Multistack Modbus Driver: Standard Unit

Similar documents
APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

Honeywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

McQuay Microtech III BACnet MS/TP Application 4181 Point Map

LONWORKS Solution for Orion PT-LON-Link

McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)

Pneumercator Driver: TMS 2000/3000

Modbus RTU RS485 Manual

POWERS CONTROLS Pneumatic Thermostat Covers

POWERS Pneumatic Thermostat Covers

Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

MRMS Multi-Room Monitoring Station

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen

MicroTech Unit Ventilator

Technical Instructions Document No P25 ET September 28, ET 141 Electric Surface Mounted Thermostat.

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application

Table of Contents. W2W Open

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

Introduction. What is the W2W Open controller?

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3.

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

Predator Controller Hardware Family

Sequence of operation

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

Database for CTS6000 MODBUS

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Capacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING. Manual

Installer Manual KNX Touchscreen Thermostat

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

SCA 620C AIR COOLED SCREW CHILLER

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

Animals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618

Instructions AK-PC 520

Tri-Stack Smart System

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

ER65 - Mini Rack Controller Electronic Refrigeration Line

Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

Powers Controls Free Energy Band TH 193 HC Hesitation Room Thermostat

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

Presented By: John Dolan, P.E.

PROFESSIONAL - SSE. Stainless steel interior and exterior (with galvanized back and bottom)

Sales and Engineering Data Sheet ED

CONTROL PANEL INSTRUCTIONS RSQ-4

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1

QuickStat-TC Installation & Operation Manual

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

EC3-X33 Stand-alone Superheat Controller Technical Data

Troubleshooting & faults guide

Sales and Engineering Data Sheet ED

Room Temperature Controller

Follett Performance Plus

Emerson Superheat Control. The smart solution for your application

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Capacity controller for water chiller AK-CH 650

Instruction Sheet. ERC2 Retrofit Instructions Series Refrigerators/Freezers and SPEC LINE Refrigerators 6000 & SPEC LINE SERIES

Modbus protocol REGO I

MicroTech Series 200 Centrifugal Chiller

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

NA G µair CONNECT 2

ERC2 Control Instructions

QPM21 Series Duct CO 2 and Air Quality Sensors

TS Series. Technical Instructions. Document No. TS-4000 June 25, TS-CE Combustion Enclosures with LMV5. Description

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

Retrostat Kits for Johnson Controls D/N or H/C Thermostats

Temperature controller for limitation for the discharge gas temperature EKC 319A REFRIGERATION AND AIR CONDITIONING. Manual

EVF818 Installer manual ver. 1.0 Code 144F818E104 EVF818. Split execution controller for temperaturecontrolled

SEQUENCE OF OPERATIONS

METEOROLOGICAL INSTRUMENTS

Room thermostats with LCD for wall mounting

Open Protocol Data Communications

For Raychem ACS-30 Controls Systems

OTFAMU Fresh Air Make Up System For Chilled Water OPERATOR S MANUAL. Technicold Marine Systems

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Water-cooled chillers with High Speed Centrifugal Compressors

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Flush-mounted room thermostats

MicroTech Self-Contained Air Conditioning System

Transcription:

Point Map October 27, 2006 Systems Integration Multistack Modbus Driver: Standard Unit Table 1. Multistack Modbus Standard APOGEE Points, Application Number: 4726. 1 LAO Address 2 LAI Application 3 LDI No Communication Off/On 4 LAO IP Address Byte 1 5 LAO IP Address Byte 2 6 LAO IP Address Byte 3 7 LAO IP Address Byte 4 8 LAO Modbus IP Port 9 LAO Base Offset 10 LAO Send Initial Value 11 LDO On/Off Control On/Off 12 LDI On/Off Status No/Yes 13 LDI EX1 Fault Display No/Yes 14 LDI EX2 Remote Off No/Yes 15 LDI EX3 Fault Display No/Yes 16 LDI EX4 Fault Display No/Yes 17 LDI Low Chilled Water Flow No/Yes 18 LDI Low Condenser Water Flow No/Yes 19 LDI Low Chilled Water Temperature System No/Yes 20 LDI Compressor 1 Fault Status Normal/Alarm 21 LDI Compressor 2 Fault Status Normal/Alarm 22 LDI Compressor 3 Fault Status Normal/Alarm 23 LDI Compressor 4 Fault Status Normal/Alarm 24 LDI Compressor 5 Fault Status Normal/Alarm 25 LDI Compressor 6 Fault Status Normal/Alarm 26 LDI Compressor 7 Fault Status Normal/Alarm Siemens Building Technologies, Inc. Page 1 of 8

27 LDI Compressor 8 Fault Status Normal/Alarm 28 LDI Compressor 9 Fault Status Normal/Alarm 29 LDI Compressor 10 Fault Status Normal/Alarm 30 LDI Compressor 11 Fault Status Normal/Alarm 31 LDI Compressor 12 Fault Status Normal/Alarm 32 LDI Compressor 13 Fault Status Normal/Alarm 33 LDI Compressor 14 Fault Status Normal/Alarm 34 LDI Compressor 15 Fault Status Normal/Alarm 35 LDI Compressor 16 Fault Status Normal/Alarm 36 LDI Compressor 17 Fault Status Normal/Alarm 37 LDI Compressor 18 Fault Status Normal/Alarm 38 LDI Compressor 19 Fault Status Normal/Alarm 39 LDI Compressor 20 Fault Status Normal/Alarm 40 LDI Compressor 21 Fault Status Normal/Alarm 41 LDI Compressor 22 Fault Status Normal/Alarm 42 LDI Compressor 23 Fault Status Normal/Alarm 43 LDI Compressor 24 Fault Status Normal/Alarm 44 LAI Total Compressors 45 LAI Percent of Compressors Running (Capacity) % 46 LAI Demand 47 LAI Total Compressors In Fault 48 LAI Entering Chilled Water System Temperature F C 49 LAI Leaving Chilled Water System Temperature F C 50 LAI Entering Condenser Water System Temperature F C 51 LAI Leaving Condenser Water System Temperature F C 52 LAI Current Lead Compressor 53 LAI Active Load Limit % 54 LAI Active Upper Setpoint F C 55 LAI Active Lower Setpoint F C 56 LAI Active Variable Setpoint F C 57 LAI Active Delay Time sec 58 LAI Active Failure Indicator % 59 LAI Active Flush Time hrs 60 LAI Active Flush Duration sec 61 LAI Current Month mo Page 2 of 8 Siemens Building Technologies, Inc.

62 LAI Current Day day 63 LAI Current Year yr 64 LAI Current Time hr 65 LAI Current Time (Minutes) min 66 LAI Module Fault Compressor 1 67 LAI Module Fault Compressor 2 68 LAI Module Fault Compressor 3 69 LAI Module Fault Compressor 4 70 LAI Module Fault Compressor 5 71 LAI Module Fault Compressor 6 72 LAI Module Fault Compressor 7 73 LAI Module Fault Compressor 8 74 LAI Module Fault Compressor 9 75 LAI Module Fault Compressor 10 76 LAI Module Fault Compressor 11 77 LAI Module Fault Compressor 12 78 LAI Module Fault Compressor 13 79 LAI Module Fault Compressor 14 80 LAI Module Fault Compressor 15 81 LAI Module Fault Compressor 16 82 LAI Module Fault Compressor 17 83 LAI Module Fault Compressor 18 84 LAI Module Fault Compressor 19 85 LAI Module Fault Compressor 20 86 LAI Module Fault Compressor 21 87 LAI Module Fault Compressor 22 88 LAI Module Fault Compressor 23 89 LAI Module Fault Compressor 24 90 LAI Compressor 1 Suction Temperature F C 91 LAI Compressor 1 Chilled Water Temperature F C 92 LAI Compressor 2 Suction Temperature F C 93 LAI Compressor 2 Chilled Water Temperature F C 94 LAI Compressor 3 Suction Temperature F C 95 LAI Compressor 3 Chilled Water Temperature F C 96 LAI Compressor 4 Suction Temperature F C Siemens Building Technologies, Inc. Page 3 of 8

97 LAI Compressor 4 Chilled Water Temperature F C 98 LAI Compressor 5 Suction Temperature F C 99 LAI Compressor 5 Chilled Water Temperature F C 100 LAI Compressor 6 Suction Temperature F C 101 LAI Compressor 6 Chilled Water Temperature F C 102 LAI Compressor 7 Suction Temperature F C 103 LAI Compressor 7 Chilled Water Temperature F C 104 LAI Compressor 8 Suction Temperature F C 105 LAI Compressor 8 Chilled Water Temperature F C 106 LAI Compressor 9 Suction Temperature F C 107 LAI Compressor 9 Chilled Water Temperature F C 108 LAI Compressor 10 Suction Temperature F C 109 LAI Compressor 10 Chilled Water Temperature F C 110 LAI Compressor 11Suction Temperature F C 111 LAI Compressor 11 Chilled Water Temperature F C 112 LAI Compressor 12 Suction Temperature F C 113 LAI Compressor 12 Chilled Water Temperature F C 114 LAI Compressor 13 Suction Temperature F C 115 LAI Compressor 13 Chilled Water Temperature F C 116 LAI Compressor 14 Suction Temperature F C 117 LAI Compressor 14 Chilled Water Temperature F C 118 LAI Compressor 15 Suction Temperature F C 119 LAI Compressor 15 Chilled Water Temperature F C 120 LAI Compressor 16 Suction Temperature F C 121 LAI Compressor 16 Chilled Water Temperature F C 122 LAI Compressor 17 Suction Temperature F C 123 LAI Compressor 17 Chilled Water Temperature F C 124 LAI Compressor 18 Suction Temperature F C 125 LAI Compressor 18 Chilled Water Temperature F C 126 LAI Compressor 19 Suction Temperature F C 127 LAI Compressor 19 Chilled Water Temperature F C 128 LAI Compressor 20 Suction Temperature F C 129 LAI Compressor 20 Chilled Water Temperature F C 130 LAI Compressor 21 Suction Temperature F C 131 LAI Compressor 21 Chilled Water Temperature F C Page 4 of 8 Siemens Building Technologies, Inc.

132 LAI Compressor 22 Suction Temperature F C 133 LAI Compressor 22 Chilled Water Temperature F C 134 LAI Compressor 23 Suction Temperature F C 135 LAI Compressor 23 Chilled Water Temperature F C 136 LAI Compressor 24 Suction Temperature F C 137 LAI Compressor 24 Chilled Water Temperature F C 138 LAI Fault Review Type 1 139 LAI Fault Review Type 2 140 LAI Fault Review Type 3 141 LAI Fault Review Type 4 142 LAI Fault Review Type 5 143 LAI Fault Review Type 6 144 LAI Fault Review Type 7 145 LAI Fault Review Type 8 146 LAI Fault Review Type 9 147 LAI Fault Review Type 10 148 LAI Fault Review Type 11 149 LAI Fault Review Type 12 150 LAI Fault Review Type 13 151 LAI Fault Review Type 14 152 LAI Fault Review Type 15 153 LAI Fault Review Type 16 154 LAI Fault Review Type 17 155 LAI Fault Review Type 18 156 LAI Fault Review Type 19 157 LAI Fault Review Type 20 158 LAI Fault Review Compressor Number 159 LAI Fault Review (History) 2 Compressor Number 160 LAI Fault Review (History) 3 Compressor Number 161 LAI Fault Review (History) 4 Compressor Number 162 LAI Fault Review (History) 5 Compressor Number 163 LAI Fault Review (History) 6 Compressor Number 164 LAI Fault Review (History) 7 Compressor Number 165 LAI Fault Review (History) 8 Compressor Number 166 LAI Fault Review (History) 9 Compressor Number Siemens Building Technologies, Inc. Page 5 of 8

167 LAI Fault Review (History) 10 Compressor Number 168 LAI Fault Review (History) 11 Compressor Number 169 LAI Fault Review (History) 12 Compressor Number 170 LAI Fault Review (History) 13 Compressor Number 171 LAI Fault Review (History) 14 Compressor Number 172 LAI Fault Review (History) 15 Compressor Number 173 LAI Fault Review (History) 16 Compressor Number 174 LAI Fault Review (History) 17 Compressor Number 175 LAI Fault Review (History) 18 Compressor Number 176 LAI Fault Review (History) 19 Compressor Number 177 LAI Fault Review (History) 20 Compressor Number 178 LAI Time @0-9% Load hrs 179 LAI Time @10-19% Load hrs 180 LAI Time @20-29% Load hrs 181 LAI Time @30-39% Load hrs 182 LAI Time @40-49% Load hrs 183 LAI Time @50-59% Load hrs 184 LAI Time @60-69% Load hrs 185 LAI Time @70-79% Load hrs 186 LAI Time @80-89% Load hrs 187 LAI Time @90-100% Load hrs 188 LAO Upper Setpoint F C 189 LAO Lower Setpoint F C 190 LAO Variable Setpoint F C 191 LAO Load Limit Setpoint % 192 LAO Time Delay Setpoint sec 193 LAO Failure Indicator Setpoint % 194 LAO Lead Compressor Setpoint 195 LAO Flush Time hrs 196 LAO Flush Duration sec Page 6 of 8 Siemens Building Technologies, Inc.

Table 2. Fault Conditions. Value Description 1 High Pressure Cutoff (Off mode) 2 Low Pressure Cutoff (Off mode) 64 Low Suction Temperature (Current) 65 High Pressure Cutoff (Current) 66 Low Pressure Cutoff (Current) 72 Low Leaving Chilled Water Temperature (Current) 96 Communication Error (Current) 128 Low Suction Temperature (Reset) 129 High Pressure Cutoff (Reset) 130 Low Pressure Cutoff (Reset) 132 Thermal Fault (Reset) 136 Low Leaving Chilled Water Temperature (Reset) Table 3. System Fault Type (Fault Review Compressor Number = 0). Value Description 1 EX1 FAULT (Record) 2 EX3 FAULT (Record) 4 EX4 FAULT (Record) 8 Low Leaving Chilled Water Temperature (Record) 16 Low Chilled Water Flow (Record) 32 Low Condenser Water Flow (Record) 65 EX1 FAULT (Current) 66 EX3 FAULT (Current) 68 EX4 FAULT (Current) 72 Low Leaving Chilled Water Temperature (Current) 80 Low Chilled Water Flow (Current) 96 Low Condenser Water Flow (Current) 129 EX1 FAULT (Reset) 130 EX3 FAULT (Reset) 136 Low Leaving Chilled Water Temperature (Reset) 144 Low Chilled Water Flow (Reset) 160 Low Condenser Water Flow (Reset) Siemens Building Technologies, Inc. Page 7 of 8

Table 4. Module Fault Type Fault Review Compressor Number > 0). Value Description 0 Low Suction Temperature (Record) 1 High Pressure Cutout (Record) 2 Low Pressure Cutout (Record) 4 Thermal Fault (Record) 8 Low Leaving Chilled Water Temperature (Record) 16 High Suction Temperature (Record) 32 Communication Error (Record) 64 Low Suction Temperature (Current/Reset) 65 High Pressure Cutout (Current/Reset) 66 Low Pressure Cutout (Current/Reset) 72 Low Leaving Chilled Water Temperature (Current/Reset) 80 High Suction Temperature (Current/Reset) 96 Communication Error (Current/Reset) Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2006 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. 1000 Deerfield Parkway Country of Origin: US Buffalo Grove, IL 60089-4513 Page 8 of 8 U.S.A.