Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Similar documents
Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Performance Optimization of the Evaporative Condenser Design

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Design & Fabrication of Hybrid Cooler

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Enhancement of COP in Vapour Compression Refrigeration System

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Modified Air Cooler with Split Cooling Unit

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

η second law = Second law efficiency

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Performance investigation of Air-conditioning system using ejector as expansion device

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Assessment of Water Cooled Condenser Refrigeration System

HVAC Fundamentals & Refrigeration Cycle

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

Waghmare Tushar Ramrao, D.S.Nakate

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Experimental Analysis and Performance Comparison between Evaporative Cooling System and Air Conditioning System

Scientific Journal Impact Factor: (ISRA), Impact Factor: Methodology. [Yadav, 3(9): September, 2014] ISSN:

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

DEEPAK PALIWAL, S.P.S.RAJPUT

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Performance Evaluation of Evaporated Water In Cooling Towers

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Fabrication of A Prototype for Condensation of Water on Metal Surface Using Peltier Modules

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

Design and Development of Water Cooled Condenser for Domestic Refrigerator

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Design, Manufacturing of Chilled Water System for Process Cooling Application

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Design and Development of Modified Air Cooler and Storage System

DESIGN, DEVELOPMENT AND TESTING THE

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

REFRIGERATION AND AIR CONDITIONING

ISSN Vol.08,Issue.21, November-2016, Pages:

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

II. OBJECTIVE OF RESEARCH

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

A Review of Different Types of Combine Cooling System

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

Evaluation of COP in Refrigeration System by using Different Refrigerants

International Journal of Informative & Futuristic Research ISSN (Online):

R07. Answer any FIVE Questions All Questions carry equal marks *****

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Cost-Effective COP Enhancement of a Domestic Air Cooled Refrigerator using R-134a Refrigerant

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

Experimental Investigations of Heat Pump for Domestic and Light Commercial Market.

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Analysis of Vapour Compression Refrigeration System with Refrigerants R134a, R143a, R152a, R290 and R32

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer


Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Pressure Enthalpy Charts

Transcription:

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Dr. Akash Langde 1, Zeeshan Jamal 2, Shahrukh Jamal 3, Mohammad Shumoil Ansari 4 1Professor, Department of Mechanical Engineering, Anjuman College of Engg. & Tech Nagpur, India 2Department of Mechanical Engineering, Anjuman College of Engg. & Tech Nagpur, India 3Department of Mechanical Engineering, ITM College of Engg, & Tech Nagpur, India 4Department of Mechanical Engineering, Sinhgad College of Engineering, Pune, India. ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - The performance of a refrigeration cycle can be increased by reducing the compressor work or by increasing the refrigeration effect. It was found through the literature that advancement in the design of compressor reduce the compressor work and also the advancement in the capillary tube increased the refrigerating effect. Modifications in condenser are meant to increase degree of sub-cooling of refrigerant which in turn increases refrigerating effect. The improvement in coefficient of performance and reduction of energy consumption of a window air conditioning system when retrofitted with ducts and evaporative cooling in the condenser of Window air conditioner is reviewed in the study. The condensing unit is fitted with evaporative air cooling unit. This condenser can exchange heat with the ambient air, cooled with evaporative cooling which is much lower in temperature than atmospheric air. By application of evaporative air cooling it is possible to ex-change more heat. A Window air conditioner is introduced by putting evaporative air cooler which includes the cooling pads system and injecting water on them in order to cool down the air before it passes over the condense. This paper presents the concept of effect of Undercooling on the Coefficient of Performance of Vapor Compression Refrigeration System mainly carried out to improve the coefficient of performance of system. Key Words: Window Air-Conditioning system, Dessert Air cooler, Modified condenser with ducts, Undercooling, Coefficient of performance. 1. INTRODUCTION Energy consumption has become an important aspect when it comes to system optimisation. Energy costs and environmental concerns have made energy optimization a critical issue. Therefore, energy efficiency is the major aspect in reducing global warming emissions. In context to this, new technologies to conserve energy, to use energy effectively, to use alternative energy sources and to reduce the energy costs such as solar energy, wind energy, tidal energy etc. are under continuous development. This study shows theoretical and experimental studies of improved vapour compression refrigeration cycles capable of improving the efficiency of cycle and making it cost effective. The least expensive way of reducing operational costs in a system is to lower its energy consumption best done by increasing energy efficiency. The improvement of refrigeration cycle performance can be done by reducing the compressor work consumption, increasing the condenser heat rejection capacity or reducing the difference between condenser and evaporator pressures. Because of its simplicity and compactness window air conditioner is generally used in small size in residential and commercial buildings. The condenser used in this system for heat rejection process which is generally air cooled, it seems reasonable as far as the air temperature in summer is moderate and not too high (about 45º C). But when the air temperature increase and approaches 50º C or higher Window air conditioner that consist of two parts fan coil unit and condensing unit gives poor performance. The performance of window air conditioner depends on heat transfer between the condenser coils and the airflow. Hence by cooling ambient air temperature by evaporative cooling could results in substantial energy and demand saving, this small saving could save considerable amount of watts unit. In air conditioning system generally there are three types of condensers using air cooled, water cooled, and evaporative cooled. Condensers used in small residential Window air conditioners are mostly air cooled condenser. Changes in condenser to improve coefficient of performance refers to increase degree of under-cooling. The evaporative cooler is retrofitted in front of air-cooled condenser to precool outdoor air before entering the condenser. The precooled air is carried through the duct to the condenser. Tests were carried out and results were predicted that the use of the evaporative cooler results in an increase in the refrigeration effect. 2. WORKING PRINCIPLE If unsaturated air is passed through a spray of continuously re-circulated water, the specific humidity will increase while the dry bulb temperature decreases. This process is called adiabatic saturation or evaporative cooling. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 548

Air movement over the surface of condenser tubes is by natural convection. As air comes in contact with the warmcondenser tubes, it absorbs heat from the refrigerant and thus the temperature of the air increases. Warmer air being lighter rises up and cooler air replaces it from below to take away the heat from the condenser. This cycle goes on. Since air moves very slowly by natural convection, the rate of flow of heat from the refrigerant to air will be small. Thus a natural convection condenser is not capable of rejecting heat rapidly. Therefore a relatively large surface area of the condenser is required. Fig-1: Working Principle. Air cooler pumps water on the evaporative honey comb cooling pad which is kept in the way of air over the condenser and provides cooling effect by evaporation of water. This provides the cooled & humidified air. This cooled & humidified air flow over the condenser surface by forced draft fan. The place of air cooler should be installed in a way to give a good cooling effect and also takes minimum space from out-side partition of our equipment 3. EXPERIMENTAL SETUP AND COMPONENTS Window A.C. Dessert Air Cooler. 3.1 Window A.C Window Air-Conditioner selected for the project has the following specifications: Refrigerant used: R-22 Capacity of the AC: 1TR Compressor capacity: 1HP The suggested window air conditioner consists of 4 major parts they are as follows: Compressor (operating pressure limits 3 to 15 bars). Expansion device (Capillary Tube). Evaporator. 3.2 Modified Condenser with Ducts The functions of the condenser are to cool the high pressure gas, condense it and also sub-cool the liquid. Heat from the hot refrigerant gas is rejected in the condenser to the condensing medium air. Air is chosen because they are naturally available. The normal temperature range is satisfactory for condensing refrigerants. Advancements in condenser in order to increase the coefficient of performance can be achieved by increasing degree of sub cooling. This is done by the use of direct evaporative cooler to improve the energy efficiency of aircooled condenser. The evaporative cooler is installed in front of air-cooled condenser to pre-cool outdoor air before entering the con-denser. The pre-cooled air is carried to the condenser through ducts. These ducts are thermally insulated from inside and arrangements were made to make the assembly air sealed. 3.3 Desert Air Cooler The principle of working of a desert cooler is Evaporative cooling. Evaporative cooling is a process in which the sensible heat is rejected and moisture is added to the ambient dry air. When dry air is passed through a spray of water or cooling pad, it rejects heat to water, some of water evaporates and picks up heat from the air equivalent to the latent heat of air. The vapors thus formed are taken along in air stream. In this way air is cooled and humidified. The water is filled in the sump of the cooler from water supply tank. Water pump create suction and lifts the water to supply it at the top of the cooler to the water distribution system which consist of small branches of pipes or so equipped with orifices which deliver equal amount of water to the toughs which in turn supply water to the wetted pads. The water which drops back on the pad is recirculate. The blower fan drags the air through the moist pads and delivers it to the space to be cooled through an opening in the fourth side of the cabinet of desert cooler. The air which is pulled through the pads is cooled by the principle of evaporative cooling. The blower gives considerable velocity to the air before it is delivered to the space to be cooled. In this setup the air cooled by the pads of the desert cooler is carried to the condenser through retrofitted ducts. Provisions were made to seal the blower opening of the desert cooler to make sure only cooled air from wetted pads goes to condenser. Hence only pre-cooled air was supplied to the condenser. The experimental setup can be seen in fig-2. Showing Window AC assembled over desert cooler. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 549

Fig-3: T-S and P-H diagram without under-cooling. 4.2 WITH EVAPORATIVE COOLING 4. OBSERVATIONS Fig-2: Experimental setup. The following tests were carried out in the laboratory of Anjuman College of engineering and technology, Nagpur India during mid-daytime in the month of March (summer). The lab was sealed with plastic curtains to prevent heat dissipation into the room from the surrounding. Other heat radiating machines were also removed from the lab. The condenser ducts were also insulated with thermal insulation lining. The following arrangements were done to achieve least amount of variation during the test. After recording the observation without evaporative cooling of the air, the pump supplying water to the pads was operated and temperature readings were recorded between time intervals of 5mins. Following observations are recorded in the Table-2 given below. Time. (mins) Table -2: Observation table (with Evp. Cooling) Room Temperat ure (Tr) Evaporato temp. (T1) Condenser inlet Temp. (T2) Condense temp. (T3) Evapora tor inlet Temp. (T4) 5 29.9 26.2 57.9 34 20 4.9 15 29.2 21.3 70.3 35.7 23.2 3.6 25 28.2 19.4 73.9 35.2 23.5 3.43 COP The tests were conducted under two sections; Without evaporative cooling. With evaporative cooling. Readings were recorded at an interval of 5 minutes and the data was tabulated. 4.1 WITHOUT EVAPORATIVE COOLING The window AC was run on conventional cycle (i.e. without evaporative cooling). Data recorded is tabulated as under in Table -1. Time. (mins) Table -1: Observation table (without Evp. Cooling) Room Temperatur e (Tr) Evaporato temp. (T1) Condense r inlet Temp. (T2) Condens e temp. (T3) Evaporator inlet Temp. (T4) 5 30.2 31.1 58.9 39.6 25.4 4.46 15 28.5 19.2 80.9 40.1 29.5 2.86 25 28 18.4 84.7 40.3 31.2 2.72 COP Fig-4: T-S and P-H diagram with under-cooling. 5. RESULTS The results of COP for the simple conventional refrigeration cycle and cycle with modified condenser ducts for evaporative cooling is shown in the chart given below. It is clear that the COP is increased. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 550

Temperature( C) International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-0056 Hence, there will be reduction in size and cost of the condenser. ACKNOWLEDGEMENT The Authors express their sincere appreciation and gratitude to Dr. Sajid Anwar, Principal, Anjuman College of Engineering & Technology and Head of the Mechanical Engineering Department, Dr. Akash Langde for guiding us and encouraging us in our endeavor and proving us essential research facilities. Chart-1: Time VS COP chart. The condense temperature for both the cycles is shown below; We are also thankful to the faculty of Mechanical Engineering of Anjuman college of Engineering and Technology for their valuable guidance. REFERENCES 42 40 38 36 34 32 30 Condenser Outlet Temperature 39.6 34 40.1 40.3 35.7 35.2 5mins 15mins 25mins Condense temperature without evaporative cooling [1] Refrigeration & Air conditioning by R.S..Khurmi, J.K. Gupta. [2] Aprea C, Mastrullo R and Renno C (2004) An Analysis of the Performance of a Vapor Compression Refrigeration Plant Working Both as a Wate r Chiller and a Heat Pump Using R-22 and 417A,Applied Thermal Engineering, Vol. 24,pp. 487-499. [3] Bilal Ahmed Qureshi and Syed M Zubair(2011), Performance Degradation of a Vapour Compression Refrigeration System Under Fouled Conditions,International Journal of Refrigeration, Vol. 34, pp. 1 016-1027. [4] Comakli K, Simsek F, Comakli O andsahin B (2009), Determination of Optimum Conditions R-22 and R404a Refrigerant Mixtures in Heat Pumps Using Taguchi Method, Applied Energy, Vol. 86, pp. 2451-2458. 6. CONCLUSIONS Fig-5: Condense temperature. 1. The experimental results revealed that with evaporative cooling system, the cooling capacity and coefficient of performance increased considerably. 2. The cooling-down of air for condenser caused by its interaction with the cooling pad water is much better than during the conventional flow around the condenser tube. 3. The pressure of condenser and evaporator reduces. 4. By sub-cooling enthalpy of vaporization of refrigerant increases, so refrigerating effect increase thus COP increases. [5] Douglas J D, Braun J E, Groll E A and TreeD R (1999), A Cost Method Comparing Alternative Refrigerant Applied to R-22System, International Journal of Refrigeration, Vol. 22, pp. 107-125. [6] Bukola Olalekan Bolaji, Effects of Sub-Cooling on the Performance of R12 Alternatives in a Domestic Refrigeration System, Thammasat International Journal Science and Technology, Vol. 15, No. 1, January-March 2010, pp. 12-19. [7] V. Siva Reddy, N.L Panwar, S.C Kaushik(2012) Exergy analysis of a vapor compression refrigeration system with R134a,R143a,R152a,R404A,R407C,R410A,R502 and R507A Int. Journal of.clean Technical Environment Poli-cy;14, pp.47-53. 5. COP of Vapor Compression Cycle is increased by increasing the refrigerating effect. The heat transfer will increase due to increase in pressure and temperature. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 551

BIOGRAPHIES Prof, Dr. Akash Langde. Anjuman College of Engineering and Technology, Nagpur, India. Zeeshan Jamal. Anjuman College of Engineering and Technology, Nagpur, India. Shahrukh Jamal. ITM College of Engineering and Technology, Nagpur, India Mohammad Shumoil Ansari. Sinhgad College of Engineering, Pune, India. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 552