A CRYOGENIC TEST STATION FOR SUBCOOLING HELIUM HEAT EXCHANGERS FOR LHC

Similar documents
Measured Performance of Four New 18 K Helium Refrigerators for the LHC Cryogenic System

SPECIFICATION OF FOUR NEW LARGE 4.5 K HELIUM REFRIGERATORS FOR THE LHC

LARGE CRYOGENIC HELIUM REFRIGERATION SYSTEM FOR THE LHC

Cryogenic refrigeration for the LHC

Available online at ScienceDirect. Physics Procedia 67 (2015 )

A Microcryostat for Refrigeration at 1.8 K

Air Liquide Advanced Technologies Division Sassenage, 38360, France

The superconducting TF magnetic system of Tore Supra

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

3.2 Cryoplant and Cryodistribution

Pocket Dilution Cooler

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Performance test of a helium refrigerator for the cryogenic hydrogen system in J-PARC

OPERATIONAL EXPERIENCE ON CRYOGENIC SYSTEMS FOR LARGE-SCALE ACCELERATORS AT CERN

THE TORE SUPRA CRYOGENIC SYSTEM. Design and operation

AVAILABILITY AND RELIABILITY OF CERN CRYOPLANTS

Market Survey. Technical Description Supply of Helium Leak Detectors

Remote Helium Cooling Loops for Laboratory Applications

Development of a measurement and control system for a 10 K refrigerator based on Siemens PLC S7-300

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY

Cryogenics for Neutral Beam Injector System

Sub-Critical Operation of the CO2 Expander/ Compressor

Metal hydride storage system for MICE experiment at Rutherford Appleton Laboratory. Technical specification.

Linde Kryotechnik AG. Liquefaction and refrigeration plants for research, science and industry. Helium solutions.

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

THE THERMOSIPHON COOLING SYSTEM OF THE ATLAS EXPERIMENT AT THE CERN LARGE HADRON COLLIDER

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

Cooling test results C-side replacement detector

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

2008 JINST 3 S The CMS experiment at the CERN LHC THE CERN LARGE HADRON COLLIDER: ACCELERATOR AND EXPERIMENTS.

The dilution process. 4K flange. Still. Heat exchangers. Mixing chamber

Can one cool the MICE magnets and the Hydrogen Absorbers with Small Coolers? Michael A Green Oxford University Physics Oxford OX1 3RH, UK

Title: Measurement of dryness fraction by Separating Calorimeter,

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

AN EXPERIMENTAL REFRIGERATOR WITH AN INVERSE AIR CYCLE FOR FREEZING IQF FOOD PRODUCTS

ESS Accelerator Cryoplant Process Design

TRACI, A MULTIPURPOSE CO 2 COOLING SYSTEM FOR R&D

A 2 K Active Magnetic Regenerative Refrigeration System for Remote Cooling

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance of a MEMS Heat Exchanger for a Cryosurgical Probe

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

1 /35 2 /35 3 /30 Total /100

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

10 K Airborne Cryocooler and

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

High Efficiency Heat Pump for Domestic Hot Water Generation

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

Concept of a Powerful Cryogen-Free Dilution Refrigerator with Separate 1K Stage

The Refrigeration Cycle

Reconfiguration of a B&W/SSC/LINDE Liquefier to Meet SLAC-BaBar Detector Magnet Requirements * Abstract

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

The Refrigeration Cycle

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

API MANUAL OF PETROLEUM MEASUREMENT STANDARDS

PERFORMANCE EVALUATION OF GAS COOLER/ CONDENSER FOR CO2 REFRIGERATION SYSTEMS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Reliability and availability analysis of a 10 K helium refrigerator

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

Properties of a two stage adiabatic demagnetization refrigerator

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

A Small Refrigerator System for Cooling Thermal Shield of a Large Superconducting Magnet

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Thermal performances of a meter-scale cryogenic pulsating heat pipe.

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

DESIGN, MANUFACTURE AND TEST RESULTS OF THE VTCS CO 2 EVAPORATOR FOR THE LHCB EXPERIMENT AT CERN.

CO 2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN.

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Modelling the Performance of a Diffusion Absorption Refrigeration System

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Low GWP Refrigerants for Air Conditioning Applications

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD

High Efficiency Heat Pump with Subcooling for Sanitary Hot Water Production Working with Propane

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Thermodynamics: Homework A Set 7 Jennifer West (2004)

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Cryogenics. Overview of the Jefferson Lab 12GeV Upgrade. J. Creel, K. Dixon, P. Knudsen, J. Wilson Jr.

Transcription:

EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH European Laboratory for Particle Physics Large Hadron Collider Project LHC Project Report 386 A CRYOGENIC TEST STATION FOR SUBCOOLING HELIUM HEAT EXCHANGERS FOR LHC P. Roussel, B. Jager, L. Tavian* Abstract The superconducting magnets of the Large Hadron Collider (LHC) will be cooled at 1.9 K by distributed cooling loops where counter-flow heat exchangers will be integrated. To qualify potential suppliers for the 250-units series production, prototypes of various technologies have been selected by CERN and a test station was set up at CEA-Grenoble. This test station, is constituted of a cryostat allowing an easy access to the heat exchanger to be tested as well as very low pressure pumping facilities. DSM/DRFMC/SBT, C.E.A, F-38054 Grenoble Cedex 9 (France) * LHC Division Presented at the Eighteenth International Cryogenic Engineering Conference (ICEC 18) 21-25 February 2000, Bombay Mumbai, India Administrative Secretariat LHC Division CERN CH - 1211 Geneva 23 Switzerland Geneva, 26 July 2000

A Cryogenic Test Station For Subcooling Helium Heat Exchangers For LHC. P. Roussel, B. Jager, and L. Tavian* DSM/DRFMC/SBT, C.E.A, F-38054 Grenoble Cedex 9 (France) *LHC Division, CERN, CH-1211 Geneva 23 (Switzerland) The superconducting magnets of the Large Hadron Collider (LHC) will be cooled at 1.9K by distributed cooling loops where counter-flow heat exchangers will be integrated. To qualify potential suppliers for the 250-units series production, prototypes of various technologies have been selected by CERN and a test station was set up at CEA-Grenoble. This test station, is constituted of a cryostat allowing an easy access to the heat exchanger to be tested as well as very low pressure pumping facilities. 1 INTRODUCTION The superconducting magnets of the LHC [1] under construction at CERN will be cooled at 1.9K by distributed cooling loops working with saturated two-phase helium, and supplied with cold supercritical helium. In order to minimise the vapour fraction produced in the final expansion, counter-flow heat exchangers will be needed. These 250 subcooling heat exchangers will be integrated in the cryogenic distribution lines [2] so that a high reliability as well as good efficiency are expected. Prototypes of different technologies have been selected. Their qualification for the series production is depending on the results of cryogenic tests at their nominal and low-flow operating conditions carried out in CEA-Grenoble where a dedicated test station was set up, in the frame of collaboration between CEA and CERN for the construction of LHC. This papers describes this test facility and gives first results. 2 LHC SPECIFICATION To fulfil CERN specifications, the heat exchangers must comply with constraints on dimensions, thermal efficiency, and pressure drop in the very low pressure stream. 2.1 Thermodynamics. The heat exchanger has to operate at full capacity in nominal operation mode, as well as at low capacity in reduced operation mode. In steady-state operation, with the inlet conditions specified, the heat exchanger has to fulfil the functional requirements [3] listed in Table1. 2.2 Pressure drops. For any operation modes, on the VLP stream, the pressure drop must remain below 100Pa. This restrictive specification is imposed by the pumping facility and is the obliged condition to guarantee the temperature of 1.9K [4] in the LHC magnets. Concerning the HP stream, the maximum pressure drop in any operation modes must not overtake 20kPa.

Table 1 Steady-state operation modes Process Interface Operation mode Location Condition Nominal Reduced Supercritical inlet Pressure [kpa] 240 to 360 240 to 360 Temperature [K] 4.9 4.9 Flow [g/s] 4.5 1.5 to 4.5 Very low pressure inlet Pressure [kpa] 1.64 1.64 Temperature [K] 1.8 1.8 Flow [g/s] 4.5 1.5 to 4.5 Supercritical outlet Temperature [K] 2.20 2.20 Very low pressure outlet Temperature [K] 3.38 3.38 3 THE TEST STATION 3.1 Description The design of the test station must permit to check all these operation modes. Figure 1 shows the process flow diagram of the test station composed of a cryostat, pumps and screw compressor. In order to test the subcooling heat exchangers at their nominal and reduced operating conditions, supercritical helium at 0.36MPa and 4.9K is produced in the high pressure (HP) stream by passing through counter flow perforated plates heat exchangers HX1 and HX2 [5]. Cooling down of this HP stream is also improved by exchange in a nitrogen bath at 80K and in the 4.5K helium bath. At the outlet of this helium bath the temperature is adjusted with an electrical heater in order to control a temperature of 4.9K at the inlet of the subcooling heat exchanger. At the outlet of the heat exchanger, the HP stream is expanded in a Joule Thomson control valve which regulates the level of 1.8K superfluid helium bath. A by-pass is needed on the HP side to perform cool-down of this heat exchanger. The very low pressure cold gas from 1.8K helium bath is pumped through the subcooling heat exchanger and a 15kW heater by a roots pump in series with an oil ring pump. This heater was developed by CERN and produces very low pressure drop (less than 100Pa for a 20g/s mass flow at 1.8K). The low pressure circuit starts from the 5000l helium tank which fills in the 4.5K helium bath in the cryostat allowing the cooling of the supercritical flow thanks to a coiled heat exchanger; then the vaporised gas is returning to the inlet of the screw compressor, exchanging enthalpy with the HP circuit in heat exchangers HX1 and HX2. The mass flow varying between 1.5 and 4.5g/s is created by an electrical heater located in the 1.8K helium bath. The standard operation of this test station consists in remaining this heating power constant, while the level regulation of the 1.8K helium bath is performed by the Joule Thomson control valve. In order to reduce heat losses, the 4.5K ring shaped bath and the 1.8K bath are concentric. The 80K thermal shields are actively cooled by liquid nitrogen. This nitrogen cooling loop ensures a fast cool-down. The heat exchangers are tested one by one, but the design of the cryostat allows easy access to the heat exchanger to be tested so that only one day is necessary before next exchanger can be tested. The heat exchanger is connected with Kenol flanges. The instrumentation is linked to the cryostat and therefore, the same sensors are used for all the tests. 3.2 Instrumentation. Temperature: At each end of the heat exchanger to be tested two temperatures measurements are installed. The first one measures the temperature of the pipe, the second one the temperature of the fluid. The accuracy is about +/- 0.05K.

Pressure: on the supercritical side at the inlet of the heat exchanger pressure is monitored thanks to a pressure transmitter working at very low temperature. Differential Pressure: measurement is done at room temperature with the help of a pressure transmitter whose accuracy is 0.1%. Mass flow is monitored via a thermal flow metre on the HP stream. In order to be sure that flows is identical in each stream of the heat exchanger to be tested, the level of the 1.8K bath is kept constant. Oil ring pump Screw compressor Recovery 4500 Pa Roots pump LP 0.1MPa FT HP 0.36MPa GN2 From 5000 l LHe Tank LN2 15kW heater HX1 LN2 80K VLP 1550Pa HX2 4.5K, 0.13MPa TT TT PT PDT TT TT SUBCOOLING HEAT EXCHANGER TO BE TESTED LT TT: Temperature Transmitter PT: Pressure Transmitter PDT: Differential Pressure Transmitter LT: Level Transmitter FT: Flow Transmitter. 1.8K; 1640Pa Figure 1 Process flow scheme of the test station 3.3 Uncertainty. Taking into account the accuracy of measurement sensors, we have performed calculations of its influence on the performances of the subcooling heat exchanger. For instance, concerning thermometers, a difference of +/- 1% which corresponds to +/-0.05K on the inlet of heat exchanger on the HP side, would involve a mistake of +/- 1.1% on the calculation of the heat exchanger efficiency. Consequently, it seems that the accuracy of temperature measurements allows an acceptable estimation of the performances of the subcooling heat exchangers. The stability of the liquid helium bath at 1.8K must be carefully monitored. Indeed, this parameter ensures that heat exchanger to be tested is perfectly balanced, with identical flows in each stream, HP and VLP. Taking into account the geometry of the 1.8K vessel, and the superconducting level gauge indications, we know that a level variation of 0.5% per minute represents a mass flow unbalance in the heat exchanger of 0.13g/s which is 3% of the nominal flow.

4 PUMPING FACILITY 4.1 Roots pump skid. The characteristics of the Roots pump are as follows: for nominal operation mode: mass flow 4.5g/s, inlet pressure 1250 Pa, outlet pressure 4300Pa. For ultimate performance: 18g/s, inlet pressure 5700Pa, outlet pressure 15,5kPa. This roots pump is equipped with a variable speed drive unit which regulates the temperature of the 1.8K helium bath. 4.2 Oil Ring Pump. This pump can deal with a 4.5g/s mass flow at 4000Pa inlet pressure and recover it at atmospheric pressure. This oil ring pump has been under operation in CEA-grenoble for several years. Its integration in the cryogenic test facility has requested the set up of a new process control system. 5 FIRST RESULTS Four suppliers were selected by CERN and asked to provide two identical prototypes subcooling heat exchangers, to be tested at their nominal working point in the test station. Indeed, CERN s requirement was to verify the reproducibility of production as well as the technical specification in view of a series. Several technologies were proposed and some have already been tested in the cryogenic test station. K; g/s; hpa 6 5 4 3 2 1 0 T outlet H P (K) T inlet VLP (K) T inlet HP (K) Mass flow (g/s) T outlet V LP (K ) T helium bath (K) 0 60 120 180 240 300 Time (s) L evel of liquid helium bath (% ) P ressure drop on VLP stream (hpa) 32 31,5 31 30,5 30 29,5 29 28,5 28 level of helium bath (%) Figure2 Measurements during tests of prototype heat exchanger 6 CONCLUSION These first results have demonstrated the capacity of this test station to perform tests at nominal and lowflow condition. Several prototypes of heat exchangers have already been tested in 1999. Other tests will continue in 2000. This test facility is dedicated to test one heat exchanger over ten of the 250 subcooling heat exchangers needed for LHC. 1. Evans, L. The Large Hadron Collider Project In: Proc.ICEC16, Elsevier science, Oxford, UK (1997) 45:52. 2. Erdt,W., Riddone,G. and Trant,R. The cryogenic distribution line for the LHC: Functional specification and conceptual design. In: CEC-ICMC 99. 3. Millet, F., Roussel, P., Tavian, L. and Wagner,U. In: CEC-ICMC 97. 4. Lebrun, P. superfluid helium cryogenics for the Large Hadron Collider Project In: Cryogenics (1994) vol 34 ICEC. 5. Viargues, F., Claudet, G., and +Seyfert, P. Construction and preliminary testing of perforated-plate heat exchangers for use in HeII refrigerators. In ICEC 95 proceedings.