Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Similar documents
The Use Of Attic Space For Cooling and Dehumidification

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Desiccant Cooling with Solar Energy

Recent Advances in Energy, Environment and Economic Development

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector

Solar Heating and Cooling Systems

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Performance Analysis of a Solid Desiccant Air Dehumidifier

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

A study of radiant cooling for a room with daytime application in tropical climate

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Next Generation Passivhaus Archives

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Figure 1: Low energy dwellings testsite

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Impact of indirect evaporative air cooler type on the performance of desiccant systems

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

A Liquid Desiccant System for Solar Cooling and Dehumidification

AR/IA 241 LN 231 Lecture 6: Passive Cooling

Department of Mechanical Engineering, Mirpur University of Science and Technology, Mirpur, AJK, Pakistan

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Performance evaluation of a liquid desiccant solar air conditioning system

Comfort and health-indoor air quality

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

Systems engineering Slide 1

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Ultra Efficient Desiccant Based Evaporative Cooling for Air- Conditioning

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS

ANALYSIS OF DESICCANT COOLING SYSTEM

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

Dynamic performance of a novel dew point air conditioning for the UK buildings

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

Heat pump and energy recovery systems

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system

An experimental study of the impact of tunnel suppression on tunnel ventilation

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Australian Solar Cooling Interest Group (ausscig) Conference

THE EFFECT OF HIGH TEMPERATURE AIR DRYING ON EVAPORATION, RUNNABILITY AND COATED PAPER PROPERTIES. Pertti Heikkilä and Pasi Rajala

Chapter 10. Passive Cooling Contents

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

Purdue e-pubs. Purdue University

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

PRODUCING COOLING FROM SOLAR ENERGY BY USING ADSORPTION CYCLE WITH ACTIVATED CARBON AND METHANOL PAIR

DOMESTIC DEHUMIDIFIERS IN COOL CONDITIONS: I PERFORMANCE FACTORS

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

DESIGN AND CONSTRUCTION OF FORCED/NATURAL CONVECTION SOLAR VEGETABLE DRYER WITH HEAT STORAGE

A new method for preventing air-source heat pumps and refrigerators from frosting

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Optimize Evaporative Cooler

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

K.F. Fong *, C.K. Lee, T.T. Chow

ISSN: [Agcaoili S. O., 7(3): March, 2018] Impact Factor: 5.164

Design, fabrication and testing of Evaporative Desiccant Cooling system

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Design and Optimization of Domestic Solar Dryer

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Benefits Offered by Passive Dehumidification Wheel Speed Control

HYGROTHERMAL PERFORMANCE BENEFITS OF THE CELLULOSE FIBRE THERMAL INSULATION STRUCTURES

REDUCTION IN ENERGY CONSUMPTION BY AIR-CONDITIONER IN RESIDENCES UNDER HOT AND HUMID CLIMATES

Available online at ScienceDirect. Energy Procedia 78 (2015 )

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

Experimental Investigation to Assess the Performance of Desiccant Integrated Chilly Dryer

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

SOLAR HEATING AND COOLING FOR THE SOLAR CITY GLEISDORF

The Corbioli House is a single-family house situated

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Transcription:

International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement N. Areemit and Y. Sakamoto The University of Tokyo, Japan ABSTRACT Substantial effort has recently been devoted to passive solar desiccant air dehumidification. This research aims to describe the passive room dehumidifying system with the combination of an existing wooden attic space as a chamber and desiccant; an optimization of system and solar energy as system operation. The field measurement was carried out in the test house in Japan over hot humid summers in 2003 and 2004. It was found that the dehumidification rate of the wooden attic space was approximately 25 g/h per square meter of floor area of attic space. The electric coefficient of performance was approximately 15. In addition to the attic space, regarding to the investigation on the system including the between the attic space and the bedroom, in the presence of an occupant, the humidity of the bedroom during the nighttime was lower compared to the traditional natural approach throughout the night. Therefore, the system outlined in this study could be promising as a new passive tool for moisture control in hot humid region. 1. INTRODUCTION In hot humid regions, air dehumidification is considered to be an issue of increasing concern as an important aspect of indoor environment. A good air dehumidification is crucial to moisture related problems, e.g. human health and comfort, building energy performance and building durability and maintenance. At the present, an air conditioning system plays an important part in decreasing air humidity and has become a necessity for almost all buildings. However, it often consumes a great deal of energy and releases CFCs of HCFCs, which is harmful to environment. To produce an alternative solution to this issue, desiccant dehumidification applications have been studied by several researchers whose studies were reviewed (Waugaman et al., 1993). Of particular interest are those with passive approach, using solar energy to regenerate desiccant materials. With regard to the fundamentals of desiccant, it initially attracts moisture from surrounding air until equilibrium state with the surrounding moisture is reached. In order to attract moisture once again, the desiccant needs to be dried or so technically called regeneration process. A typical regeneration process includes heating and exposure to scavenger air stream. As this cycle repeats, the moisture in air absorbed by the desiccant could be defined as the level of air dehumidification. In these systems, the chamber of the system consists of netting solid desiccant bed. During nighttime, the desiccant bed dehumidifies air and releases sensible heat due to an absorption process through nocturnal radiation. During daytime, the bed is regenerated by solar energy and exhaust and ready again for air dehumidification in nighttime. In addition to commercial chemical desiccant materials, natural fiber materials such as kenaf core (Williams, 1991), coconut coir and durian peels (Khedari et al., 2003), can attract and hold water as commercial chemical desiccants. Wood has also been investigated as potential desiccant material in many studies. It is demonstrated that moisture transfer between indoor air and wood based hygroscopic material could reduce the daily peak indoor humidity (Simonson et al., 2002). Furthermore, wood based material has enough potential to keep the room humidity be-

652 International Conference Passive and Low Energy Cooling low 60% for a period of time after the air conditioning system is switched off (Sakamoto and Zhu, 1996). Although a great deal of research has been done on air dehumidification with mechanical equipment which requires high cost investment and degradable commercial chemical desiccant material, little research on passive air dehumidification using building component, such as a wooden attic, in existing building has yet been done. This paper reports on the results in an attempt to describe the passive room dehumidifying system with the combination of an existing attic space as a chamber; wood as a desiccant material; an optimization of and solar energy as a system operation. 2. CONCEPT OF THE ROOM DEHUMIDI- FYING SYSTEM In Figure 1, the operation of the system during daytime and nighttime is illustrated. An airtight wooden attic space plays a role as a chamber while wood compositions of the attic, especially underneath roof material, work as desiccant material. During daytime, high temperature in the attic space regenerates wood and Solar radiation Natural Nocturnal radiation Heat and moisuture generated by human's activity desorped Moisture absorbed Moisture Exhaust air Bedroom Dried air Day time Night time Supply to bedroom Bedroom moist air is to be vented out by exhaust. Inversely, during nighttime, low moisture content generated during daytime induces wood to adsorb moisture from humid air, supplied from the bedroom while sensible heat of the absorption process relieved through nocturnal radiation. Here, the moisture load from the bedroom represents the latent heat production of human's activity. After the air is dried by the absorption process of the attic space, it is subsequently fed back into the bedroom. This cycle is repeated throughout nighttime. The decrease in air humidity of the bedroom during nighttime due to the moisture absorption of the attic space is taken into consideration as the quantity of dehumidification. 3. EXPERIMENT METHOD The measurement was conducted during the hot humid season in the test house in an open suburban area of Saitama city, Japan (latitude 36 o 00 N, longitude 139 o 12 E). As a preliminary study, the dehumidification potential of the wooden attic space alone was investigated in 2003. In addition to the attic space, the investigation on the system including the between the attic space and the bedroom was performed in 2004. Here, our main target of dehumidification is the bedroom. 3.1 Building Description The two-story north-south oriented wooden structure building, which is illustrated in Figure 2, is mainly comprised of four rooms which two main rooms on each floor, a staircase and an attic space. The main room on 2 nd floor is assumed as the bedroom in this study. All connections between rooms were closed while measurements were performed. Particularly the connection between the attic space and the other rooms is assumed to be hermetic sealed besides the of the system. Additionally, in order to eliminate the effect of the sorption property of the components of the bedroom, vinyl sheet was attached to all component surfaces. The configuration of the attic space is illustrated in Table 1. Figure 1: Schematic view of the operation of the system during day and nighttime.

International Conference Passive and Low Energy Cooling 653 5460 3640 1820 3640 stair case 1 st floor main room North colonial roof asphalt Attic polyethelyne air space Bedroom air space 1 st floor main room Figure 2: Plan and section view of the test house. Table 1: Characteristics of the attic space and bedroom of the test house. Attic space Bedroom Floor area (m 2 ) 19.87 13.25 Height (m) 1.15 2.40 Room volume (m 3 ) 11.50 31.75 Air infiltration (cm 2 /m 2 ) 0.70 1.00 3.2 Measurement and Control 3.2.1 Experimental Instruments and Parameters Thermo couples and salt-phase heated hygrometers (Dew-cell) were applied to measure temperature and humidity as main dependent parameters in this study. Furthermore, rate measured by tracer gas monitors (Bruel and Kjaer type 1312, 1303) and small anemometers along with heat and moisture generation played a role as control parameters. For gathering and storing measured data, the data acquisition was set up in the container room close to the test house and monitored by using an interval time of 1 minute. 3.2.2 Control and Operation To control parameters, the set of equipments was setup. With regard to the daytime exhaust, two dampers were installed in both the north and south gable walls along with weather cover hoods. Additionally, one fan installed at the north gable wall, with a capacity of 470 m 3 /h, was employed to induce the exhaust. For the between the attic space and bedroom, the fan with a capacity of 250 m 3 /h was installed at bedroom ceiling for Table 2: Operation mode for the investigation on the standalone wooden attic space. Operation mode Daytime exhaust Nighttime heat and moisture generation Mode1 No No Mode2 No Yes Mode3 Yes Yes Table 3: Operation mode for the investigation on the whole system. Nighttime Nighttime Daytime Daytime be- Operation ventila- natural exhaust natural tween mode of bedroom attic tion of of bedroom attic and bedroom Mode4 Yes No Yes Yes Mode5 Yes(high) Yes(high) No No Mode6 Yes(low) Yes(low) No No exhausting air from bedroom to attic space along with another opening for the purpose of supplying back the air to the bedroom. To reduce temperature and humidity stratification in the attic space, 7 small fans were installed in the attic space with one fan in the bedroom. Furthermore, to simulate the effect of a sleeping adult in the building, the humidifier and heat generator produced approximately moisture of 60 g/h and sensible heat load of 100 W respectively as a constant rate. In the investigation on the attic space alone, 3 operation modes that differ in the operation of the daytime exhaust and the nighttime heat and moisture generation were investigated as shown in Table 2. Mode1 aimed to describe the nature of the sorption property of the attic space. In addition, by comparing Mode2 and Mode3, the effect of the daytime exhaust on the dehumidification potential of the wooden attic space is determined. Furthermore, 3 operation modes were set up for the investigation of the whole system as shown in Table 3. Mode4 describes the result of this system while Mode5, 6 simulate that of the natural with high and low rate respectively. In the presence of the daytime exhaust of the attic space, the dampers played a major role in controlling as well as the exhaust fan. The dampers and fan were programmed to open when the level of the absolute humidity of the attic space exceeded that of

654 International Conference Passive and Low Energy Cooling outdoor air to exhaust the moist air and close vice versa to allow the absorption process to begin. On the other hand, in the operation mode with the absence of the daytime exhaust, the dampers were always closed regardless of the level of absolute humidity. In addition, in the presence of the nighttime sensible heat, moisture generation and between the attic space and bedroom, they were operated 8 hours a day, from 10 p.m. until 6 a.m. of the next day. The high and low rates in natural Mode 5, 6 were induced by opening east-west windows and sole east window of the bedroom respectively. 4. RESULTS AND DISCUSSIONS Results and discussions are categorized into two parts as the measurement of the standalone wooden attic space measured in 2003 and the whole system measured in 2004. 4.1 The Standalone Wooden Attic Space Figure 3a indicates the daily pattern distribution of temperature, absolute and relative humidity in Mode1. Apparently, there was a clear absolute humidity variation of 30 g/kg between daytime and nighttime. Furthermore, the level of the absolute humidity in the attic space approached lower than that of outdoor throughout the night by approximately 8 g/kg. This phenomenon can be explained that during the daytime, high temperature especially in roof components induces wood to release moisture into the attic space and vice versa during the nighttime. Consequentially, it significantly confirms the sorption potential of the attic space through this study. Figures 3b, c indicate the daily pattern distribution of temperature, absolute and relative humidity in Mode 2-3. In absence of the daytime exhaust, the absolute humidity during the nighttime remained close to that of outdoor, while in the presence of the exhaust, the absolute humidity of the attic space was kept much below than that of outdoor air all night even though the heat and moisture generation were applied. Moreover, while the relative humidity of outdoor air reached 90% during the nighttime, that of the attic space in case of presence and absence of exhaust were retained below 60% and 85% respectively. Evidently, these results indicate that the absorb potential of the attic space during the nighttime, due to the presence of the daytime exhaust, can maintain the level of absolute humidity in the attic space lower than outdoor and keep the relative humidity below 60% through- Attic mode1 Outdoor Attic mode2 Outdoor Attic mode3 Outdoor 17/9/2003 18/9/2003 19/9/2003 20/9/2003 9/9/2003 10/9/2003 11/9/2003 12/9/2003 22/8/2003 23/8/2003 24/8/2003 25/8/2003 (a) Mode1 (b) Mode2 (c) Mode3 Figure 3: The daily pattern distribution of temperature, absolute and relative humidity of the standalone attic space.

International Conference Passive and Low Energy Cooling 655 Attic Bedroom Outdoor Attic Bedroom Outdoor Attic Bedroom Outdoor ambient air - 2nd floor(solid line) attic - 2nd floor(dotted line) 12/8/2004 13/8/2004 14/8/2004 15/8/2004 2/8/2004 3/8/2004 4/8/2004 5/8/2004 6/8/2004 7/8/2004 8/8/2004 9/8/2004 (a) Mode4 (the system) (b) Mode5 (natural (high)) (c) Mode6 (natural (low)) Figure 4: The daily pattern distribution of temperature, absolute and relative humidity of the whole system. out the period of moisture generation in the nighttime. 4.2 The Whole System Figures 4a, b, c illustrate the daily pattern distribution of temperature, humidity while operating the system, high and low rate of natural respectively. By comparing the result of the system with the high and low rate of natural operations, even in the presence of the nighttime heat and moisture generation, apparently the absolute humidity of the bedroom when operating the system were lower by 5 g/kg than outdoor while that of the natural operations had a certain parallel with outdoor air. Furthermore, by operating the system, the level of the relative humidity of the bedroom was under 50 % throughout the night while the natural s were over 60 %. However, the temperature of the bedroom by operating system was higher comparatively. Therefore, it can be inferred that the system has sufficient dehumidification potential to lower the humidity of the bedroom during the nighttime comparing to the natural. In addition, for the purpose of system evaluation, the calculation of dehumidification rate based on the summation of the humidity change of processed air (differentiating the moisture of air supplied from the attic space to the bedroom and that of air exhausted vice versa) is shown in equation (1). In order to calculate the moisture flow, the velocity and absolute humidity, which were measured by the anemometers and hygrometers installed in the openings for exhausting and supplying air between the bedroom and attic, were applied. D= ρ v A X v ρ A X (1) ( ) a E E E S a S S where: D: dehumidification rate (g/h), v: velocity (m/h), ρ a : Air density (kg/m 3 ), A: area of opening (m 2 ), X: absolute humidity of outdoor (g/kgda), E: exhaust from bedroom, S: supply to bedroom. As illustrated in Figure 5, besides the start period of the operation, the dehumidification rate of the system maintained unvaried at 500 g/h, which is equal to approximately 25 g/h per square meter of attic floor area throughout the night. The dehumidification rate of 500 g/h could be considered that while the absolute humidity of the bedroom was likely constant throughout the night, apart from moisture generation of 100 g/h

656 International Conference Passive and Low Energy Cooling 1000 750 500 250 0 22:00 0:00 2:00 4:00 6:00 Figure 5: Dehumidification rate of the system during the nighttime. and moisture gained due to air infiltration of 150-250 g/h, another 150-250 g/h would be the moisture desorbed from the components of the bedroom although it was expected that the vinyl sheet attached on all component surfaces could prevent moisture desorption. Since the system operation is completely a daily cycled, it would be the most efficient evaluation to make use of daily coefficient of performance (COP). Based on the summation of latent heat change of processed air, the change in latent heat of processed air was estimated to be approximately 4,722 Wh per day. On the other hand, the electric consumption by means of one exhaust fan operated during the daytime and one ventilated fan operated during the nighttime, operated for about 8 hours of each, was approximately 330 Wh per day. As a result, the electric coefficient of performance of this passive dehumidification system was considered to be relatively high as approximately 15, which is 3 times as more than the normal dehumidification system is. The utilization of free renewable solar energy as a major advance in COP would be the most likely reason for this finding. also worth mentioned that parametric study is needed to achieve the optimization of the system as well as discussion on comfort caused by the system. ACKNOWLEDGEMENTS The authors would like to express the deepest gratitude to Fujishima Co., Ltd. for providing the test house and cooperation in all aspects. REFERENCES Khedari, J., et al., 2003. Feasibility study of using Agriculture Waste as Desiccant for Air Conditioning System. Renewable Energy, volume 28: 1617-1628. Sakamoto, Y. and J. Zhu, 1996. Application of the Hygroscopic Materials to Domestic Air-conditioning. The Proceedings of Architectural Institute of Japan, 26 th Thermal Environmental Symposium: 91-100. Simonson, C.J., et al., 2002. The Effect of Structures on Indoor Humidity Possibility to Improve Comfort and Perceived Air Quality. Indoor air, volume 12: 243-251. Waugaman, D.G., et al., 1993. A Review of Desiccant Cooling System. Energy Resources Technology Journal, volume 15: 1-8. Williams, J.B., 1991. Evaluation of kenaf core as a desiccant. web:http//www.abe.msstate.edu/personnel/epc/ absorbman.htm. Department of anumal and Dairy Science Box 9815 Mississippi State, MS 39762. 5. CONCLUSIONS The significant dehumidification potential of the passive solar room dehumidifying system was realized by means of field measurement. It can be inferred that the system has relatively high dehumidification potential to lower the humidity of bedroom during nighttime comparing to natural approach. Therefore, the system outlined in this study could be an alternative tool for moisture problem. However, it is