CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Similar documents
CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

CSAGV 27 / 80. GROUPE FRIGORIFIQUE A CONDENSATION PAR AIR HELICOÏDE Fluide réfrigérant R 407 C

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

HT V2 HT Split

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

High temperature air-to-water heat pumps

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

Chiller units and air-water heat pumps RANGE OPERATING LIMITS

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

ECOCIAT. Domestic hot water heat recovery unit. Use. Range

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

KPSW CONSOLE TERMINAL UNIT

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Aquaflair TRAC-TRAF-TRAH

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw.

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

VEXTRA. acoustic comfort Saves up to. 40% floor space. Use. Range. Description. Drycoolers. Slim design and. Capacity up to kw.

30RH B Nominal cooling capacity kw Nominal heating capacity kw

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

MAC N-407 Air-Cooled Chiller

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

AQUASNAP JUNIOR 30RHV

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Water chillers water/water type SIGMA Technical information manual

MACH N-407 Heat Pump Air-Cooled Chiller

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

Process glycol chillers

LZT High efficiency air to water heat pumps with E.V.I. compressors

Compact and silent Scroll compressors All-season operation

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Be sustainable while protecting your business

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Modular Air-cooled Chillers

Air Cooled Chillers & Heat Pumps WinPACK HE-A

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

DYNACIAT POWER. High energy efficiency Compact and quiet

Galletti Water chillers and heat pumps catalogue

Roof top SPACE RPC 450Z R407C M011

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

LZA High efficiency air to water heat pumps with HP compressor

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

Roof top SPACE RPC 315Z R407C MA00

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

GeoCIAT Modular. Components. Heat pump Heating only, Glycol/water mix/water. Refrigerant and hydraulic module diagram. HomeConnect control.

CRIMSON & CRIMSON MAX

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

HYDRONIC RESIDENTIAL

SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER)

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-120HE-03 Air-Cooled Chiller

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

OPERA MORE. Use. Range. Drycoolers Air-cooled condensers. for LESS. Capacity: up to 1100 kw. Water misting. Free cooling

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Transcription:

TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB - 02

MARKING This product marked conforms to the essential requirements of the Directives: - Low voltage no 2006/95/EC. - Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 EEC and 93/68 EEC. - Pressure Equipment Directive No. 97/23/EC. CONTENTS 1 - Application - Use...................................... 2 2 - Presentation......................................... 3 3 - Technical characteristics................................ 4 4 - Physical characteristics................................. 5 5 - Description.......................................... 6 6 - Cooling performances..................................7 7 - Corrections to be made when using anti-freeze..............8 8 - Curves of available pressures............................8 9 - Sound levels.........................................8 10 - Accessories..........................................8 11 - "ECH" electronic control................................10 12 - Installation information.................................10 R 407 C Fluid R 407 C, as opposed to R22, is not a pure fluid but a blend composed of: - 23% R 32 + 25% R 125 + 52% R 134 A. The compressors approved for operation with this fluid are filled beforehand with polyalcohol oil. Contrary to mineral oil, it is very hygroscopic: it absorbs the humidity of the ambient air very quickly. This can modify its lubricant properties and lead in time to the destruction of the compressor. MAINTENANCE INSTRUCTIONS 1 - Never add oil to the appliance; the compressor is filled with polyalcohol oil, a special oil which cannot tolerate the presence of other oils. 2 - The instruments used for: - filling, - pressure measurements, - emptying under vacuum, - recovering the fluid, must be compatible and only used for the R 407 C fluid. 3 - The weight of the refrigerant contained in the storage bottle must be checked constantly. Do not use it from the moment the remaining weight is less than 10% of the total weight. APPLIANCES FILLED WITH R 407 C 4 - In the case of a new charge: - do not use the charging cylinder, - use a balance and a dip pipe type R 407 C cylinder, - charge the weight of R 407 C as per the value indicated on the unit s identification plate, - IMPORTANT: see instruction 3 above. 5 - The charge must be undertaken in liquid phase. 6 - In case of leakage, do not complete the charge: recover the remaining refrigerant for recycling and perform a total charge. Recovery, recycling or the destruction of the fluid must be done in compliance with the laws in force in the country concerned. 7 - If the refrigerant circuit is opened, you must: - avoid the entry of air into the circuit as much as possible, - replace the filter drier, - perform the "vacuum operation" at a minimum level of 0.3 mbar (static). 8 - Do not release R 407 C fluid into the atmosphere. This fluid is a fluorinated greenhouse gases, covered by the Kyoto Protocol with a Global Warming Potential (GWP) = 1653 - (CE Directive 842 / 2006). 1 - APPLICATION - USE Air cooled type chilled water generator intended for climate control in buildings. Single package unit, factory assembled and tested. Designed for outdoor installation. Supplied fully charged with R 407 C refrigerant. Convenient hydraulic and electrical connections. Practical service access via removable panels. 2

2 - PRESENTATION CHGV: An air cooled chilled water generator with built-in hydraulic equipment. Refrigerant Model 2 refrigerant circuits R 407C 50 / 64 / 72 / 80 4 9 5 a 3 b 2 1 Water inlet Water outlet 7 8 6 1 2 3 4 5 SCROLL COMPRESSOR Mounted on vibration pads with sound insulation. 1 per circuit. WATER EXCHANGER Plate water exchanger with heat insulation. 1 per circuit. AIR EXCHANGER Thin plate air exchanger with protective grille. 1 per circuit. ELECTRIC FAN UNIT Electric fan unit with protective grille. 1 per circuit. SWITCH BOX ECH electronic control. Main switch. Phase-sequence tester. Power and control circuitry protected by magnetothermal circuit breakers. Complies with standard EN 60 204-1. Short circuit current 10 ka, as per IEC 947-2. 6 CIRCULATING PUMP Circulating pump with heat insulation. 7 EXPANSION TANK 8 REFRIGERATION CIRCUITS R407C loads. Copper piping. Thermostatic regulator. Filter-dryer. HP and LP safety pressure switches. 9 CHASSIS - BODYWORK Galvanised sheet metal with light grey oven-baked polyester powder paint (RAL 7035). 3

3 - TECHNICAL CHARACTERISTICS Model Heating capacity Nominal power consumption * Effictuiveness heating * Total Max. power consumption ** Total Max. current consumption ** Rated total input amperage Starting current Electrical supply cable section Nominal water flow Available pressure CHGV 50 CHGV 64 CHGV 72 CHGV 80 kw 47.60 62 67 78 kw 20.60 26.40 28.80 29.40 (EER) 2.31 2.35 2.33 2.65 kw 25 32 36 36.6 A 42.80 56.30 60.40 64.80 A 38.70 47.70 54 55.50 A 170 185 225 225 mm 2 16 16 25 25 m 3 /h 8.21 10.66 11.52 13.43 L/s 2.28 2.96 3.20 3.73 kpa 220 160 180 90 (*) Gross value without hydraulic pump. (**) In the operating range. Power supply: 400V (±10%) / 3 Ph + Neutral + Earth / 50Hz Nominal operating conditions: - water inlet temperature : + 12 C - water outlet temperature : + 7 C - outdoor dry bulb temperature (dry) : + 35 C Operating limits (pure water): - temperature of inlet air to condenser : - 10 C to + 45 C - water outlet temperature : + 4 C to + 20 C Water system pressure: 1.5 to 3 bar. Consult us for any special climatic conditions departing significantly from the nominal conditions. 4

4 - PHYSICAL CHARACTERISTICS Dimensions (in mm) are given for standard units without options. General tolerance ±10 mm. a b c Condenser air discharge Condenser air suction Chilled water inlet connection Chilled water outlet connection HP and LP hose entry G Electrical connections Location of the 4 anti-vibration pads (accessory) (100 x 100 x 25 mm) under girders Centre of gravity (in the centre of the unit) 4.1 - CHGV Clearances to be respected for unit operation and maintenance. No obstacle less than 3 m above the unit. 2 HP pressure gauges (Accessory) 2 LP pressure gauges (Accessory) 300 (600 with tank) 300 1,175 (1,425 CHGV 80) b c a 1000 125 Front 300 1,050 4 Ø 22.5 mm holes for sling attachment 180 1,955 950 Net Packed Overall packed dimensions x G CHGV weight weight Length 2,015 mm 50 500 kg 540 kg Depth 1,135 mm 64 534 kg 574 kg 1,370 mm 72 556 kg 596 kg Height 1,620 mm 80 606 kg 646 kg CHGV 80 Access to switch box 4.2-300-LITRE BUFFER TANK (ACCESSORY) Clearances to be respected for maintenance. 600 300 Hydraulic connection tube c a 1000 Front 300 611 b 315 40 Buffer tank 160 1,050 1,300 1,955 Overall packed dimensions Net Packed weight weight Length 1,990 mm Tank Depth 1,110 mm 185 kg 207 kg without heating Height 806 mm 4 Ø 22.5 mm holes for passing slings for handling the tank only 5

5 - DESCRIPTION Model Cooling circuit (number) with HP and LP pressure switches R 407 C refrigerant charge CHGV 50 CHGV 64 CHGV 72 CHGV 80 2 2 2 2 kg 2 x 7.25 2 x 8 2 x 9 2 x 12.5 Hermetic SCROLL compressor with soundproofing and internal thermal protection Number 2 2 2 2 Power supply 400V / 3 / 50Hz Nominal current per compressor A 17.00 20.80 23.10 23.80 Nominal power consumed by the compressor kw 9.90 12.50 14.30 14.70 Helicoidal electric fan, direct coupling, with internal thermal protector Number 2 2 2 2 Air flow m 3 /h 9,800 11,000 11,000 11,000 Diameter mm 760 760 760 760 Max. rotation speed (motor) rpm 620 660 660 660 230V / 1 / 50Hz power supply with speed control for condensation pressure control Nominal current per motor (single-phase 230 VAC) A 3.50 3.90 3.90 3.90 Power consumption per motor kw 0.75 0.85 0.85 0.85 Air exchanger with protective grille, copper tubes, aluminium fins Number 2 2 2 2 Water exchanger with stainless steel brazed plates AISI 316 L with thermal insulation Number 2 2 2 2 Water capacity liters 4 5 6 7 Hydraulic circuit Male 1"1/2 coupling (40x49) Minimum installation water volume * liters 120 160 170 200 Maximum installation water volume ** liters 1,500 1,500 1,500 1,500 Expansion tank (1.5 bar) Tank capacity liters 18 18 18 18 Safety valve (3 bar) with pressure gauge Differential water output pressure switch Output control valve Fill valve (ø 1/4" female) Water filter supplied (not installed) Circulating pump Maximum power consumption (pump only) kw 1.40 1.40 1.90 1.90 Maximum current A 2.70 2.70 3.50 3.50 Power supply 400V / 3 / 50Hz General electrical power supply 400V / 3N + Earth / 50Hz Equipment protection index Electrical equipment IP 24 IP 24 IP 24 IP 24 Mechanical risks B B B B (*) If the water volume of the system is below the minimum, a buffer tank must be installed. (**) If the water volume of the system is above the maximum, an additional expansion tank is required. 6

6 - COOLING PERFORMANCES COOLING CAPACITY TOTAL INPUT POWER CHGV 50 Cooling capacity (kw) 78 74 70 66 62 58 54 50 46 42 Out. temp. = 19 C 38 Total input power (kw) 24 22 20 18 16 14 Out. temp. = 19 C 12 CHGV 64 Cooling capacity (kw) 110 100 90 80 70 Out. temp. = 19 C Total input power (kw) 33 31 29 27 25 23 60 50 40 21 19 Out. temp. = 19 C 17 CHGV 72 Cooling capacity (kw) 110 100 90 80 70 Total input power (kw) 38 36 34 32 30 28 Out. temp. = 19 C 60 50 Out. temp. = 19 C 40 26 24 22 CHGV 80 Cooling capacity (kw) 130 120 110 100 90 80 Out. temp. = 15 C Total input power (kw) 50 40 30 Out. temp. = 15 C 70 20 60 50 10 T (water) between 4 and 6 K. 7

7 - CORRECTIONS TO BE MADE WHEN USING ANTI-FREEZE IMPORTANT: Use monopropylene glycol; a minimum rate of 15% to 20% is needed to avoid any risk of corrosion. PRINCIPLE OF USING THE CURVES A- Choose the percentage of glycol according to the minimum temperature to protect the hydraulic circuit against frost. B - Example: Protection at an external temperature of -15 C, which gives 30% monopropylene glycol (freezing points curve). The loss of capacity is given on the "Reduction of cooling capacity" curve (0.94). The new flow is given by the coefficient on the water flow curve (1.113). Likewise, to determine the new pressure drop coefficient in relation to the nominal flow, read the pressure drop curve (1.19). Valid curves for setting temperature at the water inlet. Outdoor temperature C Correction factors 1.30 1.20 1.19 1.113 1.10 1.00 0.94-25 -20-15 -10 Freezing points Pressure drop Water flow Reduction of cooling capacity -5 0 0 10 20 30 40 % Glycol in weight 8 - AVAILABLE PRESSURE CURVES ON THE HYDRAULIC SYSTEM Available head (kpa) 300 250 200 150 100 50 0 CHGV 80 CHGV 72 CHGV 64 CHGV 50 5 6 7 8 9 10 11 12 13 14 15 Water flow rate (m 3 /h) Values at apparatus outlet without tank. (See 10.5 for tank pressure losses). 9 - SOUND LEVELS CHGV Power level Sound-pressure level (dba) (dba) 50 78 50 64 82 54 72 87 59 80 87 59 db to be deducted from the sound power level 40 35 30 Nominal operating conditions: - Ambient temperature: 35 C. Sound-pressure level: - Unit installed outdoors (free field) on a reflective surface. - Measurement carried out at a distance of 10 m. 25 10 15 20 25 30 Distance in meters 10 - ACCESSORIES 10.1 - ANTI-VIBRATION KIT Kit includes: - 1 set of 4 anti-vibration plates, thickness 25 mm - code 70600035. - 1 set of 2 flexible hoses: length 1.5 m, Ø 1" 1/2 - code 70600034. 8

10.2 - HP AND LP PRESSURE GAUGES The accessory includes 1 set of 2 pressure gauges (HP and LP). Two per apparatus must be ordered. Code 70970007. These elements, mounted on the vertical members of the unit's front face, display the high and low pressure values for the refrigeration circuit. 10.3 - REMOTE CONTROL Code 70250057. Enables reporting of the controller's display keypad functions up to a distance of 100 meters. 10.4 - SERIAL COMMUNICATIONS INTERFACE RS 485 (MODBUS PROTOCOL) Code 70250056. Interface module installed inside the unit's electrical box. MODBUS protocol. Please consult us for details concerning the protocol and addressing of data. 10.5-300-LITRE BUFFER TANK Code 70600120: model without supplementary heating with 800 W anti-freeze resistance (single-phase 230 VAC), Designed to be installed either underneath the unit, or separately. For installation underneath the unit, the tank is supplied with mounting brackets and an insulated tube for connection between the unit's water outlet and the tank's water inlet. Composition: 5 1 2 3 4 6 Water inlet (Male 1 1/2) Water outlet (Male 1 1/2) 70600120 Mark without heating 1 Sheetmetal buffer tank - polyurethane insulation 2 800 W anti-freeze resistance 3 Fill valve 4 Drain valve 5 Purge 6 Safety valve (5 bar) Galvanized steel chassis, painted RAL 7035 Anti-freeze resistance: Immersion heater mounted on the tank. Power: 800 W, single-phase 230 VAC. With limiting thermostat. The power supply and heating element control are to be done separately at the time of installation (not supplied). Pressure losses in 300-litre tank: Kp a 16 14 12 10 8 6 4 2 0 7 8 9 10 11 12 13 14 Output m 3 /h 9

11 - "ECH" ELECTRONIC CONTROL Microprocessor control module, including: - chilled water temperature control (water inlet), - control of operating parameters, - self-adapting algorithm for water volume reduction, - circulating pump control (frost protection and anti-sticking function), - dynamic setpoints are possible according to the outside temperature (to be activated at the time of installation by means of special parameterization). - anti-short cycle system, - hour counter compressor and circulating pump, - alarm management, - anti-freeze security (temperature probes at water exchanger outlet), - digital display of:. water temperature,. set-point,. alarm code (HP, LP, water output, probes, anti-freeze...). - remote alarm reporting is possible via a potential-free contact, - integrated condensation pressure control (with pressure sensors), - remote control with display unit (accessory), - serial communications port (RS 485 interface, accessory) - MODBUS Protocol. 12 - INSTALLATION INFORMATION See details in the installation manual. 12.1 - INSTALLATION Protection index of the unit: - IP 24 : for the electrical equipment, (IPXXB : for the mechanical hazards). Before installation, verify the following points: - the unit must be installed outside in an appropriate location and in compliance with environmental requirements (sound level, integration, etc...), - the water chiller s installation location must be perfectly level and strong enough to support the weight of the unit and must have adequate inundation protection, - sufficient space around the unit should be provided in order to facilitate servicing and maintenance operations, - air suction to the coil and fan discharge must not be obstructed, - install the unit above the region s average snowfall level, - vibrations and noise must not be transmitted to adjacent buildings, - install the machine on anti-vibration pads and fit hoses on piping elements, as required, - if necessary, consult an acoustics specialist concerning the unit s optimum location, - 4 holes Ø 22.5 enable to place hoisting hooks and lift the unit. 12.2 - ELECTRICAL CONNECTIONS All required information is indicated on the electrical diagram provided with the unit and in the installation manual. Connections are to be made in compliance with the standard code of practice and as per the standards in force at the site of installation. 12.3 - HYDRAULIC CONNECTIONS The hydraulic connections are to be made in compliance with the standard code of practice. IMPERATIVE: Install the filter supplied on the water inlet of the unit. 12.4 - STARTING - MAINTENANCE Refer to the installation guide and the maintenance manual. IMPORTANT: - The unit's electronic control features a frost protection device that automatically starts the water circulating pump depending on the outside temperature (adjustable threshold), even if the unit is turned off. - In the event the unit may be taken out of service or in the case of a high risk of freezing: - either drain the installation, - or add glycol to the circuit. - Tank anti-freeze resistance: its electrical power supply and control must be separate from those of the unit. 10

11

Due to our policy of continuous development, our products are liable to modification without notice. R.D. 28 Reyrieux BP 131 01601 Trévoux CEDEX France Phone 33 4 74 00 92 92 - Fax 33 4 74 00 42 00 R.C.S. Bourg-en-Bresse B 759 200 728