Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

Similar documents
Solid Core and Split Core 4-20 ma Output Current Sensors CTS-20; CTP-20

Solid Core and Split Core Fixed Current Status Switches CSS-O,C; CSP-O,C -F (FIXED) SERIES

T7079A,B Solid State Remote Temperature Controllers

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

CR Series Command Relays

C554A Cadmium Sulfide Flame Detector

T6984F,G Electronic Floating Control Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats

The T6140A,B Remote Bulb Temperature Controller

L8005A,B; LS8005A,C,D Electronic Pool and Spa Controllers

C7031D,G,J C7041B,C,D,F,J,K,P,R Series 2000 Electronic Temperature Sensors

T4398A,B High Performance Electric Heat Thermostats

T4098A,B Deluxe Electric Heat Thermostats

Commercial/Industrial Combustion Control Level Three Announcement

CR7075 Two-Stage Lighting Controller

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

C7232A,B Sensor and Controller

F150E Media Air Cleaner

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

T6984 A,D,E Electronic Floating Control Thermostats

F200E Charged-Media Air Cleaner

RA889A Switching Relay

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

TG509, TG510, TG511, TG512 Versaguard Universal Thermostat Guards

C6097A,B Pressure Switches

M6063A Compact Rotary Mixing Valve Actuator

F25F Media Air Cleaner

H1008A,D Automatic Humidity Controls

Instructions For A and Flame Simulators

L8151A Triple Aquastat Relay

Sensors Product Overview. Reliable And Accurate Honeywell Sensors

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats XE88/XE100 SERIES

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

T8011R Programmable Heat Pump Thermostat

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

AQ475A Aquatrol Outdoor Temperature Compensator for Boilers

R7824, R7847, R7848, R7849, R7851,R7861, R7886 Amplifiers for 7800 SERIES Relay Modules

Greentrol Automation, Inc.

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

F59A Console 3-Speed Electronic Air Cleaner

P7810A-D Pressuretrol Controller

AQ255 and AQ257 Series Expansion Zoning Panels

Sensor Selection Guide. Sensing for Building Applications

Analog Room Pressure Monitor RPC Series

C7004B Flame Rod Holder

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

T8524 Deluxe Electronic Thermostat

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Current and Voltage Sensors

HE365A,B Powered Flow-Through Humidifier

T4398A,B Precision Electric Heating Thermostat

INTRODUCTION / TABLE OF CONTENTS

AQ250 Series Hydronic Control Panels

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

T834C Heating-Cooling Thermostat

MBCE-110/230UV Flame Sensor Module

Public Safety DAS Annunciator Panel

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

Sensor Interface Module Installation/Operation Instructions

Temperature Controllers

HE225A,B and HE265A,B Bypass Flow-Through Humidifier

Setra Model SRH Relative Humidity Sensor Series with Active or Passive Temperature Sensing Installation Instructions

LC1350 Level Controller

T874 Multistage Thermostat and Q674 Subbase

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats

Duct and Rough Service Carbon Monoxide Sensor

IS Series Pressure Sensing Switches

QPM21 Series Duct CO 2 and Air Quality Sensors

Sitron s CF Line of Flow Switch Monitors

4 Channel Contact Closure SFP DIN Fiber Link System

LC2200 Level Controller Installation and Maintenance Instructions

Installation Instructions for the Honeywell Force Sensors FSA Series Compensated/Amplified

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

Pump-Up Controller MODEL 4062

RA889A Switching Relay

Introducing SlimSeal SSL Connector

Flame Rod Manual. Publication Rev A

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Pump-Down Controller MODEL 4052

Power Supply Display Module PSDM. Installation and Operation Manual

19 mm Series Low Cost, Stainless Steel, Isolated Pressure Sensors

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Model HL-Z. High Line Wet/Wet Differential Pressure Transducer DESCRIPTION FEATURES POTENTIAL APPLICATIONS

SOLARLOK Interconnection System Installation Manual

Accuracy by Design Products for the HVAC Professional

Model SC3004. Transducer Display and Signal Conditioning Unit DESCRIPTION. Fourteen channel chassis FEATURES

HE420A Steam Power Humidifier

Carbon Monoxide Transmitter

U86B. Urea Dosing SPECIFICATIONS FEATURES APPLICATIONS

Model 3140 Series. Tension/Compression Pancake Load Cell DESCRIPTION FEATURES

Transcription:

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10 DESCRIPTION FEATURES PRODUCT DATA Solid and Split Core Vdc Output Current Transmitters. Fast Response Time. Integral Din Rail Mounting Flange. Easy Wiring, Polarity Sensitive Output. Accepts up to a 350 MCM (17.3 mm) Cable. Operates up to 250 continuous Amps. ly Accurate. 5 Year Limited Warranty. RoHS and WEEE Complaint. The CTS-05,-10 and CTP-05,-10 series current sensors monitor the current flowing to electrical equipment or buildings. The magnitude of this current is then converted into a linear and proportional 0 to 5 or 0 to 10 Vdc output signal, which can be monitored by your Building Management, DDC, or PLC controller. The CTS-05,-10 and CTP-05,-10 series current sensors have jumper selectable input ranges except for the 0 to 5 Amp input range. These current sensors should be used in load trending (current monitoring) type applications. The CTS-05,-10 and CTP-05,-10 series current sensors are an excellent choice for new installations, since you will not have to power down the unit and disconnect any wires during the installation process. The CTS-05,-10 and CTP-05,-10 series current sensors are fast acting, reliable, and extremely easy to install. No din rail mounting clips are necessary. All current sensors have an integral din rail mounting flange. The CTS-05,-10 and CTP-05,-10 series current sensors are fast acting and extremely accurate. All of the CTS-05,-10 and CTP-05,-10 series current sensors are factory calibrated using a NIST Traceable standard and shipped with the jumper placed in the largest jumper selectable range. A span adjustment potentiometer is included for minor field calibration or adjustments. The power for the CTS-05,-10 and CTP-05,-10 series current transmitter is induced from the conductor being monitored. This means that no external power supply is necessary for the installation of these sensors. The CTS-05,-10 and CTP-05,-10 series current sensors come with a limited five year factory warranty. Contents Description...1 Features...1 Specifications...2 Ordering Information...2 Safety...4 Installation...4 Troubleshooting...6 Current Conversion Formulas...6 63-2656

SPECIFICATIONS Supply Voltage: Induced from monitored conductor. Output Voltage: CTS-05; CTP-05 Series: 0 to 5 Vdc. CTS-10; CTP-10 Series: 0 to 10 Vdc. Amperage Ranges: 0 to 250 Amps (See Table 1). Accuracy: CTS-05; CTP-05: ±1.0% (2 to 100% FSO). CTS-10; CTP-10: ±1.0% (5 to 100% FSO). Response Time: CTS-05; CTP-05 Series: <100 ms. CTS-10; CTP-10 Series: <100 ms. Load: Calibrated into a 1 mohm Load. Operating Frequency Range: 50 to 600 Hz. Isolation Voltage: 1270 Vac. Aperture (Hole) Size: 3/4 in. (19 mm), Accepts up to 350 MCM (17.3 mm) Cables. Dimensions: See Figures 1 and 2. Din Rail Size: 1-3/8 in. (35 mm). Unit Weight: CTS-05,-10: 0.22 lbs. (0.1 kg). CTP-05,-10: 0.24 lbs. (0.1 kg). Enclosure Rating/Color: UL94-5VB. Operating Temperature Range: 5 to 140 F (-15 to 60 C). Operating RH Range: 0 to 95% RH, non-condensing. Agency Approvals: CE, UL. Environmental Compliance: RoHS-Directive 2002/95/EC. WEEE-Directive 2002/96/EC. Table 1. Operating Specifications. Product Number Core Type Output Range Jumper a Max. Current Cont. Max. Current for 6 secs. CTS-05-050-VDC Solid Core 0 to 5 Vdc 0-10 Amps 0-20 Amps 0-50 Amps CTS-05-250-VDC Solid Core 0 to 5 Vdc 0-100 Amps 0-0-250 Amps CTS-10-050-VDC Solid Core 0 to 10 Vdc 0-10 Amps 0-20 Amps 0-50 Amps CTS-10-250-VDC Solid Core 0 to 10 Vdc 0-100 Amps 0-0-250 Amps 100 Amps 150 Amps 360 Amps 60 Amps 100 Amps 160 Amps 160 Amps 320 Amps 125 Amps 225 Amps 300 Amps 250 Amps 450 Amps 500 Amps 80 Amps 300 Amps 500 Amps ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. 63-2656 2

Table 1. Operating Specifications. (Cont.) Product Number Core Type Output Range Jumper a Max. Current Cont. Max. Current for 6 secs. CTP-05-050-VDC Split Core 0 to 5 Vdc 0-10 Amps 0-20 Amps 0-50 Amps CTP-05-250-VDC Split Core 0 to 5 Vdc 0-100 Amps 0-0-250 Amps CTP-10-050-VDC Split Core 0 to 10 Vdc 0-10 Amps 0-20 Amps 0-50 Amps CTP-10-250-VDC Split Core 0 to 10 Vdc 0-100 Amps 0-0-250 Amps 100 Amps 150 Amps 360 Amps 60 Amps 100 Amps 160 Amps 160 Amps 320 Amps a All current sensors are shipped from the factory with the jumper set in the high range. 125 Amps 225 Amps 300 Amps 250 Amps 450 Amps 500 Amps 80 Amps 300 Amps 500 Amps TOP VIEW 13/32 (10) H ML INPUT H=0-250A RANGE: M=0-200A L=0-100A COM 0-10 VDC 13/64 (5) TYP. LEFT SIDE VIEW 2-27/32 (72) FRONT VIEW RIGHT SIDE VIEW 25/32 (20) 2-17/64 (58) TERMINAL BLOCK C U L US 9/64 (4) 1-3/8 (35) 3-3/8 (86) 63/64 (25) M23583 Fig. 1. CTS-05,-10 Current Switch Dimensions in inches (mm). TOP VIEW 1/2 (13) H M L INPUT H=0-250A RANGE: M=0-200A L=0-100A COM 0-10 VDC 7/32 (6) TYP. 2-27/32 (72) LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW C U R L US TERMINAL BLOCK 3/4 (19) 49/64 (19) 2-45/64 (69) 9/64 (4) 1-3/8 (35) 3-21/64 (85) 1-5/64 (25) M23593 Fig. 2. CTP-05,-10 Current Switch Dimensions in inches (mm). 3 63-2656

C R U L US SOLID CORE AND SPLIT CORE 0-5, 0-10 VDC OUTPUT CURRENT SENSORS SAFETY WARNING For CTS-05,-10 ensure that all power sources are disconnected and locked out before installation as severe injury or death may result from electrical shock due to contact with high voltage wires. 3X CAUTION This product is not intended to be used for Life or Safety applications. CAUTION This product is not intended for use in any hazardous or classified locations. C R U L US INSTALLATION M23603 Make sure that all installations are in compliance with all national and local electrical codes.only qualified individuals that are familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation.the current sensor will not require external power, since the power for the current sensor is induced from the conductor being monitored. The current sensors may be mounted in any position using the (2) #8 x 3/4 in. (19 mm) Tek screws and the mounting holes in the base or snapped directly on to the 1-3/8 in. (35 mm) DIN rail (See Figures 3 and 4). Leave a minimum distance of 1 in. (25 mm) between the current sensor and any other magnetic devices such as contactors and transformers. 3X Fig. 3. Sensor Placed on Rail. M23604 Fig. 4. Sensor Removed from Rail. 63-2656 4

R SOLID CORE AND SPLIT CORE 0-5, 0-10 VDC OUTPUT CURRENT SENSORS Latch Operation (for Split Core) Pressing down on the two (2) side tabs and swinging the cover open opens the split core current sensor as shown in Fig. 5. Lifting up on the latch with a flat-tip screwdriver as shown in Fig. 6 can also open the unit. Press down firmly on the cover to close the current sensor. An audible click will be heard as the tab slides over the tongue on the base. CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open. Silicone grease, present on the cores to prevent rust, can capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good contact between pole pieces. Visually check the mating parts of the core before closing the current sensor. C U R L US U L C US M25298 Fig. 5. Opening Sensor by Hand. Wiring Honeywell recommends the use of 16 to 22 AWG (1.3 to 0.3 mm 2 ) twisted pair wires or shielded cable for all current sensor applications. NOTE: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop. C US R U L M25299 When removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The current sensors terminals are polarity sensitive and represent a linear 0 to 5 or 0 to 10 Vdc output signal. The recommended torque to be used on the terminal block connections is 5.93 in-lbs (0.67 Nm). The aperture (hole) size of the current sensor is 3/4 in. (19 mm) and will accept a maximum cable diameter of 350 MCM (17.3 mm). Fig. 6. Opening w/screwdriver. + +12 TO 35 VDC _ DC POWER SUPPLY _ + 4 TO 20 MA + SIGNAL INPUT COMMON BUILDING AUTOMATION SYSTEM M23607 Fig. 7. Wiring Example. 5 63-2656

CONNECTIONS: SHIELDED, TWISTED PAIR CABLE IS RECOMMENDED FOR THESE CONNECTIONS. NOTE: GROUND THE SHIELD AT THE CONTROL SYSTEM END ONLY! POWER: THESE CURRENT SENSORS DO NOT NEED AN EXTERNAL POWER SOURCE, SINCE THE POWER IS SELF-INDUCED FROM THE MONITORED LOAD OR CONDUCTOR. (-) SIGNAL COMMON + 0-5 OR 0-10 VDC ANALOG INPUT GND (SHIELD) PLC, DDC, OR DATA ACQUISITION SYSTEM M23767 Fig. 8. Shielded Cable Example. TROUBLESHOOTING Table 2. Troubleshooting Problem Solution No reading. Verify that there is current flowing through the conductor being monitored with a clamp-on current probe. The power for the current sensors is induced from the conductor being monitored. Check the polarity of the circuit. Verify that the terminals are screwed down, wires are firmly in place. Disconnect the wires from the current sensor output. Measure the voltage across the current sensor output with a Voltmeter to verify that the sensor is working properly. Erratic readings. Verify that the wires are terminated properly. In areas of high RF interference, shielded cable may be necessary to stabilize signal. Inaccurate readings. If you suspect that the current sensor is not reading within the accuracy specifications, please contact the factory for assistance. CURRENT CONVERSION FORMULAS To convert the voltage Vdc output signal to a current reading. For 0-10 Vdc, Current Reading = Vdc output/vdc span x amp span. For example: For a reading of 4 Vdc on a 0-10 Vdc output with a 0-150 amp span: Current reading = 4 Vdc/10 Vdc x 150 A = 60 Amp. 63-2656 6

7 63-2656

Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com U.S. Registered Trademark 2007 Honeywell International Inc. 63-2656 J.I. 01-07