PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL

Similar documents
Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

GENESIS Air Conditioner. M52 3-Phase Model INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. D 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T53 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Equipment Protection P/N

INSTRUCTION MANUAL. T-SERIES Air Conditioner. T29 Model Pentair Equipment Protection P/N McLean Parts 5736 N. Michigan Rd.

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL. Rev. F 2015 Pentair Equipment Protection P/N

PROAIR Air Conditioner

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL. Rev. B 2016 Pentair Equipment Protection P/N

T-Series Air Conditioner

T-Series Air Conditioner

PROAIR Air Conditioner

SPECTRACOOL Air Conditioner. N17 Model INSTRUCTION MANUAL. Rev. G 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

SPECTRACOOL Air Conditioner. N16 Model INSTRUCTION MANUAL. Rev. A 2016 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

SPECTRACOOL Air Conditioner

T-Series Air Conditioner T15 Model

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

GENESIS Top-Mount Air Conditioner. HB16 Model INSTRUCTION MANUAL. Rev. J 2013 Pentair Equipment Protection P/N

T-Series Air Conditioner T20 Model

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

T-Series Air Conditioner T53 Model

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

M52 3-Phase INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

GENESIS AIR CONDITIONERS

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

Blade Series Heat Exchanger Operation and Installation

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

ClimaGuard Outdoor Heat Exchanger All Models

ADVANTAGE SERIES KXRP33 AIR-TO-AIR HEAT EXCHANGER

Air-To-WATer HeAT exchangers WcHe Models INSTRUCTION MANUAL Rev. J 2018 nvent P/N

KNHX32 SERIES NEMA 4/4X AIR-TO-AIR HEAT EXCHANGERS

SPECTRACOOL Air Conditioner

Panel Mounted Heat Exchangers by Dantherm, Inc.

Rev. F 2014 Pentair Equipment Protection P/N Distributed by: McLean Parts. fax

SPECTRACOOL Air Conditioner. G57 Model INSTRUCTION MANUAL. Rev. E 2014 Pentair Equipment Protection P/N

ADVANTAGE SERIES KXRP47 AIR-TO-AIR HEAT EXCHANGER

AIR CONDITIONER OPERATOR'S MANUAL

RPI Industries, Inc.

InstructIon Manual KrEs EQuIPMEnt stands

SPECTRACOOL Air Conditioner. G28 Model INSTRUCTION MANUAL nvent Rev. D P/N

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRADITIONAL SERIES P47 P52 P59

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE WNP28 SERIES

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SPECTRACOOL Air Conditioner

RPI Industries, Inc.

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner ADVANTAGE RP55 SERIES

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

USER S OPERATING AND INSTRUCTION MANUAL

Intelligent Electronic Enclosure Thermal Management Systems

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner NPT SERIES K_A6C_NPT47L

Installation and Operations Manual

RPI Industries, Inc.

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTEGRITY SERIES K_NA4C4P32L KNA6C4P32L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner WATER-COOLED RACK MOUNTED

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Intelligent Electronic Enclosure Thermal Management Systems

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers

Wax Base Heater & Dispenser

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

APPLICATION MANUAL FOR SCU SERIES COMPRESSOR UNITS AND SWU SERIES WATER COOLED CONDENSING UNITS

Installation & Operation Manual Ice Cream Freezers

Intelligent Electronic Enclosure Thermal Management Systems

Service Manual Models CPH2 & CPH3

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K2A3C14DP50L

XC Portable Air Conditioning

Rev. A AUGUST 2012 RNP SERIES REFRIGERATED COMPRESSED AIR DRYERS OPERATOR MANUAL RNP25 RNP35 RNP50

Horizontal Bottle Cooler Installation and Operation Manual

The Da-Lite Difference.

Manual For Panel Air Conditioner. Table of Contents

TL-105 COLUMN HEATER

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Hazardous Location Heaters. 50W and 80W Models INSTRUCTION MANUAL. Rev. I 2018 nvent P/N

A910.8A Remote Water Chiller, 8 GPH A A / A A-220V TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K_A4C5DP33L

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Transcription:

PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. F 2018 nvent P/N 10-1008-167 87976466

TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION INSTRUCTIONS...4 TECHNICAL INFORMATION...4 Design Data... 4 DIMENSIONAL DRAWINGS... 5 Components List... 6 STANDARD WIRING DIAGRAM, 115 / 230 VOLT... 7 TIME DELAY RELAY OPTION WIRE DIAGRAM, 115 / 230 VOLT... 7 TEMPERATURE CONTROL... 8 PRINCIPLES OF OPERATION... 8 WATER USAGE... 8 Condenser... 8 Manual Reset High Pressure Limit Switch... 8 Water Valve... 8 Water... 9 MAINTENANCE...9 Compressor... 9 Evaporator Blower... 9 Refrigerant Loss... 9 Freezing and Draining the System... 9 WARRANTY...10 RETURN AND REPAIR POLICY...10 LIMITATION OF LIABILITY...11 NOTE: Some of the information in this manual may not apply if a special unit was ordered. If additional drawings for a special unit are necessary, they have been inserted. Contact Pentair Equipment Protection if further information is required. - 2-2018 nvent 87976466

RECEIVING THE AIR CONDITIONER Inspect the thermoelectric cooler. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose assemblies, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -- within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier. Pentair Equipment Protection cannot accept responsibility for freight damages; however, we will assist you in any way possible. HANDLING & TESTING THE AIR CONDITIONER If it is necessary to place the air conditioner in a horizontal position after unpacking, be certain it is placed in an upright, vertical or mounting position for a minimum of five (5) minutes before operating. Never attempt to operate the air conditioner while it is horizontal or on its side, back or front. The refrigeration compressor is filled with lubricating oil. Running the compressor without oil in the lower part of the housing will cause permanent damage to the air conditioner. This also voids the warranty. TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE. Refer to the nameplate for proper electrical current requirements, then connect power cord to a properly grounded power supply. Minimum circuit ampacity should be at least 125% of the amperage shown in the design data section for the appropriate model. No other equipment should be connected to this circuit to prevent overloading. Connect to clean, pressurized water supply and provide drain. Operate the air conditioner for five (5) to ten (10) minutes. No excessive noise or vibration should be evident during this run period. The evaporator blower (enclosure air), and the compressor should be running. The compressor is provided with automatic reset thermal overload protection. This thermo-switch is located and mounted inside the plastic enclosure clipped to the compressor. The only time this switch should operate is when the compressor overheats due to ambient air temperatures exceeding nameplate rating or if enclosure dissipated heat loads exceed the rated capacity of the air conditioner. The thermal overload switch will actuate and stop compressor operation. The blower will continue to operate and water will continue to flow for a short period. The compressor will restart after it has cooled to within the thermal overload cut-in temperature setting. The unit will also shut down if water supply is interrupted. See WATER USAGE section. 2018 nvent 87976466-3 -

INSTALLATION INSTRUCTIONS 1. Inspect air conditioner. Verify functionality before mounting the air conditioner, see HANDLING & TESTING THE AIR CONDITIONER on page 3 2. Using the cutout dimensions shown in this manual or the cutout template printed on the units shipping carton, prepare the air IN and air OUT openings, and mounting bolt hole pattern for the enclosure. 3. Using the gasket kit provided, install gaskets to air conditioner. See gasket kit illustration in this manual for proper location. 4. Mount air conditioner on enclosure using mounting bolts and screws provided. EZ-mount tabs can be used to hold unit on enclosure while mounting in place. Connect water inlet and outlet fittings to a clean pressurized water supply. Allow unit to remain upright for a minimum of five (5) minutes before starting. Caution! Air conditioner must be in upright position during operation. 5. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly grounded power supply. Use of an extension cord is not recommended. Electrical circuit should be fused with slow blow or HACR circuit breaker. TECHNICAL INFORMATION DESIGN DATA Model Voltage Hertz Full Load Amps Phase BTU/Hr. @ 131 F Enclosure Temperature Maximum F Water Temperature Maximum Water Usage (GPM) Shipping Weight lb./kg CR43-0816-GWXXX 115 50/60 13.0 / 13/0 1 8500 90 1.5 137 / 62 CR43-0826-GWXXX 230 50/60 6.6 / 6.5 1 8500 90 1.5 137 / 62 -XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers. - 4-2018 nvent 87976466

DIMENSIONAL DRAWINGS 2018 nvent 87976466-5 -

MOUNTING GASKET KIT MOUNTING CUTOUT DIMENSIONS Rear view of mounting gasket kit part number 43-2000-02 COMPONENTS LIST Part Description Part Number 115 Volt 230 Volt Blower, Evaporator 38-2019-04 38-2020-04 Capacitor, Compressor 10-1032-15 10-1032-18 Coil, Condenser Water 47-6121-00 47-6121-00 Coil, Evaporator 43-2002-01 43-2002-01 Compressor 10-1016-68 10-1026-80 Contactor (optional) 10-1005-41 10-1005-42 Filter/Dryer 52-6028-00 52-6028-00 Relay, Compressor Start 10-1028-14 10-1028-15 Relay, Time Delay, (optional) 10-1005-71 10-1005-71 Service Cord 52-6035-01 52-6035-74 Switch, Manual Reset Pressure 52-6104-48 52-6104-48 Thermal Overload, Compressor 10-1007-50 10-1007-49 Thermostat, SPST, 55-100F 10-1061-02 10-1061-02-6 - 2018 nvent 87976466

STANDARD WIRING DIAGRAM, 115 / 230 VOLT TIME DELAY RELAY OPTION WIRE DIAGRAM, 115 / 230 VOLT 2018 nvent 87976466-7 -

TEMPERATURE CONTROL The electromechanical thermostat is factory preset to 75 F / 23 C. To change the temperature setting, remove the front cover. Use a standard screwdriver to adjust thermostat. For cooler temperatures turn clockwise, for warmer temperatures turn counterclockwise. PRINCIPLES OF OPERATION If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), the compressor may not restart due to the high back pressure of the compressor. It takes a minimum of one (1) minute after shut-down for the compressor suction and discharge pressures to equalize in order for the air conditioner to restart. Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties. It is recommended that the warranty section of this manual be read in order to familiarize yourself with parameters of restricted operation. The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously this can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the enclosure s door admits humid air which the air conditioner must then dehumidify. WATER USAGE CONDENSER The water cooled air conditioner uses water as the cooling medium for the condensing side of the hermetic refrigeration system. This water is passed through a heat exchanger that uses the cool water to lower the temperature of the hot gaseous refrigerant, causing it to condense. The water is warmed by this exchange of heat, and is passed out of the air conditioner at an elevated temperature. The inlet and outlet water fittings are located on the bottom of the air conditioner. A sealant is recommended when connecting the inlet and outlet water lines to prevent leakage. It is extremely important for the air conditioner to have an uninterrupted supply of clean cooling water. Interference with the water supply will cause the unit to automatically shut down and require manual reset. MANUAL RESET HIGH PRESSURE LIMIT SWITCH The manual reset high pressure limit switch is located behind the front cover. This limit switch interrupts compressor operation when condenser refrigerant exceeds 310 PSIG, which most frequently occurs as a result of the condenser water supply being reduced or shut down. After identifying and correcting the problem with the water supply to the unit, compressor operation can be restored by pushing the manual reset button located on the switch. WATER VALVE The valve that controls the flow of condensing water is also located behind the front cover. This valve modulates the flow of water to the condensing coil. Water flow varies according to a variety of loading conditions, including electrical load, inlet water temperature, ambient air temperature, cabinet construction, etc. The maximum flow rate in the DESIGN DATA is given for the conditions of maximum rated load, maximum water temperature, and maximum ambient temperature, and reflects the highest flow rate anticipated for the unit. NOTE: This valve has been preset at the factory for the correct operation of the unit. The setting of the valve should not be altered. - 8-2018 nvent 87976466

WATER The air conditioner water supply does not require special treatment, but care should be taken to avoid any gross contamination. Corrosives may cause leakage within the coil and water lines. Mineral rich water will cause scaling of the coil, degrading performance. Particulates may cause rapid erosion of the coil, and could result in clogging of the control valve. NOTE: A filter to clean the air conditioner water supply is recommended. If the temperature of the inlet water is higher than that shown in the DESIGN DATA, it will result in a higher flow rate, and may cause shut-down of the unit. High inlet water temperatures should be avoided. When the air conditioner is shut-down, either because of a thermostatic cut-out or a loss of power, the water flow should gradually diminish to zero. If water flow persists, it may indicate a malfunction of the control valve. Information on the specific valve employed is supplied with the air conditioner. MAINTENANCE COMPRESSOR The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should provide years of satisfactory operating service. Should the refrigerant charge be lost, recharging ports (access fittings) on the suction and discharge sides of the compressor are provided for recharging and/or checking suction and discharge pressures. Under no circumstances should the access fitting covers be loosened, removed or tampered with. Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system. Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner. EVAPORATOR BLOWER Blower motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life of the motor. REFRIGERANT LOSS Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system. This work should only be performed by qualified professionals, generally available through a local, reputable air conditioning repair or service company. Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in ounces. Before recharging, make sure there are no leaks and that the system has been properly evacuated into a deep vacuum. FREEZING AND DRAINING THE SYSTEM WARNING The air conditioner can be severely damaged by freezing if not properly drained. Damage due to freezing is not covered by the warranty. If the unit is to be shipped to, or stored in an area that experiences climatic extremes, care must be taken to fully drain the unit to avoid freezing. The location of the drain is shown in the OUTLINE DRAWING. To completely drain the unit, it is recommended that 100 psi maximum compressed air be applied to the water inlet, while lifting the spring of the valve with a screwdriver to allow free passage of water. An alternate means would be to start the air conditioner and allow the refrigeration system pressure to open the valve while air pressure is applied to inlet. 2018 nvent 87976466-9 -

WARRANTY Pentair Equipment Protection warrants that the Goods manufactured by Pentair Equipment Protection will be free from defects in material and workmanship for a period of one (1) year from the date of shipment by Pentair Equipment Protection, subject to the following conditions and exclusions: A. Conditions. All Goods must be installed and operated according to the following specifications: 1. Maximum voltage variation no greater than plus or minus 10% of nameplate nominal rating; 2. Maximum frequency variation no greater than plus or minus 3 Hz. of nameplate nominal rating; 3. Must not exceed minimum and maximum stated temperatures on the nameplate; 4. Must not exceed (BTU/Hr) rating, including any heat sink as indicated on the nameplate; 5. Refrigerant bearing Goods must not be restarted for a period of one (1) minute after intentional or accidental shut-off; 6. The filters (if applicable) must be cleaned regularly; 7. The Goods and any parts thereof must not be modified, unless prior written authorization is received from Pentair Equipment Protection; and 8. All Goods must be installed and grounded in accordance with all relevant electrical and safety codes, as well as the National Electric Code and OSHA rules and regulations. 9. All Goods must be installed in a stationery application, free of vibration. A violation of any one of these conditions shall render the warranty hereunder void and of no effect. B. Exclusions. This warranty shall be void if product is misapplied in any way or: 1. Buyer specified product is inappropriate for system or environment in which it is operating. 2. Pentair Equipment Protection product modified in any way without prior written authorization from Pentair Equipment Protection. 3. Removal or modification of Pentair Equipment Protection label affixed to product without written Pentair Equipment Protection approval. Pentair Equipment Protection must be notified of a claim in writing not later than fourteen (14) days from the date when Buyer has become aware of such occurrence, or where the defect is such that it may cause damage, immediately, such notice containing a description of how the defect manifests itself. Failure to provide such prompt notice to Pentair Equipment Protection shall result in forfeiture of Buyer s rights under this warranty. In the event of a warranty claim, Buyer is to return defective goods to Pentair Equipment Protection in accordance with Pentair Equipment Protection Return Policy. Warranty period for repaired goods remains at 1 year from shipment of original goods. Pentair Equipment Protection sole obligation to Buyer under this warranty will be, at Pentair Equipment Protection option: A. Repair or replace Pentair Equipment Protection products or parts found to be defective in material or workmanship. B. Issue credit for the purchase price paid by Buyer relating to such defective Goods or part. THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE GOODS AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY AND IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. RETURN AND REPAIR POLICY Pentair Equipment Protection products that: (i) are made to order, (ii) have been modified by Buyer, (ii) have special finishes, or (iv) are determined by Pentair Equipment Protection to constitute custom products that cannot be returned to stock or resold to other Buyers, will not be accepted for return by Pentair Equipment Protection. All returns require a Return Material Authorization number (RMA #), regardless of reason for return, whether it be for warranty or out of warranty repair. Returns without an RMA # will be refused by our Receiving Department. An RMA # is valid for 60 days. - 10-2018 nvent 87976466

A. An RMA # will be issued by our Repair Department in Anoka, MN at 866-545-5252. Buyer should have following information available at time of RMA request: 1. Complete Model Number, Serial Number and description of damaged unit being returned. 2. Original Buyer Purchase Order number and date product was received by Buyer. 3. Quantity to be returned and a brief description of failure for each unit, if different. 4. Contact information of Buyer that must include: name of company, billing and shipping address, phone, number, fax number, freight carrier and the name and phone number of a Buyer contact who can elaborate on the claimed defect in detail. 5. Buyer must provide a Repair Purchase Order number for both warranty and out of warranty repairs. The PO will not exceed 50% of a new unit. Buyer will be notified of repair charges that exceed approved PO amount. B. All returns to Pentair Equipment Protection must be securely packed, using original cartons if possible. All returns must have the RMA number visible on the outside of the carton. Pentair Equipment Protection is not responsible for material damaged in transit. Any refrigerant-bearing Goods must be shipped upright for return. C. Shipping cost for all non-warranty repairs is the responsibility of the sender and must be shipped prepaid. Shipping costs for all warranty related repairs will be covered by Pentair Equipment Protection provided the goods are returned using a Pentair Equipment Protection approved carrier. If after diagnoses the product is determined by Pentair Equipment Protection not be covered under warranty, Buyer will be responsible for all shipping charges and will be billed accordingly. D. Non-warranty repairs are subject to a $75 minimum analysis fee. Analysis fee will be waived if Buyer approves repair work. If approval is not received within 30 days, material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer. E. At Buyer s request, Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge. Failure analysis for non-warranty repairs are subject to a $100 per hour Engineering charge plus any other incurred testing costs. F. All returned merchandise must be sent to the following address: Pentair Equipment Protection, 2100 Hoffman Way, Anoka, MN 55303-1745. G. Credit for accepted returns shall be at the original selling price or the current selling price, whichever is lower, less the restocking charge indicated as follows: 1. Within 60 days of invoice date - 20% of applicable selling price. 2. Within 61-120 days of invoice date - 30% of applicable selling price. 3. Within 121-180 days of invoice date - 40% of applicable selling price. 4. Beyond 180 days - subject to individual review by Pentair Equipment Protection. If product being returned for credit requires repair or modification, the cost of any labor or material necessary to bring product into saleable condition will be deducted from credit. Buyer may not take credit against returns without prior written Pentair Equipment Protection approval. LIMITATION OF LIABILITY PENTAIR EQUIPMENT PROTECTION WILL NOT BE LIABLE UNDER ANY CIRCUMSTANCES FOR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES, INCLUDING WITHOUT LIMITATION ANY LOST PROFITS OR LABOR COSTS, ARISING FROM THE SALE, USE OR INSTALLATION OF THE GOODS, FROM THE GOODS BEING INCORPORATED INTO OR BECOMING A COMPONENT OF ANOTHER PRODUCT, FROM ANY BREACH OF THIS AGREEMENT OR FROM ANY OTHER CAUSE WHATSOEVER, WHETHER BASED ON WARRANTY (EXPRESSED OR IMPLIED) OR OTHERWISE BASED ON CONTRACT, OR ON TORT OR OTHER THEORY OF LIABILITY, AND REGARDLESS OF ANY ADVICE OR REPRESENTATIONS THAT MAY HAVE BEEN RENDERED BY PENTAIR EQUIPMENT PROTECTION CONCERNING THE SALE, USE OR INSTALLATION OF THE GOODS 2018 nvent 87976466-11 -

2018 nvent 87976466 Rev. F P/N 10-1008-167