72 34.6 17.1 2.89 32.8 16.4 3.07 31.0 15.7 3.24 29.1 15.0 3.40 27.2 14.4 3.59 1000 67 31.6 28.7 21.7 26.0 2.80 2.71 29.9 27.2 20.9 25.2 2.97 2.87 28.2 25.6 20.2 24.4 3.13 3.02 26.5 24.0 19.5 23.4 3.20 3.10 24.7 22.5 18.8 22.4 3.45 3.33 57 27.5 27.5 2.67 26.2 26.2 2.84 25.0 25.0 3.00 23.7 23.7 3.10 22.4 22.4 3.33 72 35.2 17.7 2.95 33.3 17.0 3.13 31.4 16.3 3.31 29.4 15.7 3.40 27.5 15.0 3.65 1125 67 32.1 29.2 22.8 27.4 2.86 2.78 30.4 27.6 22.0 26.6 3.03 2.94 28.6 26.0 21.3 25.6 3.20 3.09 26.8 24.5 20.6 24.4 3.30 3.20 25.0 23.1 19.9 23.1 3.52 3.41 57 28.4 28.4 2.75 27.1 27.1 2.92 25.8 25.8 3.08 24.4 24.4 3.20 23.1 23.1 3.42 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ 030 1.00 1.00 F(A,B)4ANF 030 0.98 1.00 CD5BA 036 1.03 1.01 036 1.00 1.02 CC5A/CD5A FC4BNF 030 0.98 1.00 CD5BW 030 0.99 1.00 033 1.01 1.01 CD5A/CD5BW 036 1.03 1.01 036 1.00 1.02 CD3(A,B)A 030 0.99 1.00 FD3ANA 030 0.99 1.00 036 1.03 1.01 FF1(A,B)NA 030 0.99 1.01 CE3AA 030 0.99 1.00 FG3AAA 036 0.99 1.01 036 1.01 1.01 FK4CNF 001 1.03 0.95 CF5AA 036 1.02 1.01 002 1.03 0.95 CG5AA 036 1.02 1.01 003 1.06 0.95 710A036-A,B,C Outdoor Section With CC5A/CD5A/CD5BA036 Section 72 39.6 19.4 3.04 38.1 18.9 3.40 36.4 18.3 3.77 34.6 17.6 4.15 32.6 16.9 4.53 1050 67 36.3 33.1 24.6 29.5 3.00 2.96 34.8 31.7 24.0 28.8 3.34 3.29 33.2 30.1 23.3 28.0 3.70 3.63 31.4 28.5 22.6 27.2 4.06 3.97 29.5 26.7 21.8 26.1 4.41 4.29 57 31.6 31.6 2.90 30.5 30.5 3.23 29.3 29.3 3.57 27.9 27.9 3.91 26.4 26.4 4.29 72 40.2 20.3 3.10 38.7 19.7 3.46 37.0 19.1 3.83 35.1 18.5 4.21 33.1 17.7 4.59 1200 67 36.9 33.8 26.1 31.5 3.05 3.01 35.5 32.4 25.5 30.8 3.40 3.34 33.8 30.8 24.8 29.9 3.76 3.69 32.0 29.1 24.1 28.9 4.12 4.03 30.0 27.4 23.3 27.4 4.48 4.37 57 32.8 32.8 2.97 31.7 31.7 3.30 30.4 30.4 3.64 29.0 29.0 3.99 27.4 27.4 4.38 72 40.7 21.1 3.15 39.2 20.5 3.51 37.5 19.9 3.88 35.6 19.3 4.26 33.5 18.5 4.65 1350 67 37.4 34.4 27.5 33.2 3.10 3.06 35.9 32.9 26.9 32.4 3.45 3.40 34.3 31.4 26.2 31.3 3.81 3.74 32.4 29.9 25.5 29.9 4.17 4.10 30.4 28.3 24.7 28.3 4.53 4.46 57 33.9 33.9 3.06 32.7 32.7 3.36 31.4 31.4 3.71 29.9 29.9 4.06 28.3 28.3 4.47 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ 036 1.00 1.00 FC4BNF 033 0.99 1.01 CD5BA 042 1.00 1.00 036 0.98 1.01 CD5A/CD5BW 036 1.00 1.00 038 1.04 1.03 CC5A/CD5A/ 054 1.05 1.01 CD5BW 042 0.99 1.00 FG3AAA 036 0.98 0.99 CE3AA 036 0.99 1.00 FK4CNF 001 0.98 0.96 042 0.99 1.00 002 0.98 0.96 CF5AA 036 0.99 1.00 003 0.99 0.94 CG5AA 036 0.99 1.00 005 1.04 0.95 F(A,B)4ANF 036 0.98 1.01 006 1.04 0.95 F(A,B)4AN(F,B) 042 1.00 1.01 9
EVAPORATOR CFM EWB See notes on page 11. DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING TEMPERATURES F 75 85 95 105 115 Sens Kw** Sens Kw** Sens Kw** Sens Kw** Sens 710A042-A, B, C Outdoor Section With CC5A/CD5AA042 Section Kw** 72 46.4 22.7 3.72 44.6 22.1 4.09 42.7 21.3 4.46 40.6 20.6 4.85 38.4 19.8 5.23 1225 67 42.9 39.5 28.8 34.8 3.64 3.57 41.2 38.0 28.1 34.0 3.99 3.91 39.4 36.3 27.4 33.1 4.36 4.25 37.5 34.5 26.6 32.2 4.72 4.59 35.5 32.6 25.7 31.2 5.08 4.93 57 37.4 37.4 3.50 36.2 36.2 3.84 34.8 34.8 4.18 33.4 33.4 4.53 31.9 31.9 4.88 72 47.1 23.7 3.80 45.2 23.0 4.17 43.2 22.3 4.55 41.1 21.5 4.94 38.8 20.7 5.33 1400 67 43.7 40.3 30.5 37.0 3.73 3.65 41.9 38.6 29.8 36.2 4.08 3.99 40.0 36.9 29.0 35.2 4.44 4.34 38.0 35.1 28.2 34.2 4.81 4.69 35.9 33.2 27.4 33.0 5.18 5.04 57 38.8 38.8 3.60 37.5 37.5 3.95 36.1 36.1 4.30 34.6 34.6 4.65 32.9 32.9 5.02 72 47.7 24.6 3.88 45.7 23.9 4.25 43.6 23.1 4.63 41.4 22.3 5.02 39.1 21.5 5.41 1575 67 44.2 40.9 32.1 39.0 3.80 3.73 42.4 39.2 31.4 38.1 4.16 4.08 40.4 37.5 30.6 37.0 4.53 4.43 38.4 35.6 29.8 35.6 4.90 4.78 36.2 33.9 28.9 33.9 5.26 5.15 57 40.0 40.0 3.70 38.6 38.6 4.04 37.1 37.1 4.40 35.5 35.5 4.77 33.8 33.8 5.14 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ CF5AA 048 1.01 1.00 CD5BA 042 1.00 1.00 CG5AA 048 1.01 1.00 CC5A/CD5A/ F(A,B)4AN(F,B) 042 1.00 1.01 CD5BW 042 1.00 1.00 048 1.02 1.02 CD3(A,B)A 042 1.00 1.00 FC4BN(F,B) 042 1.00 1.01 048 1.01 1.00 048 1.02 1.02 CD5A/CD5BA 048 1.01 1.00 FC4BNF 038 1.01 1.03 CC5A/CD5A/ FC4BNB 054 1.04 1.01 CD5BC 048 1.00 1.00 FG3AAA 048 1.00 1.00 CC5A/CD5A/ FK4CNF 003 1.00 0.95 CD5BW 048 1.01 1.00 005 1.02 0.97 CE3AA 042 1.00 1.00 006 1.05 0.96 048 1.01 1.00 710A048-B, C Outdoor Section With CC5A/CD5A/CD5BA048 Section 72 52.9 25.8 4.26 51.0 25.1 4.65 49.0 24.4 5.08 47.1 23.7 5.58 45.2 23.0 6.12 1400 67 49.0 45.2 32.7 39.5 4.21 4.16 47.2 43.5 32.0 38.7 4.59 4.54 45.3 41.8 31.2 37.9 5.02 4.97 43.4 40.0 30.4 37.0 5.49 5.43 41.5 38.0 29.6 36.0 6.03 5.94 57 42.7 42.7 4.12 41.5 41.5 4.51 40.1 40.1 4.94 38.7 38.7 5.41 37.1 37.1 5.92 72 53.7 26.9 4.36 51.7 26.1 4.74 49.9 25.5 5.19 48.0 24.8 5.69 45.7 24.0 6.21 1600 67 49.8 45.9 34.6 42.0 4.30 4.24 48.0 44.3 33.8 41.1 4.68 4.63 46.0 42.5 33.0 40.2 5.11 5.06 44.0 40.6 32.2 39.2 5.58 5.52 42.0 38.6 31.4 38.0 6.12 6.03 57 44.3 44.3 4.22 42.9 42.9 4.61 41.5 41.5 5.04 40.0 40.0 5.51 38.3 38.3 6.03 72 54.3 27.8 4.44 52.2 27.1 4.83 50.6 26.5 5.30 48.4 25.7 5.77 46.0 24.9 6.30 1800 67 50.4 46.6 36.3 44.2 4.38 4.33 48.5 44.8 35.6 43.3 4.77 4.71 46.5 43.0 34.8 42.2 5.20 5.14 44.6 41.2 34.0 40.9 5.69 5.61 42.4 39.3 33.2 39.3 6.20 6.12 57 45.5 45.5 4.32 44.1 44.1 4.71 42.6 42.6 5.14 41.0 41.0 5.61 39.3 39.3 6.13 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CD5A/CD5BA 048 1.00 1.00 CG5AA 048 1.01 0.99 CC5A/CD5A/ F(A,B)4AN(F,B) 048 1.02 1.02 CD5BA 060 1.01 1.00 060 1.03 1.04 CC5A/CD5A/ FB4ANB 070 1.04 1.03 CD5BC 048 0.99 0.99 FC4BN(F,B) 048 1.02 1.02 CC5A/CD5A/ 048 1.00 1.00 060 1.03 1.04 CD5BW 060 1.03 1.01 FC4BNB 054 1.04 0.98 CD3(A,B)A 048 1.00 1.00 070 1.04 1.03 060 1.01 1.00 FG3AAA 048 1.00 1.00 CE3AA 048 1.01 1.00 060 1.02 1.01 060 1.03 1.01 FK4CNB 006 1.04 0.97 CF5AA 048 1.01 0.99 FK4CNF 005 1.03 0.97 10
EVAPORATOR CFM EWB DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING TEMPERATURES F 75 85 95 105 115 Sens Kw** Sens Kw** Sens Kw** Sens Kw** Sens 710A060-B, C Outdoor Section With CC5A/CD5A/CD5BW060 Section Kw** 72 66.2 32.4 5.35 63.5 31.4 5.83 60.6 30.4 6.35 57.9 29.4 6.90 55.2 28.4 7.53 1750 67 61.4 56.8 41.3 49.9 5.24 5.14 59.0 54.5 40.3 48.8 5.71 5.59 56.3 52.1 39.1 47.6 6.21 6.08 53.8 49.8 38.1 46.5 6.70 6.60 51.3 47.5 37.1 45.3 7.35 7.20 57 53.9 53.9 5.08 52.1 52.1 5.53 50.4 50.4 6.03 48.7 48.7 6.50 46.9 46.9 7.17 72 67.1 33.7 5.47 64.3 32.7 5.95 61.3 31.6 6.47 58.6 30.6 7.00 55.6 29.6 7.65 2000 67.3 57.7 43.6 53.0 5.36 5.26 59.8 55.3 42.5 51.8 5.83 5.71 57.0 52.8 41.4 50.5 6.33 6.20 54.5 50.5 40.4 49.2 6.80 6.70 51.8 48.1 39.3 47.7 7.49 7.33 57 55.8 55.8 5.22 53.9 53.9 5.67 52.1 52.1 6.18 50.2 50.2 6.70 48.0 48.0 7.32 72 67.7 34.9 5.58 64.9 33.9 6.06 61.8 32.8 6.58 59.0 31.8 7.10 56.0 30.8 7.76 2250 67 63.0 58.4 45.8 55.8 5.47 5.37 60.4 56.0 44.7 54.5 5.94 5.83 57.5 53.4 43.5 52.9 6.45 6.32 54.9 51.2 42.5 51.2 7.00 6.80 52.2 49.1 41.5 49.1 7.60 7.47 57 57.3 57.3 5.34 55.3 55.3 5.81 53.5 53.5 6.32 51.5 51.5 6.80 48.8 48.8 7.46 Multipliers for Determining the Performance With Other Sections Section Size Power Section Size Power CC5A/CD5A/ FB4ANB 070 1.02 1.02 CD5BA 060 0.98 0.98 FC4BNB 054 1.02 0.99 CC5A/CD5A/ 070 1.02 1.02 CD5BW 060 1.00 1.00 FC4BN(F,B) 060 1.01 1.04 CD3(A,B)A 060 0.98 0.98 FG3AAA 060 1.00 1.00 CE3AA 060 1.00 1.00 FK4CNB 006 1.02 0.98 F(A,B)4AN(F,B) 060 1.01 1.04 * Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. and sensible capacities are net capacities. Blower motor heat has been subtracted. Sensible capacities shown are based on 80 F (27 C) entering air at the indoor coil. For sensible capacities at other than 80 F (27 C), deduct 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80 F (27 C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80 F (27 C). When the required data falls between the published data, interpolation may be performed. ** Unit kw is total of indoor and outdoor unit kilowatts. SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55 F (12.8 C). 3. Maximum outdoor operating air temperature is 125 F (51.7 C). 4. For reliable operation, unit should be level in all horizontal planes. 5. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 6 and 7 following.) 6. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor. 7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft. 8. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical rise to the valve connections at the unit. 9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. 11
ACCESSORY DESCRIPTION AND USAGE 1. Coastal Filter A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. SUGGESTED USE: In geographic areas where salt damage could occur. 2. Compressor Start Assist Capacitor/Relay Type Start capacitor and start relay gives hard boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations where outdoor design temperature exceeds 105 F (40.6 C). Replacement installations with hard shutoff expansion valve on indoor coil. 3. Compressor Start Assist PTC Type Solid-state electrical device which gives a soft boost to the compressor at each start-up. SUGGESTED USE: Installations with marginal power supply. Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil. 4. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft. When unit will be operated below 55 F (12.8 C) outdoor air temperature. (Use with low-ambient controller.) All commercial installations. 5. Cycle Protector Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including normal room thermostat cycling. SUGGESTED USE: Installations in areas where power interruptions are frequent. Where user is likely to play with the room thermostat. All commercial installations. Installations where interconnecting tube length exceeds 50 ft. High-rise applications. 6. Evaporator Freeze Thermostat A SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE: All units where winter start control has been added. 7. High-Pressure Switch Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about 400 psig. Provides additional protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling, cycle protector can be used with this switch. SUGGESTED USE: Installations exposed to very dirty outdoor air. Installations where condenser inlet air temperature exceeds 125 F (51.7 C). 8. Liquid Solenoid Valve (LSV) An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. Note: Compressor start assist capacitor/relay type must also be used. SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) In certain long line applications. (Refer to Long-Line Application Guideline.) 9. Low-Ambient Controller This solid-state head pressure controller is a cycle control device activated by a temperature sensor. It is specifically designed to control outdoor fan motor run time in response to saturated condensing temperature. For outdoor air temperatures between 55 F and 0 F (12.8 C and 17.8 C), it maintains condensing temperature between 75 F and 130 F (23.8 C and 54.4 C). SUGGESTED USE: operation at outdoor temperatures below 55 F (12.8 C). 10. Low-Pressure Switch Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27 psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Also, provides additional protection against compressor damage due to loss of refrigerant charge. To prevent rapid compressor recycling. Cycle protector can be used with this switch. SUGGESTED USE: Where indoor coil is exposed to dirty air. All commercial installations. 11. Thermostatic Expansion Valve (TXV) Kits A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB type valves are available. SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) 12. Time-Delay Relay A SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) 13. Winter Start Control A SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions. SUGGESTED USE: All air conditioners where low-ambient controller has been added. SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE PAYNE Heating & UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 710A.18.2P 1995 BDP Co. Indpls, IN 406 PRINTED IN U.S.A. 12 Catalog No. PA-3271-002 5-96