SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

Similar documents
SSL & SBS Engineering Guide

PRODUCT CATALOG BLOWER COILS.

FCC Fan-Coil Units High-Performance, Vertical

catalog CDV Fan-Coil Units High-Performance, Vertical

Horizontal and Vertical DIRECT DRIVE BLOWER COIL UNITS. Rating and selection at

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

engineering guide FH Fan-Coil Units Low-Profile, Horizontal

CATALOG. MQL Modular Air-Handling Units

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

Chilled Water DOAS Fan Powered Terminal Units

engineering guide FN Fan-Coil Units High-Performance, Horizontal

NEW FAN COILS BLOWER COILS AIR HANDLERS NEW PRODUCT OFFERING.

AIR HANDLER SPECIFICATION

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION FAN COIL UNITS

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

SECTION AIR HANDLING UNIT

XeteX, Inc. All Rights Reserved.

1.1 This section applies to air handling units for HVAC Systems.

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

RAV Engineering Guide

SECTION AIR COILS

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Modular Supply Make-Up Air Unit

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

Catalog Destiny Indoor Air Handler. Models Horizontal Configuration. Vertical Configuration

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Modular Heating & Ventilating Unit Model IGX-HV

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

New Product Offering BLOWER COILS ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

SKYPAK II, 3 Ton Series, gives you a

TABLE OF CONTENTS. FCV Nomenclature 3. FCV Features & Construction 4. FCV Engineering Specifications 5. FCV Fan/Coil Data 6

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

KIC Air Curtains. Technical Guide

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Commercial Fan Coil and Air Handling Equipment

Direct Fired Heater Model AD Specification

SKYPAK II, 3 Ton Series, gives you a

Large Capacity Fan Coil Units Belt and Direct Drive Cabinet and Hideaway

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Warm. IFR Indirect Fired Gas Heating Systems. Applied Air. Keeps You

TYPICAL CPA SPECIFICATIONS

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

SECTION CONVECTION HEATING AND COOLING UNITS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SeasonMaker ThinLine Fan-coil Units

Titus Quick Reference Guide ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

CWA4 Chilled & Hot Water Fan Coil

SECTION ROOFTOP REPLACEMENT AIR UNITS

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

SECTION AIR COILS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

BLOWER COILS BLOWER COILS. Providing You With Air Distribution Solutions F2-1 KRUEGER 2014 FORM - BC.HV /05/14

DUCTED SPLIT AIR CONDITIONERS GCUN-A/GDS-A SERIES

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

Product Specifications. Vertical Floor Consoles By First Co.

SeasonMaker ThinLine Fan-coil Units

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

Construction Standards Page

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

SECTION CONVECTION HEATING AND COOLING UNITS

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You.

Indirect Gas-Fired Make-Up Air

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

A. This Section includes air-handling units with coils for indoor installations.

MERIT Series R-410A - Upflow / Horizontal

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

MACH N-407 Heat Pump Air-Cooled Chiller

Transcription:

SO TOUGH, WE GUARANTEE IT. SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL SSL SBS www.superiorrex.com

SSL / SBS Series: BIG ON FEATURES; SMALL IN SIZE Contractors All SSL/SBS model blower-coil units are shipped completely assembled, reducing field-installation time and labor. All units are thoroughly inspected and tested prior to shipment, eliminating potential problems at startup. Motor wiring is brought to a junction box and terminated. The junction box is located on the outside of the unit casing, reducing electrical hook-up time. A wide variety of fan-discharge configurations allow for increased flexibility and easier installation on the jobsite, resulting in cost reductions by eliminating expensive elbows, etc. Designers The extensive variety of standard options available on the SSL/SBS units are where you find the versatility to fit any HVAC system designer s needs. High-efficiency motors, starters, disconnects and fusing mean easier coordination between mechanical and electrical trades. Coil options allow for 4 or 6-row cooling coils. Owners SSL/SBS model blower coils are constructed from galvanized steel, surpassing the ASTM 125-hour, salt-spray test for corrosion and rust. Insulation, which is 1-inch thick, scrimreinforced, and foil-faced, is glued, pinned and taped for maximum adhesion. Insulation complies with UL 181, ASTM-C1071, NFPA 90A and 90B and meets bacteriological standard ASTM-C665 and C1136 for mold, mildew and humidity resistance. All units, with or without electric heat, are cetl-listed and labeled. All wiring is in compliance with NEC, assuring safety and quality for the owner. Options include: Mixing boxes with standard low-leak dampers, blowthru electric heat with single-point power connection. All electric heat units are listed with ETL as an assembly and carry the cetl label. Typical Installations Model SBS, Rear Return with Mixing Box Mechanical Room Layout Model SSL, Bottom Return with Return Plenum Closet or Confined Space Layout 02

SSL / SBS Series: DIMENSIONS, COIL & FILTER DATA SSL SSL SBS Unit Size H W L A B C D 08 46 [1168] 26 [660] 19 [483] 6½ [165] 6 7 /8 [175] 9 9 /16 [243] 16 [406] 12 46 [1168] 26 [660] 21 [533] 7½ [190] 8¼ [210] 8 7 /8 [225] 20 [508] 16 54 [1372] 29 [737] 25 [635] 7½ [190] 10¼ [260] 9 3 /8 [238] 24 [610] 20 54 [1372] 29 [737] 28 [711] 11 3 /8 [289] 13¼ [337] 7 7 /8 [200] 24 [610] 25 30 60 [1524] 60 [1524] 39 [991] 39 [991] 28 [711] 28 [711] 13½ [343] 15¼ [387] 12 7 /8 [327] 15 [381] 13 1 /16 [332] 12 [305] 24 [610] 24 [610] SBS Coil Face Area and Filter Data Unit Size Nominal CFM Internal Cooling and Heating Coils Discharge Section Heating Coils 2 Filters (Quantity) and Size Filter Face Area 08 800 2.1 [0.20] 2.1 [0.20] (1) 16 x 20 x 2 [406 x 508 x 51] 2.2 [0.20] 12 1200 2.8 [0.26] 2.1 [0.20] (1) 20 x 20 x 2 [508 x 508 x 51] 2.8 [0.26] 16 1600 3.6 [0.33] 3.2 [0.30] (1) 24 x 24 x 2 [610 x 610 x 51] 4.0 [0.37] 20 2000 4.8 [0.45] 3.2 [0.30] (1) 24 x 24 x 2 [610 x 610 x 51] 4.0 [0.37] 25 2500 5.7 [0.53] 4.6 [0.43] 30 3000 6.8 [0.63] 5.7 [0.53] Notes: 1. Standard filters are 2 throwaway; optional filters are 2 pleated 2. Filter sizes are nominal and standard size, measured in inches [mm] 3. Coil and filter face areas are measured in square feet [square meters] (1) 24 x 24 x 2 [610 x 610 x 51] (1) 12 x 24 x 2 [305 x 610 x 51] (1) 24 x 24 x 2 [610 x 610 x 51] (1) 12 x 24 x 2 [305 x 610 x 51] 6.0 [0.56] 6.0 [0.56] Notes: 1. All dimensions are inches [mm] and are +/- ¼ [6mm] Metric values are soft conversions 2. Motor/drive location may be specified Left or Right Hand. Standard control-enclosure location matches motor/drive position. 3. Provide sufficient clearance to access electrical controls and comply with all applicable codes and ordinances 4. Maximum total internal coil rows: 6 5. Left-hand unit shown; right-hand unit has CW and HW piping connections mirrored 6. Filter assembly runs the full length of the unit size 7. Drawings not for installation purposes Note: Drawings are not to scale and are not for installation purposes. Contact your Superior Rex representative for more information. All data and dimensions are subject to change without notice. 03

SSL / SBS Series: BLOWER-COIL UNIT FEATURES Standard Features: Construction Galvanized-steel cabinet construction, minimum 18 gauge 1 -thick, 1.6-lb/ft,3 scrim-reinforced, foil-faced insulation, glued, taped and pinned in place 1 supply duct collars Gasketed, removable access panel sized for easy handling Galvanized-steel drain pan with 1-1/8 ODM copper pipe outlet Left- and right-hand arrangement Fan Assembly Forward-curved (double-width, double-inlet) fans Statically and dynamically balanced Solid steel shafting Ball bearings with a minimum design-average life (L 50 ) of 100,000 hours Fan Motor and Drive NEMA-design ODP motors 1750 RPM, single-speed, 60 Hertz Single-phase motors with inherent thermal protection Three-phase motors Rigid-mount, adjustable, motor base Standard cross-section V-belt drive with 1.2 service factor Adjustable-pitch motor pulley and fixed-pitch blower pulley Coils AHRI Standard 410-certified and labeled 1/2 O.D. seamless copper tubes Collared and corrugated aluminum fins Manual air-vent plug on all water coils 300 PSIG working pressure at 200BF Steam coils rated at 15 PSIG maximum Copper ODM sweat connections 0.016 tube wall on water and evaporator coils 0.025 tube wall on steam coils High-efficiency, aluminum-fin surface for optimizing heat transfer, pressure drop, and carryover Filters and Filter Rack Top-access, flat-filter rack (SBS only) Front-access filter rack (SSL only) Standard-size, 2 nominal, throwaway filters Electrical Fan motor wired and terminated to J-box All units ETL-listed in compliance with UL/ANSI Optional Features: Construction Stainless-steel drain pan with 1 MPT galvanized pipe outlet External rubber-in-shear or spring-type vibration isolators, floor mount Fan-discharge arrangements Discharge plenum w/dbl.-deflection discharge grille Access panel with lift-and-turn fasteners Double wall access panel w/lift-and-turn fasteners Return plenum with removable panels (SSL only) Base rails with rigging slots, factory-assembled and installed Fan Motor and Drive TEFC motors High-efficiency motors Coils 4 and 6-row chilled-water or DX coils 1 and 2-row hot-water coils 1 and 2-row hot-water or standard-steam coils in discharge-coil section only Hot-water coil in preheat or reheat position Stainless-steel coil casings 0.025 tube wall on water and evaporator coils Auto air vents on water coils Filters and Filter Rack Side-access filter rack (SBS only) 2 pleated filter (MERV 8) Spare throwaway or pleated filters Inlet-Damper Section (SBS rear-return unit) Factory-assembled and installed Heavy-gauge, galvanized-steel, formed blade dampers Low-leak dampers with extruded-vinyl blade seals and flexible-metal jamb seals Parallel-blade operation Interconnecting damper linkage Electrical Motor wiring in conduit Motor starter (contactor with overload for three-phase; contactor for single-phase), factory-installed (mounted and wired) Door-interlocking disconnect switch (non-fused) (with main fusing) Hand-off-auto switch (HOA) Main fusing 04

Notes Electric-Heat Section Factory-mounted electric heater with single-point power connection, ETL-listed as an assembly 05

Notes 06

Notes 07

Superior Rex 605 Shiloh Road Plano Texas 75074 (ofc): 972.212.4800 (fax): 972.212.4884