A FREAK INCIDENT OF A BED SUPERHEATER FAILURE

Similar documents
A CASE OF BOILER FAILURE DUE TO OVERSIZING OF BOILER FEED PUMP

Problem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4.

CASE STUDY ON EFFICIENCY & AVAILABILITY DETERIORATION IN AN AFBC BOILER

SURGING AND BLOW OUT OF LOOP SEALS IN A CFBC BOILER. By K.K.Parthiban Venus energy audit system

LESSONS LEARNT FROM TROUBLESHOOTING

Document Code: 1 (15) Issuing date: Status:

CIRCULATION FAILURE IN A BOILER. By K.K.PARTHIBAN, Boiler Consultant Venus Energy Audit System /

AUDITING ENERGY SYSTEM EFFECTIVELY

A Newsletter published by. for Industrial Steam and Power Users

STEAM & POWER ENGINEERS

Document Code: 1 (13) Issuing date: Status:

Boiler. Fire tube Boiler:

2x58 MW Coal Fired Power Plant at Mauritius

Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS

BHEL Steam Generators Material Selection Overview by Veerendar Aluvala DM/BHEL/Trichy

CORTEC. CORTEC

Akiki Engineering Est.

ROTARY DRYER CONSTRUCTION

The equipment and materials shall be designed and constructed in accordance with the ASME code section I 2001 ED A02 and Chinese Standards.

BASIC BOILERS NAME :- DATE :-

CHAPTER 2: PROPERTIES OF STEAM AND STEAM POWER

Biomass Energy Systems

WATER TUBE SOLID FUEL SERIES YOSHIMINE CO., LTD

Boiler Light-up. Kumar Rupesh Date: 03-Sep-13

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

Steam and Gas Power Systems Prof. Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee

A CASE STUDY ON BOILER TUBE FAILURE AT JPL

Tuesday, 18 November Video Links. Oil Blow Through 13 November BLOW THROUGH ON BOILER UNIT 6 BEGINS.

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

AIM OF THE EXPERIMENT:- Study of boilers (fire tube, water tube) APPARATUS REQUIRED: - SL.NO NAME OF THE APPARATUS SPECIFICATION QUANTITY 01 Fire tube

Boiler Mountings. Engr. Omar Sadath, Maritme Lecturer & Trainer, Bangladesh

ELECTRO STATIC PRECIPITATOR [ESP]

Medupi Unit 6 ACC hot cleaning: Method and results

SCHNEIDER-KESSEL BERLIN

CONTROLLING BOILER SWELL AND SHRINK

2.0 VISIT TO SITE. It was immediately evident entering the boiler house that there are several issues with the existing installation.

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

USER S MANUAL, MAINTENANCE MANUAL INSTALLATION INSTRUCTIONS

Boiler Basics. Design and operation

FLUIDIZED BED BOILERS

TEPZZ 87_ 6A_T EP A1 (19) (11) EP A1 (12) EUROPEAN PATENT APPLICATION

ACC is suitable for all types of diesel engines. The ACC / fresh water mixture has no flash point and cylinder lubrication is not impaired.

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

ProMoss TM Plant-Based Water Treatment Solves Problems in Tobacco Manufacturing Plant Air Washer Systems

SECTION Boiler Controls & Waste Heat Recovery

WHAT IS A BOILER? BOILER IS AN EQUIPMENT WHICH PRODUCES STEAM AT THE REQUIRED PRESSURE AND TEMPERATURE. BOILER DESIGN, MANUFACTURE & INSTALLATION ARE

500 EX Fusion Compressor Series

Solution of I Mid Term Steam Engineering 6ME5A

Series 300 VTB. Installation Instructions

Optimizing Strategy for Boiler Drum Level Control

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices

Main components. Buying all components from same manufacturer or reseller it guarantees better compatible and service if something happens

THERMAL ENGINEERING & GAS DYNAMICS ME-6002

Descaler & Prevention

Boiler Basics: Design & Application Differences. Presented by Steve Connor July 30, 2014

HEIN-HESØ cleanliness in perfection Worldwide distribution of German/Danish quality Our recipe for success customer orientation

CHP-turbine room. CHP can capture almost EXTRACTED STEAM 20 PSI HIGH-PRESSURE STEAM 1250 PSI HEAT EXCHANGER HOT WATER SUPPLY F

Operating instructions

Tier1 Water Home Filtration System

CONTENTS. B. System Design and Performance Requirements

Gulf Perlite L.L.C: Perlite Filter Aid Technical Brochure

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SULPHUR RECOVERY UNIT

BACK WASH INSIDE THE SPA

Green Energy Engineering, Inc.

Biomass Drum Dryer LMK 2000 Model

S. P. THERMAL SYSTEMS INC.

Learning From Risk Control System Failures. Mike Jones

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Tel: Fax: Website:

CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings

Boiler drum level controller using Microcontroller

MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel.

Thank You for Attending Today s Webinar:

Water Treatment Improves Your Bottom Line DAVE PICOU WATER CARE SERVICES DIVISION JOHN SCHULTZ TEXTILE CARE DIVISON

Water Technologies. PolyBlend DP Series Dry/Liquid Polymer Feed Systems

Commercial dishwashing & cleaning agents

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007

IFE Level 3 Diploma in Fire Science and Fire Safety

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

M-Sens 2 Application overview. FlowJam application overview. Online moisture measurement for solids. For measuring capillary and surface humidity

TEMPLATE ASSISTED CRYSTALLIZATION. Presented By Ryan Lessing 11/13/2014

Speransa 2008: Round table: Nuclear and sustainable development Universitad Politecnica de Valencia \UPV - Passive safety systems -

Akiki Engineering Est.

Steam Systems 101. Understanding Your Energy Systems Better. May 5, 2016

SUSHI SHOWCASE BMCSS05

.2 Section Waste Management and Disposal..5 Section Cleaning and Startup of Mechanical Piping Systems.

VENDING PROVEN HYGIENE & CLEANING FOR WATER COOLERS. Performance Focus. Recommended Products

Industrial Dust Aspiration Solutions. For optimal protection of plant and environment.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

AUTOMATION OF BOILERS USING LABVIEW

Originators of the Flexible Water Tube design

Vent-Rite. Cast Iron And Steel Receivers. Simplex, Duplex, Triplex And Quadruplex Units. Pump Capacities To 150 GPM. Discharge Pressure To 75 PSI

Installation, Operation and Maintenance Manual

Polaris PHEs vs. Shell-and-Tube Exchangers

Transcription:

A FREAK INCIDENT OF A BED SUPERHEATER FAILURE Case studies are interesting. This case is very interesting one. The customer had a bed SH failure. At the time of the visit, the failed bed SH tube was not available at the plant. It was sent to boiler manufacturer for their analysis. However the photograph was available to see the nature of failures. A brief on the boiler This is a 100 TPH, 105 kg/cm2, 520 deg C coal fired AFBC boiler. The unit has been in operation for more than 3 years. The boiler is equipped with under bed feeding arrangement. The boiler has 5 compartments. Occurrence of failure It was informed that there had been coal flow problems in the bunker & fuel line choking problems. This had led to the frequent non availability of the compartments. The turbine had come to base load often and at times the turbine had to be tripped. During the turbine trip, the MSSV was closed after slumping of the boiler. As the lines were being cleared, the compartment no 3 was activated and at this moment the bed SH had bursted. The bed SH tubes are located in 3 rd, 4 th & 5 th compartments. The failure had occurred just above the fuel feed point. Analysis of the appearance of the failed portion As the failed bed SH tube edge appeared sharp ( see photo 1) and there was no long term swelling of the tubes, it was concluded that the tube had failed due to sudden & localized overheating (no indication of starvation). Other bed tubes did not indicate any burning appearance nor did the tubes show up any swelling in OD. Suggested failure mechanism Localized overheating failure takes place when the metal is insulated from steam cooling by the presence of a dirt / deposit. The dirt gets transported from the steam drum to the failure spot. Above the fuel feed point the heat flux being high, the tube can fail. The combustion can take place when the coal is available from the fuel line or when the coal is spilled from the adjacent compartments. Diagnosis of the failure Up to this point summarizing the cause was easy for me. I had to now prove the carryover mechanism. I requested for the inspection of steam drum. 1. The steam drum was opened and checked for possible carryover. The evidence of foaming & carryover was seen inside the drum. 2. The foaming had occurred due to high phosphate chemical dosage in the slumped boiler. In the discussion, it came out that the HP dosing pump used to be in operation during the when the boiler was hot slumped for attending coal jamming in fuel lines. On restart of the boiler, water being hot and concentrated with phosphate, foaming had taken place. The presence of foams could be seen up to the secondary drier. See photographs 2 to 7. At two or three places the whitish powder accumulations were seen. 3. For the last three months prior to failure, the boiler had been on high ph (values seen up to 9.8) and phosphate level was seen up to 15 ppm. Though this is not a direct cause for this failure, but

the boiler had been corroding and the drum water is seen to be dirty. The drum surface up to NWL is seen to be brownish indicating there had been corrosion at times. The corroded iron particulate remains could be seen in the surfaces of drum internals. 4. It was learnt that the boiler was filled always through the economiser for hydrotest purpose. This can transport any dirt from the boiler water to SH circuit. At some point of the time the dirt can get inside the tube and lead to localized overheating failure. I suggested following remedial actions to avoid future failure 1. The HP dosing pump start / stop shall be interlocked with the boiler feed pump. 2. The chemical dosing shall be regulated with respect to steam flow. For this purpose VFD is required at HP dosing pump. There can be additional control loop. 3. Always the SH should be filled first and the water should spill in to the steam drum and then filling can be continued through the economiser. A 65 nb filling line can be connected to SH drain header with suitable valves for isolation. 4. I advised customer not to operate the bed SH compartment unless the compartments with evaporator tubes are in operation. I suggested the following permanent remedial actions to avoid boiler operational disturbances 1. The root cause of the problem is basically from the coal handling plant. The vibratory screen blinding seemed to have caused all the troubles. Screen blinding is a serious problem during monsoon in the conventional vibratory screen. Flip flop screen is the right choice to handle high moisture coals. 2. The present coal feed arrangement above the drag chain feeder is not OK. The load of coal in the bunker allows compacting of coal. This sort of defect is seen in several installations. The feeder chute should be designed in such a way, that the pressure from the coal column is used for loosening the coal. 3. When the coal has more powder content and water content, the lumps form in the bunker. Rectangular shaped bunkers have sharp corners where the hopper walls join. Circular bunker with conical hoppers avoid this problem. A static bar screen above the feed hopper was recommended so that lumps could get filtered. This will prevent the lumps going to feeder & fuel feed line. This will avoid the PA line choking. Lesson learnt For every problem the diagnosis must be completed before simply putting back the boiler in operation. I liked the customer approach that he did not give up after the manufacturer failed to identify the cause. At least the future failure can now be avoided. I was very happy to talk in the group discussion arranged for the entire operating team. The author is a Graduate from IIT (Madras) and Postgraduate from Madras University in Thermal Engg. He is a Boiler specialist with 28 years experience and had worked for Indian boiler manufacturing companies. He extends service for trouble shooting of boilers and systematic auditing of boilers at design / construction / operation / shut down.

Photo 1: This is the bed SH tube failure experienced. The failed portion is in the 3 rd compartment. The edge of the failed portion of the tube is thin in nature. This indicates there has been sudden overheating situation. Photo 2: The drum is with the mark of excess of phosphate in the drier area.

Photo 3: Presence of whitish deposit in the second stage drier. Photo 4: The presence of whitish marks along the edge of the primary drier in the steam space.

Photo 5: The whitish sparkling particles seen above the normal water level in the drum. This must be due to foaming created by excess phosphate chemical dosing in the drum. The dosing had been on when the boiler was under slumped condition. Photo 6: The whitish deposit seen at the weldment. The sparkling particles are seen above the normal water level. The dark colored water indicates that there had been high ph in the boiler water corroding the boiler.

Photo 7: The boiler water chemistry had not been alright. The boiler water regime had been outside the even the coordinated phosphate control curve. Photo 10: Presence of mud in the boiler water. The back filling of SH to be practiced to avoid carryover of dirt to SH sections.

Photo 11: This is a boiler wherein the drum internal surface & turbo separators indicate the perfect boiler water chemistry. Photo 12: The fuel feeding on the left side is what is in this plant. The weight of the coal acts on the feeder. It makes cakes of coal. The one on the right is what is in another plant. The coal slides through by virtue of the hydrostatic head of coal. The lump formation will be avoided.

Figure 1: This is an illustration of the bunker outlet chute in which the hydrostatic pressure does not act on the feeder. At the same time the pressure helps in loosening the coal avoiding the coal flow problems and caking of coal powder during monsoon times. Figure 2: The flip flop screen is designed to work on high moisture.